General Terminal Boards (for FIO)


Specifications
GS 33J60H50-01EN

[Release 6]

n GENERAL
This document describes the specifications of terminal boards used for FIOs of CENTUM VP systems.

n STANDARD SPECIFICATIONS
Modules Connection
Model Description Points Terminals Weight Specifications
Connected Cable
For 2-wire Transmitter AAI135
Approx.
AEA3D (for single or dual redundant 8 pts x 4 M4 screws AAI835 KS1
1.8 kg
modules) AAP135
AAI135
8 pts x 2 M4 screws AAI835
AAP135
AAI141
AAV141
For analog signals AAV142 Approx.
AEA4D (for single or dual redundant AAV144 KS1
1.5 kg
modules) AAB841
16 pts x 2 M4 screws
AAI841
AAV542
AAV544
AAI143 Insulation resistance: 100
AAI543 MΩ or greater at 500 V DC
For thermocouple
Approx. Withstanding voltage: 500
AET4D (for single or dual redundant 16 pts x 2 M4 screws AAT145 KS1
1.8 kg V AC for 1 minute
modules)
ADV151
AKB331
ADV551
For digital signals
ADV161 Approx.
AED5D (for single or dual redundant 32 pts x 1 M4 screws
(*1) 1.5 kg
modules) AKB337
ADV561
(*1)
For fieldbus
Approx.
AEF9D (for single or dual redundant 4 ports x 4 M4 screws ALF111 AKB336
1.8 kg
modules)
For resistance temperature Approx.
AER4D 16 pts M4 screws AAR145 AKB335
detectors 1.5 kg
For resistance temperature Approx.
MRT(*2) 16 pts x 2 M4 screws AAR145 KS8
detectors 1.8 kg

Note: Be sure to leave the connector caps on connectors that are not used, in order to protect the connector pins and prevent
dust from accumulating on them.
*1: Two sets of AED5D or AKB337 are required for one set of ADV161 or ADV561.
*2: For details on the MRT, see GS 33K55R40-50E.

Yokogawa Electric Corporation GS 33J60H50-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Feb. 2015 (YK)
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 5th Edition Apr. 26, 2017 (YK)
<<Contents>> <<Index>> 2
n EXTERNAL DIMENSIONS
l Terminal Boards
AEA3D
Unit: mm
(85) 482.6
18.4 66.6 8.75 465.1
34.6 21.3 440

57.15
132.5

37.7 Hole for 19-inch rack mounting


(4 M5 screw holes)

When option code is “/NTRY”

(53)
18.4 34.6

F01E.ai

Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined
nominaltolerance is ± 1.5 mm
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.
.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60H50-01EN Apr. 26, 2017-00
<<Contents>> <<Index>> 3
AEA4D, AET4D
Unit: mm
(85) 482.6
18.4 66.6 8.75 465.1
34.6 21.3 440

88.1

37.7 Hole for 19-inch rack mounting


(2 M5 screw holes)
When option code is “/NTRY”
(53)
18.4 34.6

F02E.ai

Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined
nominaltolerance is ± 1.5 mm
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.in accordance with JEM 1459.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60H50-01EN Apr. 26, 2017-00
<<Contents>> <<Index>> 4
AED5D
Unit: mm
(85) 482.6
18.4 66.6 8.75 465.1
34.6 21.3 440

88.1

37.7 Hole for 19-inch rack mounting


(2 M5 screw holes)

When option code is “/NTRY”


(53)

18.4 34.6

F03E.ai

Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined
nominaltolerance is ± 1.5 mm
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.in accordance with JEM 1459.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60H50-01EN Apr. 26, 2017-00
<<Contents>> <<Index>> 5
AER4D
Unit: mm
(85) 482.6
18.4 66.6 8.75 465.1
34.6 21.3 440

88.1

37.7 Hole for 19-inch rack mounting


(2 M5 screw holes)
When option code is “/NTRY”
(53)

18.4 34.6

F05E.ai

Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined
nominaltolerance is ± 1.5 mm
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.in accordance with JEM 1459.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60H50-01EN Apr. 26, 2017-00
<<Contents>> <<Index>> 6
AEF9D
Unit: mm
(85) 482.6
18.4 66.6 8.75 465.1
34.6 21.3 440

57.15
132.5

37.7 Hole for 19-inch rack mounting


(4 M5 screw holes)

When option code is “/NTRY”


(53)

18.4 34.6

F06E.ai

Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined
nominaltolerance is ± 1.5 mm
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.in accordance with JEM 1459.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60H50-01EN Apr. 26, 2017-00
<<Contents>> <<Index>> 7
n MODELS AND SUFFIX CODES
Terminal Board for Analog Terminal Board for Digital (single and
(single and dual-redundant) dual-redundant)
Description Description
Terminal Board for Analog Terminal Board for Digital
Model AEA3D (single and dual-redundant, Model AED5D (single and dual-redundant,
8-channel) 32-channel)
-0 Without surge absorber -0 Without surge absorber
Basic type with no explosion Basic type with no explosion
5 5
protection protection
Suffix With ISA Standard G3 option and no Suffix With ISA Standard G3 option and no
6 6
Codes explosion protection Codes explosion protection
E Basic type with explosion protection E Basic type with explosion protection
With ISA Standard G3 option and With ISA Standard G3 option and
F F
explosion protection explosion protection
Option Option
/NTRY Without cable tray /NTRY Without cable tray
Code Code

Note: When the AED5D is used in voltage output mode,


Terminal Board for Analog it does not conform to Non-Incendive standard.
(single and dual-redundant)
Terminal Board for Resistance Temperature
Description Detectors (single and dual-redundant)
Terminal Board for Analog
Description
Model AEA4D (single and dual-redundant,
16-channel) Terminal Board for resistance
temperature detectors
-0 Without surge absorber Model AER4D
(single and dual-redundant,
Basic type with no explosion 16-channel)
5
protection
-0 Without surge absorber
Suffix With ISA Standard G3 option and no
6 Basic type with no explosion
Codes explosion protection 5
protection
E Basic type with explosion protection
Suffix With ISA Standard G3 option and no
With ISA Standard G3 option and 6
F Codes explosion protection
explosion protection
E Basic type with explosion protection
Option
/NTRY Without cable tray With ISA Standard G3 option and
Code F
explosion protection
Option
Terminal Board for Thermocouple /NTRY Without cable tray
Code
(single and dual-redundant)
Description Terminal Board for Fieldbus
Terminal Board for Thermocouple
(single and dual-redundant)
Model AET4D (single and dual-redundant,
Description
16-channel)
Terminal Board for Fieldbus
-0 Without surge absorber Model AEF9D
(single and dual-redundant)
Basic type with no explosion
5 -0 Without surge absorber
protection
Basic type with no explosion
Suffix With ISA Standard G3 option and no 5
6 protection
Codes explosion protection
Suffix With ISA Standard G3 option and no
E Basic type with explosion protection 6
Codes explosion protection
With ISA Standard G3 option and
F E Basic type with explosion protection
explosion protection
With ISA Standard G3 option and
Option F
/NTRY Without cable tray explosion protection
Code
Option
/NTRY Without cable tray
Code

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60H50-01EN Apr. 26, 2017-00
<<Contents>> <<Index>> 8
n APPLICABLE STANDARDS
Refer to the GS "Integrated Production Control System
CENTUM VP System Overview (GS 33J01A10-01EN)."

n ORDERING INFORMATION
Specify models and suffix codes when ordering.
For selecting the right products for explosion protection,
please refer to TI 33Q01J30-01E without fail.

n TRADEMARK
• CENTUM is a registered trademark of Yokogawa
Electric Corporation.
• Other company names and product names in this
document are registered trademarks or trademarks of
their respective holders.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60H50-01EN Apr. 26, 2017-00
Subject to change without notice.