Sie sind auf Seite 1von 8

SSPC-Guide 10

August 1, 1994
Editorial Revisions November 1, 2004

SSPC: The Society for Protective Coatings

TECHNOLOGY guide No. 10


Guide to Specifying Coatings Conforming to
Volatile Organic Compound (VOC) Content Requirements

1. Scope 2.2 VOC LEVELS: Coatings are typically regulated by


establishing limits on the VOC content of the coating at the
1.1 This guide describes procedures for preparing a time of application after addition of any thinners. (See Note
specification for protective coatings conforming with volatile 9.1)
organic compound (VOC) content requirements. This guide identifies six possible levels of VOC content
which might be adopted for various coating categories:
1.2 Procedures cover determining VOC content, com- • VOC Level 1 - less than or equal to 60 9/L (0.5 Ibs/
pliance requirements, qualifying, selecting, and evaluating gal)
performance of coatings, and assembling the specification. • VOC Level 2 - less than or equal to
120 g/liter (1.0 Ibs/ gal)
1.3 This guide is intended to be used by specifiers, end • VOC Level 3 - less than or equal to 250 g/liter (2.1
users, and others who are required to select, test, or specify Ibs/ gal)
coatings to meet VOC regulations. • VOC Level 4 - less than or equal to 340 g/liter (2.8
Ibs/ gal)
2. Description and Definitions • VOC Level 5 - less than or equal to 420 g/liter (3.5
Ibs/ gal)
2.1 This guide describes the major steps needed to prepare • VOC Level 6 - unrestricted VOC content
a specification to comply with VOC regulations. (Editor's Note: As of the Eighth Edition of Volume 2 [September,
2000], these categories are no longer used in SSPC standards
2.1.1 Understanding VOC Regulations (Section 4): This for paints and painting systems.)
section describes the basis of regulations and how VOCs are
regulated. The types of regulations and the various coating 2.3 DEFINITIONS
categories are outlined.
2.3.1 Volatile Organic Compound (VOC)
2.1.2 Determining VOC Requirements (Section 5):
Specific procedures include determining location of the coating 2.3.1.1 ASTM D 3960: Volatile Organic Compound
application, identifying the agency having jurisdiction, determin- (VOC): In coatings, any compound of carbon that evaporates
ing the category of coating, determining the VOC level that from a paint or coating film under specific test conditions is a
must be met, and selecting the test method for determining VOC. It thus does not include water and exempt solvents that
VOC content. are volatile. VOC may be determined at a specified temperature
for a specified baking or air dry time and at a controlled film
2.1.3 Selecting Coatings to Meet VOC Requirements thickness.
(Section 6): This section establishes the requirements for
qualifying and selecting coatings to meet VOC requirements. 2.3.1.2 U.S. Environmental Protection Agency Refer-
Requirements include coating performance properties, applica- ence Method 24 - Volatile Organic Compound (VOC): Any
tion properties, field case histories, and supplier service. For organic compound which participates in atmospheric photo-
each set of requirements the guide describes approaches for chemical reactions is a VOC; that is, any organic compound
developing specific criteria and rating schemes. other than those which the administrator designates as having
negligible photochemical reactivity (known as “exempt sol-
2.1.4 Preparing Specifications (Section 7): This section vents;” see Note 9.2). VOCs may be measured by a reference
gives guidance on assembling the specification. Key com- method, an equivalent method, an alternative method or by
ponents include performance and application requirements, procedures specified under any subpart.
supplier qualification, VOC classification, thinning, and quality
control provisions. 2.3.2 Transfer Efficiency: The ratio of the mass or volume
of coatings solids adhering to an object to the total mass or
2.1.5 State Contacts for Air Quality Control Regula- volume, respectively, of coating solids used in the application
tions (Appendix A): Information is also provided on state air process, expressed as a percentage (see Note 9.3).
quality contacts.

1
SSPC-Guide 10
August 1, 1994
Editorial Revisions November 1, 2004

2.3.3 Attainment Area: An area considered to have air 4. Understanding VOC Regulations
quality as good as or better than the national ambient air quality
standards as defined in the Clean Air Act. An area may be an 4.1 REGULATING VOCS
attainment area for one pollutant and a non- attainment area for
others. For ozone, attainment requires that the ozone concen- 4.1.1 Basis of Regulation: EPA and other environmental
tration not exceed 0.12 ppm (as a one-hour weighted average) agencies regulate the VOC emission of coatings because
more than once a year for three consecutive years. VOCs are a precursor to ozone (a component of smog, the
adverse effects of which have been extensively demonstrated).
2.3.4 Control Technique Guidelines (CTG): A series of EPA was authorized by Congress through the Clean Air Act of
EPA documents designed to assist states in defining Reason- 1970 and the Clean Air Act Amendments of 1977 and 1990 to
able Available Control Technology (RACT) for major sources coordinate and guide the state efforts to assure that all citizens
of volatile organic compounds. have air of acceptable quality. To that end Federal and State
agencies are developing regulations to control the production
2.3.5 State Implementation Plans (SIP): EPA-approved of ozone producing VOCs.
state plans for the establishment, regulation, and enforcement
of air pollution standards. 4.1.2 How VOCS Are Regulated

2.3.6 Material Safety Data Sheet (MSDS): A compilation a. VOC Content: The most common method for regulat-
of information required under the OSHA Hazard Communica- ing VOCs is by the mass of VOC emitted per volume of liquid
tion Standard on the identity of hazardous chemicals, health coating less water and exempt solvents (see 2.3.1.2 and Note
and physical hazards, exposure limits, and precautions. Sec- 9.2). Typical units are grams of VOC per liter (g/L) of coating or
tion 311 of SARA requires facilities to submit an MSDS under pounds of VOC per gallon of coating (Ib/gal) (see Note 9.2.1).
certain circumstances. As described in Section 2.3.1, it is necessary to subtract the
volume of water or of exempt solvents from the overall coating
3. Referenced Standards volume before computing VOC content. (Note: The “less water
and exempt solvent” phrase has been omitted hereafter, but it
3.1 SSPC STANDARDS: should be understood to be an integral part of all subsequent
quantitative terms.)
Guide 9 Guide for Atmospheric Testing of Coatings Commonly specified VOC levels are 420 g/L (3.5 Ib/gal),
in the Field 340 g/L (2.8 Ib/gal), and 250 g/L (2.1 Ib/gal). These are defined
as SSPC VOC Levels 5, 4, and 3, respectively. Other levels
3.2 ASTM INTERNATIONAL STANDARDS: established by SSPC include: Level 1 - less than or equal to
60 g/L (0.5 Ib/gal), Level 2 - less than or equal to 120 g/L (1.0
D 610 Standard Method for Evaluating Degree of Ibs/gal), and Level 6 - unrestricted VOC content. These levels
Rusting on Painted Steel Surfaces have been established to encourage uniformity throughout
D 1640 Test Methods for Drying, Curing, or Film the industry in regulation of VOCs and product development
Formation of Organic Coatings at Room efforts. Other levels (such as 350 g/L [2.92 Ibs/gal] or 380
Temperature g/L [3.17 Ibs/gal]) have also been used by various regulatory
D 3960 Practice for Determining Volatile Organic agencies.
Compound (VOC) Content of Paints and
Related Coatings. b. Total VOCs Emitted: Some agencies set limits on the
total weight of VOCs that can be emitted from a plant or facility
3.3 U.S. ENVIRONMENTAL PROTECTION AGENCY in a day or year (kilograms or pounds). This type of rule has
METHOD: been applied for regulating VOC content for miscellaneous
metal parts. (See 4.3.1.)
40 CFR Ch. 1, Part 60, Appendix A, Method 24
Determination of Volatile Matter Content, Water c. Transfer Efficiency: Transfer efficiency is defined in
Content, Density, Volume Solids and Weight Solids Section 2.3.2 (see also Note 9.3). A few agencies have imposed
of Surface Coatings a minimum transfer efficiency (e.g., 65%) for the application
of a coating to a substrate. Any reduction in the amount of
3.4 ENVIRONMENTAL STATUTES: coating wasted will of necessity reduce the amount of VOC
emitted into the atmosphere. There is no direct correlation
Clean Air Act 1990 between transfer efficiency and VOC content of coatings, as a
Clean Air Act Amendments, 1977 and 1990 high VOC coating can be applied with high transfer efficiency
Superfund Amendment and Reauthorization Act or low transfer efficiency.
(SARA), 1986

2
SSPC-Guide 10
August 1, 1994
Editorial Revisions November 1, 2004

4.2 TYPES OF REGULATIONS 4.3.1. Miscellaneous Metal Parts and Products: This
category includes coatings applied to various factory finished
4.2.1 EPA Control Technique Guidelines: Control metals, including fabricated metal structures. Typical applica-
Technique Guidelines (CTGs) are documents prepared by tions include shop-applied primers for bridges, water towers,
EPA which establish the level of control deemed to represent and other steel structures, and coatings applied in railcar
“Reasonably Available Control Technology.” Publication of a shops.
CTG triggers a requirement that the states develop a state rule Typically, these rules are based on a CTG issued in 1978
for major industries of the type for which the CTG was writ- by EPA as a guidance document for areas that have been des-
ten. In many cases, states promulgated the recommendation ignated as exceeding the national ambient air quality standard
in the CTG. In other cases, states developed different rules. (NAAQS) for ozone. Coatings are classified as follows, with
Typically, a state is required to develop a State Implementation their recommended VOC limits:
Plan (SIP) describing the methods to achieve the guidelines • Air-dried coatings: 3.5 Ibs/gal (420 g/L) - dried by the
and the means to verify compliance. Another important feature use of air or forced warm air at temperatures up to
of a CTG is that it is only applicable to those areas which are 194 ˚F (90 ˚C).
designated by EPA as non-attainment for ozone. The definition • Clear coatings: 4.3 Ibs/gal (520 g/L) - unpigmented
of attainment for ozone is given in 2.3.3. or transparent coating lacking color and opacity.
• Extreme performance coatings: 3.5 Ibs/gal (420 g/L)
4.2.2 EPA National Rule: A National Rule establishes a - designed for harsh exposure or extreme environ-
national requirement for controlling VOCs (i.e., by setting a mental conditions.
standard level of compliance for total amount of VOC emitted, • All other coatings: 3.0 Ibs/gal (360 g/L) - any other
or limitations of VOC content of a coating). Unlike the CTG, a type of coating.
National Rule applies to all areas of the U.S. National Rules
may be preemptive or non-preemptive. Preemptive rules 4.3.2 Marine Coatings: These are coatings applied to
prevent any air quality district (e.g., state, county, district) ships, boats, and their appurtenances, and to buoys and oil
from having a rule more restrictive than the Federal rule. In drilling rigs intended for the marine environment. (See Note
a non-preemptive rule, individual states or air quality districts 9.2.2.)
are permitted to have more stringent rules. Any local rule must
be at least as stringent as the National Rule. To date, EPA has 4.3.3 Architectural and Industrial Maintenance (AIM)
not issued any National Rules regarding protective coatings Coatings: This category, which is often referred to as Archi-
for structures. tectural Coatings, is a broad category encompassing most
field-applied coatings for residential, commercial, or industrial
4.2.3 State and Local Regulations: Most states have applications. It also includes pavement marking coatings. Be-
environmental agencies charged with protecting air quality. cause of this diversity, it is useful to subdivide this category as
In many cases, they issue statewide regulations to meet EPA follows:
CTGs. However, because the CTGs do not mandate specific a. Architectural Coatings: These are coatings applied
VOC levels or total emissions, the states are required to de- to exteriors and interiors of residential and commercial struc-
velop their own approaches to controlling VOCs from different tures, including houses, warehouses, commercial buildings,
surface coating operations. Many states have designated air stadiums, hospitals, and schools. Coatings are intended to
quality districts based on geographical factors or population provide good appearance properties and to protect against
distributions. Thus, areas with higher potential for air pollu- wear and weather in normal indoor and outdoor environments.
tion will tend to have stricter regulations regarding VOCs and (see Note 9.2.3).
other ozone-producing activities. For example, California has b. Industrial Maintenance: These are coatings ap-
established approximately 30 air quality districts, each of which plied to steel and concrete industrial facilities or structures.
has authority to regulate the VOC content of coatings. Also, The coatings are intended to provide long-term protection
most large metropolitan areas (e.g., New York area, Chicago against corrosion and weathering in exposures ranging from
area) have air quality jurisdictions which may overlap cities, mild to severe atmospheric, salt or potable water immersion,
counties, or states. Any facility or structure owner requiring intermittent or continual immersion in chemicals or solvents,
surface coating must be aware of the jurisdictions within which abrasive conditions, and extremes of pH, temperature, and
the coating application (and hence the VOC emissions) will pressure. (See Section 9.4 for a definition from the California
occur. Air Resources Board.)

4.3 COATING CATEGORIES: EPA has established a 5. Determining VOC Requirements


variety of categories for coatings typically used for heavy-duty
industrial maintenance and new construction and architectural 5.1. DETERMINE LOCATION OF PAINT APPLICATION:
coating applications. The principal ones are as follows: Identify the location or locations where paint will be applied, as

3
SSPC-Guide 10
August 1, 1994
Editorial Revisions November 1, 2004

the VOC content permitted depends on the site of application. specification. For each one selected, follow the guidelines in
Be sure to include both shop and field painting. the appropriate sections that follow.
• Laboratory and short-term field performance
5.2 IDENTIFY THE AGENCY HAVING JURISDICTION: (Section 6.3).
For each location where paint will be applied, determine the • Application properties (Section 6.4).
agency which has jurisdiction over air quality regulations. The • Case histories (Section 6.5).
jurisdiction may be a state, county, city, or air quality district. • Availability and quality of supplier service (Section
A list of state air quality contacts is attached as Appendix A. 6.6).
This information is regularly updated by the Air and Waste
Management Association. If a formal numerical evaluation will be conducted, iden-
tify the relative weighting factors for the various criteria. Also
5.3 DETERMINE CATEGORY OF COATING: Select the determine if the comparisons will be relative (i.e., select the
coating category based on the descriptions in Section 4.3. If top 1, 2, or 3) or absolute (i.e., establish a level in advance
there is some question about the classification, contact the which all qualified coatings or suppliers must meet). Prepared
appropriate air quality district officials. detailed criteria based on Sections 6.3 through 6.6.

5.4 DETERMINE VOC LEVEL THAT MUST BE MET: 6.3 DEVELOP CRITERIA FOR PERFORMANCE
Obtain a copy of the specific regulations for the category of TESTS
coatings and for the air quality jurisdiction. Please note the
following points: estimated volume of coating to be applied, 6.3.1 Identify Specific Laboratory Performance Tests:
limitations on total VOC emissions, limitations on VOCs for The industry has developed a wide range of different types of
coating, test methods (see also 5.5 and Note 9.5), and spe- performance tests for protective coating systems, depending
cific definitions regarding generic types or conditions (e.g., on the intended service and other requirements and the time
temperature or composition). Prepare a written list of all the and resources available to conduct the testing. Among the
regulations and provisions that must be met prior to selecting most widely used performance tests are the following:
or applying a coating. • Accelerated Laboratory Aging and Corrosion Tests: These
include humidity testing, salt fog testing, cyclic salt spray,
5.5 SELECTION OF THE TEST METHOD FOR DETER- and immersion.
MINING VOCS: After identifying the VOC compliance require- • Accelerated Weathering Testing: These include exposure
ments outlined in Sec. 5.4, determine if the regulatory agency to fluorescent UV, carbon and xenon arcs, and cycling of the
has referenced a specified method for testing. If so, that method exposures with humidity, condensation or water spray.
shall be used. If no test method is specified, EPA Method 24 • Physical Tests: These include hardness, abrasion resis-
shall be used. (See Note 9.5 for alternate methods.) tance, and flexibility.
Although a calculation based on formulation may be used • Chemical Tests: Coating specimens are immersed in
to estimate VOC, compliance penalties will be based on VOC chemical solutions or the chemicals are applied to small
as measured by the referenced analytical method. Measure- spots on the coating to determine resistance.
ments and calculations should be based on the level of VOC • Short-Term Test Fence Exposures: Coating systems are
of the coating as applied in the field after thinning. applied to metal or other panels and placed on an outdoor
rack or fence and evaluated periodically for up to one or
6. Selecting Coatings to Meet VOC Require- two years for rusting, blistering, or loss of gloss or color
ments (see SSPC-Guide 9).

6.1 GENERAL APPROACH: Because many currently used 6.3.2 Provide Details on Conducting Performance
coatings do not meet current or proposed VOC requirements, Tests: These include the generic types of coatings to be tested,
there is a need to establish a program to select coatings that level of VOC sought, test methods to be used (including ASTM
meet these requirements. A program for accomplishing this standard numbers where available), number of test specimens,
would be similar to any other program used to select coatings method of preparation and application, duration of test, and
and should start with establishment of selection criteria. One methods of evaluating and rating specimens. Also identify the
criterion would be that the coatings meet the required VOC types of control coatings. These are coatings that are to be
levels. Normally it is necessary that each coating in a coating used as reference coatings based on their past performance
system (primer, intermediate, and topcoat) not exceed the or their common acceptance as industry standards. These
maximum VOC content permissible. may not necessarily meet the VOC requirements.

6.2 ESTABLISH SELECTION CRITERIA TO BE USED 6.3.3 Determine Who Will Perform the Testing: This
may be done by facility owner/specifier, paint supplier, or
6.2.1 Listed below are criteria that can be used to qualify independent testing laboratory.
VOC-compliant coatings. Select the criteria to be used for the

4
SSPC-Guide 10
August 1, 1994
Editorial Revisions November 1, 2004

6.3.4 Select Candidate Coatings: Prepare a list of 6.4.2 Evaluate Coating Application Properties
required VOC-compliant coatings. The following information
should be furnished: • Determine who will perform the testing. This can be the
• Maximum VOC content acceptable. owner, the supplier, a painting contractor, or an indepen-
• Service environments. dent laboratory.
• Types of generic coating systems currently used in these • Select application equipment which will be compa r a b l e
environments. Note: It is often advantageous to give the to that used in the production application.
supplier the choice of a generic system. Conventional • Select structural configuration. The coating sys-tem should
systems formulated at high VOC levels may not be avail- be applied to a minimum of 46 square feet on a structure
able or may give reduced performance at reduced VOC representative of that to be coated under the expected
levels. application conditions (see SSPC-Guide 9). Evaluate the
• Identify other restrictions or conditions (e.g., lead- and application based on criteria such as absence of runs,
chromate-free, limitations on blast cleaning or other sags, dry spray, and voids.
surface preparation, other material restrictions, drying, • Determine time for coating to dry to touch and to dry hard
curing or other application requirements). in accordance with ASTM D 1640.
• Quantity required and date of delivery. • Verify that coating is properly cured based on standard
Supplier should be required to furnish current Material procedures.
Safety Data Sheets (MSDS), Technical Data Sheets, and • Determine if coating has met application criteria.
application instructions for each coating furnished. (See Note
9.6.) 6.5 DEVELOP CRITERIA FOR CASE HISTORIES

6.3.5 Implement Testing Program: Conduct or direct 6.5.1 Significance: Case histories can often provide
testing in accordance with Section 6.3.1 to 6.3.4 above. If test insight into the practical aspects of a coatings performance
is to be run by a supplier, consider requiring written certification and identify special precautions or problems that have been
of the test results, as well as copies of raw data. encountered in production applications. The value depends
on how closely the conditions (i.e., structure and exposure)
6.3.6 Evaluate Test Results: Determine relative rating match the intended use. Also of significance are the duration
or ranking and whether the coatings have met the designated of the case history, the validity of the ratings, and the quality
performance criteria. of the documentation of performance.

6.4 DEVELOP CRITERIA FOR APPLICATION PROPERTIES 6.5.2 Document Case History: The following information
should be sought:
6.4.1 Identify Specific Requirements for Coating Ap- • Identification of structure, including location, owner, type,
plication Properties: Coatings to be applied to structures size, and configuration.
(particularly field applications) must be capable of being ap- • Exposure environment, including the presence of salts,
plied under the various weather and other conditions that may sulfur dioxide, or other contaminants, as well as the typical
occur. Coating application tests that can be incorporated into humidity, rainfall, and other aggressive conditions.
a program include: • Condition of structure prior to coating application (the
• Application by various types of equipment, including amount of rust, deteriorated paint, pitting, or other condi-
brush, roller, airless spray, air spray, or new specialized tions prior to surface preparation as well as the degree
techniques. of cleaning that has been achieved).
• Tolerance to film thickness range. One cannot assume • Coating system applied. Information should in-
that in the field the coating will be applied at precisely the clude the method of surface preparation, surface
DFT recommended by the manufacturer. More realistically, profile achieved (if blast cleaned), dry film thick-ness
lower or higher DFTs may be encountered. (including ranges and averages), and method
• Ability to wet and penetrate different substrates and of application.
configurations. Coatings must be able to flow out and • Dates of application and inspection.
level under a variety of geometries and over substrates • Control (reference coatings) used, if any.
cleaned to different degrees and contaminated with salts, • Criteria for evaluating condition (e.g. rusting, undercut-
old paint, or rust. ting) as well as the specific standards utilized (e.g.,
• Tolerance to weather conditions. Coatings are often ap- ASTM D 610/SSPC-VIS 2).
plied in conditions of moderate wind (up to10 mph [16 • Name and phone number of the facility owner’s
km/hr]) and at the extremes of humidity and temperature representative and the painting contractor or applicator.
limitations imposed by the manufacturer (50 to 90˚F [10
to 31˚C] and up to 85% relative humidity).

5
SSPC-Guide 10
August 1, 1994
Editorial Revisions November 1, 2004

6.5.3 Evaluate Case History 6.7 OVERALL RATING: Prepare a consolidated list of
the criteria and results of the evaluation for each of the criteria
• The duration of exposure should be rated as follows: selected. Rank the different coatings selected from best to
• Inadequate - less than 18 months worst, and if possible, identify a minimally acceptable set of
• Adequate - 24 months coating materials for inclusion in the specification.
• Superior - greater than three to five years
• Evaluate the validity of the ratings based on the source 7. Prepare Specification for VOC-Compliant
of the ratings and the extent of documentation as follows: Coatings
Inadequate, Adequate, Superior.
• Determine the similarity of the case history to the Specifications must be written for coatings or coating sys-
proposed application as follows: Inadequate,Adequate, tems that meet the performance requirements of the intended
Superior. service and other criteria described in Section 6. They must
• Provide an overall case history rating as Inadequate, also meet the VOC requirements determined in Section 5.
Adequate, or Superior.
• 7.1 PERFORMANCE AND APPLICATION REQUIRE-
6.6 DEVELOP CRITERIA FOR SUPPLIER SERVICE MENTS: Incorporate the criteria for the performance and ap-
plication tests and case histories from Sections 6.3, 6.4, and
6.6.1 Significance: Successful field application of coatings 6.5 into this portion of the specification.
is not achieved automatically, but rather requires cooperation
among the coating supplier, the facility owner, and the applicator. 7.2 SUPPLIER QUALIFICATIONS: Incorporate the re-
The supplier should provide accurate information on technical quirements of Section 6.6 into this portion of the specification
and application properties and on safety or health hazards, as if the facility owner intends to evaluate suppliers.
well as advice on correcting application or problems.
7.3 VOC CLASSIFICATION: Incorporate in the specifica-
6.6.2 Availability of Materials: It is important that the tion the VOC class or other VOC requirements for the jurisdic-
coating supplier be able to furnish the quantity of coating tion. The VOC classes are listed in Section 2.2. Also include
required to the facility being coated in a timely manner. Some the test method for measuring VOC from Section 5.5.
coatings may be in limited production or may require shipping
from another region. These factors could affect the cost as well 7.4 THINNING RESTRICTIONS: The specification should
as the timing of delivery. require that the coating shall not be thinned in the field beyond
the level given in the coating supplier’s written technical data
6.6.3 Document Past Service: Identify specific jobs or sheets. The data sheet should indicate the VOC content of
experience with the supplier. If the facility owner has not had the coating after maximum thinning.
specific experience, it may be possible to contact other owners
in the vicinity. Other information may be obtained from repu- 7.5 QUALITY CONTROL PROVISION: The specifica-
table contractors who have utilized the company’s products tion should require that the coating supplied will have met
or services. A qualitative rating scheme may be established the requirements of Section 6. Examples of tests to verify
for the qualifications of technical and other service provided the composition of coatings are as follows: viscosity, density,
by the coatings supplier as follows: Inadequate, Adequate, infrared spectrum of vehicle (binder and solvent), fineness of
Superior. dispersion, percent solids by weight or volume, and color. If
Specific information sought is as follows: required by owner, request a letter from the supplier certifying
• Accuracy, clarity and completeness of technical and ap- the above, and identify the specific test conditions.
plication data sheets and MSDS.
• Promptness and quality of response to requests for 8. Disclaimer
information.
• Presence and availability of technical or sales representa- 8.1 This guide is designed to describe, review, or analyze
tive at major jobs or where problems have arisen. new or improved technology and does not meet the definition
• Overall strength of product line, i.e., whether this company of a standard as defined by SSPC. A guide differs from a stan-
can meet the majority of the coating materials requirements dard in that it is not suitable for referencing in a specification
for the various types of applications required. or procurement document.
• Product availability and timeliness of delivery.
• Rate each of the above items as Inadequate, Adequate, 8.2 While every precaution is taken to ensure that all in-
or Superior. At a minimum, the supplier should receive an formation furnished in SSPC guides is as accurate, complete,
overall rating of Adequate. and useful as possible, SSPC cannot assume responsibility

6
SSPC-Guide 10
August 1, 1994
Editorial Revisions November 1, 2004

nor incur any obligation resulting from the use of any materials, 9.3. TRANSFER EFFICIENCY
coatings, or methods described herein, or of the guide itself.
Transfer efficiency (defined in Section 2.3.2) is a measure
8.3 This guide does not attempt to address problems of the proportion of the mass or volume of coating solids adher­
concerning safety associated with its use. The user of this ing to an object.
specification, as well as the user of all products or practices
described herein, is responsible for instituting appropriate Mass of solid coating on item x 100
Transfer Efficiency (%) =
health and safety practices and for ensuring compliance with Mass of solid coating consumed
all governmental regulations.
OR

9. Notes
Volume of solid coating on item x 100
Transfer Efficiency (%) =
Volume of solid coating consumed
9.1 EPA has traditionally expressed limitations on allow-
able VOC emissions from factory­-applied coatings in terms of Factors that most affect paint transfer efficiency are:
the maximum “VOC content” of a coating. By expressing the • Item size and shape
limitations in terms of the allowable VOC content of the coating, • Type of application equipment
the Agency’s intent was to spur pollution prevention efforts on • Distance of spray gun from item
the part of paint and resin manufacturers as they attempted to • Spray gun pressure
develop coatings that could comply without the need for their • Wind speed and direction
customers to invest in abatement equipment. As the Agency
follows the instructions of Congress to limit emissions from The smaller and more complex the item, the lower the
field- applied coatings, the abatement option will frequently transfer efficiency. The greater the distance of spray gun from
not be a realistic option and lower VOC coatings will be the item and the greater the atomizing pressures, usually the lower
only practical avenue for compliance. One regulatory possibil- the transfer efficiency. The relative order of transfer efficiencies
ity would exclude from commerce any coating after addition of different types of application equipment, from high to low,
of thinners that exceeded some specific predetermined VOC is:
content. • Manual (brush or roller)
• Electrostatic spray
9.2 A reference method, an equivalent method, or an • High-volume, low-pressure spray
alternative method, however, may also measure nonreactive • Air-assisted airless spray
organic compounds. In such cases, an owner or operator may • Airless spray
exclude the nonreactive compounds when determining compli- • Conventional air spray
ance with a standard. The EPA administrator has designated the
following organic compounds as negligibly reactive: methane, 9.4 The following definition of Industrial Maintenance
ethane, 1,1,1­-trichloroethane (methyl chloroform), methylene Coatings has been prepared by ARB­-CAPCAA, California Air
chloride (dichloromethane), trichlorofluoromethane (CFC-11), Resources Board.
dichlorodifluoromethane (CFC-12), chlorodifluoromethane Industrial Maintenance Coatings: High-performance ar-
(CFC-22), trifluoromethane (CFC-23), trichlorotrifluororethane chitectural coatings formulated for and applied to substrates
(CFC-113), dichloro-tetrafluoroethane (CFC-114), and chloro- that are exposed to one or more of the following extreme
pentafluoroethane (CFC-15). environmental conditions:
a. Immersion in water, wastewater, or chemical solutions
9.2.1 At least one state (Texas) computes VOC on the (aqueous and non-aqueous solutions), or chronic
basis of mass (wt) of solvent per volume of solid coating ap- exposure of interior surfaces to moisture condensa-
plied to the surface. tion.
b. Acute or chronic exposure to corrosive, caustic,
9.2.2 This definition of marine coatings is derived from or acidic agents, or to chemicals, chemical fumes,
Rule 1106, “Marine Coating Operations” from the South Coast chemical mixtures, solutions, or salt spray.
Air Quality Management District. c. Repeated exposure to temperatures in excess of
200°F.
9.2.3 Sometimes an additional subset of “high-performance d. Repeated heavy abrasion, including mechanical
architectural coatings” is defined, which includes commercial wear and repeated scrubbing with industrial solvents,
structures intended to give long-term protection in normal or cleansers, or scouring agents.
aggressive environments. e. Exterior exposure of metal surfaces.

7
SSPC-Guide 10
August 1, 1994
Editorial Revisions November 1, 2004

9.5 The methods in 3.4 and 3.5 may not be applicable for
testing for VOCs in all jurisdictions. It will be necessary for the
specifier, end user, or others to verify whether these methods
are applicable in the area that the coating is to be used. Other
methods are described in more detail in “VOC Test Methods for
Surface Coatings,” by Christine Stanley (Journal of Protective
Coatings and Linings, Vol. 7, No. 7, July 1990, pp. 20-24).

9.5.1 Bay Area Air Quality Management District (BAAQMD)


Method 21 and 22 (water based and solvent based coat-
ings).

9.5.2 South Coast Air Quality Management District


(SCAQMD), Rule 107.

9.6 The MSDS is required under OSHA Hazard Com-


munications Standard 29 CFR 1926.59.

State Contacts for Air Quality Control Regulations
are listed at:
http://www.epa.gov/epahome/state.htm

Das könnte Ihnen auch gefallen