Sie sind auf Seite 1von 2

Effective January 2016

Application Paper AP01001003E Supersedes April 2009

Application considerations for surge


protective devices when used with
generators and automatic transfer switches
Introduction What is thermal runaway?
The purpose of this paper is to address the subject Thermal runaway describes a condition where an
of how to properly apply surge protective devices increase in temperature causes a condition that
(SPDs) to systems using transfer switch equip- further increases the temperature and can quickly
ment and generators, and to avoid common pitfalls lead to the destruction of the device. The main
associated with the application of surge protection building block of an SPD is a metal-oxide varistor
to these systems. SPDs are widely used in (MOV). An MOV is a nonlinear device that has a
virtually all modern electrical systems. The use of very high impedance when the applied voltage is
electronic and computer controls in almost every below the threshold voltage, and a low impedance
aspect of industrial, commercial, institutional, and when the applied voltage is above the threshold
residential applications makes surge protection a voltage. An increase in voltage past its threshold
necessity. However, improper application of surge causes an increase in current flow that, in turn,
suppression can result in suboptimal performance causes an increase in the temperature of the MOV.
and reduced SPD life. An MOV that sees an increase in temperature will
decrease in impedance, causing a further increase
in current flow that leads to rapid thermal runaway
What is the purpose of a surge condition. An MOV can quickly and safely recover
protective device? from a short-duration voltage transient; however,
when an MOV is subjected to a sustained over-
The purpose of an SPD is to protect electrical voltage, the MOV goes into thermal runaway and
and electronic equipment from damage and can not recover. Figure 1 shows a graph that indi-
degradation due to short duration, high-energy cates typical threshold levels of time and voltage
transients. Typical voltage transients have a above which an MOV will go into thermal runaway.
duration of microseconds to a few milliseconds.
IEEET C62.41.2 describes a number of transient
waveforms that might be found on an electrical Voltage (per Unit MCOV)
system. They range in magnitude up to 10 kV, 1.6
10 kA with a typical duration of 20 microseconds.
1.5
Sustained overvoltage, also called temporary
overvoltage (TOV), is another power quality event. 1.4
A TOV is an overvoltage that lasts at one or more
cycles, which is about 17 milliseconds on a 60 Hz 1.3
system. Typically, TOVs have a much lower
magnitude, 1.7 to 3.0 times the nominal system 1.2

voltage, but a much longer duration, from a few


1.1
seconds to many minutes.
While SPDs do an excellent job of mitigating 1.0
0.01 0.1 1 10 100 1000 10,000
voltage transients, they are not designed to Time (sec)
provide continuous sinusoidal voltage regulation.
When an SPD is subjected to a sustained
Figure 1. Typical sustained overvoltage damage
overvoltage, there is a very real danger of the
curve for an MOV
SPD going into a thermal runaway and being
permanently damaged. Modern surge suppressors
that have passed ULT 1449 4th Edition testing
should pose no external threat of damage even
when exposed to a sustained overvoltage. When
exposed to a sustained overvoltage, the SPD
should safely disconnect itself from the circuit.
Application Paper AP01001003E Application considerations for surge
Effective January 2016 protective devices when used with
generators and automatic transfer switches
Overvoltages in generators Specifying a surge unit for generators
Overvoltages in generators can occur for a number 1. Eaton recommends installing the following voltage coded SPD
of reasons: units in or on all three-phase emergency electrical equipment to
• Initial startup overshoot improve the reliability of emergency power systems.
• Poor voltage regulation System applied voltage Eaton SPD voltage code
• Step change in load 600 volts wye (4W+G) 600D
• Single-phase ground fault 600 volts delta (3W+G) 600D
600 volts resistance grounded 600D
• Excitation control failure
480 volts delta (3W+G) 480D
• Overspeed
277/480 volts wye (4W+G) 480D
Thermal runaway, as described above, can have a devastating effect 480 volts resistance grounded 480D
on MOVs in a matter of a few cycles. Power obtained from the 120/208 volts wye (4W+G) 240D
electrical utility typically has very good voltage regulation due to
the large size of the generators, or most often multiple generators, Units with the voltage codes in the table above are capable of
versus the relative size of the individual loads. Utility generators also continuously withstanding the nominal system line-to-line voltage
have very precise regulators and sophisticated protection schemes in the line-to-ground mode. As such, the line-to-ground mode
to ensure that the voltage stays within a very tight band, even down can ride through typical emergency system voltage events that
to a few cycles duration. would cause thermal runaway in units with other voltage codes.
Standby or emergency generators, however, typically have poorer 2. Eaton recommends specifying the kA rating of the SPD unit per
voltage regulation. Voltage overshoot at startup and during a step the location categories as outlined in the latest IEEE C62.41.1
change in load is very common. Also, for cost considerations, standard. Most typical emergency power systems equipment
many voltage regulators do not regulate well in the short term, falls under the location category B. These SPD units should have
for example, cycles-to-seconds time frame. Most standby power a minimum kA rating of 80 kA to 160 kA per phase. Actual kA
or emergency power generation systems are designed with the rating can be adjusted depending upon site conditions.
purpose of keeping critical loads, such as emergency lighting, sump
3. A UL nominal discharge current is defined as the peak value
pumps, and critical loads, operating “no matter what” with power
of 8/20 microsecond surge current conducted through the SPD.
quality as a secondary consideration.
The let-through voltage cannot change by more than 10% after
It is not uncommon that the voltage fluctuations of a typical standby 15 surges are applied to the SPD. Eaton recommends a minimum
generator exceed the limits of the voltage damage curve of a nominal discharge current rating of 20 kA. This is the most durably
typically rated SPD (see “Specifying a surge unit for generators”). recognized SPD unit per the latest UL 1449 standards.
The failure of SPDs due to a sustained overvoltage is typically not
4. The 2014 National Electrical Code, Article 700.8, requires a
covered under manufacturers’ warranties, as this is clearly outside
listed SPD to be installed in or on all emergency power systems
of the designed operating parameters of an SPD.
switchboards and panelboards to protect the downstream loads.
For generator or transfer switch surge protection applications,
Recommendations for SPDs when used in please consult with Eaton’s TRC at 1-800-809-2772 option 4,
option 3.
emergency power systems equipment
The 2014 National Electrical CodeT, Article 700.8, defines emergency
power systems as systems legally required to automatically supply
Conclusion
power to designated loads upon loss of normal power. The code SPDs offer many positive benefits and can successfully prevent
requires a listed SPD to be installed in or on all emergency systems damage and disruption to electrical and electronic equipment.
switchboards and panelboards. Per the 2014 National Electrical Code, Article 700.8, a listed SPD
shall be installed in or on all emergency systems switchboards and
1. Make sure that the generator is sufficiently sized. Take into panelboards. Eaton’s recommendations for specifying a surge unit
account any motor loads or other loads that have a high inrush for generators is designed to improve the reliability of emergency
current. Electric motors typically draw 6 to 10 times their full load power systems. For new construction applications, integrating
current when started. Make sure your generator is sufficiently surge products into panelboards and switchboards provides the
sized to handle the startup of these motors. An undersized most reliable solution with superior performance. For existing
generator is prone to severe undervoltages as connected motors installations, Eaton makes a complete line of products to meet
are started followed by a severe overvoltage when the motors your risk exposure needs.
reach their operating speed. Most generator manufacturers offer
software that will assist in sizing the generator properly.
2. Invest in a high-quality voltage regulator for the generator.
Mechanical governors and low-cost electronic regulators may
be a tempting option in cost-sensitive applications; however,
the long-term effects of damage to SPDs and other equipment
due to sustained overvoltages often quickly outweigh the cost
For technical support and application engineering
savings of a low-cost regulator. assistance, please consult with Eaton’s TRC at
Eaton
1000 Eaton Boulevard
1-800-809-2772, option 4, option 2
Cleveland, OH 44122
United States
Eaton.com

© 2016 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. AP01001003E / Z17598 All other trademarks are property
January 2016 of their respective owners.

Das könnte Ihnen auch gefallen