Breaker / Starter Easy Selection

Motor Power
Sr Equipment Min TPN MCCB Rating Starting Method
Rating(kW) Source
(A)
1 0.37 400/3/50 EAF/FAF 20 DOL
2 0.55 400/3/50 20 DOL
3 0.75 400/3/50 20 DOL
4 1 400/3/50 20 DOL
5 1.1 400/3/50 20 DOL
6 1.7 400/3/50 20 DOL
7 2.2 400/3/50 FAF 20 DOL
8 3 400/3/50 20 SD
9 4 400/3/50 FAF/EAF 30 SD
10 4.5 400/3/50 30 SD
11 5.5 400/3/50 30 SD
12 6.3 400/3/50 30 SD
13 7.5 400/3/50 FAF 30 SD/VSD
14 11 400/3/50 FAF 63 SD
15 15 400/3/50 63 SD
16 22 400/3/50 FAF 30 VSD
17 23 400/3/50 FAF 80 SD
18 30 400/3/50 EAF/FAF/AHU 80 SD / VSD
19 40 400/3/50 125 VSD
20 45 400/3/50 150 VSD
21 50 400/3/50 AHU 150 VSD
22 60 400/3/50 150 VSD
23 75 400/3/50 200 VSD
24 160 400/3/50 CHW pump 300 VSD

Remark - All AHU starter should be VSD


Minimum Out Going Cablee Size
No Of Spares
4 x 4 sq mm/ 1 C PVC+ 4 sqmm CPC in Trunking

3 x 10 sq mm/ 1 C PVC+ 10 sqmm CPC in Trunking


3 x 4 sq mm/ 1 C PVC+ 4 sqmm CPC in Trunking

4 x 4 sq mm/ 1 C PVC+ 4 sqmm CPC in Trunking

4 x 10 sq mm/ 1 C PVC+ 10 sqmm CPC in Trunking 1 x20 A TPN MCCB

4 x 10 sq mm/ 1 C PVC+ 10 sqmm CPC in Trunking


3 x 6 sq mm/ 1 C FR+ 6 sqmm CPC in Trunking
4 x 6 sq mm/ 1 C FR+ 6 sqmm CPC in Trunking
4 x 10 sq mm/ 1 C PVC+ 10 sqmm CPC in Trunking
6 x 25 sq mm/ 1 C PVC+ 16 sq mm CPC In Trunking
4 x 70sq mm/ 1 C FR+ 35 sqmm CPC in Trunking
4x 35 sq mm/ 1 C PVC +16 sq mm CPC in Trunking
3 x 35 sq mm/ 1 C FR+ 16 sqmm CPC in Trunking
3 x 50 sq mm/ 1 C FR+ 25 sqmm CPC in Trunking
4 x 70sq mm/ 1 C FR+ 35 sqmm CPC in Trunking
4 x 70sq mm/ 1 C FR+ 35 sqmm CPC in Trunking
3 x 70sq mm/ 1 C FR+ 35 sqmm CPC in Trunking
4 x 95sq mm/ 1 C FR+ 50 sqmm CPC in Trunking
4 x 150sq mm/ 1 C XLPE / PVC + 95 sqmm CPC in Trunking CHW pump