DIGITAL TEMPERATURE CONTROLLER Ambient pressure:86 kPa to 106 kPa。Ambient temperature:0 ℃ to 50 ℃.Ambient humidity:45% to 85%RH.

YLD- INSTRUCTION MANUAL (2) Following cautions must be kept in mind while mounting:

Rapid changes in ambient temperature, which may cause condensation.


2000 Corrosive or inflammable gases.

Before using this product, please carefully read this manual for its correct use. In addition, after reading the Direct vibration or shock to the mainframe.

manual, keep it available easily anytime. Water, oil, chemicals, vapor or steam splashes.

OPERATION PRECAUTIONS Excessive dust, salt or iron particles.

Before cleaning the instrument, check that the power is turned off. Excessive induction noise, static electricity, magnetic fields or noise.

Please using the soft clothes or tissue paper to remove stains on the display unit. Direct airflow from an air conditioner.

Because the display unit is easily scratched, please do not scrub or touch it with a hard object. Should be used indoors where the system is not exposed to direct sunlight.

Do not operate the front key with a pointed object such as a ballpoint pen or screwdriver, as this may scratch or Shanghai Yatai Address:No.1851 North Sichuan Road, Shanghai, China

damage the key. Instrumentation Co., Ltd. Tel:021-51053127 51053128 Fax : 086-021-51053123

Email:jiejieb@online.sh.cn Mail Code: 200081

1. PRODUCT CHECK 2.2 Principle technical performances


(1) Power supply voltage: 198 to 242 VAC(50/60Hz)(rated voltage 220VAC)
This instrument is applicable for constant temperature control for the electro thermal dryness, constant
(2) Power consume: less than 5VA
temperature water groove, germ cultivation, biochemistry cultivation and etc. This instrument can be also used in
(3) Control mode: Half proportional or on-off PID control
the temperature control of medicine appliances, laboratory apparatus and so on.
(4) The load power for heating output<=0.8KW
Check whether the delivered product is as specified by referring to the following model code list.
(5) The refrigeration output: Relay 240VAC,5A to drive the immediately switch
■ Model code
(6) The size of panel hole: 91×91(mm)
YL □-□□□□ □ □—□
(7)external thyristor(Max41A)(10)(11)(12)。
① ②③④⑤ ⑥ ⑦

1 Panel Dimensions(mm) ④ Type of refrigeration control

D:96×96 ;E:72×72 1: refrigeration control with time delayed function 3. WIRING


②Series code (used to control compressor)

③Type of heating control ⑤Type of the sensor Power supply

3: half proportional control 2: Thermo-resistance(RTD) ⑴


4: On-off PID control with auto tuning ⑥Calibration of the sensor Pt100 ⑵
heating device
⑦The range of measurement
YLD-2000 ⑶

2. MOUNTING ⑸

2.1 Mounting cautions ⑹

(1) This instrument is intended to be used under the following environmental condition ⑺
Pt100
⑻ input low limit(Display input Lange) Automatically turn over after 4 seconds displaying


Upper row displays process value, lower Automatically return over when not press any key over 1 minute

After pulling out it the buzzer will be open current, the sound will cease. row displays set value(Standard mode)

4. Configuration of the Instrument Panel


Press function key Upper row displays setting code (SP,St), lower row

displays set value(Update the setting mode )


①PV display unit(Red)

 Displays measured value or the various characters


Press function over 4 seconds Upper row displays function code (AL…), Lower row displays
depending the statue of the instrument
control parameters(Changing the control parameters)
②SV display unit(Green)
5.2 The detail description for every function
①  Displays the set value or the timing and rated parameters
 If upper row displays “OVER” the sensor is in open circuit or the input signal excesses the range of measurement.
③Indicators
The method for changing set value:
②  RUN working indicator(Green), Flashes during auto-tuning execution.
Press  /set key the upper row displays SP. Press or key the low row displays the needed
 HAT heating output indicator(Green), turned on when outputs operate
value. Again press  the upper row displays st key. Press  or key, the lower row displays the timing time
③  ALM alarming indicator(Red),
needed. Again press  key, the instrument return to the standard display mode.
turned on when alarming output operate and the buzzer sounds
Timing function
  COL refrigeration output(Green) turned on when the refrigeration is working
When the value of St is setting to zero, the timing function is canceled. Otherwise when the
④Function key
value of St is not setting to zero the timing function is available.
 Used for displaying the change and confirm of the parameters
When the power is turned on, the timing function starts . In case of achieving the setting timing the heating
⑤Add or Subtract key for changing the digital code
output is close. and the buzzer sounds four times to notice the operator.
④ ⑤ and/or the key to express entering the auto-tuning state
But the refrigeration output is working continuously. When the system is starting with auto tuning, the timing
. Used for adjusting the digital code displayed or entering the auto-tuning state.
function is also canceled. When the auto tuning process is completed, the
5. OPERATION timing function would start again. During the operating period of the instrument, it is allowed to update the

5.1 Sequence to pick up the functions of the instrument value of St online, and the time passed can be memorized and the instrument will operate the updated timing

time. When the updated time is less than the passed accumulative

Power on time, the heating output close immediately, the buzzer sounds 4 times. The refrigeration output is working

continuously.

Upper row displays code(Sn),lower Row The method for changing control parameter:

displays type No. (Display input type) After press key over 4 seconds, find LK. Then press  or key to the lower displayer display 18.Again
press the  key to find the symbol character for the needed parameter. Through press the  or key till the

Upper row: Input high limit, lower row high row displays display the parameter needed is reached. Some parameters may be setting at once. Press the

 key over 4 seconds the instrument returned to


the standard mode. If no key is press down the instrument return to its standard mode after 1 minute. constant which equals 1.5~2 times of the ratio of

5.3 The function of the controller Auto-tuning on time to the on-off period in the equilibrium

After pressing /TIME key, The instrument displays the time have operated.
Ar (re-setting) 0100% 100
state. In the half proportional control, the Ar

After pressing /AT key 20 seconds the AT indicator flashes and the auto-tuning press starts; after the end of equals coefficient/P.

auto-tuning the AT indicator then be turned out. A set of PID parameters can be got automatically for overcoming For the thyristor output it is about 13 seconds.
temperature overshoot. The controller operates according to this set of PID parameters. For those equipment that the superfluous power
is working continuously. heating period 1300 seconds provided is comparatively larger, select larger T 3
In the period of auto tuning, if press /AT key beyond 20 seconds the AT indicator turn out and the auto tuning
T would decrease the stable error caused by PID
process is canceled. The instrument operated according to the original PID parameters. control.
 Following table lists the function parameters When the zero error comparatively smaller and

Zero point adjust -100100 -100.0 the full point error comparatively larger, to
factory set 0
Symbol Name Setting range Description
value Pb (intersection) 100.0 update this value should be needed. Ordinary for

Pt100,updating this value is rarely needed.

When temperature is beyond SP+AL, the ALM 50 When the zero error comparatively larger and
0 Full Range
Alarming setting indicator turn on. The buzzer sounds and the the full point error also comparatively larger, to
AL 0.0Full Range
heating power turn off. (50.0) Full point adjust
-10001000 update this value should be needed.
0
(intercept) seconds PK=4000×setting value –actual value  /actual
When the temperature less than SP+COL, the PK
50 value. For Pt100 adjusting this value is need at
Refrigeration 0Full Range 0.0
refrigeration point is turn on to drive the
first time.
CL control setting Full Range
compressor. (50.0)
Refrigeration
When measuring value reaches its alarm value,
Proportional control action . if P is larger then 30 control Time 03600 seconds 60
1Full Range 1.0
Proportional Band the gain of system is lower. it only use on the Ct delayed
the alarm relay output will be delayed this time..
P Full Range
heating side. (30.0)
When D=0 the display resolving power is
The decimal Point
03600 0 1 1℃and when DP=1 the display resolving power 1
Integrated time constant. I larger, then the
Integral Time 240 dP setting
is 0.1℃
I seconds
integrated action is smaller.

0400℃ 0.0 Adjusting rH can make the instrument range


Derivative time constant. D larger, then the The range setting Range
derivative action is also larger. D can overcome
rH 99.9℃ equals 0rH(℃)
Derivative Time 03600 seconds 60
d overshoot. I=0 and D=0 is called half
when Lk=18 the parameters listed above then the
proportional control. Password key 0255 0
LK above parameters can be updated.
Overshoot Control At on-off PID control, the value of Ar is a