Sie sind auf Seite 1von 6

Olinda Star- Grounding Measurements / Readings 11/12/2018

No. Tag Description Location R (Ω) I (mA)

1 _ Fire pump Beside helideck, level below 1.388 0

2 _ Life boat panel - Stbd Below helideck 0.314 1.69

3 _ Life boat panel - Port Below helideck oo _

4 SB-402+DGE Electrical panel Emergency Generator Room 0.45 3.5

5 _ UPS Panel Emergency Generator Room 0.44 2.5

6 TR-402E Electrical Panel Emergency Generator Room 0.045 3.5

7 _ Emergency Generator Emergency Generator Room oo _

8 _ Battery charger panel Emergency Generator Room _ _

9 _ UPS Emergency Generator Room 0.45 30

10 SB-102 Emergency Distribution Panel 115V Emergency Generator Room 0.44 1.7

11 SB-114 Rectif. Battery charger panel 110Vcc Emergency Generator Room 0.054 0

12 _ Panel SCEPP Emergency Generator Room 0.225 15.7

13 SS-20 Control Panel Radio Room _ _

14 SB 220 E 220V Electrical Panel Radio Room - below 0.56 21

15 SB218 Navigation Light Panel Control Room next to Radio Room No access _

16 SB 21E Accommodation distribution panel L.2 Accommodation - Level 2 _ _

17 _ Uninterrupted system panel C.A Stairs on level 2 towards level 1 0.161 1.21

18 PL-EM-001 Distribution Panel C.A Stairs on level 2 towards level 1 0.148 13.5

19 SB-215 N Emergency panel Accommodation - level 1 0.51 12

20 SB-219 Electrical Panel Accommodation - level 1 0.046 0.54

21 _ Kitchen Distribution Panel 220VAC Kitchen 5.2 0.54

22 SB414N Laundry Emergency Shutdown Panel Accommodation - level 1 oo _

23 S-01 Dryer Laundry Room 0.1 1.1

24 S-02 Dryer Laundry Room 0.4 3.1

25 _ Test Panel 440V Electrical Workshop _ _

26 _ Transformer #3 600/480V SCR Room 0.053 0

27 SCR1 Recactor L01 SCR Room 0.205 2.1

28 SCR2 Recactor L02 SCR Room 1.78 0.38

29 _ Electrical cabinet (cubiculo 1) - 600V SCR Room 0.305 0.21

30 _ Control cubicle set panel SCR Room 0.305 0.21

31 _ Electrical cabinet (cubiculo 2) - 600V SCR Room 0.305 0.21

32 _ SCR PLC cubicle SCR Room 1.2 0.35

33 SCR4 Recactor L04 SCR Room 0.234 2.25

34 _ Transformer #1 600/480V SCR Room _ _

35 SB-401 Coluna 1A-9A set panel SCR Room 2.14 0.54

36 SB.418A "General Electric" set panel SCR Room _ _

37 SCR3 Reactor L03 SCR Room 0.24 2.14

38 SB-409N Coluna A-C set panel SCR Room 2.32 4.8

39 SB-409E Coluna A panel SCR Room 3.4 1.2

Page 1 of 6
Olinda Star- Grounding Measurements / Readings 11/12/2018

No. Tag Description Location R (Ω) I (mA)

40 SB-201N Coluna A-B set panel SCR Room _ _

41 SB-209N / SB211N Distribution Panel SCR Room _ _

42 SB-209E / SB-211E Distribution Panel SCR Room _ _

43 TR-201N Coluna A-D set panel SCR Room _ _

44 _ Aircon motor 01 SCR Room 0.204 0.517

45 _ SCR No.1 Aircon Panel SCR Room 0.044 3.2

46 SB-200 UPS Panel SCR Room 0.044 3.2

47 SB 101 Normal distribution set panel 115V SCR Room 4.56 11.12

48 5B 110 SCEPP Panel SCR Room 0.046 0

49 _ Aircon SCR's 1,2 and 3 distribution panel SCR Room 0.044 31

50 _ SCR No.2 Aircon Panel SCR Room 0.305 4.5

51 _ Aircon No.3 Panel SCR Room 0.102 2.45

52 _ Aircon No.3 Motor SCR Room 2.45 11

53 _ Booster Pump 1 Main Generator Room 2.54 0.7

54 _ Booster Pump 2 Main Generator Room 2.15 0.4

55 _ Pump near booster pump 1 and 2 Main Generator Room 0.95 3.4

56 _ Booster pump panel Main Generator Room 0.45 0.1

57 _ Auxiliary pump panel Main Generator Room 0.044 0

58 _ Auxiliary pump Main Generator Room _ _

59 _ Alpha Laval Skid 1 Main Generator Room 0.044 0.306

60 Alpha Laval Skid 2 Main Generator Room 0.056 0.206

61 SB 416 Emergency auxiliary diesel panel Main Generator Room 0.48 0

62 Pre lub panel Main Generator Room 0.045 3.5

63 SB 419N Water heating panel Low Compressor Room 0.044 0

64 SB-210N Electrical Panel Low Compressor Room 0.054 0

65 SB-210E Electrical Panel Low Compressor Room 0.048 0.4

66 Hot water panel 1 Low Compressor Room 3.34 0.2

67 Hot water panel 2 Low Compressor Room 2.45 0.3

68 Hot water panel 3 Low Compressor Room 4.25 0.4

69 D-50 Desalator D-50 Panel Low Compressor Room 5.45 0.8

70 Unidentified pump - Siemens Low Compressor Room 0.44 2.5

71 Low compressor unit 1 Low Compressor Room 6.54 0.8

72 Low compressor unit 2 Low Compressor Room 5.5 0.4

73 Low compressor unit 3 Low Compressor Room 4.8 0.6

74 Compressor motor 2 HVAC Room 0.05 35

75 Compressor motor 1 HVAC Room 0.086 19

76 Recirculation motor 1 HVAC Room _ _

77 Recirculation motor 2 HVAC Room 0.01 0.2

78 SB-410N Coluna 1-4 set panel HVAC Room 5.25 0.4

Page 2 of 6
Olinda Star- Grounding Measurements / Readings 11/12/2018

No. Tag Description Location R (Ω) I (mA)

79 SB 104 Electrical panel Corridor from "Coluna 3" to "Coluna 4" 0.045 20

80 SB-207N Electrical panel Corridor from "Coluna 3" to "Coluna 4" 0.044 1.2

81 SB-207E Electrical panel Corridor from "Coluna 3" to "Coluna 4" 0.046 0.5

82 SB-213E Electrical panel Corridor from "Coluna 3" to "Coluna 4" 0.048 0

83 SB-213N Electrical panel Corridor from "Coluna 3" to "Coluna 4" 0.056 2.4

84 SB 214N Electrical panel Corridor from "Coluna 3" to "Coluna 4" 0.42 3.5

85 SB 214E Electrical panel Corridor from "Coluna 3" to "Coluna 4" 0.45 4.2

86 SB.405N Electrical panel Corridor from "Coluna 3" to "Coluna 4" 1.4 5.2

87 SB 403N Mud Pump Panel Mud Pump Room 0.095 7.1

88 Base oil pump Mud Pump Room 4.8 18

89 Brine oil pump Mud Pump Room 6.54 1.4

90 SB-206E Electrical Panel Mud Pump Room 4.58 0.4

91 SB-206N Electrical Panel Mud Pump Room 3.5 0.3

92 SB-105N Electrical Panel Mud Pump Room 2.8 0.8

93 _ Mud pump #1 Mud Pump Room 0.117 12

94 _ Mud pump #2 Mud Pump Room 0.324 6.5

95 _ Mud pump #3 Mud Pump Room 0.07 11

96 _ Pump P3 Mud Pump Room 0.048 0.2

97 _ Pump P2 Mud Pump Room 0.052 0.5

98 _ Pump M2 Mud Pump Room 0.049 0.4

99 _ 440V Panel next to mud pump 3 Mud Pump Room 0.052 16.2

100 _ Mud pump console Mud Pump Room 0.049 12.8

101 _ Pump below stairs towards mud pit room Sack Store _ _

102 SB-411 Tank 1-7 Panel Riser Tool Store 5.42 2.8

103 _ HPU Pump starter panel 1 BOP Control Room 0.044 21.5

104 _ HPU Pump starter panel 2 BOP Control Room 0.044 4.2

105 _ HPU Pump 1 BOP Control Room 0.048 1.99

106 _ HPU Pump 2 BOP Control Room 0.048 9.57

107 _ Shimpo drive pump 1 BOP Control Room 0.049 2.5

108 _ Shimpo drive pump 2 BOP Control Room 0.048 3.8

109 _ Shimpo drive pump 3 BOP Control Room 0.051 1.4

110 SB 412 Mechanical Workshop Panel Mechanical workshop 0.048 0

111 _ Lathe Machine / Machine Panel Mechanical workshop 0.046 3.5

112 M-3002 Pump motor Mud Pit Room _ _

113 M-3001 Pump motor Mud Pit Room _ _

114 M-3004 Pump motor Mud Pit Room _ _

115 M-3003 Pump motor Mud Pit Room _ _

116 M-3006 Pump motor Mud Pit Room _ _

117 M-3005 Pump motor Mud Pit Room 0.098 5.4

Page 3 of 6
Olinda Star- Grounding Measurements / Readings 11/12/2018

No. Tag Description Location R (Ω) I (mA)

118 M-3008 Pump motor Mud Pit Room 0.072 8.5

119 M-3007 Pump motor Mud Pit Room _ _

120 Unidentified motor next to Pump M-3007 Mud Pit Room _ _

121 _ Ventilation Motor Mud Pit Room 0.582 0

122 SB-406 Electrical Panel Cementing Room 0.049 2.5

123 _ Transformer 440 / 220 Cementing Room 0.54 8.2

124 SB-106N Electrical Panel Cementing Room 0.62 1.4

125 SB 221N Electrical Panel Cementing Room 0.45 2.7

126 SB-208N Electrical Panel Cementing Room 0.045 1.23

127 SB-208E Electrical Panel Cementing Room 0.045 1.23

128 SB-203N Electrical Panel Corridor from "Coluna 5" to "Coluna 6" 0.049 0

129 SB-203E Electrical Panel Corridor from "Coluna 5" to "Coluna 6" 0.049 0

130 _ Rescue boat winch motor Main Deck - AFT 0.082 1.2

131 _ Rig power supply panel Main Deck - AFT/PORT 0.047 3.1

132 _ Electrical Panel (refer to picture log) Main Deck - AFT/PORT 6.5 4.3

133 _ Electrical Panel (refer to picture log) Main Deck - FWD/STBD 7.2 1.6

134 _ Electrical Panel (refer to picture log) Main Deck - AFT-STBD 5.4 2.1

135 SB-423N Electrical Panel Welding Workshop - Main Deck _ _

136 _ Desilter pump Shale Shaker Room 0.093 5.4

137 _ Desander pump Shale Shaker Room 0.092 1.5

138 _ Degasser pump Shale Shaker Room 0.89 0

139 TAG-0114 Pump - outside shale shaker room Shale Shaker Room 0.049 0

140 _ Pump - outside shale shaker room Shale Shaker Room 0.048 0.5

141 SB.421N MCC Panel Column 4 0.08 17.4

142 CB.26 Valve control panel - Stbd Column 4 0.045 2.6

143 SB 205 Pump Room Column 4 Panel Column 4 0.054 17.9

144 SB-407G Coluna A-C set panel Column 4 0.046 21.5

145 SB-407N Coluna A-C set panel Column 4 0.046 21.5

146 Elevator Panel 440V Column 4 0.045 18

147 Valve panel Column 4 - Pump Room _ _

148 Drill water pump #2 Column 4 - Pump Room 5.2 0

149 Ballast pump #3 Column 4 - Pump Room 9.95 15.1

150 Emergency discharge pump Column 4 - Pump Room _ _

151 Potable water pump #2 Column 4 - Pump Room _ _

152 Fire pump #2 Column 4 - Pump Room 0.21 5.4

153 Diesel oil pump #1 Column 4 - Pump Room _ _

154 Diesel oil pump #2 Column 4 - Pump Room _ _

155 Service cooling system pump #1 Column 4 - Pump Room _ _

156 Service cooling system pump #2 Column 4 - Pump Room _ _

Page 4 of 6
Olinda Star- Grounding Measurements / Readings 11/12/2018

No. Tag Description Location R (Ω) I (mA)

157 Sea water cooling pump Column 4 - Pump Room 0.314 0

158 Sewage pump Column 4 - Pump Room 0.48 3.2

159 Ballast pump #4 Column 4 - Pump Room 9.25 12.3

160 Bilge pump Column 4 - Pump Room 3.2 1.1

161 Agitator / Bilge pump panel Column 3 0.68 4.5

162 CB25 Valve control panel - Port Column 3 0.045 3.2

163 SB-204N Electrical Panel Column 3 0.045 7.5

164 SB-204E Electrical Panel Column 3 0.045 7.5

165 SB-408E Coluna A-C Panel Column 3 0.048 3.2

166 SB-408N Coluna A-C Panel Column 3 0.048 3.2

167 Elevator Panel 440V Column 3 0.045 23

168 Drill water pump #1 Column 3 - Pump Room 0.047 2.1

169 Ballast pump #1 Column 3 - Pump Room 0.222 0

170 Emergency bilge pump Column 3 - Pump Room _ _

171 Potable water pump Column 3 - Pump Room _ _

172 Fire pump #1 Column 3 - Pump Room 0.054 5.6

173 Ballast pump #2 Column 3 - Pump Room 0.045 1.2

174 Sea water pump Column 3 - Pump Room 0.064 13

175 Water cooling pump #1 Column 3 - Pump Room 0.62 11

176 Water cooling pump #2 Column 3 - Pump Room 6.1 0.1

177 Diesel oil pump Column 3 - Pump Room 0.048 2.9

178 SB-109N Electrical Panel Column 1 5.5 0

179 CB.23 Valve control panel Column 1 0.051 0

180 Winch water cooling unit 1/2 Column 1 0.047 1.2

181 Winch water cooling pump Column 1 0.047 0.34

182 SB-110N Electrical Panel Column 2 _ _

183 CB.24 Valve control panel - stbd Column 2 0.048 0

184 Winch water cooling unit 3/4 Column 2 0.048 1.2

185 Winch water cooling pump Column 2 0.044 1.2

186 Valve panel Column 3 - Pump Room _ _

187 SB.112 Electrical Panel Column 6 0.046 0.2

188 C.28 Valve control panel Column 6 _ _

189 Winch cooling water unit Column 6 0.48 0

190 Winch cooling water pump Column 6 0.48 0

191 SB.111 Electrical Panel Column 5 0.048 13

192 Valve control panel Column 5 0.54 9.5

193 Winch cooling water unit Column 5 6.8 11.4

194 Winch cooling water pump Column 5 6.8 11.4

195 SB 404N Electrical panel Local Instrumention Room - Drill Floor 0.046 7.79

Page 5 of 6
Olinda Star- Grounding Measurements / Readings 11/12/2018

No. Tag Description Location R (Ω) I (mA)

196 SB 212N Electrical panel Local Instrumention Room - Drill Floor 0.046 21.5

197 SB 212E Electrical panel Local Instrumention Room - Drill Floor 0.046 2.68

198 On track AWD cubicle group panel Local Instrumention Room - Drill Floor 0.68 3.4

199 Aircon Panel 440V Local Instrumention Room - Drill Floor 0.048 1.2

200 Zone management patriots control panel Local Instrumention Room - Drill Floor 0.046 3.1

201 LER VFD Distribution panel Local Equipment Room - Drill Floor 0.044 4.6

202 Transformer 480V;208/120VAC Local Equipment Room - Drill Floor 0.045 8.6

203 Rotary table / Top drive / Drawworks Panel Local Equipment Room - Drill Floor no access

204 VFD PLC cubicle Local Equipment Room - Drill Floor no access

Page 6 of 6