Test Set Used: Primary Current Injection Test Set

Atmospheric Temperature: 25°C

Current Transformer
Sr# Applied Current (Ip) A CT Ratios Cores
Connection

2 1600 1
1600 1

CT1
5 1600 2
35-40A

8 1600 4

Current Transformer
Sr# Applied Current (Ip) A CT Ratios Cores
Connection
Current Transformer
Sr# Connection Applied Current (Ip) A CT Ratios Cores

10

11 1600 4

12

13

CT3
14 1600 5
35-40A

15
16

17 1600 6

18

Remarks:

Contractor
ETERN-CCCE-HEI Consortium

Name:
Signature:

Date:

Note:
ETERN-CCCE-HEI Consortium
ICB-102 500kV Existing Switchyard Up gradation Project
Primary Injection Current Test of Bay 09 CT's
Model:
Date: 09-07-2018
Measured
B0
Injected Current Marshalling Box (Is)
Phase
Phase Common Phase Phase
Neutral
ø Neutral

40A R 25mA 24.9mA - - 25mA

30A Y 19mA 18.8mA - - 19mA


40A B 25mA 24.9mA - - 25mA

40A R 25mA 25mA - - 25mA

30A Y 19mA 18.8mA - - 19mA

40A B 25mA 24.9mA - - 25mA

40A R 27mA 26.8mA - - 27mA

30A Y 19mA 19mA - - 19mA

40A B 26mA 25.9mA - - 26mA

Measured
B9
Marshalling Box (Is) Bus Protecti
Phase Phase Phase
Common Neutral
ø Phase Neutral
Injected Current

40A R 25mA 24.9mA - - 25mA

30A Y 19mA 18.8mA - - 19mA

40A B 25mA 24.9mA - - 25mA

40A R 25mA 25mA 0 0 25mA

30A Y 19mA 18.8mA 0 0 19mA

40A B 25mA 24.9mA 0 0 25mA


40A R 27mA 26.8mA 0 0 27mA

30A Y 19mA 19mA 0 0 19mA

40A B 26mA 25.9mA 0 0 26mA

Engineer
T4CJV

Name:
Signature:

Date:
Measured Current (mA)
B09CT1
Relays Terminal Box
Phase Phase
Neutral Common Neutral
Phase Neutral

24.9mA - - 0 0

18.8mA - - 0 0
24.9mA - - 0 0

25mA - - 0 0

18.8mA - - 0 0

24.9mA - - 0 0

26.8mA - - 0 0

19mA - - 0 0

25.9mA - - 0 0

Measured Current (mA)


B9CT3
Bus Protection CT Cabinet Relays Terminal Box
Phase Phase
Neutral
Common Neutral
Phase Neutral

24.8mA - - 0 0

18.9mA - - 0 0

24.9mA - - 0 0

25mA 0 0 0 0

18.8mA 0 0 0 0

24.9mA 0 0 0 0
26.8mA 0 0 0 0

19mA 0 0 0 0

25.9mA 0 0 0 0