Beruflich Dokumente
Kultur Dokumente
Abstract—The microgrid is a very effective way of inte- the transient and steady state power flow without any commu-
grating various distributed generation resources into the AC nication. This is a significant advantage in terms of system
power system. To provide electric power of high reliability, the reliability.
converters in the microgrid often rely on autonomous droop
control methods to reduce their dependency on communication,
and need to operate in both the islanded mode or the grid- Traditionally, the real power-frequency droop (P −ω droop)
connected mode. In this paper, a grid synchronization method for control and the reactive power-voltage droop (Q − V droop)
a multi-converter distributed generation system is proposed. The are generally adopted in the droop controlled DGS [6], [7],
proposed grid synchronization method allows multiple droop- [8]. The P − ω droop control can achieve accurate real power
controlled converters to adjust the frequency, phase, and am-
plitude of their output voltages to prepare for grid connection. sharing results. However, the Q − V droop control is highly
The entire synchronization process can be executed with very dependent on the line impedances seen from the converters
limited communication requirement. This paper provides detailed [9], [10]. Therefore, the Q − V̇ droop control method has
explanation on the proposed grid synchronization method. Ex- been proposed to overcome the impedance mismatch among
perimental test results are presented to validate the effectiveness converters and achieve better proportional sharing of reactive
of the proposed method.
power [11].
Index Terms—Distributed generation systems, droop control,
grid synchronization, Microgrid. To ensure the uninterrupted operation of its critical loads,
the microgrid must be capable of operating in both the grid-
connected mode and the islanded mode, and offer a smooth
I. I NTRODUCTION
transition between these two modes. Thus the grid synchro-
In the pursuit of low carbon emissions, renewable en- nization, which prepares islanded microgrid for grid connec-
ergy resources, such as solar power, and wind power, have tion, is a critical procedure of the entire operation. The grid
been widely adopted in recent years. Other alternative en- synchronization method has been elaborately discussed for
ergy resources have also become significant research topics. single grid-connected converter [5], [12], [13], [14]. However,
Considering their generation scale and characteristics, the it is not often explored for multi-converter oriented systems or
most effective way to utilize these alternative resources is to droop controlled DGS. Droop controllers are adopted in [15],
integrate them into a distributed generation system (DGS). The [16] during their islanded operation. However, during the grid
microgrid, for example, has demonstrated this concept very synchronization, the droop controllers are restrained and the
successfully [1], [2], [3]. power flow of converters are altered from their droop control
The control of distributed energy resources converters operating point in order to accommodate their synchronization
(DERCs) in DGS have been explored over the years. The design.
main approaches include the master-slave control [4], [5] and
autonomous droop control [6], [7], [8], [9], [10]. In the master- This paper proposes a grid synchronization method based on
slave framework, one converter in the DGS is assigned to be the frequency restoration and voltage restoration mechanism
the master, and it operates as a voltage stiff while the other of the P − ω and Q − V̇ droop controls [11]. The frequency,
converters in this system are controlled as current sources. the phase angle, and the magnitude of DERCs’ output voltages
This master converter acts as a virtual inertia [2], and will are smoothly adjusted so that the proportional sharing of active
pick up most dynamic power flows within the DGS. Therefore, power and reactive power among DERCs, an important feature
this master converter must be sufficiently large in its power of the droop controls, are not disturbed. To maintain the
capacity and sufficiently fast in its control bandwidth in order autonomous nature of the droop controls, a low bandwidth
to absorb all the transients in this system. A sophisticated communication is required only during the synchronization
communication network is also required to coordinate the process. A similar synchronization design had been presented
operations of all converters. On the other hand, the droop in [17] for a P − ω, Q − V droop controlled microgrid. A
control method allows multiple DERCs to proportionally share center-controlled frequency and voltage restoration mechanism
is required for its grid synchronization and for its islanded
C. -T Lee and P. -T. Cheng are with the Center for Adavanced mode operation, thus its dependency on the communication
Power Technologies, Department of Electrical Engineering, National Ts- increases. Test results are provided to illustrate the operation
ing Hua University, Hsinchu, 30013, TAIWAN (email: atonis5@gmail.com;
ptcheng@ieee.org). R. -P. Jiang is with the Taiwan Army (email: of the proposed grid synchronization method under low band-
g9761586@oz.nthu.edu.tw). width communication.
Distributed Generation System
PWM Bypass Switch Utility Grid
gate V1 θ1 R1+jX1
Autonomous signal
controller 1 Lf1
Cf1
i1,abc
v1,abc Sensor feedback
DERC1 Load Communication signal
PWM
gate V2 θ2 R2+jX2 vPCC,abc vG,abc Switch CLOSE/OPEN signal
Autonomous signal
controller 2 Lf2
Cf2
i2,abc Main controller
v2,abc
DERC2
operation
mode control
ωG,θdiff,Vdiff
Central console
DGS
Frequency and phase angle difference detection Control signals of bypass switch
Main controller
Autonomous controller x
Fig. 3. Control block diagram of autonomous controller.
2π·60 ω0x
horizontally in a dynamic sense. As the loading within the Operation FR=1
FR=0
DGS remains unchanged, this adjustment leads to the change mode control Px,FR=1
Px S/H FR=1
P0x
of operating frequency ω x and the phase angle of DERCx’s PRx FR=0
output voltage. Eventually this PI regulator settles into the Frequency restoration
steady state when θdif f become zero, which means v P CC ΔP0x
and vG are synchronized in both their frequencies and phase θdiff PS=1
PRx kp,Psyn
angles, and DERCx operates based on Equation (3) with 0 PS=0
ΔPx = 0. ki,Psyn 1
s
In the proposed phase angle synchronization control, θ dif f Phase angle synchronization
is first multiplied by PRx before being fed into the PI regulator
for the reason that the adjustment of the real power set- Fig. 5. Frequency restoration and phase angle synchronization controller.
points should be in proportion to their converter’s real power
capacities. This ensures that the same frequency change is
introduced for all the DERCx while their individual droop
lines are shifted. Therefore the relative phase angle differences
among all the DERCs are kept unchanged, and the proportional ω Droop line of islanded mode
After frequency restoration
real power sharing in the islanded mode can also be maintained During phase angle synchronization
[rad/sec]
377.1
377
376.9
V. E XPERIMENTAL T EST R ESULTS 376.8
0 10 20 30 40 50 60 70 80 90 100
The DGS test bench shown in Fig. 10 is constructed to 377.2 ωP CC
[rad/sec]
377.1
validate the effectiveness of the proposed grid synchronization 377
control method. Two DERCs are installed in the testbench in 376.9
376.8
the same configuration as in Fig. 1. The detailed descriptions 0 10 20 30 40 50 60 70 80 90 100
[rad]
0.2
• The system voltage is V L−L = 220 Vrms, and the 0
frequency is 60 Hz. The power line impedances are R 1 + −0.2
0 10 20 30 40 50 60 70 80 90 100
jX1 = 1+j0.754 Ω and R2 +jX2 = 1+j0.754 Ω. A total 15 Vdif f
of 1000 W and 200 VAR are made up by resistor loads 10
[V]
5
and an unloaded induction machine. The bypass switch 0
−5
is implemented by anti-parallel connected thyristors. 0 10 20 30 40 50 60 70 80 90 100
Time[sec]
• The DERCs are three-phase, hard-switched PWM con-
verters switching at f switch = 10 kHz. The output filter (a)
inductor is Lf = 2 mH, and the output filter capacitor is FR = 1 PS = 1 Islanded operation
Step load changes V S = 1 Bypass switch closes
Cf = 10 μF. The 400Vdc bus of the DERC is supported t1 t2 t3 t4 t5
1000
by a DC power supply. 750
[W]
500
• The main controller and the autonomous controllers 250
0 P1 P2
are implemented with the digital signal processor 0 10 20 30 40 50 60 70 80 90 100
TMS320F28335 individually, and the sampling frequency 377.2 ω1 ,ω2
[rad/sec]
0
−3000
P01
console, main controller, and autonomous controllers. −6000
−9000
0 10 20 30 40 50 60 70 80 90 100
The bandwidth of these communication units are set at x 10
−3
5
approximately 152 Hz. θ1 − θ2
[rad]
0
Fig. 11 shows the experimental test results of the proposed −5
100
operate in parallel with DERC1 in the islanded mode opera- 50
Q1 Q2
tion. Load changes are introduced by line-starting an induction 0
0 10 20 30 40 50 60 70 80 90 100
motor and connecting a resistor load bank. P 1 = 472 W, 50
40
[V/sec]
8000
voltage magnitudes, thus V dif f and θdif f in Fig. 11(a) exhibit 4000
certain variations when the inductive load and the resistive 0
−4000
0 10 20 30 40 50 60 70 80 90 100
load are added.
184
At t = t1 , the central console issues the command of
181
[V]
Main controller
PLL kpllp = 0.025 rad/Vsec, kplli = 0.75 rad/Vsecsec
Autonomous controllers
Section IV Section V
P − ω droop control m1 = 2 · m2 = −18.85 × 10−6 rad/Wsec m1 = m2 = −18.85 × 10−6 rad/Wsec
Rated real power capacity 2 · PR1 = PR2 = 2.0 kW PR1 = PR2 = 1.0 kW
Q − V̇ droop control n1 = 2 · n2 = −8.0 × 10−3 V/VARsec n1 = n2 = −2.0 × 10−3 V/VARsec
Rated reactive power capacity 2 · QR1 = QR2 = 2.0 kVAR QR1 = QR2 = 1.0 kVAR
V̇ restoration kp,Qres = 0.025 V−1
Phase angle synchronization kp,P syn = 20.0 rad−1 , ki,P syn = 15.0 rad−1 sec−1
Voltage magnitude equalization kp,Qsyn = 1.0 sec/V, ki,Qsyn = 1.0 V−1
Synchronous voltage PI controller kV p = 0.04 A/V, kV i = 6.0 A/Vsec
Predictive current controller kC = 30.0 V/A
Autonomous
DERC1 controller 1 connection mode smoothly with little transients. The system
operates in the grid connection mode for nearly one minute.
Autonomous
At t = t5 , the central console commands the DGS to go back
controller 2
DERC2 into the islanded mode.
As shown in Fig. 11(b), the grid synchronization process
Central between t1 and t4 does not affect the power sharing accom-
Thyristor-based
bypass switch console plished by the droop controls in the islanded operation. This
outcome shows that the proposed grid synchronization method
DC Main effectively preserve the relative phase angle difference and
sources controller voltage magnitude difference between DERC1 and DERC2
while adjusting their operation frequencies and output voltage
Line Load
impedances
magnitudes.
Test results in Fig. 11(b) shows errors in the sharing of
Fig. 10. The constructed DGS in the laboratory. real power and reactive power. The finite resolution of the
phase angle look up table (2π × 10 −3 rad) with respect to
the droop slope (m 1 , m2 ) can be one potential cause. The
VAR consumption of the filter capacitor must be removed from
At t = t2 , the central console initiates the voltage equal- the reactive power calculation before the Q − V̇ controller.
ization (V S = 1). The positive V dif f in Fig. 11(a) raises the However, it is estimated based on the capacitor name plate
reactive power set-points Q 01 and Q02 in DERC1 and DERC2 value, thus the reactive power calculation may have certain
respectively. This leads to positive V˙1 and V˙2 in their Q − V̇ errors. The unbalance within the testbench, which comes from
droop controls so their output voltage magnitude increases, the filter inductors, filter capacitors, and the three-phase line
and then the PCC voltage magnitude rises to match the chokes which emulate the power line impedance, may also
grid voltage magnitude and complete the voltage magnitude contribute to the power sharing errors.
equalization. In the meantime, the output power of DERCs are Note that DERCs’ real power output P 1 , P2 , and reactive
increased as P1 = 452 W, P2 = 640 W, Q1 = 123 VAR, and power output Q 1 , Q2 show certain deviations in the grid-
Q2 = 100 VAR as a result of the raised voltage magnitude. connected mode as shown in Fig. 11(b). A power flow con-
At t = t3 , the central console starts the phase angle trol [17] at PCC can be implemented in the central console to
synchronization (P S = 1). The real power set-points P 01 and adjust the droop control set-points of autonomous controllers
P02 of DERC1 and DERC2 increases as a result of the positive to mitigate such problems.
θdif f at this moment. The operating frequencies of DERCs go Fig. 12 compares the line-to-line voltages of the util-
up because of their P − ω droop controls, and the phase angle ity grid, PCC, DERC1, and DERC2 at various instances.
of vP CC gradually catches up with the phase angle of v G and After the frequency restoration is accomplished, v G,ab and
reduce θdif f to zero. As the grid synchronization completes, vP CC,ab have the same frequency, and v G,ab leads ahead
the power sharing of DERCs is maintained at P 1 = 496 W, of vP CC,ab by 85.8◦ . The voltage magnitude difference be-
P2 = 610 W, Q1 = 121 VAR, and Q2 = 95 VAR. tween |vG,ab | = 212.6 Vrms and |vP CC,ab | = 206.7 Vrms
At t = t4 , the central console confirms that the grid is also obvious. After the voltage magnitude equalization is
synchronization is accomplished, v P CC and vG are matched completed, The magnitude difference is effectively eliminated
in their frequencies, phase angles, and magnitude. So the and these voltage magnitudes become |v G,ab | = 214.0 Vrms
command of grid-connection is issued to the main controller. and |vP CC,ab | = 215.0 Vrms. By commencing the phase
The bypass switch is closed and the DGS enters the grid angle synchronization, the phase angle difference driven down
Voltage magnitude Bypass switch Voltage magnitude Bypass switch
equalization is closed equalization is closed
2 DERCs Frequency Phase angle 2 DERCs Frequency Phase angle
Islanded mode Islanded mode
are connected restoration synchronization are connected restoration synchronization
t0 t1 t2 t3 t4 t5 t0 t1 t2 t3 t4 t5
ωG ωG
377 377
4rad/sec 4rad/sec
θdiff
θdiff
0 0
4rad 4rad
Vdiff
0 Vdiff 0
10V 10V
ωPCC
377 377
ωPCC 20sec
4rad/sec
20sec
4rad/sec
(a) Detected information in the main controller. (ωG , ωP CC : X-axis: (a) Information in the main controller during the grid synchronization
20s/div, Y-axis: 4rad/sec/div; θdif f : X-axis: 20s/div, Y-axis: 4rad/div; process with 91 Hz communication bandwidth.
Vdif f : X-axis: 20s/div, Y-axis: 10V /div) Voltage magnitude Bypass switch
Voltage magnitude Bypass switch equalization is closed
2 DERCs Frequency Phase angle
equalization is closed Islanded mode
are connected restoration synchronization
2 DERCs Frequency Phase angle
are connected restoration synchronization
Islanded mode t0 t1 t2 t3 t4 t5
t0 t1 t2 t3 t4 t5 ωG
377
4rad/sec
0 1kW
0 θdiff
Load change P1 P2 4rad
0
1kVAR Vdiff
0
Load change Q1 Q2 10V
0 ωPCC
50kW
377
P01 P02 4rad/sec
20sec
0
20sec 20kVAR
Q01 Q02
(b) Information in the main controller during the grid synchronization
(b) Responses in the DERCs. (P1 , P2 : X-axis: 20s/div, Y-axis: 1kW/div; process with 65 Hz communication bandwidth.
Q1 , Q2 : X-axis: 20s/div, Y-axis: 1kV AR/div; P01 , P02 : X-axis: 20s/div,
Y-axis: 50kW/div; Q01 , Q02 : X-axis: 20s/div, Y-axis: 20kV AR/div) Fig. 13. Experimental test results with different communication band-
width. (ωG , ωP CC : X-axis: 20s/div, Y-axis: 4rad/sec/div; θdif f : X-axis:
Fig. 11. Experimental test results of grid synchronization process as the 20s/div, Y-axis: 4rad/div; Vdif f : X-axis: 20s/div, Y-axis: 15V /div)
rated power capacities of DERCs are the same.
VI. C ONCLUSION
The proposed method maintains the phase angles relation-
ship and voltage magnitude relationship among DERCs during
to zero. At this point, v G,ab and vP CC,ab have the same the synchronization process, therefore the proportional power
frequency, the same phase angle, and the same magnitude, sharing accomplished in the islanded operation mode can be
so their waveforms are closely matched. Finally the bypass maintained. Laboratory test results show the frequency, the
switch is closed and the DGS becomes grid-connected. phase angle and the magnitude of the PCC voltage are matched
to those of the grid voltage without disturbing the real and
The proposed method achieves the grid synchronization by reactive power output of DERCs, and then the DGS moves into
transmitting the PCC information from the main controller to the grid- connected mode smoothly. The proposed method is
the central console, and then to the autonomous controllers built upon the foundation of the P − ω and Q − V̇ droop
through the RS-232 communication links. Fig. 13 shows the controls of the autonomous controller within each DERC.
grid synchronization test results of the proposed method under The central console only transmits the frequency, phase angle
slow communication with equivalent bandwidth of 91 Hz and voltage magnitude. Based on these information, the au-
and 65 Hz. Test results show that the proposed method can tonomous controller fine-tunes the droop control set-point, and
accomplish the grid synchronization operation even with the manipulates the output voltage of its DERC. This architecture
low-bandwidth communication. uphold the autonomous nature of the DGS by constraining the
Bypass switch closes
Islanded mode
P-ω, Q-V Frequency Voltage magnitude Phase Grid-connected mode
droop control restoration equalization synchronization
time
After frequency restoration After voltage magnitude equalization After phase angle synchronization After grid connection
0
vG,ab vPCC,ab 200V vG,ab vPCC,ab 200V vG,ab, vPCC,ab 200V vG,ab, vPCC,ab 200V
10msec 10msec 10msec 10msec
0
vDERC1,ab , vDERC2,ab 0
vDERC1,ab , vDERC2,ab vDERC1,ab , vDERC2,ab vDERC1,ab , vDERC2,ab
Fig. 12. The variations of line-to-line voltage of the utility grid, PCC, DERC1, and DERC2 during the grid synchronization process. (VG,ab , VP CC,ab ,
VDERC1,ab , VDERC2,ab : X-axis: 10ms/div, Y-axis: 200V /div)
role of the central console in the synchronization process. Thus [12] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, “Overview
the proposed method can operate with the very low bandwidth of control and grid synchronization for distributed power generation
systems,” IEEE Transactions on Industrial Electronics, vol. 53, no. 5,
communication. pp. 1398–1409, Oct. 2006.
[13] J. Rocabert, M. S. Azevedo, I. Candela, F. Blaabjerg, and P. Rodriguez,
“Connection and disconnection transients for micro-grids under unbal-
ACKNOWLEDGMENT ance load condition,” in Proc. IEEE Power Electronics and Applications
(EPE 2011), 2011-14th European Conference, 2011, pp. 1–9.
This research is funded by the National Science Council of [14] M. Rizo, E. Bueno, A. Dell’Aquila, M. Liserre, and R. A. Mastromauro,
Taiwan under grant NSC-98-2221-E-007-121-MY3. “Generalized controller for small wind turbines working grid-connected
and stand-alone,” in Proc. IEEE Clean Electrical Power (ICCEP), 2011,
2011, pp. 51–55.
R EFERENCES [15] Y. A. I. Mohamed and A. A. Radwan, “Hierarchical control system
for robust microgrid operation and seamless mode transfet in active
[1] R. Lasseter, “Microgrids,” in Proc. IEEE Power Engineering Society distribution systems,” IEEE Transactions on Smart Grid, vol. 2, no. 2,
Winter Meeting, 2002, pp. 305–308. pp. 352–362, Jun. 2011.
[2] M. Barnes, J. Kondoh, H. Asano, J. Oyarzabal, G. Ventakaramanan, [16] J. Kim, J. M. Guerrero, P. Rodriguez, R. Teodorescu, and K. Nam,
R. Lasseter, N. Hatziargyriou, and T. Green, “Real-world microgrids- “Mode adaptive droop control with virtual output impedances for an
an overview,” in IEEE International Conference on System of Systems inverter-based flexible ac microgrid,” IEEE Transactions on Power
Engineering, 2007, pp. 1–8. Electronics, vol. 26, no. 3, pp. 689–701, Mar. 2011.
[3] F. Katiraei, R. Iravani, N. Hatziargyriou, and A. Dimeas, “Microgrids [17] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. de Vicuna, and M. Castilla,
management,” IEEE Power and Energy Magazine, vol. 6, no. 3, pp. “Hierarchical control of droop-controlled ac and dc microgrids-a general
54–65, May./Jun. 2008. approach toward standardization,” IEEE Transactions on Industrial
[4] C. L. Chen, Y. Wang, J. S. Lai, Y. S. Lee, and D. Martin, “Design Electronics, vol. 58, no. 1, pp. 158–172, Jan. 2011.
of parallel inverters for smooth mode transfer microgrid applications,” [18] L. N. Arruda, S. M. Silva, and B. J. C. Filho, “Pll structures for utility
IEEE Transactions on Power Electronics, vol. 25, no. 1, pp. 6–15, Jan. connected systems,” in Proc. IEEE Industry Applications Conference,
2010. Thirty-Sixth IAS Annual Meeting, 2001, pp. 2655–2660.
[5] J. Rocabert, G. M. S. Azevedo, A. Luna, J. M. Guerrero, J. I. Can- [19] V. Kaura and V. Blasko, “Operation of a phase locked loop system
dela, and P. Rodriguez, “Intelligent connection agent for three-phase under distorted utility conditions,” IEEE Transactions on Industry Ap-
grid-connected microgrids,” IEEE Transactions on Power Electronics, plications, vol. 33, no. 1, pp. 58–63, Jan./Feb. 1997.
vol. 26, no. 10, pp. 2993–3005, Oct. 2011. [20] S. K. Chung, “A phase tracking system for three phase utility interface
[6] M. C. Chandrokar, D. M. Divan, and R. Adapa, “Control of parallel inverters,” IEEE Transactions on Industry Applications, vol. 15, no. 3,
connected inverters in standalone ac supply systems,” IEEE Transactions pp. 431–438, May 2000.
on Industry Applications, vol. 29, no. 1, pp. 136–143, Jan./Feb. 1993. [21] T. G. Habetler, “A space vector-based rectifier regulator for ac/dc/ac
[7] M. C. Chandrokar, D. M. Divan, and B. Banerjee, “Control of distributed converters,” IEEE Transactions on Power Electronics, vol. 8, no. 1, pp.
ups systems,” in Proc. IEEE Power Electronics Specialists Conference, 30–36, January 1993.
1994, pp. 197–204.
[8] P. Piagi and R. Lasseter, “Autonomous control of microgrids,” in Proc.
IEEE Power Engineering Society General Meeting, 2006, p. 8pp.
[9] J. M. Guerrero, L. G. de Vicuna, J. Matas, M. Castilla, and J. Miret,
“Output impedance design of parallel-connected ups inverters with wire-
less load-sharing control,” IEEE Transactions on Industrial Electronics,
vol. 52, no. 4, pp. 1126–1135, Aug. 2005.
[10] C. K. Sao and P. W. Lehn, “Autonomous load sharing of voltage source
converters,” IEEE Transactions on Power Delivery, vol. 20, no. 2, pp.
1009–1016, Apr. 2005.
[11] C. T. Lee, C. C. Chu, and P. T. Cheng, “A new droop control method
for the autonomous operation of distributed energy resource interface
converters,” in Proc. IEEE Energy Conversion Congress and Exposition
(ECCE), 2010, pp. 702–709.
Chia-Tse Lee was born in Tainan, Taiwan in 1985.
He received the B.S. degree in electrical engineer-
ing from National Tsing Hua University, Hsinchu,
Taiwan in 2007, where he is currently pursuing the
Ph.D. degree.
His research interests include power electronics on
distributed power systems and applications of power
converter controls.