Preface
___________________
Working with the library 7
09.2018
A5E37763954-08-76
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 3
Table of contents
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
4 Function Manual, 09.2018, A5E37763954-08-76
Warranty and liability 1
Note
The application examples are not binding and do not claim to be complete with regard to
configuration, equipment or any contingencies. The application examples do not represent
customer-specific solutions. They are only intended to provide support for typical
applications, you are responsible for the correct operation of the described products. These
application examples do not relieve you from responsibilities of using, installing, operating
and servicing the equipment safely and professionally. When using these application
examples, you recognize that we are not liable for any damage/claims beyond the liability
clauses described.
We reserve the right to make changes to these application examples at any time and without
prior notice. If there are any deviations in the recommendations provided in this application
example and other Siemens publications, for example catalogs, the contents of the other
documents shall have priority.
We do not accept any liability for the information contained in this document. Any claims
against us – based on whatever legal reason – resulting from the use of the examples,
information, programs, engineering and performance data etc., described in this application
example shall be excluded. Such an exclusion shall not apply in the case of mandatory
liability, for example under the German Product Liability Act ("Produkthaftungsgesetz"), in
case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a
product, fraudulent concealment of a deficiency or breach of fundamental contractual
obligations ("wesentliche Vertragspflichten").
The compensation for damages due to a breach of a fundamental contractual obligation is,
however, limited to the foreseeable damage, typical for the type of contract, except in the
event of intent or gross negligence or injury to life, body or health. The above provisions do
not imply a change of the burden of proof to your detriment. Any form of duplication or
distribution of these application examples or excerpts hereof is prohibited without the
expressed consent of Siemens AG.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 5
Warranty and liability
1.1 Security information
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
6 Function Manual, 09.2018, A5E37763954-08-76
Preface 2
Purpose of this documentation
This document describes the PSU8600 TIA Portal Block Library. The block library provides
tested code with clearly defined interfaces. You can use it as the basis for the task you wish
to realize.
The main focus of this document is to describe:
● All blocks pertaining to the block library
● The functionality implemented through these blocks.
The documentation furthermore illustrates the possible applications of the library, and step-
by-step instructions to help you integrate the library into your SIMATIC STEP 7 project.
Note
In this document, the function blocks for S7-1200/1500 are described. Any deviations in the
function blocks for S7-300/400 will be pointed out where applicable.
Note
Difference between TIA V14 SP1 and TIA V15
In this document, working with function blocks in TIA V14 SP1 and TIA V15 is described
keeping TIA V15 Portal as reference. To work with TIA V14 SP1 you need to import library
package "PSU8600_Library_V14_SP1_V2-4" block library and to work with TIA V15 you
need to open library package "PSU8600_Library_V15_V2-4" block library.
References
For more information on SITOP manuals and documentation, refer to the following links,
● Siemens Industry Online Support (https://support.industry.siemens.com)
● SITOP PSU8600: Faceplates and Communication Bocks (TIA Portal, STEP 7 and
WinCC) (https://support.industry.siemens.com/cs/ww/en/view/102379345)
● SITOP PSU8600 Power Supply System Manual: Basic devices with four outputs
(https://support.industry.siemens.com/cs/ww/en/view/105867947)
● SITOP PSU8600 Power Supply System Manual: Basic devices with one output
(https://support.industry.siemens.com/cs/ww/en/view/109482936)
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 7
Preface
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
8 Function Manual, 09.2018, A5E37763954-08-76
Overview of the library 3
Introduction
SITOP PSU8600 allows you to integrate the power supply into your automation network.
In the PROFINET network, SITOP PSU8600 behaves as an Input/output (I/O) device.
Controllers and Human Machine Interface (HMI) systems can communicate with SITOP and
exchange data.
Figure 3-1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 9
Overview of the library
Figure 3-2
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
10 Function Manual, 09.2018, A5E37763954-08-76
Overview of the library
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 11
Overview of the library
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
12 Function Manual, 09.2018, A5E37763954-08-76
Hardware and software requirements 4
Hardware requirements
Table 4- 1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 13
Hardware and software requirements
Software requirements
Table 4- 2
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
14 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks 5
5.1 Introduction
Variants
The library contains two variants of the Function Blocks (FB) and User Data Types (UDT) for
the following controllers:
● S7-1200/1500
● S7-300/400
The function blocks and UDTs have the same tasks and are almost identical.
Table 5- 1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 15
SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
Function principle
The block reads data from the SITOP PSU8600 main module (power supply with 4 outputs)
and writes it to the global transfer data block.
Note
SITOP_PSU8600 is compatible with Firmware version 1.1 - 1.3.
SITOP_PSU8600_1 is compatible with Firmware version 1.4.
Block diagram
Figure 5-1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
16 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
Function characteristics
Figure 5-2
Input parameters
Table 5- 2
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 17
SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
Note
For S7-300/400
• The procedure for naming the device is slightly different from S7-1200/1500.
• The data type HW_IO is not used in S7-300/400.
For more details, refer to the sections Device_name_PSU8600 (Page 19) and Data type
HW_IO (Page 20).
Input/Output parameters
Table 5- 3
Note
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB in your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data” data type.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
18 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
Device_name_PSU8600
The device name of SITOP PSU8600 must be entered in the instance data block of
FB SITOP_PSU8600 as a start value (A) of input parameter Device_name_PSU8600 (B).
Use the address of the input parameter as the address for the device name at
FB SITOP_PSU8600 (C).
Figure 5-3
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 19
SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
Figure 5-4
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
20 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
Note
All the addresses in decimal values should be converted into hexa decimal format when
they are assigned to FB.
Note
Requirements for reading cyclic data
If the addresses of the configured modules are outside the process image address range,
then the function block cyclic data parameters will be assigned to "zero" values.
In order to avoid this problem, you can:
1. Increase the process image input size or change the addresses of the modules to
keep the address in process image range.
2. Use peripheral addressing. For this you need to add ":P" in the function blocks where
"%IW" instructions are there.
Preferably, it is recommended to use first solution, because process image has following
advantages:
• This is part of CPU system memory and updated periodically by CPU.
• Advantages of the process image access compared to direct access to the
input/output modules, offers the advantage that a consistent image of process signals
is made available to the CPU during cyclic program processing. If the signal state at
an input module changes during program execution, the signal status in the process
image is maintained until the process image is updated in the next cycle. Moreover,
since the process image is stored in the CPU's system memory, access to the process
image is significantly faster than direct access to the signal modules.
• Process image comparatively takes less time to access. For example, CPU 317-2 DP
takes 0.05 μs with process image and 15.01 μs with peripheral addressing.
• Bit addressing is possible.
For more details, Please refer below links:
• https://support.industry.siemens.com/cs/document/18325417/where-and-when-do-
you-need-peripheral-addressing-?dti=0&lc=en-WW
• https://support.industry.siemens.com/tf/WW/en/posts/increasing-pip-piq-vs-peripheral-
addressing/62626?page=0&pageSize=10
4. Function blocks and input parameters are slightly different for 1200/1500 and 300/400
PLCs. Cyclic Input and output addresses are represented by single hardware identifier in
1200/1500 PLCs, whereas cyclic input and output addresses are different for 300/400
PLCs. For any input parameter with Cyclic_IO_IN_<submodule>_address
(Cyclic_IO_IN_HeadModule_address), cyclic input address needs to be given as the input.
For any output parameter with Cyclic_IO_OUT_<submodule>_address
(Cyclic_IO_OUT_Output1_address), cyclic output address needs to be given as the ssinput.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 21
SIMATIC STEP 7 function blocks
5.3 FB SITOP_CNX8600
5.3 FB SITOP_CNX8600
Function principle
The block reads data from all the SITOP CNX8600_4x5A and CNX8600_4x10A expansion
modules and writes it to the global transfer data block.
Block diagram
Figure 5-5
Function characteristics
Figure 5-6
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
22 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.3 FB SITOP_CNX8600
Input parameters
Table 5- 4
Note
Cyclic_IO_Output1_address parameter
The system tag is automatically generated by the TIA Portal when creating the expansion
module.
Note
For S7-300/400
For addressing data type HW_IO, refer to the section Data type HW_IO (Page 20).
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 23
SIMATIC STEP 7 function blocks
5.3 FB SITOP_CNX8600
Input/Output parameters
Table 5- 5
Note
Data parameter
DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data” data type.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
24 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.4 FB SITOP_CNX8600_8X
5.4 FB SITOP_CNX8600_8X
Function principle
The block reads data from all the SITOP CNX8600_8x2.5A expansion modules and writes it
to the global transfer data block.
Block diagram
Figure 5-7
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 25
SIMATIC STEP 7 function blocks
5.4 FB SITOP_CNX8600_8X
Function characteristics
Figure 5-8
Input parameters
Table 5- 6
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
26 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.4 FB SITOP_CNX8600_8X
Note
Cyclic_IO_Output1_address parameter
The system tag is automatically generated by the TIA Portal when creating the expansion
module.
Note
For S7-300/400
For addressing data type HW_IO, refer to the section Data type HW_IO.
Input/Output parameters
Table 5- 7
Note
Data parameter
DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data” data type.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 27
SIMATIC STEP 7 function blocks
5.5 FB SITOP_BUF8600_MS
5.5 FB SITOP_BUF8600_MS
Function principle
The block reads data of the SITOP BUF8600 (100 ms/40 A and 300 ms/40 A) buffer
modules and writes it to the global transfer data block.
Block diagram
Figure 5-9
Function characteristics
Figure 5-10
Input parameters
Table 5- 8
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
28 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.5 FB SITOP_BUF8600_MS
Note
For S7-300/400
For addressing data type HW_IO, refer to the section Data type HW_IO (Page 20).
Input/Output parameters
Table 5- 9
Note
Data parameter
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" checkbox.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data" data type.
Output parameters
Table 5- 10
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 29
SIMATIC STEP 7 function blocks
5.6 FB SITOP_PSU8600_MainUnit
5.6 FB SITOP_PSU8600_MainUnit
Function principle
The block reads the main-module-specific data from the global DB for data exchange and
supplies it at its output parameters.
On request, the block writes main-module-specific data first into the Cyclic Output Memory
area (if address is provided) and then into the PSU8600 device.
Block Diagram
Figure 5-11
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
30 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.6 FB SITOP_PSU8600_MainUnit
Function characteristics
Figure 5-12
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 31
SIMATIC STEP 7 function blocks
5.6 FB SITOP_PSU8600_MainUnit
Input parameters
Table 5- 11
Table 5- 12
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
32 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.6 FB SITOP_PSU8600_MainUnit
Input/Output parameters
Table 5- 13
Note
Data parameter
DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data" data type.
Output parameters
Table 5- 14
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 33
SIMATIC STEP 7 function blocks
5.6 FB SITOP_PSU8600_MainUnit
Table 5- 15
Table 5- 16
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
34 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.6 FB SITOP_PSU8600_MainUnit
Table 5- 17
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 35
SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
5.7 FB SITOP_PSU8600_Output
Function principle
The block reads the output-specific data of PSU8600/CNX8600 from the global DB for data
exchange and supplies it at its output parameters.
On request, the block writes output-specific data into the PSU8600/CNX8600.
Note
For S7-300/400
Input Parameters are different for S7-300/400 controllers. For addressing data type HW_IO,
refer section Data type HW_IO (Page 20).
Block diagram
Figure 5-13
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
36 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
Function characteristics
Figure 5-14
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 37
SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
Input parameters
Table 5- 18
Table 5- 19
Input/Output parameters
Table 5- 20
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
38 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
Note
Data parameter
DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data" data type.
Output parameters
Table 5- 21
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 39
SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
Table 5- 22
Table 5- 23
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
40 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.8 FB SITOP_PSU8600_S/SITOP_PSU8600_S1
5.8 FB SITOP_PSU8600_S/SITOP_PSU8600_S1
Function principle
The block reads data of the PSU8600 main module (single power supply with 1 output
channel) and writes it to the global transfer data block.
Note
SITOP_PSU8600_S is compatible with Firmware version 1.1 - 1.3.
SITOP_PSU8600_S1 is compatible with Firmware version 1.4
Block diagram
Figure 5-15
Function characteristics
Figure 5-16
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 41
SIMATIC STEP 7 function blocks
5.8 FB SITOP_PSU8600_S/SITOP_PSU8600_S1
Input parameters
Table 5- 24
Note
For S7-300/400
For addressing data type HW_IO, refer section Data type HW_IO (Page 20).
Input/Output parameters
Table 5- 25
Note
Data parameter
DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" checkbox.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data” data type.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
42 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.9 FB SITOP_BUF8600_S
5.9 FB SITOP_BUF8600_S
Function principle
The block reads data of the SITOP BUF8600 (4 s/40 A and 10 s/40 A) buffer modules and
writes it to the global transfer data block.
Block diagram
Figure 5-17
Function characteristics
Figure 5-18
Input parameters
Table 5- 26
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 43
SIMATIC STEP 7 function blocks
5.9 FB SITOP_BUF8600_S
Note
For S7-300/400
For addressing data type HW_IO, refer section Data type HW_IO (Page 20).
Input/Output parameters
Table 5- 27
Note
Data parameter
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
General > Attributes, clear the "Optimized block access" checkbox.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data” data type.
Output parameters
Table 5- 28
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
44 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.9 FB SITOP_BUF8600_S
Structure of UDT_BUF8600_S_OUT
Table 5- 29
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 45
SIMATIC STEP 7 function blocks
5.10 FB SITOP_PSU8600_MainUnitSingle
5.10 FB SITOP_PSU8600_MainUnitSingle
Function principle
This block is used for SITOP PSU8600 with single output only. The block reads the main-
module-specific data from the global DB for data exchange and supplies it at its output
parameters.
On request, the block writes main-module-specific data first into Cyclic Output Memory area
(if address is provided) and then into the PSU8600 device.
Block diagram
Figure 5-19
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
46 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.10 FB SITOP_PSU8600_MainUnitSingle
Function characteristics
Figure 5-20
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 47
SIMATIC STEP 7 function blocks
5.10 FB SITOP_PSU8600_MainUnitSingle
Input parameters
Table 5- 30
Table 5- 31
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
48 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.10 FB SITOP_PSU8600_MainUnitSingle
Input/Output parameters
Table 5- 32
Note
Data parameter
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" checkbox.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data" data type.
Output parameters
Table 5- 33
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 49
SIMATIC STEP 7 function blocks
5.10 FB SITOP_PSU8600_MainUnitSingle
Table 5- 34
Table 5- 35
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
50 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.10 FB SITOP_PSU8600_MainUnitSingle
Table 5- 36
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 51
SIMATIC STEP 7 function blocks
5.11 FB SITOP_PSU8600_Buffering
5.11 FB SITOP_PSU8600_Buffering
Function principle
The block reads the main-module-specific data for buffering from the global DB for data
exchange and supplies it at its output parameters.
On request, the block writes main-module-specific data first into Cyclic Output Memory area
(if address is provided) and then into the PSU8600 device.
Block diagram
Figure 5-21
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
52 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.11 FB SITOP_PSU8600_Buffering
Function characteristics
Figure 5-22
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 53
SIMATIC STEP 7 function blocks
5.11 FB SITOP_PSU8600_Buffering
Input parameters
Table 5- 37
Table 5- 38
Input/output parameters
Table 5- 39
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
54 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.11 FB SITOP_PSU8600_Buffering
Note
Data parameter
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" checkbox.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data" data type.
Output parameters
Table 5- 40
Table 5- 41
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 55
SIMATIC STEP 7 function blocks
5.12 FB SITOP_UPS8600
5.12 FB SITOP_UPS8600
Function principle
The block reads the data from UPS8600 and stores in the global DB for data exchange and
supplies it at its output parameters.
On request, the block writes UPS8600-module-specific data first into Cyclic Output Memory
area (if address is provided) and then into the UPS8600 device.
Block diagram
Figure 5-23
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
56 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.12 FB SITOP_UPS8600
Function characteristics
Figure 5-24
Table 5- 42
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 57
SIMATIC STEP 7 function blocks
5.12 FB SITOP_UPS8600
Table 5- 43
Table 5- 44
Input/output parameters
Table 5- 45
Note
Data parameter
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" checkbox.
(Reference, symbolic name of the DB for global data exchange)
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
58 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.12 FB SITOP_UPS8600
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data" data type.
Output parameters
Table 5- 46
Table 5- 47
Table 5- 48
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 59
SIMATIC STEP 7 function blocks
5.12 FB SITOP_UPS8600
Table 5- 49
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
60 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.13 FB SITOP_PSU8600_Buffering_1
5.13 FB SITOP_PSU8600_Buffering_1
Function principle
The block reads the main-module-specific data for buffering from the global DB for data
exchange and supplies it at its output parameters.
On request, the block writes main-module-specific data first into Cyclic Output Memory area
(if address is provided) and then into the PSU8600 device.
Block diagram
Figure 5-25
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 61
SIMATIC STEP 7 function blocks
5.13 FB SITOP_PSU8600_Buffering_1
Function characteristics
Figure 5-26
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
62 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.13 FB SITOP_PSU8600_Buffering_1
Input parameters
Table 5- 50
Table 5- 51
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 63
SIMATIC STEP 7 function blocks
5.13 FB SITOP_PSU8600_Buffering_1
Input/output parameters
Table 5- 52
Note
Data parameter
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" checkbox.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data" data type.
Output parameters
Table 5- 53
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
64 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.14 FB SITOP_BAT_3P
5.14 FB SITOP_BAT_3P
Function principle
The block reads data from third-party battery and supplies it at its output parameters. On
request, the block writes general data to the third party battery.
Block diagram
Figure 5-27
Function characteristics
Figure 5-28
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 65
SIMATIC STEP 7 function blocks
5.14 FB SITOP_BAT_3P
Input parameters
Table 5- 55
Table 5- 56
Output parameters
Table 5- 57
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
66 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.14 FB SITOP_BAT_3P
Table 5- 58
Table 5- 59
Input/Output parameters
Table 5- 60
Note
Data parameter
DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 67
SIMATIC STEP 7 function blocks
5.14 FB SITOP_BAT_3P
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data” data type.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
68 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.15 FB SITOP_BAT8600
5.15 FB SITOP_BAT8600
Function principle
The block reads data from BAT8600 LiFePO4 and Pb batteries.
Block diagram
Figure 5-29
Function characteristics
Figure 5-30
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 69
SIMATIC STEP 7 function blocks
5.15 FB SITOP_BAT8600
Input parameters
Table 5- 61
Output parameters
Table 5- 62
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
70 Function Manual, 09.2018, A5E37763954-08-76
SIMATIC STEP 7 function blocks
5.15 FB SITOP_BAT8600
Input/Output parameters
Table 5- 65
Note
Data parameter
DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
For S7-300/400 controllers, the procedure may change.
1. In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
2. Select the symbolic name of your data block. A list of global DB contents is displayed.
3. Select "UDT_PSU8600_Data” data type.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 71
SIMATIC STEP 7 function blocks
5.16 UDT_PSU8600_Data
5.16 UDT_PSU8600_Data
Structure of UDT_PSU8600_Data
Figure 5-31
Note
For S7-1200/1500
Parameter "PSUModulestatus" does not exist in S7-1200/1500 systems.
Purpose of UDT_PSU8600_Data
The UDT provides the structure in the global data block for data exchange.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
72 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates 6
6.1 Introduction
Variants
The library contains two basic variants of the function blocks for faceplates:
● Comfort Panels and WinCC Runtime Advanced
● WinCC Runtime Professional
In addition to faceplates, UDTs for data connection of faceplates and SIMATIC STEP 7
blocks are also contained.
UDTs are different for the controller types:
● S7-1200
● S7-1500
● S7-300
● S7-400
Note
The WinCC UDTs are principally identical. However, when creating an HMI UDT, the
destination controller must be specified, which makes it subject to the controller types.
Navigation
Faceplates offer various views, these views can be switched through a two-layer navigation.
Primary navigation to individual information types is located at the top of the screen.
Secondary navigation towards individual SITOP PSU8600 modules is located on the left
hand side of the faceplate.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 73
WinCC Faceplates
6.1 Introduction
Figure 6-1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
74 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.2 View: State, main module
Figure 6-2
Elements
Table 6- 1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 75
WinCC Faceplates
6.2 View: State, main module
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
76 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.3 View: State, UPS8600
Figure 6-3
Elements
Table 6- 2
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 77
WinCC Faceplates
6.3 View: State, UPS8600
Table 6- 3
Screen: Other view when UPS8600 connected battery summary information is shown
Figure 6-4
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
78 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.3 View: State, UPS8600
Elements
Table 6- 4
Figure 6-5
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 79
WinCC Faceplates
6.3 View: State, UPS8600
Elements
Table 6- 5
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
80 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.3 View: State, UPS8600
Figure 6-6
Elements
Table 6- 6
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 81
WinCC Faceplates
6.3 View: State, UPS8600
Figure 6-7
Elements
Table 6- 7
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
82 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.4 View: State, expansion modules
Figure 6-8
Figure 6-9
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 83
WinCC Faceplates
6.4 View: State, expansion modules
Figure 6-10
Elements
Table 6- 8
Screen area Parameter Description
CNX8600 Operating state The operating state displays various colors depending on the
information and <Text field> state of CNX8600.
The <text field> displays the operating state as plain text.
Text Number Color
off 0 White
Shutdown after error 1 Red
Ready for restart 2 Red,
flashing
Startup 3 White
Normal operation 4 Green
Buffer mode 5 Yellow
Out Output information If CNX8600_8X module is connected, you can select outputs 1 to
1-4, 5-8 4 by clicking on "1-4" button and to select outputs 5 to 8, you can
click on "5-8" button.
Uout [V]; (output n) Displays the output voltage of output n in Volts.
Iout [A]; (output n) Displays the load current of output n in Ampere.
State; (output n) Shows the state of output n. The following states are displayed:
Description Color
Switched off manually. Yellow
Ready to start. The power supply can be switched Red,
back on. (For example, switched off remotely or after flashing
overload with idle time.)
The output was switched off due to an error. Red
Normal operation of the output. Green
The channel in overload. (The channel can supply a Green,
higher current for a limited period of time, or the chan- flashing
nel is in current-limiting mode.)
The diagnostic LED at device or web server is flashing
in varying frequencies and can help determine the
type of overload.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
84 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.5 View: State, buffer modules
Figure 6-11
Figure 6-12
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 85
WinCC Faceplates
6.5 View: State, buffer modules
Elements
Table 6- 9
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
86 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.6 View: State, Information
Figure 6-13
Elements
Table 6- 10
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 87
WinCC Faceplates
6.7 View: Trends, main module
Figure 6-14
Element
Table 6- 11
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
88 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.8 View: Trends, expansion modules
Figure 6-15
Figure 6-16
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 89
WinCC Faceplates
6.8 View: Trends, expansion modules
Elements
Table 6- 12
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
90 Function Manual, 09.2018, A5E37763954-08-76
WinCC Faceplates
6.9 View: Trends, UPS8600
Figure 6-17
Element
Table 6- 13
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 91
WinCC Faceplates
6.10 View: Alarms
Screen: Alarms
Figure 6-18
Elements
● Pending alarms
Displays the currently pending alarms.
● Alarm history
Displays the history of the alarm.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
92 Function Manual, 09.2018, A5E37763954-08-76
Working with the library 7
7.1 Opening the library in TIA Portal
Procedure
To open the library, follow the instructions given below.
Table 7- 1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 93
Working with the library
7.1 Opening the library in TIA Portal
4 Click "Open". The library opens and is displayed in the "Global libraries" palette.
Note
For S7-300/400
When using S7-300/400 controllers, use appropriate library elements from the respective
library folders.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
94 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.2 SIMATIC STEP 7
Hardware requirements
● CPU 1214C DC/DC/RLY
● SITOP PSU8600
● TP1200 Comfort
System requirements
You have created your TIA Portal project and completed hardware and network
configurations.
● Hardware configuration
– SITOP power supply (including the expansion modules)
– Controller
● Network configuration
– PROFINET connection between the controller and SITOP power supply
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 95
Working with the library
7.2 SIMATIC STEP 7
Table 7- 2
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
96 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.2 SIMATIC STEP 7
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 97
Working with the library
7.2 SIMATIC STEP 7
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
98 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.2 SIMATIC STEP 7
Note
The function blocks work properly with both, English and German mnemonics. In case the
source code of the function blocks is required for a project, consider the following
constraints:
• In case the language setting of your project is English, then the source code of the
function blocks can be used as it is.
• In case the language setting of your project is German, then the entries IB (Input Byte)
and IW (Input Word) of the sources have to be replaced with EB (EingangsByte)
Note
You can now use the blocks you need. However, there are some dependencies.
• Function blocks SITOP_PSU8600 or SITOP_PSU8600_S depending on the type must
always be available and called.
• If SITOP outputs of an expansion module shall be processed with the
"SITOP_PSU8600_Output" block, then block "SITOP_CNX8600 / SITOP_CNX8600_8X"
must also exist for the respective module and be called.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 99
Working with the library
7.2 SIMATIC STEP 7
Table 7- 3
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
100 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.2 SIMATIC STEP 7
Note
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB of your project in the "Project tree" window and select "Properties". Navigate to
"General > Attributes", clear the "Optimized block access" checkbox.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 101
Working with the library
7.2 SIMATIC STEP 7
Calling up blocks
Table 7- 4
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
102 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.2 SIMATIC STEP 7
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 103
Working with the library
7.2 SIMATIC STEP 7
Note
Use the predefined UDTs (refer respective function block description for which UDT is to be
used) for different input and output parameters to create necessary data fields in the DBs.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
104 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.2 SIMATIC STEP 7
Note
If your communication blocks are called cyclically (example. in OB1), results in a slow
behavior of the web server integrated in SITOP PSU8600 due to high communication load.
If there aren’t any high demands regarding accurate time behavior, you can also call the
communication blocks in a time-controlled block (example. OB35).
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 105
Working with the library
7.3 WinCC Comfort/Advanced
System requirements
You have created your TIA Portal project and the hardware and network configurations are
completed.
● Hardware configuration
– SITOP power supply (including the expansion modules)
– Controller
– HMI operator panel (Comfort Panel or Runtime Advanced)
● Network configuration
– PROFINET connection between controller and SITOP power supply
– HMI connection between controller and operator panel
You have integrated the SIMATIC STEP 7 blocks into your control project. (See chapter
Integrating the library blocks into SIMATIC STEP 7 (Page 95))
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
106 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.3 WinCC Comfort/Advanced
Inserting faceplates
Follow these steps to insert faceplates:
Table 7- 5
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 107
Working with the library
7.3 WinCC Comfort/Advanced
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
108 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.3 WinCC Comfort/Advanced
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 109
Working with the library
7.3 WinCC Comfort/Advanced
7.3.2 Creating a connection to the data block for global data exchange
Procedure
Follow these steps to create a connection to the data block for global data exchange:
Table 7- 6
3 Select required connection for the controller and the operator panel.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
110 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.3 WinCC Comfort/Advanced
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 111
Working with the library
7.3 WinCC Comfort/Advanced
Introduction
Connect the trends to the data sources of the individual outputs. This graphically displays the
power consumption of the individual outputs over time.
Table 7- 7
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
112 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.3 WinCC Comfort/Advanced
5 Select the trend colors for the individual outputs according to the legend.
Assign the following colors so they match the legend of the faceplate.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 113
Working with the library
7.3 WinCC Comfort/Advanced
If you are using CNX8600 8X expansion modules ensure to add 4 more trends and ensure the following
HMI tags are mapped:
CNX8600 module1: CNX1_Output5_Trend_Current to CNX1_Output8_Trend_Current
CNX8600 module2: CNX2_Output5_Trend_Current to CNX2_Output8_Trend_Current
CNX8600 module3: CNX3_Output5_Trend_Current to CNX3_Output8_Trend_Current
CNX8600 module4: CNX4_Output5_Trend_Current to CNX4_Output8_Trend_Current
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
114 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.3 WinCC Comfort/Advanced
Select left side axis for SOC and right side axis for Pcharge.
Note
Follow the same procedure for PSU8600 Single Power Supply Device where one trend has
to be created.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 115
Working with the library
7.3 WinCC Comfort/Advanced
Table 7- 8
3 Enable the“S7 diagnostic alarms” and “With event text” check boxes.
Note
When configuring an S7-300/400 controller in TIA Portal, you also need to activate the S7
diagnostic alarm on the controller side. For more details see Configuration of Messages and
Alarms in WinCC (TIA Portal)
(https://support.industry.siemens.com/cs/ww/en/view/62121503).
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
116 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.3 WinCC Comfort/Advanced
Table 7- 9
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 117
Working with the library
7.3 WinCC Comfort/Advanced
4 Drag-and-drop the "Alarm windows" library element into your global screen.
The alarm displays for pending and historical alarms are created.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
118 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.3 WinCC Comfort/Advanced
Table 7- 10
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 119
Working with the library
7.3 WinCC Comfort/Advanced
4 Repeat step 3 for the HMI tag you linked to the control tag "AlarmPending" and click "Properties > Events"
tab.
Insert the "ShowAlarmWindow" action and select "Alarmview_PSU_pending" as the object.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
120 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.4 WinCC Professional
Prerequisites
You have created your TIA Portal project and the hardware and network configurations are
completed.
● Hardware configuration
– SITOP power supply (including the expansion modules)
– Controller
– HMI operator panel (Comfort Panel or Runtime Advanced)
● Network configuration
– PROFINET connection between controller and SITOP power supply
– HMI connection between controller and operator panel
You have integrated the SIMATIC STEP 7 blocks into your control project. (See chapter
Integrating the library blocks into SIMATIC STEP 7 (Page 95))
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 121
Working with the library
7.4 WinCC Professional
Procedure
Follow these steps to insert HMI tag table in WinCC:
Table 7- 11
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
122 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.4 WinCC Professional
4 Drag-and-drop the library element "Tag Table-1200_Professional" into the "HMI tag" folder.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 123
Working with the library
7.4 WinCC Professional
Table 7- 12
3 For the "PSU_Data" tag, define the address of the data block for global data exchange.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
124 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.4 WinCC Professional
Table 7- 13
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 125
Working with the library
7.4 WinCC Professional
4 Drag-and-drop the "PSU8600_Professional" library element to the "Screens" folder of your WinCC project.
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
126 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.4 WinCC Professional
Table 7- 14
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 127
Working with the library
7.4 WinCC Professional
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
128 Function Manual, 09.2018, A5E37763954-08-76
Working with the library
7.4 WinCC Professional
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1 and V15 (TIA)
Function Manual, 09.2018, A5E37763954-08-76 129