Checking operation data The operation data is saved when the situation of abnormal operation happen, and the data
can be confirmed by remote controller.
Operation data can be checked with remote
Number Data Item
control unit operation. 01 (Ope ration Mode)
Error Code of indoor unit
02 (Set Temperature)
1. Press the button.
03 (Return Air Temperature)
Display on LED on indoor circuit board
The display change “ ” 04 (Remote Control ThermistorTemperature)
remote Content
05 (Indoor Unit Heat Exchanger Thermistor / U Bend) red (checking) green (normal)
2. Press the (SET) button while controller
06 (Indoor Unit Heat Exchanger Thermistor /Capillary)
07 (Indoor Unit Heat Exchanger Thermistor /Gas Header) Off Continuous blinking Normal
“ ” is displayed.
08 (Indoor Unit Fan Speed) Off Fault on power, indoor power off or lack
When only one indoor unit is connected to 09 (Frequency Requirements)
Off Off phase
10 (Response Frequency) Fault on the transmission between
remote control, “ ” is Off Continuous blinking
11 (Pulse of Indoor Unit Expansion Value)
E1 indoor circuit board and remote control
displayed (blinking indication during data 12 (Total Running Hours of The Indoor Unit)
Not sure Not sure Indoor computer abnormal
21 (Outdoor Air Temperature)
loading). E5 Blinking twice Continuous blinking Fault on outdoor-indoor transmission
22 (Outdoor Unit Heat Exchanger Thermistor)
Next, operation data of the indoor unit 23 (Outdoor Unit Heat Exchanger Thermistor) Indoor heat exchange sensor interrupted or
E6 Blinking once Continuous blinking short-circuit
will be displayed. Skip to step 7. 24 (Compressor Frequency)
25 (High Pressure) Indoor air inhaling sensor broken or
4. When plural indoor units is connected, the 26 (Low Pressure)
E7 Blinking once Continuous blinking short-circuit
27 (Discharge Pipe Temperature)
smallest address number of indoor unit The temperature of heat exchange
28 (Comp Bottom Temperature) E8 Blinking once Continuous blinking abnormal
among all connected indoor unit is displayed. 29 (Current)
30 (Target Super Heat) E9 Blinking once Continuous blinking Float SW actions (only with FS)
[Example]:
31 (Super Heat) Excess number of remote control
“ ” (blinking 1 seconds) E10 Off Continuous blinking connections
32 (Discharge Pipe Super Heat)
“ ” blinking. 33 (Protection State No. of The Compressor)
E14 The communication fault for master/slave
34 (Outdoor Unit Fan Speed) Blinking for three times Continuous blinking indoor units
5. Select the indoor unit number you would 35 (63H1 On/Off)
E16 Blinking once Continuous blinking Fan motor abnormal
like to have data displayed with the 36 (Defrost Control On/Off)
Configuration fault on running checking
37 (Total Running Hours of The Compressor) E19 Blinking once Continuous blinking
button. 38 (Pulse of The Outdoor Unit Expansion Valve EEVC)
model
39 (Pulse of The Outdoor Unit Expansion Valve EEVH) E28 Off Continuous blinking Remote control sensor interrupted
6. Determine the indoor unit number with the
̪Depending on outdoor unit model, there are data not shown. Outdoor unit checking (outdoor circuit board
(SET) button. Over E30 Off Continuous blinking LED checking)
(The indoor unit number changes from blinking indication to continuous indication)
[Operating procedure]
“ ” (The address of selected indoor unit is blinking for 2 seconds.)
1. Press the button.
“ ” (A blinking indication appears while data loaded.)
The display change “ ”
2. Once, press the button, and the display change
Next, the operation data of the indoor unit is indicated.
“ ”.
7. Upon operation of the button, the current operation data is displayed in order from data
number 01. 3. Press the (SET) button and abnormal operation data mode is started.
The items displayed are in the above table. 4. When only one indoor unit is connected to remote control, following is displayed.
̪Depending on models, the items that do not have corresponding data are not displayed. ԘThe case that there is history of abnormal operation.
8. To display the data of a different indoor unit, press the button, which allows you to go back to Error code and “ ” is displayed.
the indoor unit selection screen. [Example]: [E8] (ERROR CODE)
9. Pressing the button will stop displaying data. “ ” is displayed (blinking indication during data loading).
Pressing the (RESET) button during remote control unit operation will undo your last operation and Next, the abnormal operation data of the indoor unit will be displayed. Skip to step 8.
allow you to go back to the previous screen. ԙThe case that there is not history of abnormal operation.
٧If two (2) remote control are connected to one (1) inside unit, only the master controller is available for trial “ ” is displayed for 3 seconds and this mode is closed.
operation and confirmation of operation data. (The slave remote control is not available.)
5. When plural indoor units is connected, following is displayed.
ԘThe case that there is history of abnormal operation.
ԜControl mode switching Error code and the smallest address number of indoor unit among all connected indoor
unit is displayed.
٨The control content of indoor units can be switched in following way.
[Example]: [E8] (ERROR CODE)
( is the default setting)
“ ” blinking
Switch No. Control Content ԙThe case that there is not history of abnormal operation.
SW2 Indoor unit address (0-Fh) Only address number is displayed.
SW5-1 6. Select the indoor unit number you would like to have data displayed with the
Master/Slave Switching (plural /Slave unit Setting)
SW5-2 button.
Model capacity setting 7. Determine the indoor unit number with the (SET) button.
SW6-1㨪4
ON Operation check, Drain motor test run
[Example]: [E8] (ERROR CODE)
SW7㧙1 “ ” (The address of selected indoor unit is blinking for 2 seconds.)
OFF Normal operation
PGAO12D405
- 165 -
'14 • PAC-SM-215
2. MAINTENANCE DATA
2.1 Diagnosing of microcomputer circuit
(1) Selfdiagnosis function
(a) Check Indicator Table
Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote control error code,
indoor/outdoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
(i) Indoor unit
Remote control Indoor control PCB Outdoor control PCB
Location of Reference
Green Green Description of trouble Repair method
Error code Red LED Red LED Red LED trouble page
LED (1) LED (1)
Keeps Keeps
Stays OFF Stays OFF — • Normal operation — —
flashing flashing
Stays OFF Stays OFF 2-time flash Stays OFF Indoor unit power source • Power OFF, broken wire/blown fuse, broken transformer wire Repair 69
No-indication Stays OFF
* Remote control wires • Poor connection, breakage of remote control wire * For wire breaking at power ON, the LED is OFF. Repair
Keeps Keeps
3-time Stays OFF Replacement of 70
flashing flashing Remote control • Defective remote control PCB
flash remote control
Indoor-outdoor units
WAIT or Keeps 2-time Keeps • Poor connection, breakage of indoor-outdoor units connection wire
Stays OFF connection wire Repair 71-74
INSPECT I/U flashing flash flashing
Remote control • Improper setting of master and slave by remote control
• Poor connection of remote control signal wire (White)
* Remote control
* For wire breaking at power ON, the LED is OFF Repair
Keeps Keeps wires (Noise)
Stays OFF Stays OFF • Intrusion of noise in remote control wire 76
flashing flashing
Remote control Replacement of remote
indoor control PCB *• Defective remote control or indoor control PCB (defective communication circuit)? control or PCB
Indoor-outdoor • Poor connection of wire between indoor-outdoor units during operation
2-time Keeps 2-time Keeps
units connection (disconnection, loose connection) Repair
flash flashing flash flashing wire • Anomalous communication between indoor-outdoor units by noise, etc.
Power reset or
(Noise) • CPU-runaway on outdoor control PCB
2-time Keeps Keeps Repair
Stays OFF 77
flash flashing flashing Outdoor control *• Occurrence of defective outdoor control PCB on the way of power source (defective com- Replacement of
PCB munication circuit)? PCB
Outdoor control
2-time Keeps Keeps • Defective outdoor control PCB on the way of power source
Stays OFF PCB Replacement
flash flashing flashing
Fuse • Blown fuse
Indoor heat • Defective indoor heat exchanger temperature thermistor (defective element, bro- Replacement, repair
1-time Keeps Keeps exchanger tempera- ken wire, short-circuit) of temperature
Stays OFF ture thermistor • Poor contact of temperature thermistor connector thermistor 78
flash flashing flashing
Indoor control PCB *• Defective indoor control PCB (Defective temperature thermistor input circuit)? Replacement of PCB
Indoor return air • Defective indoor return air temperature thermistor (defective element, broken wire, Replacement, repair
1-time Keeps Keeps temperature therm- short-circuit) of temperature
Stays OFF istor • Poor contact of temperature thermistor connector thermistor 79
flash flashing flashing
Indoor control PCB *• Defective indoor control PCB (Defective temperature thermistor input circuit)? Replacement of PCB
Installation or oper-
• Heating over-load (Anomalously high indoor heat exchanger temperature) Repair
ating condition
1-time Keeps Keeps Indoor heat Replacement of
Stays OFF exchanger tempera- • Defective indoor heat exchanger temperature thermistor (short-circuit) temperature therm- 80
flash flashing flashing
Keeps ture thermistor istor
flashing
Indoor control PCB *• Defective indoor control PCB (Defective temperature thermistor input circuit)? Replacement of PCB
Replacement, repair
Drain trouble • Defective drain pump (DM), broken drain pump wire, disconnected connector
of DM
Float switch • Anomalous float switch operation (malfunction) Repair
1-time Keeps Keeps
Stays OFF 81
flash flashing flashing
Indoor control PCB *• Defective indoor control PCB (Defective float switch input circuit) Replacement of
*• Defective indoor control PCB (Defective DM drive output circuit)? PCB
Option • Defective optional parts (At optional anomalous input setting) Repair
Keeps Keeps Number of con- • When multi-unit control by remote control is performed, the number of units
Stays OFF Stays OFF Repair 82
flashing flashing nected indoor units is over
Keeps Keeps Keeps Address setting
Stays OFF • Address setting error of indoor units Repair 83
flshing flshing flshing error
3-time Keeps Keeps Indoor unit No. setting •No master is assigned to slaves.
Stays OFF Repair 84
flash flashing flashing Rcmote control wires •Anomalous remote control wire connection, broken wire between master and slave units
1(2)-time Keeps Keeps Fan motor • Defective DC fan motor Replacement, repair
Stays OFF 85
flash flashing flashing Indoor power PCB • Defective indoor power PCB Replacement
1-time Keeps Keeps Address
Stays OFF • Address setting error of master and slave indoor units Repair 86
flash flashing flashing setting error
1-time Keeps Keeps
Stays OFF Indoor control PCB • Improper operation mode setting Repair 87
flash flashing flashing
1(2)-time Keeps Keeps Fan motor • Indoor DC fan motor rotation speed anomaly Replacement, repair
Stays OFF 88
flash flashing flashing Indoor power PCB • Defective indoor power PCB Replacement
1-time Keeps Keeps Panel switch
Stays OFF • Defective panel switch operation (FDT only) Repair 89
flash flashing flashing detection
Keeps Keeps Remote control
Stays OFF Stays OFF • Broken wire of remote control temperature thermistor Repair 90
flashing flashing temperature thermistor
Note (1) Normal indicator lamp (Indoor, outdoor units: Green) extinguishes (or lights continuously) only when CPU is anomalous. It keeps
flashing in any trouble other than anomalous CPU.
(2) * mark in the description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing
the part, it is judged consequently that the replaced part was defective.
- 36 -
'14 • PAC-SM-215
Installation or operating
• Higher outdoor heat exchanger temperature Repair
condition
Keeps 1-time Keeps Outdoor heat exchanger Replacement of
Stays OFF • Defective outdoor heat exchanger temperature thermistor 91
flashing flash flashing temperature thermistor temperature thermistor
*• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB Replacement of PCB
circuit)?
Installation or operating • Higher discharge temperature Repair
condition
Keeps 1-time Keeps Discharge pipe Replacement, repair of
Stays OFF • Defective discharge pipe temperature thermistor 92
flashing flash flashing temperature thermistor temperature thermistor
*• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB Replacement of PCB
circuit)?
Outdoor heat exchanger • Defective outdoor heat exchanger temperature thermistor, broken wire or poor Replacement, repair of
Keeps 1-time Keeps Keeps temperature thermistor connector connection temperature thermistor
Stays OFF flashing 93
flashing flash flashing *• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB Replacement of PCB
circuit)?
Outdoor air temperature • Defective outdoor air temperature thermistor, broken wire or poor connector Replacement, repair of
Keeps 1-time Keeps thermistor connection temperature thermistor
Stays OFF 94
flashing flash flashing *• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB Replacement of PCB
circuit)?
Discharge pipe • Defective discharge pipe temperature thermistor, broken wire or poor Replacement, repair of
Keeps 1-time Keeps temperature thermistor connector connection temperature thermistor
Stays OFF 95
flashing flash flashing *• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB Replacement of PCB
circuit)?
Installation or operating
Keeps 1-time Keeps • Rising high pressure (Operation of 63H1) • Service valve closing operation Repair
Stays OFF condition 96
flashing flash flashing
Outdoor control PCB *• Defective outdoor control PCB (Defective 63H input circuit)? Replacement of PCB
Keeps 1-time Keeps 2-time or Inverter PCB or radiator Replacement of PCB
Stays OFF • Power transistor overheat 97
flashing flash flashing 8-time flash fin or Repair
Outdoor control PCB
• Current cut (Anomalous compressor over-current) Replacement of PCB
Keeps 1-time Keeps 1-time or compressor
Stays OFF 98・99
flashing flash flashing 9-time flash Installation or operating
• Service valve closing operation Repair
condition
Service valve opening
Keeps 1-time Keeps Outdoor control PCB • Anomalous outdoor control PCB communication
Stays OFF check 100
flashing flash flashing
Inverter PCB • Anomalous inverter PCB communication Replacement of PCB
Keeps 1-time Keeps Outdoor fan motor • Anomalous outdoor fan motor Replacement, repair
Stays OFF 101
flashing flash flashing Keeps Outdoor control PCB *• Defective outdoor control PCB (Defective motor input circuit)? Replacement of PCB
flashing Installation or operating
• Low pressure error • Service valve closing operation Repair
condition
Keeps 1-time Keeps • Anomalous low pressure, broken wire of low pressure sensor or poor Replacement, repair of
Stays OFF Low pressure sensor
connector connection sensor 102・103
flashing flash flashing
Replacement of control
Outdoor control PCB *• Defective outdoor control PCB (Defective sensor input circuit)?
PCB
Keeps 1-time Keeps 2-time or
Stays OFF Inverter PCB • Anomalous inverter PCB Replacement of PCB 104
flashing flash flashing 8-time flash
Suction pipe • Defective suction pipe temperature thermistor, broken wire or poor connector Replacement, repair of
Keeps 1-time Keeps temperature thermistor connection temperature thermistor
Stays OFF 105
flashing flash flashing Replacement of control
Outdoor control PCB *• Defective outdoor PCB (Defective thermistor input circuit)?
PCB
Low pressure sensor • Defective low pressure sensor Replacement of sensor
Keeps 1-time Keeps
Stays OFF Replacement of control 106
flashing flash flashing Outdoor control PCB • Defective outdoor control PCB (Defective sensor input circuit)?
Keeps PCB
flashing Compressor under dome • Defective compressor under dome temperature thermistor (Model FDC 250 Replacement of
Keeps 1-time Keeps temperature thermistor only) temperature thermistor
Stays OFF 107
flashing flash flashing • Defective outdoor control PCB (Defective thermistor input circuit)? (Model Replacement of control
Outdoor control PCB
FDC 250 only) PCB
Operation status • Shortage in refrigerant quantity Repair
Keeps 1-time Keeps
Stays OFF Service valve opening 108
flashing flash flashing Installation status • Service valve closing operation
check
Keeps 5-time Keeps Compressor inverter
Stays OFF 4-time flash • Anomalous compressor startup Replacement 109・110
flashing flash flashing PCB
Note (1) * mark in the description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing the
part, it is judged consequently that the replaced part was defective.
- 37 -
'14 • PAC-SM-215
Keeps flashing Stays OFF Keeps flashing Stays OFF Keeps flashing • Communication error (Defective communication circuit on the main unit of SC-SL2N-E or SC-SL4-E) ete. Replacement
- 38 -
'14 • PAC-SM-215
- 61 -
'14 • PAC-SM-215
(2) Troubleshooting
It is normal.
(This unit is designed to
Is the start in the soft start mode
temperature difference Does the by detecting the under dome
between return and supply air YES heat load increase after NO
temperature of compressor
10-20°C at installation?
when it restart after power
cooling? reset.
2. Error detection method
YES
NO
Note:
- 62 -
'14 • PAC-SM-215
It is normal.
(This unit is designed to
Is the start in the soft start mode
temperature difference Does the by detecting the under
between return and supply air YES heat load increase after NO dome temperature of
10-30°C at installation? compressor when it restart
2. Error detection method heating? after power reset.
YES
NO
It is necessary to replace to
Mistake in model selection. higher capacity one or to
Calculate heat load once again. install additional unit.
Is the compressor
operating? NO Compressor refrigerant oil
protection control at starting
“ WAIT ” is activated. For the contents
message is displayed (for 3 seconds) when of control, refer to the
performing cooling, defrosting and heating YES
operations from the remote
compressor start control of
control. the microcomputer control
functions.
Compressor may be
stopped by the error
YES
NO
detection control.
For the contents of control,
3. Condition of Error displayed refer to anomalous stop
control by controlling
compressor rotation speed
of microcomputor control
functions.
Is the
Inspect the followings.
compressor rotation NO
speed low?
• Minor clogging of filter
• Minor clogging of heat
exchanger
YES • Minor short-circuit
• Minor shortage of
Check which control “Determination control of refrigerant amount
conpressor rotation speed” or “Protective control • Poor compression of
by controlling compressor rotation speed” is compressor
appropriate to this phenomenon.
4. Presumable cause Considering appropriate
operation control, check
• Faulty 4-way valve operation (1)
suspicious points.
Are the Inspect the followings for
• Poor compression of temperature conditions
compressor of room and outdoor air close YES reference.
to the rated • Major clogging of filter
• Faulty expansion valve conditions?
operation Note (1) Outdoor: 7°C, Indoor: 20°C
• Major clogging of heat
NO exchanger
• Major short-circuit
• Major shortage of
The unit is operating normally but is refrigerant amount
operating under the contol for protecting • Compressor protection ON
compressor or other respective parts.
• Indoor fan tap
• Valid setting of silent mode
Note:
- 63 -
'14 • PAC-SM-215
Are OK the
insulation resistance and NO Replace compressor.*
coil resistance of
compressor?
YES
YES
Note:
- 64 -
'14 • PAC-SM-215
If excessive noise/vibration
Does persists when sufficient
noise/vibration time has elapsed after
occur during or soon NO stopping the unit, it is
after stopping operation considered that the air-
of air-conditioner? conditioner is not the
source.
Note:
- 65 -
'14 • PAC-SM-215
To next page
The noise/vibration occurs
Are hissing sounds YES when the refrigerant starts
heard at the startup or or stops flowing. It is
stopping? normal.
When the defrosting starts
NO
or stops during heating,
the refrigerant flow is
reversed due to switching
Is blowing sound 4-way valve. This causes
3. Condition of Error displayed heard at the start/stop YES a large change in pressure
of defrosting during which produces a blowing
heating? sound. It may accompany
also the hissing sounds as
mentioned above. They are
NO normal.
Note:
- 66 -
'14 • PAC-SM-215
If insufficient cooling/
Adjustment heating problem happens
during commissioning
Does noise/vibration occur when the
due to anomalous operating
cooling/heating operation is in conditions at cooling/
2. Error detection method anomalous condition? heating, followings are
suspicious.
YES • Overcharge of refrigerant
• Insufficient charge of
refrigerant
• Intrusion of air, nitrogen,
etc.
In such occasion, it is
necessary to recover
refrigerant, vacuum-dry
and recharge refrigerant.
* Since there could be
many causes of noise/
vibration, the above do not
cover all.
In such case, check the
conditions when, where,
3. Condition of Error displayed how the noise/vibration
occurs according to
following check point.
• Indoor/outdoor unit
• Cooling/heating/fan
mode
• Startup/stop/during
operation
• Operating condition
(Indoor/outdoor
temperatures, pressure)
• Time it occurred
• Operation data retained
by the remote control
4. Presumable cause such as compressor
rotation speed, heat
exchanger temperature,
EEV opening degree, etc.
• Tone (If available, record
the noise)
• Any other anomalies
Note:
- 67 -
'14 • PAC-SM-215
Operate after
waiting for more
than 1 minute.
Is louver motor
wiring broken?
NO
Is the louver
operable with the remote YES Normal
control?
3. Condition of Error displayed
NO Adjust louver motor lever
and then check again.
4. Presumable cause
Note:
- 68 -
'14 • PAC-SM-215
Is
AC220/240V
detected between 1 and
2 on the terminal block NO
of indoor
unit?
Is
AC380/415V
YES for 3-phase unit Defective outdoor control
detected between 1, 2 and 3 NO
on the teminal block PCB (Noise filter)
of outdoor unit?
2. Error detection method
YES
Misconnection or breakage
of connecting wires
Note(1) FDT, FDUM : F1, F2, FDU : F3
FDTC, FDF : F200, F201
(1) FDEN : Fuse between wires.
Are fuses OK? NO
Is the
check of resistance
between - of CNW0 NO Defective indoor power
YES PCB ª Replace.
(FDU : T1-T2)
OK?
YES
Is the
checked result
of resistance of fan NO Replace fan motor, etc.
motor, etc
OK?
YES Replace fuse.
3. Condition of Error displayed
Is DC5V (2)
detected between - NO Defective indoor power
of CNW1? PCB ª Replace.
Note (2) for GND
YES
YES
Defective indoor control
PCB ª Replace.
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty transformer
• Faulty indoor control or
power PCB
• Broken harness
• Faulty outdoor control PCB
(Noise filter)
Note:
- 69 -
'14 • PAC-SM-215
NO
NO
Disconnect remote
control wires.
Is DC15V or
higher detected between X-Y YES Replace remote control.
of indoor unit terminal
block?
3. Condition of Error displayed
NO
FDT, FDTC, FDU, FDUM
FDEN FDF Series
Is DC18V
between - of NO Defective indoor power
CNW2? PCBªReplace.
YES
Defective indoor control
PCBªReplace.
Note:
- 70 -
'14 • PAC-SM-215
Are 2 units
of remote control
connected?
YES
NO
⑴,
⑵
⑵
Set one remote control Is it set
for “Master” and the other at the slave remote YES Set SW1 on remote control
for “Slave” control? PCB at “Master”.
2. Error detection method
Note (1) Use SW1 to set at
master or slave. Note (2)
“Slave” is displayed
Communication between on the remote
indoor unit and remote control control LCD.
is disabled for more than 30 NO
Does it
minutes after the power on. become normal?
NO
Do more than
one indoor units have the YES Set address again. (SW2 on
same address? indoor control PCB)
NO
3. Condition of Error displayed
NO
• Improper setting
• Surrounding environment Does
• Defective remote control drain motor
communication circuit start 60 seconds later YES Defective indoor control
• Faulty indoor control PCB automatically. PCBªReplace.
Note: If any error is detected 30 minutes after displaying “ WAIT ” on the remote control, the display changes to
“INSPECT I/U”.
- 71 -
'14 • PAC-SM-215
NO
Does remote
control display YES Change remote control
2. Error detection method “Slave”? setting to “Master”. (SW1
on remote control PCB)
NO
Indoor unit cannot communicate
for more than 30 minutes after
the power on with remote Do more than
control. one indoor units have the YES Change address. (SW2 on
same address? indoor control PCB)
NO
Is it set to
a slave indoor unit. YES Change to master. (SW5-1,
SW5-1, 2? 2 on indoor control PCB)
NO
Is there loose
or wrong connection at the termanal
of wiring between indoor and YES Correct
outdoor units?
3. Condition of Error displayed
NO
Same as above
Is the
grounding wire connected NO Correct
properly?
YES
Is approx.
DC20V detected between - NO Defective outdoor control
on the outdoor unit terminal
block? PCBªReplace.
YES
Note: If any error is detected 30 minutes after displaying “ WAIT ” on the remote control, the display changes to
“INSPECT I/U”.
- 72 -
'14 • PAC-SM-215
YES
Is the outdoor
unit control green LED NO
flashing?
Is the indoor
unit green LED flashing? NO Defective indoor control
PCBªReplace.
YES
Are wires
connected properly between indoor/ NO Correct connection wires
3. Condition of Error displayed outdoor units? between indoor and
outdoor units.
YES
Is approx.
DC20V detected between - on NO Defective outdoor control
the outdoor unit terminal
block? PCBªReplace.
YES
Note:
- 73 -
'14 • PAC-SM-215
NO
Does it reset normally?
2. Error detection method
YES Normal (Malfunction by
noise)
Is AC380/415V
detected at the noise filter NO Replace noise filter.
secondary side?
YES
Isn’t fuse
〔250V, 2A〕on the outdoor control NO Defective outdoor control
PCB blown? PCBªReplace.
3. Condition of Error displayed YES
Is DC5V
detected on the outdoor control PCB (Between NO Defective outdoor control
- of CNV)? PCBªReplace.
YES
Is DC5V detected
if the connector of outdoor unit fan motor NO Defective outdoor fan
is disconnected? motor
YES
Is DC5V detected
4. Presumable cause if the inverter power source connector (CNI2) NO Defective inverter PCB
is disconnected?
ªReplace.
• Faulty noise filter
• Faulty indoor control PCB
• Faulty outdoor control PCB
• Faulty inverter PCB
YES Defective outdoor control
• Faulty fan motor PCBªReplace.
Note:
- 74 -
'14 • PAC-SM-215
Is DC10V or
higher detected at remote control connection YES Defective remote control
terminals?
NO
2. Error detection method
Is DC10V or higher
detected on remote control wires if YES Defective remote control
the remote control is
removed?
NO
Are wires
connected properly between the YES Defective connecting wire.
indoor/outdoor units?
Defective remote control
wire (Short-circuit, etc.)
NO
4. Presumable cause
Note:
- 75 -
'14 • PAC-SM-215
NO
NO
Defective remote control
Note (2) Does the remote control still display “ WAIT ” even ª Replace.
after 3 minutes?
Same as above
4. Presumable cause
• Defective communication
circuit between remote
control-indoor unit
• Noise
• Defective remote control
• Faulty indoor control PCB
Note:If the indoor unit cannot communicate normally with the remote control for 180 seconds, the indoor unit PCB starts to reset
automatically.
- 76 -
'14 • PAC-SM-215
YES
2. Error detection method Note (2) Check for faulty connection or breakage of
Is the signal wires between indoor-outdoor units.
When normal communication connection of signal
wires between indoor-outdoor NO Repair signal wires.
between indoor and outdoor
units OK?
unit is interrupted for more than
2 minutes. YES
Power reset
Note: Pressing the pump-down switch cancels communications between indoor and outdoor unit so that “communication
error-E5” is displayed on indoor unit and remote control, but it is normal.
- 77 -
'14 • PAC-SM-215
Is the
connection of indoor heat
exchanger temperature thermistor NO Correct. ª Insert connector
connector OK? securely.
YES
(Short circuit)
0 10 20 30 40 50
4. Presumable cause Temperature (°C)
Note:
- 78 -
'14 • PAC-SM-215
Is the
connection of return
air temperature thermistor NO Correct. ª Connect
connector OK? connector.
YES
5k at 25°C
5
4. Presumable cause
(Short circuit)
0 10 20 30 40 50
• Defective return air
temperature thermistor Temperature (°C)
connector
• Defective return air
temperature thermistor
• Faulty indoor control PCB
Note:
- 79 -
'14 • PAC-SM-215
YES Wash.
YES
Is the unit
operating in the state of NO Check refrigerant system.
heating overload?
3. Condition of Error displayed
Note: During heating operation; After starting compressor, compressor rotation speed is decreased by detecting indoor heat
exchanger temperature (ThI-R) in order to control high pressure.
- 80 -
'14 • PAC-SM-215
Is DC12V
at CNI connector.
NO
YES Check float switch.
2. Error detection method
Is
there any
anomaly on the optional NO Defective indoor control
Is the humidifier connected? equipment? PCB ª Replace.
Is the
humidifier drain motor
interlocked by the indoor unit function NO Correct setting to
setting of remote
3. Condition of Error displayed control? NO “Humidifier drain motor
interlock”.
If the float switch OPEN YES
is detected for 3 seconds
continuously or if float
switch connector or wire is Drain motor ON from the remote control
disconnected.
Is
Does drain motor DC12V (FDTC:AC220/240V)
NO
detected at CNR connector? NO Defective indoor control
operate?
PCB ª Replace.
(Replace power PCB on
FDTC series.)
YES
YES Check wiring of drain
4. Presumable cause motor
Note: When this error occurred at power ON, disconnection of wire or connector of the float switch is suspected. Check and
correct it (or replace it, if necessary).
- 81 -
'14 • PAC-SM-215
Same as above
4. Presumable cause
Note:
- 82 -
'14 • PAC-SM-215
E11 occurs
Is “Master IU
address set” function of remote
2. Error detection method control used?
IU IU IU
R/C
Same as above
4. Presumable cause
Same as above
Note:
- 83 -
'14 • PAC-SM-215
Is it
OK the unit
address setting for master NO Correct unit address setting.
and slave indoor
units?
YES
Isn’t
the remote
control wiring between YES Correct wiring.
2. Error detection method indoor units
defective?
Note (1) Set dip switches SW5-1 and SW5-2 as shown in the following table.
(Factory default setting – “Master”)
3. Condition of Error displayed
Indoor unit
Same as above Master Slave-a Slave-b Slave-c
Dip SW5-1 OFF OFF ON ON
switch SW5-2 OFF ON OFF ON
4. Presumable cause
Note:
- 84 -
'14 • PAC-SM-215
Does any
foreign material
intervene in rotational area YES Remove foreign material.
of fan propeller?
NO
YES
YES Replace faulty fan motor
and power PCB.
Note(3) FDT:F3, FDTCFDF:F202
3. Condition of Error displayed FDU:F1,F2FDUM:F3,F4
ޓޓޓ
(4)
Is DC280V
When actual rotation speed of detected between 㽷㪄㽵㩷of
indoor fan motor drops to lower motor control PCB connector NO Replace harness assy
than 200min-1 for 30 seconds CNM? between motor PCB and
continuously, the compressor power PCB.
and the indoor fan motor Note(4) FDU(FM1) only.
stop. After 2-seconds, it starts YES
again automatically, but if this
error occurs 4 times within
60 minutes after the initial Power source reset
detection.
Note(4) Value in ( ) are for the
model FDU(FM1).
Is it normalized? (4)
4. Presumable cause (Is DC280V detected between Replace fan motor.
㽷㪄㽵㩷of㩷motor control PCB NO 〔If the error persists after
connector CNM? ) replacing the fan motor,
• Defective indoor power PCB
• Foreign material at rotational replace the indoor control
area of fan propeller PCB (FDU : Motor contrl
• Defective fan motor PCB)〕
• Dust on control PCB
• Blown fuse
YES Malfunction by temporary
• External noise, surge noise.
Note:
- 85 -
'14 • PAC-SM-215
E18 occurs
Is
“Master indoor unit
address set” function of remote
2. Error detection method control used?
Same as above
4. Presumable cause
Same as above
Note:
- 86 -
'14 • PAC-SM-215
E19 occurs
when the power ON
Same as above
4. Presumable cause
Note:
- 87 -
'14 • PAC-SM-215
Does any
foreign material
intervene in rotational area YES Remove foreign material.
of fan propeller?
NO
YES
YES Replace faulty fan motor
and power PCB.
Note(3) FDT:F3, FDTCFDF:F202
3. Condition of Error displayed FDU:F1,F2FDUM:F3,F4
ޓޓޓ
(4)
When the actual fan rotation Is DC280V
detected between 㽷㪄㽵㩷of
speed does not reach to the motor control PCB connector NO Replace harness assy
speed of [required speed CNM? between motor PCB and
-50min-1(FDU : -500min-1)] after power PCB.
2 minutes have been elapsed Note(4) FDU(FM1) only.
since the fan motor rotation YES
speed command was output, the
unit stops by detecting indoor
fan motor anomaly. Power source reset
Note:
- 88 -
'14 • PAC-SM-215
NO
Does
matter improve if panel
2. Error detection method switch is turned ON forcibly YES Insufficient push on the
after resetting <Forced panel switch ON> panel switch at the internal
error? Put the switch in the state of face of grill
Panel switch (PS) has detected
Open for more than 1 second.
ON by fixing the silicone ªAttach 3 mm thick
NO section of panel switch with rubber sheet at the section
adhesive tape while it is held
down. where the panel switch
touches the inside of grill.
Close then the grill.
YES
Panel switch
4. Presumable cause
Note:
- 89 -
'14 • PAC-SM-215
Note: After 10 seconds has passed since remote control thermistor was switched from valid to invalid, E28 will not be displayed even if the thermistor
harness is disconnected. At same time the thermistor, which is effective, is switched from remote control thermistor to indoor return air
temperature thermistor. Even though the remote control thermistor is set to be Effective, the return air temperature displayed on remote control for
checking still shows the value detected by indoor return air temperature thermistor, not by remote control temperature thermistor.
- 90 -
'14 • PAC-SM-215
YES
Is
the temperature
(measured actually) at NO Defective outdoor control
3. Condition of Error displayed detection of error PCBªReplace.
correct?
4. Presumable cause
Note:
- 91 -
'14 • PAC-SM-215
YES
Is the
discharge pipe
2. Error detection method temperature error persisted
during cooling
YES Insufficient refrigerant
operation?
amount : Recharge
refrigerant by weighing
For the error detection method, proper amount on a scale.
refer to the protective control by
controlling compressor rotation NO
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models. Is the
discharge pipe temperature NO Control operation check *
control normal?
YES
Is the
temperature (measured
actually) at detection of NO Defective outdoor control
3. Condition of Error displayed error correct? PCBªReplace.
Note:
- 92 -
'14 • PAC-SM-215
Is the
outdoor heat
exchanger temperature
thermistor connector NO Correct connector.
connected
properly?
YES
2. Error detection method
For the characteristics of outdoor heat exchanger
Detection of anomalously low temperature thermistor, see the following graph.
temperature (resistance) on Are the
characteristics of
the outdoor heat exchanger outdoor heat exchanger
temperature thermistor temperature
NO Defective outdoor heat
thermistor exchanger temperature
OK? thermistorªReplace.
(Short circuit)
0 10 20 30 40 50
4. Presumable cause Temperature (°C)
Note:
- 93 -
'14 • PAC-SM-215
Is
the outdoor air
temperature thermistor connector NO Correct connector.
connected properly?
YES
For the characteristics of outdoor air
Is the temperature thermistor, see the following graph.
Defective outdoor air
2. Error detection method characteristics of the
outdoor air temperature NO temperature thermistorª
thermistor Replace.
Detection of anomalously OK?
low temperature (resistance)
on outdoor air temperature YES Defective outdoor control
thermistor PCBªReplace.
Temperature-resistance characteristics (Defective outdoor air
(Broken wire) 35 temperature thermistor
input circuit)
Temperature thermistor resistance (k)
30
25
20
4. Presumable cause
• Defective outdoor control
PCB
• Broken thermistor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
- 94 -
'14 • PAC-SM-215
Is the
discharge pipe
temperature thermistor NO Correct connector.
connector connected
properly?
YES
100200 10
180
〔T 80 〕
温度センサ抵抗
〔T 80 〕 160
温度センサ抵抗
T 80
140 T 80
120
50100 5
3. Condition of Error displayed 80
(k) 60 (k)
When the temperature thermistor 40
detects -10°C or lower for 5
seconds continuously within 20
10 minutes to 10 minutes 20 0 0 0
0 0 20 40
50 60 80 80 100100 120 140 160
seconds after the compressor
ON, the compressor stops. After
(Short circuit)
温 Temperature
度〔T〕 ((°C)
)
3-minutes delay, the compressor
starts again automatically, but
if this anomalous temperature
is detected 3 times within 40
minutes.
4. Presumable cause
• Defective outdoor control
PCB
• Broken thermistor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
- 95 -
'14 • PAC-SM-215
Is the
service valve fully NO Open service valve.
opened?
Compressor ON
On operation YES
of 63H1
Note: In the protective control range for compressor startup (initial startup after power ON), even if 63H1 is activated only once
(63H1turns OFF), immediately the error is displayed.
- 96 -
'14 • PAC-SM-215
Is it possible to
reset the error for 10 minuted after NO
NOReplace inverter PCB
compressor stopped?
YES
Can error be reset? YES OK
Is the fixing
of power transistor to radiator fin OK?
・Fixed screw NO Fix properly.
・Application of radiating
silicone
YES
3. Condition of Error displayed Does the error recur? YES Defective inverter PCBª
Replace
Anomalously high temperature NO OK
of power transistor is detected 5
times within 60 minutes.
4. Presumable cause
Note:
- 97 -
'14 • PAC-SM-215
Is the
Power source NO Check power source.
voltage OK?
YES
Are the
2. Error detection method service valves NO Open the valves.
opened?
In order to prevent from
overcurrent of inverter,
if the current exceeds the YES Check refrigerant amount
specifications, it makes the and refregerant circuit
compressor stopping. *In case of transitional
Is the increase of high pressure
high pressure
during operation
NO and/or test run, several
OK? times restarting may
recover it, because liquid
YES refrigerant (migrated)
in the compresser is
discharged from the
Is the compressor.
checked result of
insulation resistance and Replace compressor.
coil resistance (1) of NO
compressor motor
OK? (1) 1.172 or more at 20°C (Model FDC200)
3. Condition of Error displayed 0.309 or more at 20°C (Model FDC250)
YES
• If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
• After 3-minute delay, the To next page.
compressor restarts, but if this
amonaly occurs 4 times within
30 minute after the intial
detection.
4. Presumable cause
Note:
- 98 -
'14 • PAC-SM-215
Is the
checked result of power NO Defective inverter PCBª
transistor module
OK? Replace.
*Replace also the power
transistor module.
2. Error detection method YES
(250 model)
In order to prevent from • Is the space for installation of indoor and/or outdoor unit enough?
• Is there any short circuit of air on indoor and/or outdoor unit?
overcurrent of inverter, • At cooling, does the outdoor fan motor run?
if the current exceeds the Are the service valves fully opened?
specifications, it makes the Is the filter clogged?
compressor stopping. • At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• Is there any liquid flooding?
Is the superheat within normal range?
Is the low pressure sensor and suction pipe temperature
thermistor normal?
• Is there any anoumalous sound on the compressor?
YES
After
resetting power for
3. Condition of Error displayed several times does it NO Defective inverter PCBª
become normal? Replace.
*Replace also the power
• If the output current of inveter transistor module.
exceeds the specifications, YES
it makes the compressor
stopping.
• After 3-minute delay, the Temporary noise may cause of anomaly.
compressor restarts, but if this If noise source can be found, take countermeasure.
amonaly occurs 4 times within
30 minute after the intial
detection.
4. Presumable cause
Note:
- 99 -
'14 • PAC-SM-215
Is the
connection of connectors between
the inverter PCB and the outdoor NO Correct the connection.
control PCB OK?
YES
Are both
switches of JSW10,11
2. Error detection method on the inverter PCB NO Set JSW10, 11 correctly
set correctly? ⇒ See page from54.
When the communication
between inverter PCB YES No power is supplied to
and outdoor control PCB inverter PCB.
is not established. Check the power source
Is LED voltage and correct it
on the inverter PCB NO If not solved, find the
flashing? cause by checking
following points.
• Fan motor anomaly
YES
• 52X anomaly
• Broken cement resistor
(15Ω)
Is the
communication wire between the
inverter PCB and the outdoor control NO Connect the
PCB connected properly? communication wire
securely
3. Condition of Error displayed YES
YES OK
4. Presumable cause
Note:
- 100 -
'14 • PAC-SM-215
NO
Does the
2. Error detection method fan rotate smoothly when turned NO Replace fan motor.
by hand? If resistance between
Detected by rotation speed of (Vm):red -(GND):blue is
outdoor fan motor detected 1kΩ or lower, it is
faulty.
YES
Is DC280V
detected between (CNFAN
(red)- (blue)) of fan motor NO
connector?
3. Condition of Error displayed Power source reset YES Replace faulty fan motor
and control PCB.
When actual rotation speed
of outdoor fan motor (FMo1)
drops to 100min-1 or lower
for 30 minutes continuously, Is normal state restored? NO Replace fan motor (If
the compressor and the anomaly persists after
outdoor fan motor stop. After replacing fan motor, replace
3-minutes delay, it starts control PCB.)
again automatically, but if this
anomaly occurs 5 times within
60 minutes after the initial YES Malfunction by temporary
detection. noise
4. Presumable cause
Note: When E48 error occurs, in almost cases F2 fuse (4A) on the outdoor control PCB is blown. There are a lot of cases that fuse is blown and E48
occurs due to defective fan motor. And even though only the outdoor control PCB ( or fuse) is replaced,, another trouble (*1) could occur.
Therefore when fuse is blown, check whether the fan motor is OK or not.
After confirming the fan motor normal, check by power ON. (Don't power ON without confirming the fan motor normal.)
*1 The error which does not seem to relate E48 may occur like as “ WAIT ”, Stay OFF of LED on outdoor control PCB, inverter
communication error (E45) and etc.
- 101 -
'14 • PAC-SM-215
Is the low
pressure sensor connection OK NO Correct.
2. Error detection method (at PCB side)?
YES
Detected by low pressure drop
and suction superheat
Check the low pressure value during
following state from the remote control
Compressor is stopping
Compressor is operating
Note: * Connect the gauge manifold to the service valve check joint during cooling, or connect it to the check joint at internal
piping of outdoor unit during heating.
- 102 -
'14 • PAC-SM-215
YES
Are the
connections of low
pressure sensor and suction pipe NO Correct.
temprerature thermister
3. Condition of Error displayed connector OK?
YES
Are the
characteristics of
low pressure sensor, suction NO Defective low pressure
pipe temperature sensor, suction pipe
thermistor OK?
temperature thermistorª
Replace.
YES
Is the low
pressure normal during NO Charge refrigerant.
operation?
4. Presumable cause
Note:
- 103 -
'14 • PAC-SM-215
Same as above
4. Presumable cause
Note:
- 104 -
'14 • PAC-SM-215
Are the
characteristics of suction pipe
NO Defective suction pipe
temperature thermistor OK?
temperature thermistorª
Replace.
4. Presumable cause
5k at 25°C
5
• Defective suction pipe
temperature thermistor
connection
• Defective suction pipe (Short circuit)
temperature thermistor 0 10 20 30 40 50
• Defective outdoor control Temperature (°C)
PCB
Note:
- 105 -
'14 • PAC-SM-215
Are the
connection of low pressure
sensor connectors (at sensor side NO Correct low pressure sensor
and PCB side) OK? connector connection.
YES
Are the
2. Error detection method pressure (actual
measurement) matched with the value Is refrigerant amount
YES
indicated on the remote charged properly?
control?
When anomalous voltage Is there any anomaly on the
(pressure) is detected refrigeration circuit?
NO
Is
3. Condition of Error displayed
normal condition NO Defective outdoor control
restored? PCBªReplace.
If the pressure sensor detects 0V (Defective low pressure
or lower and 4.0V or higher for sensor input circuit)
5 seconds continuously within YES OK
2 minutes to 2 minutes 20
seconds after compressor ON,
the compressor stops. When
the compressor is restarted
automatically after 3-minuts
delay, if this anomaly occurs 3
times within 40 minutes
4. Presumable cause
Note:
- 106 -
'14 • PAC-SM-215
Is the
connection of
under dome temperature NO Correct connection of
thermistor connector under dome temperature
OK?
thermistor connector.
YES
Are the
2. Error detection method characteristics of
under dome temperature NO Defective under dome
thermistor OK? temperature thermistorª
When anoumalous low Replace.
temperature (resistance) is
detected by the compressor
under dome temperature
thermistor
Temperature-resistance characteristics
(Broken wire)
15
Temperature thermistor resistance (k)
4. Presumable cause
Note:
- 107 -
'14 • PAC-SM-215
Is the
service valve fully NO Open fully.
opened?
YES
Are the
connections of indoor
heat exchanger and/or return air NO Correct indoor heat
2. Error detection method temperature thermistor
exchanger, return air
connectors OK?
temperature thermistor
• Judge insufficient refrigerant connector connections.
amount by detecting the YES
temperature differnce between
indoor heat exchanger (ThI-R) Are the
and indoor return air (ThI-A). characteristics of indoor heat
• It detects at initial startup in exchanger and/or return air NO Defective indoor heat
cooling or dehumidifying temperature thermistor exchanger, return air
OK? temperature thermistor ª
mode after power ON.
Replace.
YES
Is the low
pressure during operation NO Charge refrigerant.
normal?
15
Temperature thermistor resistance (k)
10
Note: Insufficient refrigerant amount preventive control makes compressor stopped, if it judges insufficient refrigerant amount by detecting the
temperature difference between indoor heat exchanger (ThI-R) and return air temperature (ThI-A) for 1 minute after compressor ON in
cooling or dehumidifying mode and for 9 minutes after compressor ON in heating mode. [ in cooling mode: (ThI-A)-(ThI-R)>4degC, in
heating mode: (ThI-R)-(ThI-A)<4degC]
- 108 -
'14 • PAC-SM-215
Is
power source voltage NO Check the power source
OK? voltage and correct it
YES
2. Error detection method
Is the
When it fails to change over to pressure equalized NO Check refrigerant amount
the operation for rotor position at starting OK?
and refrigerant circuit.
detection of compressor motor
(If the compressor speed cannot YES
increase 11rps or higher)
Is the
insulation resistance
and coil resistance of NO Replace compressor
compressor OK?
YES
To next page
4. Presumable cause
- 109 -
'14 • PAC-SM-215
YES
YES
Is the
inverter output OK?
(Check by inverter NO Replace inverter PCB
checker) *Replace power transistor
Note(1) Several times restarting as well.
may recover it, because liquid
refrigerant migrated in the
YES compressor could be discharged
from the compressor.
4. Presumable cause
Note:
- 110 -