Sie sind auf Seite 1von 3

19th IEEE International Conference on Dielectric Liquids (ICDL), Manchester, United Kingdom, 25 – 29 June, 2017

Compatibility of Mineral Insulating Oil with


Transformer Construction Materials
Nataša Bernard Biljana ýuþek
Physical - Chemical Transformer Diagnostics Department Physical - Chemical Transformer Diagnostics Department
Milan Vidmar Electric Power Research Institute Milan Vidmar Electric Power Research Institute
Ljubljana, Slovenia Ljubljana, Slovenia

Abstract — This study is focused on the determining the standards: new oils in IEC 60296 [1], and used oils in IEC
compatibility of mineral insulating oil with various transformer 60422 [2]. These standards also provide some
materials obtained from transformer manufacturers. For this recommendations regarding the importance of various oil
study, traditional chemical methods, in accordance with the properties. Therefore, the introduction of new construction
requirements of the IEC 60422 standard (See Table 3), were materials requires compatibility confirmation which can be
applied. The effects of the various transformer materials - such obtained according to the ASTM D3455-11 standard [3].
as epoxide, polyurethane, cyanoacrylate, polyvinyl alcohol (PVA)
adhesives and an epoxy reinforcing bar on the oil's properties
were determined. The findings were evaluated by means of the II. MATERIALS
sensitivity of individual methods to any changes in the oil’s The compatibility of some construction transformer
properties caused by the transformer materials. Furthermore, materials and the oil was studied. According to the
the oil's properties were evaluated according to the requirements manufacturer’s data referring to Table I, the specimens
of the ASTM D3455-11 standard, and some tested materials were numbered 1, 3 and 5 are cyanoacrylate adhesives, consisting of
excluded. cyanoacrylate monomer as their main ingredient. Specimen 2 is
a water-based solution of vinyl alcohol. Specimens 6 and 7 are
The aim of the study was to reveal which materials are most
compatible with the oil. This insight could be of great interest to polyurethane adhesives. Specimens 4 and 8 are epoxides.
transformer manufacturers, as it was shown that some materials Specimen 4 is a 2-component epoxy adhesive, and Specimen 8
could considerably affect the oil's properties. is an epoxy- reinforcing bar – composite made of epoxy
adhesive and glass fibers.
Keywords - compatibility; transformer oil; adhesives; acidity; IR
spectroscopy, oil interfacial tension III. TEST METHODS
The following test methods adopted from the ASTM
I. INTRODUSCTIN D3455-11 standard [3], were applied in this study: acidity (A),
Mineral insulating oil (hereafter oil) is a vital part of any interfacial tension (B) and colour (D). The determination of
liquid-filled transformer, due to its insulating and cooling dielectric dissipation factor (tan į) was omitted as it has been
properties. The condition of this oil reflects a transformer’s shown that it is complementary with interfacial tension, but
fitness of use. less sensitive [4]. On the other hand the IR spectroscopy (C)
was added as identification of chemical species in oil seemed
During the service life of a transformer, oil ages - degrading to be of crucial importance for this study.
to the point where it needs to be replaced. To prolong the
service life of these oils, some chemical species - inhibitors are A. Acidity
used. With age, the oil is subject to decomposition. The main
On the other hand, the aging of an oil can be accelerated by decomposition mechanism is oxidation, through which various
contact with and contamination by various transformer acidic products are formed. These products can be divided into
construction materials, such as: organic adhesives, sealing soluble and volatile acids. Aged oil from transformers contains
rubber, paper etc. Also, some new construction materials such only soluble acids, while in artificially aged oils, both soluble
as various organic adhesives (e.g. epoxides), have recently and volatile acids are present. Acids affect not only the
been introduced as transformer construction materials. dielectric properties of the oil, but can also contribute to the
Therefore, such materials and noncorrosive oil should be degradation of cellulosic materials and to the corrosion of
mutually compatible, exhibiting adequate chemically resistance metal parts in a transformer. The acidity was determined with
to each other. potentiometric titration of dissolved oil with 0.05 mol/l KOH.
Titration ran up to pH 11.5 and was controlled with a Metrohm
The contamination of oils is based on any electrical, combination glass pH electrode, pH 0–14./0–70 °C LiCl sat in
physical and chemical changes that take place. The EtOH.
requirements regarding oil properties are provided in IEC

1
978-1-5090-4877-9/17/$31.00 ©2017 IEEE
19th IEEE International Conference on Dielectric Liquids (ICDL), Manchester, United Kingdom, 25 – 29 June, 2017

B. Interfacial tension IV. EXPERIMENTAL WORK


The interfacial tension between the oil and water indicates The specimens consisted of 100 ml of inhibited oil with
the amount of soluble polar contaminants, and/or the properties according to requirements of IEC 60296 [1], in
degradation byproducts in the oil. The interfacial tension which various transformer materials (adhesives and a
decreases with when the polarity of the oil increases. The reinforcing bar), with surface areas ranging from 4.7 cm2 to 7
measure of interfacial tension was obtained using a digital cm2, were immersed. After that, the specimens in covered glass
tensiometer and was expressed as the force required to separate containers were conditioned for 10 days in a drying oven at 105
a planar ring of platinum wire from water in a layer of oil. °C. As a control specimen, a blank oil - inhibited oil was used.
The methods suggested by the IEC 60422 standard [2] (colour,
C. IR spectroscopy interfacial tension, acidity and inhibitor content) were used to
Infrared (IR) spectroscopy is often used for qualitative and monitor the chemical properties of the oil. Acidity was
quantitative analysis of the chemical species in various determined according to the IEC 62021-1, interfacial tension
materials. The procedure outlined in IEC 60666; method 3.2 according to the ASTM D971; ring method, and color with the
was applied in order to determine the content of the inhibitor Farbzahl nach VDEW-Ölbuch table [5]. Furthermore, the IR
and hydrocarbons (such as aromatics, naphthenes, and spectra of the specimens were obtained according to IEC
paraffins) in the oil. This method is highly sensitive, enabling 60666; method 3.2. The results of analysis of the specimens are
the detection of small quantities of soluble polar decomposition shown in Table I.
products at the very beginning of the oil aging process.
V. RESULTS AND DISCUSSION
Individual decomposition products have characteristic IR
absorption bands at specific wave numbers i.e. aldehydes and Below, the obtained analysis data (See Table I) is
ketones in-between 1690 cmí1 and 1710 cmí1, and carboxylic discussed. First with reference to the suitability of the methods
acids in-between 1720 cmí1 and 1750 cmí1. Examples of the used, then with reference to the compatibility of the
IR spectrums of new (˰a) and artificially aged (˰b) oils are construction materials with the oil.
presented in Fig. 1. The dotted area highlights the the The colour values of all the specimens were < 1, therefore
decomposition product bands. they did not differ from blank oil. The measurement
uncertainty of the method used is high i.e. ± 0.5 (k = 2),
suggesting that significant colour change would be higher than
grade 1 according to the VDEW-Olbuch table. It can be
concluded that the applied method was not sensitive enough to
allow meaningful comparison between the specimens.
Therefore, further analysis will be conducted using a
transmitted light analyzer (colorimeter), which has an
estimated uncertainty of ± 0.2, and the results will be published
elsewhere at a later stage.
The highest interfacial tension (45 mN/m) was obtained for
the Control specimen-the blank oil. The interfacial tensions of
the other specimens were lower, the lowest (14 mN/m) was
being obtained for Specimen 7 (oil + polyurethane adhesive).
The significance of these results is reinforced by their low
measurement uncertainty (± 2 mN/m (k = 2)). The reduction of
the interfacial tension of Specimens 6 and 7, compared to that
of the Control specimen was quite substantial. It can be
assumed that this reduction of the interfacial tension of the oil
originates from the polyurethane adhesive’s dissolved polar
molecules.
Figure 1. IR spectrums of uninhibited mineral oils [4].
The acidity of Specimen 8 was determined to be 0.03 mg
D. Colour KOH/ g oil, while the acidity of all other specimens was 0.01
The colour of the oil can be determined either with a mg KOH/ g oil. Considering the measurement uncertainty
transmitted light analyzer (colorimeter), or else visually by (± 0.01 mg KOH/ g oil (k=2)), no significant variations were
comparing the colour of the oil with the VDEW-Ölbuch table observed. It can be assumed that for low acidity conditions the
[5]. Colour is expressed with a numerical value. It is not an method applied here is not sensitive enough.
essential property for the evaluation of the oil’s fitness for use,
The inhibitor content of each specimen was determined
but rapidly increasing, or high, colour values may indicate
based on its characteristic IR band at 3650 cmí1 (See Fig. 2 a).
degradation or contamination of the oil [1]. For this paper the
All the Specimens had an inhibitor content of about 0.30 %
colour has been determined visually using the VDEW-Ölbuch
(m/m). The variations in the inhibitor content of the specimens
table [5] with 8 different colored foils of "Farbtafel" as colour
are insignificant as measurement uncertainty is ± 0.01 % (m/m)
number.

2
978-1-5090-4877-9/17/$31.00 ©2017 IEEE
19th IEEE International Conference on Dielectric Liquids (ICDL), Manchester, United Kingdom, 25 – 29 June, 2017

(k=2). Nevertheless, it can be observed that the inhibitor The compatibility of the specimens with the oil was
content of the specimens was not affected by the contaminants. estimated on the basis of methods relevant to the case study i.e.
interfacial tension and IR spectrometry. The findings of the
In the IR spectra of Specimen 8 IR band at 1744 cmí1 (See research are:
bordered area in Fig. 2 a) was observed. This corresponds to
C=O stretch characteristic for contamination or oil-aging The adhesives in Specimens 1 and 2 are compatible with
byproducts like ketones, aldehydes and carboxylic acids. It inhibited oil, as their chemical characteristics were not affected.
could indicate the early phase of oil degradation in Specimen 8
(Notea1). The adhesives in Specimens 3, 4 and 5 lowered the
interfacial tension of the oil moderately, but had no visible
impact on color, acidity or inhibitor content, and therefore are
conditionally compatible with inhibited oil.
Among the other studied materials, it seems that the
adhesives in Specimens 6 and 7 and the bar in specimen 8 are
the least compatible with inhibited oil. In these specimens the
interfacial tension of the oil was significantly reduced.
Additionally Specimen 8 showing a strong increase in the
acidity of the oil.

VI. CONCLUSIONS
The results suggest that cyanoacrylate and PVA adhesives
are the most compatible with inhibited mineral transformer oil.
Epoxy adhesives lowered the interfacial tension of the oil,
indicating that the epoxides are conditionally compatible with
the oil. Polyurethane adhesives and the epoxy bar significantly
lowered the interfacial tension of the oil. Additionally, the
epoxy bar increased the acidity of the oil. It can be concluded
that, according to the results of this study, polyurethane and
epoxy materials are the least compatible with transformer oil.
In this study, interfacial tension was shown to be the most
indicative measure for the estimation of a transformer
materials' compatibility, while on the other hand the colour
could be pointed out as the least indicative measure, when not
determined by a colorimeter.
Figure 2. IR spectrums of the specimens.
REFERENCES
Analysis data for the acidity, interfacial tension and colour [1] Mineral insulating oils in electrical equipment – Supervision and
of the inhibited oils are presented in Table 1. maintenance guidance, IEC 60422, Edition 4.0, January 2013.
TABLE I. CHEMICAL ANALYSIS RESULTS OF THE SPECIMENS OF [2] Fliuds for electrotechnical applications – Unused mineral insulating oils
INHIBITED OIL AFTER 10 DAYS OF CONDITIONING AT 105 °C IN THE PRESENCE for transformers and switchgear, IEC 60269, Edition 4.0, February 2012.
OF VARIOUS TRANSFORMER CONSTRUCTION MATERIALS. [3] Standard Test Methods for Compatibility of Construction Material with
Electrical Insulating Oil of Petroleum Origin, ASTM D3455-11, June
Acidity Interfacial Inhibitor 2011.
Colour
Specimen (mg KOH/ tension content
(-) [4] N. Bernard, and B. ýuþek, “Methods for monitoring age-related changes
g oil ) ( mN/m) (%(m/m))
in transformer oils”, IEEE 18th Int’l Conf. Dielectr. Liquids (ICDL),
Control specimen-blank oil 0.01 45 <1 0.30 Bled, Slovenia, pp.1-5, 2014.
1 [5] VDEW-Ölbuch, Band 1: Schmierstoffe und Steuerflüssigkeiten, VDEW,
(oil + cyanoacrylate adhesive)
0.01 44 <1 0.31
Frankfurt am Main 1996.
2
(oil + PVA adhesive)
0.01 43 <1 0.31
3
(oil + cyanoacrylate adhesive)
0.01 42 <1 0.31
4
(oil + epoxy adhesive)
0.01 38 <1 0.31
5
(oil + cyanoacrylate adhesive)
0.01 35 <1 0.31
6
(oil + polyurethane adhesive)
0.01 24 <1 0.30
7
(oil + polyurethane adhesive)
0.01 14 <1 0.30
8
(oil + epoxy bar)
0.03 36 <1 0.29
Note 1: The degradation products were qualitatively confirmed with IR spectroscopy for Specimen 8
only.

3
978-1-5090-4877-9/17/$31.00 ©2017 IEEE

Das könnte Ihnen auch gefallen