Beruflich Dokumente
Kultur Dokumente
O-Engineers
Dec-2018
Voices of Engineers
Page-77
6
When dielectric test applied on earthing switches, the
test voltage shall be applied with the earthing switch in
the open position in these condition:
8
B:Functional tests:
D:Dielectric tests:
10
4-Design and visual checks:
12
Arc Flash Risk
Assessment, An
important Analysis to
perfom on ETAP
17
For medium voltage systems (>1 kV), the arc current is
given by
Figure-1
19
Engineering Controls To Avoid Arc Flash
• Effect Of Varying FCT (Fault Clarence Time)
• Effect Of % Impedance Variation of transformer
• Effect Of Grounding
• Effect Of Feeder Loading.
Conclusion
Arc flash is a destructive phenomenon that could cause
loss of precious lives and belongings. Repercussions of
Arc flash incidents include substantial harm to workers,
including severe burn injuries and even death. This single
line diagram deals to guarantee the safety of workforce who
work on or adjacent electrical equipment voltage relative to
13.8 kilovolts or less. The major concern of the analysis was
to make the system secure i.e. suggesting “Safety by design”
and emphasizing over its implementation gradually.
Through engineering controls, it was observed that by
decreasing both Fault Clearance Time (FCT) and Incident
energy can decrease the Arc Flash incident energy up
to an acceptable level so that proper Personal protective
equipment could be worse by worker and accurate arc flash
labels could be placed on Equipment. Proper protection and
Multiple Mitigation techniques were adopted like effect of
varying FCT, effect of %Z variation, effect of feeder loading,
effect of transformer’s grounding impedance and Effect of
feeder loading to minimized the incident energy.
20
XXM Water Flood Medium
inspection and mainten
m Voltage Panels check-up/
nance-Practical Example
Duration:
every 3 monthly check up, 6 monthly PM and trouble-
shooting activity on call basis
· Hipot Test
· Timing Test
· Continuity Check
23
Please Note: in all maintenance tests, VCB Trolley must
be rack out
Hipot Test:
Hipot Test is short name of high potential (high voltage)
Test and it is also known as Dielectric Withstand Test. A
Hipot test checks for “good isolation.”
Hipot test makes surety of no current will flow from one
point to another point.
Hipot test is the opposite of a continuity test.
Continuity Test checks surety of current flows easily
from one point to another point while Hipot Test checks
surety of current would not flow from one point to
another point (and turn up the voltage really high just to
make sure no current will flow).
The hipot test is a nondestructive test that determines
the adequacy of electrical insulation for the normally
occurring over voltage transient. This is a high-voltage
test that is applied to all devices for a specific time in
order to ensure that the insulation is not marginal.
Hipot tests are helpful in finding nicked or crushed
insulation, stray wire strands or braided shielding,
conductive or corrosive contaminants around the
conductors, terminal spacing problems, and tolerance
errors in cables. Inadequate creepage and clearance
24
distances introduced during the manufacturing process.
The production-line hipot test, however, is a test of the manufacturing
process to determine whether the construction of a production unit is
about the same as the construction of the unit that was subjected to type
testing. Some of the process failures that can be detected by a production-
line hipot test include, for example, a transformer wound in such a way
that creepage and clearance have been reduced.
Such a failure could result from a new operator in the winding
department.
HIPOT test is applied after tests such as fault condition, humidity, and
vibration to determine whether any degradation has taken place.
Other examples include identifying a pinhole defect in insulation or
finding an enlarged solder footprint.
As per IEC 60950, The Basic test Voltage for Hipot test is the 2X
(Operating Voltage) + 1000 V
The reason for using 1000 V as part of the basic formula is that the
insulation in any product can be subjected to normal day-to-day transient
over voltages.
Experiments and research have shown that these over voltages can be as
high as 1000 V.
Timing Test:
Circuit breakers are one of the important and critical
part of electric power system. Circuit breakers are the
backbone of electrical protection system. Because of
their key importance, they must be checked periodically.
Circuit breaker timing test is among different
maintenance tests which should be performed regularly.
It measures the mechanical operating time of the circuit
breaker. This test is always important because delay in
operation of circuit breaker can have disastrous effects
on the equipment when fault occurs.
Closing time: The time interval between energizing
the coils of the breaker (when CB contacts are in open
position) and the instant when the contacts touch each
other.
Opening time: It is opposite to that of closing time. It is
the time interval between energizing the trip coil (CB
contacts are in open position) and the instant when
30
contacts separate from each other.
32
Circuit breaker timing test procedure and
Connections
To perform breaker timing test, following connections
are required.
· Connection to the input & output of each phase of
circuit breaker from circuit breaker analyzer.
· DC supply to the tripping coil of the circuit breaker
from external source.
· Connection to the tripping circuit of breaker from
CBA.
Following figure shows the typical connection diagram.
Accepted Results
The exact correct operation time of circuit breaker is
provided by the manufacturer. It can be mentioned on
the nameplate of circuit breaker.
However as a rule of thumb, operating time of circuit
breaker should fall in the following ranges
HT breakers (above 11kV) Opening time = 1-2 cycles
(20 – 40 ms)
Closing time = 2-5 cycle ( 40 to 100ms)
LT breakers (11kV or below) opening time = 2-3 cycles
(40 to 60ms)
Closing time = 3-6 cycles (60 to 120ms)
These are just estimated values which can be regarded as
acceptable operation time.
34
Contact Resistance Test Procedure
Contact resistance test is performed for Circuit breakers
which are very important entity of Electrical power
system. It plays a key role in protection of electrical
equipment. It conducts current during normal
condition. However in faulty condition, it interrupts the
power/current by opening its contacts. When the fault
is removed, continuity of electrical system is restored
by making contact of circuit breaker. For this to happen
reliably and smoothly, the contacts of circuit breaker
should be in good condition. There should make and
break properly. There should be no carbon or any other
unwanted material on its surface. The contacts should
be properly lubricated.
With the passage of time, contacts of circuit breaker
worn out. Since the contacts of circuit breaker are not
visible therefore contact resistance testing is necessary
to check condition of contacts of circuit breaker. It is
also necessary to select correct circuit breaker so that
the contacts lasts longer. Proper selection is explained in
article, how to select circuit breaker
36
Micro ohmmeter must have the following provisions
· Should supply as high current as 200A.
· Should have the provision of varying current
· Current meter.
· Display resistance.
There are two types of leads or connection wires in
resistance test set. One set of leads is called current
leads and other is called sensing leads or voltage
leads. The purpose of current leads is to provide
high current while that of sensing leads is to provide
voltage.
Operating principle
The operating principle of this test depends upon
balancing bridge (like Wheatstone bridge) and
Ohms law. High current is injected and small
voltage is applied to measure contact resistance. The
internal structure of micro ohmmeter is beyond the
scope of this article.
Continuity test:
At contact close position and rack out position, we
39
conduct this test by multimeter
Reference Documents:
Concerned Company Quality & HSE manual.
40
Power quality improvem
sharing in Embedded gen
ment technique and load
neration based Smart Grid
44
Fig. 1 EIPT based
current controller
to decomposed
current and
determine
compensating
reference current.
45
When two distributed energy resources is connected to centralized power generation, load power
sharing can be possible through droop control. Load power sharing through droop control among
distributed renewable energy sources does not required communication path. However droop
control has a draw back for load power sharing in DERS and a trade off between power sharing
accurate and voltage and frequency regulation, slow transient response and impedance mismatch
of DERs. So the promising alternative is to decomposed the current and determine the current
reference and through supervisor controller share the distributed load in the present of non linear
load in smart grid as shown in fig mention below.
From the above discussion, It is concluded that Enhanced instantaneous power theory must be
applied in smart grid for proper power load sharing as well as improved the power quality of the
network under non linear load as well as balanced, unbalanced and distorted voltage sources.
46
Modern Power Distr
Simulation w
ribution Analysis and
with PSCAD
PSCAD-Load Modelling
In PSCAD, the load is modeled as a function of voltage magnitude
and frequency, where the load real and reactive power are considered
50
separately using the expressions:
Voltage Regulation
The process maintaining the voltage along a
distribution feeder within the bandwidth specified by
IMPLEMENTED OR ADOPTED STANDARDS, is
51
In a distribution feeder without active generation the
highest voltage is at the substation voltage regulator
(LTC). The lowest voltage is at the far away points from
the substation.
In the case of long feeders with a high amount of
load, the feeder can experience voltages less than the
minimum indicated by the standard. Voltage regulators,
which are autotransformers with multiple taps, are used
to regulate voltage at places with low voltage.
Voltage Regulator
A voltage regulator is simply a
tapped autotransformer that
works to either raise (boost)
or lower (buck) the voltage.
This device can be conside-
-red the most important de-
-vice in the single line diagram
in order to transfer energy to
a long distance. It has the res-
ponsibility of connecting two
points with different voltage
levels. Each transformer has
the following specified name
plate values: kilo Volt Ampere (kVA) rating, voltage
52
rating, impedance, no-load loss, and saturation
condition. Transformers in a distribution system can be
three-phase connected as a Y or delta. Also, they can be
formed as three separate single-phase transformers.
In a distribution system, the main transformer usually
contains an LTC. The secondary of the transformer with
tap changer has multiple taps.
Here, to expand on the idea of voltage regulators, we
start with a simple single-phase autotransformer. An
autotransformer is a transformer with single coil,
An autotransformer consists of a single winding which
serves as primary winding as well as secondary winding,
Below mention Figure shows a single-phase transformer
used as an autotransformer. Essentially by connecting a
point on the secondary of the single-phase transformer
to a point on the primary of the transformer, the
autotransformer is formed. The device is utilizing a
single coil to change voltage and transfer energy.
53
A key advantage to the autotransformer is higher output power.
The disadvantage is lower impedance, which means in higher
voltage applications it may have a high short-circuit current.
Autotransformers are often used when voltage transformation is
small and cost is a considerable concern. Despite the advantages
of voltage regulation, larger output power, elimination of
secondary windings, and power transformation energy transfer,
common drawbacks of using an autotransformer include
risks of high short-circuit currents (due to a much smaller
impedance) and complications due to the primary windings
not being completely insulated from the secondary. The special
autotransformer, called the voltage regulator, uses the same
principle of creating a direct electrical connection between
primary and secondary windings, except that it also maintains
the capability of changing the transformer turns ratio to meet
changing voltage demands. It is designed so that the connection
between the primary and secondary can change locations.
This is done by switching the high potential connection on
the secondary side between different connection points, called
“taps.” Switching between different taps creates a range of turn
ratios that can be utilized, thus allowing the voltage at the
secondary to be controllable and variable.
(to be continue..................................................................................)
54
Carpediem
Research
Corner
Carpediem
Research Team
Automatic Car B
Battery Charger
62
The circuit uses capacitors C1 of type K50-24 for 63
V, C2 - K53-4A for 20 V, trimmer R10 of type SP5-2
(multiturn), fixed resistors R2 ... R4 of type C5-16MB,
R8 of type PEV-15 the rest are of type C2-23. Relay K1
is suitable for any, with an operating voltage of 24 V and
an allowable current through the contacts 5 A; tumblers
SA1, SA2 type T1, button SB1 type KM1-1.
The difference in the indication of the switch ampermeter and the actual
current is due to the fact that the ammeter averages the measured value
during the period of the mains voltage, and the charge is made only during
half the period.
As the battery charges, the voltage on it will gradually increase, and when
it reaches 14.7 V, the circuit will automatically shut off the charge circuit.
Automation will also disable the charging process in the event of any other
unforeseen effects, for example, if the breakdown VT1 or the disappearance
of the mains voltage. Auto-off mode can also be triggered if there is poor
contact in the circuits from the charger to the battery. In this case, press the
RESET button (SB1).
64
Wireless App
partment bell
It is important that the elements of the device are mounted by printed wiring
and their conclusions have a minimum length. Transmitter power is small
and is only 0.01 watts. This is quite enough to transmit a radio signal over a
distance of 50 m.
The most optimal operation of the transmitter is carried out at the node
supply voltage of +5 V. The power source should be autonomous or stabilized
with a down-output transformer. Current consumption 28 ... 30mA. An
increase in the supply voltage changes the operating mode of the transistor
68
VT1, which adversely affects the output amplitude and the power of the transmitter, and hence the distance
of reliable signal reception. Therefore, the working point of the offset of the transistor VT1 can be corrected
by changing the resistance of the resistor R5.
Since the output signal from pin 3 of the DA1 chip is very large in amplitude, a regulator is inserted in
the circuit. Variable resistor R4 (type SPO-1) serves as a regulator of the output level of the low-frequency
generator, assembled on the chip DA1. When setting up a node, it is necessary to set the level of the
generator output signal so that the signal received by the portable receiver is listened without distortion like
“step” or “echo”. Isolation capacitor C3 (type KM-6B) does not allow the DC component of the voltage from
the generator to the input of the transistor transmitter. An antenna is connected to the C5 capacitor, which
is a segment of a multicore mounting unshielded wire with a cross section of 1.2 mm and a length of 20 cm.
This wire antenna can be laid around the knot elements in a spiral, inside the unshielded housing.
The elements of the device are installed compactly in an unshielded plastic case, which is located, if
possible, away from network wiring.
Details. Button SA1 is a standard bell button installed at the entrance to the apartment. All permanent
resistors type MLT-0.125. Capacitors type KM-6B. Transistor VT1 can be replaced KT368A, KT355A,
KT355B. Coil L1 contains 5 turns of wire PEV-1 with a diameter of 0.5 mm, wound frameless or on a
wooden frame with a diameter of 5 mm. For the frame, a simple wooden pencil (with a graphic rod
removed) or a reel of old-fashioned threads is suitable.
The disadvantage of this scheme is the single-tone character of the signal. It is possible to supplement the
device circuit with a discontinuous signal generator or use as a sound generator a microassembly of the type
UM08 with recording a musical fragment of a melody.
69
Sound Effect
Generator
76
Voices of
Engineers
77
Professionals without tasks or goals(assigned or
aligned) grew weak in confidence and knowledge
with passage of time.
(Engr. Arsalan Hamid)
80
Please Send yo
feedbacks before
get it publish in
enpak2017@
our articles and
28th Dec 2018 to
n Jan 2019 issue.
@gmail.com