Surge Protection Introduction
Surge Protection Barriers provide protection for today's sensitive electronic instrumentation – protection from the destructive
effects of lightning and the transient surges that accompany this phenomenon. Surge Protection Barriers are used in a
wide range of applications including measurement and control, instrumentation, power, and communication. The undesired
consequences of surges include both equipment damage and equipment malfunction or lockup. Damage occurs when
excessive surge voltage flashes over or punctures semiconductor junctions. Semiconductors are also sensitive to accumulated

Surge Protection
over-voltage stress. Successive surges chip away at the insulating layers in a process often referred to as "electronic rust". When
the equipment finally fails it is often not attributed to surges because the accumulative minor events actually caused the failure
rather than a recent catastrophic event such as a localized lightning strike.

Operating principle
The Surge Protection Barrier incorporates line-to-line (differential mode) and
line-to-earth (common mode) protection. This is achieved by integrating suitable
"switching" elements into the Surge Protection Barrier and guaranteeing proper
connection to ground. Gas discharge tubes are used in the first switching stage of
a Surge Protection Barrier. They are able to clamp high voltages and divert high
currents, but their slow response time still allows dangerously high energy levels
to pass through. Therefore, a second element must be implemented to control the remaining energy. This silicon avalanche
Transient Voltage Suppressor (TVS) diode type responds to lower voltage and current levels extremely fast, clamps the voltages
to non-damaging levels, and diverts the surge currents to ground. Both protection stages are decoupled with inductance
elements.

Surge Protection 488


 Surge Protection Barriers for standard and hazardous area
applications
 Protection for instrumentation, power, and communications
 Plug-in designs for terminal wiring reduction
 Hybrid design incorporates protection for power surge and lightning
transient protection
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
487
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Solutions Surge Protection
Surge Protection

Surge Protection
DIN Rail Mount
Modules
Field Mount
Modules
Modules
Plug-In
Accessories

11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


488 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Table of Contents

System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490


DIN Rail Mount Modules

Surge Protection
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 499

Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 501

Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522

Field Mount Modules


Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 499

Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 509

DIN Rail Mount


Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522

Modules
Plug-In Modules
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500

Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512

Field Mount
Modules
Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522

Accessories
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500

Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523

Modules
Plug-In
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 489
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection

Introduction Housing types


To protect the signal lines of field devices and systems in the Depending on the location you have to protect, we offer
cabinet against lightning. Pepperl+Fuchs covers the complete 3 different versions of Surge Protection Barriers.
range of Surge Protection Barriers.
Surge Protection

DIN rail mount modules (K-LB-*.**)


• Compact housing, 12.5 mm wide
• Protection of field devices and control
devices
• Single and dual channel versions 1
3
2
4

• Grounded versions for Zener Barrier


applications
DIN Rail Mount

5 6
7 8
Modules

FS
-LB
-I

Figure 2 Surge protection K-LB-*.**

Field mount modules (F*-LB-I)


Field Mount

• Screw in type for field devices


Modules

• Protection of field devices


• ½ NPT, M20 and PG13.5 thread
versions
• Floating versions M20x15
Modules
Plug-In

FS-LB-I
Figure 1 Various Surge Protection Barriers Figure 3 Surge protection F*-LB-I

Plug-in modules (P-LB-*.*.*)


• Plug-in version for the
20 mm devices of the
Accessories

K-System
• Protection of K-System
inputs
• For isolated barriers and
signal conditioners
• Single and dual channel
versions
11/2010
908837 (US) / 208599 (EU)

Figure 4 Surge protection P-LB-*.*.*


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


490 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description

Mounting and grounding


The correct installation of the Surge Protection Barrier is very important. It must be ensured that the unprotected wiring does not
influence the wiring on the protected side. Proper cable routing should ensure a sufficient cable distance between wires of the
unprotected, earth connected and protected side. Depending on the mounting place, there are different possibilities for

Surge Protection
mounting and earthing.

Topology
To protect the electrical equipment in both the control room and the hazardous area, two Surge Protection Barriers must be
integrated into the intrinsically safe circuit loop. Following the international standard EN 60079-14, intrinsically safe circuits can
either be connected "at one point to the equipotential bonding system if this exists over the whole area in which the intrinsically
safe circuits are installed" or "isolated from earth". International Standard EN 60079-14 states "if intrinsically safe apparatus
(field devices, Surge Protection Barriers and intrinsically safe barriers) do not withstand the electrical strength test with at least
500 V from earth, a connection to earth at the apparatus is to be assumed".

DIN Rail Mount


Option 1 Option 2

Modules
F*-LB-I
P
I
+ K-LB-*.* K-LB-*.*G Zener Barrier
Protected
- electrical
equipment

Field Mount
Additional field housing

Modules
Protected
field device

Equipotential bonding (if required)


Local earth Main system earth

Modules
Plug-In
Remote earth Plant earth

Figure 5 One point ground connection

Accessories
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 491
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection

DIN rail mount modules (K-LB-*.**) Protection

Protected
Unprotected signal loop
Since lightning-induced signals show pulse characteristics,
Surge Protection

standard circuit breakers or fuses are not able to sufficiently


protect the electrical equipment. It can also be used for
protection against other sources causing transient voltages
like devices changing voltages or currents during switching
events or exhibiting a non-linear behavior. These other
sources are energy storing inductive loads, such as
transformers, motors and drives. They can induce high
transient voltages and surge currents on conductors that can
Unprotected
damage connected equipment. Each electronic device in the
loop should be protected with a Surge Protection Barrier.
Figure 6 DIN rail mount module grounding
Input
DIN Rail Mount

24 V
Field mount modules (F*-LB-I)
Modules

The screw-in F*-LB-I is screwed directly into the field device


using the spare cable entry. Three wires are connected in
parallel to the field device’s signals and earth line.

Terminal box Transmitter

F*-LB-I
Field Mount
Modules

GND

Figure 9 Unprotected signal loop

Protection of the field device


F*-LB-I

Two options are available for the protection of the field device:
Option 1
Modules
Plug-In

Figure 7 Field mount module grounding The standard DIN Rail mounted K-LB-*.** is located close to
the field device. It should be placed within a field enclosure
and mounted on a grounded rail. The Surge Protection Barrier
Plug-in modules (P-LB-*.*.*) must be locally bonded to control the local potential between
the signal cables and the structure.
Option 2
Accessories

The screw-in F*-LB-I is screwed directly into the field device


using the spare cable entry. Three wires are connected in
parallel to the field device’s signals and earth line. This will
ensure a line-to-line and line-to-earth protection.
11/2010
908837 (US) / 208599 (EU)

Figure 8 Plug-in module grounding


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


492 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description

Option 2 Option 1 Safe area

F*-LB-I Input
24 V

Surge Protection
K-LB-1.30

P-LB-*.*.*
Additional field housing Isolated Barrier

Figure 10 Protection of the field device


Figure 13 Protection with isolation

Protection of control side (cabinet)


Protection without isolation Model number description

DIN Rail Mount


To protect the Zener Barrier, a non-isolated, separately
mounted Surge Protection Barrier must be installed and DIN rail mount modules

Modules
connected to the intrinsically safe side of the Zener Barrier.
The barrier’s earth connection is made, following the – – .
described guidelines, to the main system earth in parallel to
the equipment and Zener Barrier earth cable.
G Grounded
Safe area 6 Rated voltage 6 V
Input 30 Rated voltage 30 V
24 V
1 1-channel (2-wire protection)

Field Mount
Modules
2 2-channel (4-wire protection)
LB Lightning barrier
K DIN rail mount modules
K-LB-1.30G Zener Barrier

Figure 11 Protection without isolation


Field mount modules
– – I

Modules
Plug-In
Protection with isolation
The entire intrinsically safe circuit is isolated from earth. The
Intrinsic safety Ex i
intrinsically safe barrier is an isolated barrier and no
connection to the main system earth is necessary. To LB Lightning barrier
maintain the intrinsically safe measurement loop galvanically FN Field mount modules with ½ NPT thread
isolated from earth, an isolated Surge Protection Barrier must FP Field mount modules with PG13.5 thread
be installed at both ends of the loop. This must be close to the
FS Field mount modules with M20 x 1.5 thread

Accessories
isolated barrier, connected to its intrinsically safe side in the
safe area and close to the field device in the hazardous area,
but outside Zone 0.
Plug-in modules
Safe area
Input
24 V
– – . .

Protected terminals
11/2010

1 1-channel
2 2-channel
K-LB-*.* Isolated Barrier
908837 (US) / 208599 (EU)

LB Lightning barrier

Figure 12 Protection with isolation P Plug-in modules


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 493
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection

Safety Information for K-LB-*.** Application


DIN rail mount modules Surge Protection Barriers themselves can be installed within
the hazardous area of Zone 1. They can be used for
The highest ignition protection class to be reached is intrinsically safe circuits up to Ex ia IIC. The ignition protection
Surge Protection

class is determined by the connected intrinsically safe circuit


of the corresponding electrical equipment.
¬ II 2 (1) G Ex ia IIC T6
Surge Protection Barriers are not used to separate
intrinsically safe circuits from non-intrinsically safe circuits.
Temperature class
Surge Protection Barriers must not be installed in
Explosion group
dust Ex-zones.
Protection level
Explosion protection Installation and commissioning in
identification
Gas area
connection with hazardous areas
Category Commissioning and installation must be performed only by
Device group specialists who are trained specifically for this purpose.
DIN Rail Mount

Identification for availability of explosions The quality of the ground is a significant precondition for
Modules

problem-free overvoltage protection. Short connections and


large cable cross-sections are basic requirements for effective
protection. These requirements can be fulfilled through the
The corresponding data sheets, the Declaration of
use of appropriate accessories (see data sheets).
Conformity, the EC-Type Examination Certificate and
applicable certificates (see data sheet) are an integral part of Potential compensation must be set up for Surge Protection
this document. Barriers of types K-LB-*.*G along the intrinsically safe circuits
inside and outside of the hazardous area
Intended use
Field Mount

Surge Protection Barriers modules are designed in the IP20


Modules

Laws and regulations applicable to the usage or planned protection class in accordance with EN 60529 and must be
purpose of usage must be observed. Devices are only protected against adverse environmental conditions such as
approved for proper usage in accordance with intended use. splashed water or dirt beyond pollution degree 2.
Improper handling will result in voiding of any warrantee or Depending on the ignition protection class, the circuits of
manufacturer's responsibility. Surge Protection Barriers may be directed in Zone 1 or 0.
Surge Protection Barriers are used as modules positioned Special attention must be paid to a secure separation from all
upstream in the circuit from the corresponding electrical non-intrinsically safe circuits in this context. A shortest path
equipment. They make it possible to protect against distance of at least 50 mm must be maintained between
intrinsically safe and non-intrinsically safe conducting terminal
Modules
Plug-In

overvoltages originating from various causes (lightning


strikes, switching processes, etc.). This is achieved by blocks during assembly. The ignition protection class is
diverting the transient current and limiting the voltage determined by the connected intrinsically safe circuit of the
throughout the duration of the overvoltage surge. Various corresponding electrical equipment.
modules are available for protecting 2 or 4 conductors. The installation of the intrinsically safe circuits is to be
Protection of operating personnel and the system is not conducted in accordance with the relevant installation
ensured if the product is not used in accordance with its regulations.
intended use. The respective maximum values of the field device, the Surge
Accessories

Intrinsic safety circuits that were operated with circuits of other Protection Barriers and the corresponding electrical
types of protection may not be used as intrinsically safe equipment as defined by explosion protection must be
circuits afterwards. observed for interconnecting with intrinsically safe electrical
equipment (proof of intrinsic safety). EN 60079-14/
IEC 60079-14 must be observed (where appropriate).
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


494 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description
The EC-Type Examination Certificates or standard Isolation coordinates for devices with
certificates/approvals should be observed. It is especially
Ex-certificate in accordance with EN 50020
important to observe the "special conditions" if these are
included in the certificates. and EN 60079-11
The use of this device must not change the ignition protection The devices are assessed for pollution degree 2 and

Surge Protection
category of the supplying circuit. Thus, for example, ib circuits overvoltage category II according to EN 50178.
must not enter Zone 0, even if they are controlled via this For additional details, see data sheets.
device – unless otherwise stated in the related approval.
Ambient conditions
Repair and maintenance
Ambient temperature
The transfer characteristics of the devices remain stable over
long periods of time. This eliminates the need for regular -30 °C to 60 °C (-22 °F to 140 °F) for Ex application, please
adjustment. Maintenance is not required. observe EC-Type Examination Certificate
Storage temperature
Fault elimination -30 °C to 80 °C (-22 °F to 176 °F)
No changes can be made to devices that are operated in

DIN Rail Mount


Relative humidity
hazardous areas. Repairs on the device are not allowed.

Modules
max. 75 % without moisture condensation

Field Mount
Modules
Modules
Plug-In
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 495
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection

Safety Information for F*-LB-I Installation and commissioning in


field mount modules connection with hazardous areas
Commissioning and installation must be performed only by
The highest ignition protection class to be reached is specialists who are trained specifically for this purpose.
Surge Protection

The quality of the ground is a significant precondition for


¬ II 2 G Ex ia IIC T6 problem-free overvoltage protection. Short connections and
large cable cross-sections are basic requirements for effective
protection.
Temperature class
Depending on the ignition protection class, the circuits of
Explosion group
Surge Protection Barriers may be directed in Zone 1 or 0.
Protection level
Special attention must be paid to a secure separation from all
Explosion protection identification non-intrinsically safe circuits in this context. A shortest path
Gas area distance of at least 50 mm must be maintained between
Category intrinsically safe and non-intrinsically safe conducting terminal
Device group
blocks during assembly. The ignition protection class is
determined by the connected intrinsically safe circuit of the
DIN Rail Mount

Identification for availability of explosions


corresponding electrical equipment.
Modules

The installation of the intrinsically safe circuits is to be


conducted in accordance with the relevant installation
The corresponding data sheets, the Declaration of
regulations.
Conformity, the EC-Type Examination Certificate and
applicable certificates (see data sheet) are an integral part of The respective maximum values of the field device, the Surge
this document. Protection Barriers and the corresponding electrical
equipment as defined by explosion protection must be
Intended use observed for interconnecting with intrinsically safe electrical
Field Mount

equipment (proof of intrinsic safety). EN 60079-14/


Modules

Laws and regulations applicable to the usage or planned IEC 60079-14 must be observed (where appropriate).
purpose of usage must be observed. Devices are only
The EC-Type Examination Certificates or standard
approved for proper usage in accordance with intended use.
certificates/approvals should be observed. It is especially
Improper handling will result in voiding of any warrantee or
important to observe the "special conditions" if these are
manufacturer's responsibility.
included in the certificates.
Surge Protection Barriers are used as protective modules for
The use of this device must not change the ignition protection
intrinsically safe field devices and the corresponding electrical
category of the supplying circuit. Thus, for example, ib circuits
equipment. They make it possible to protect against
must not enter Zone 0, even if they are controlled via this
overvoltages originating from various causes (lightning
Modules
Plug-In

device – unless otherwise stated in the related approval.


strikes, switching processes, etc.). This is achieved by
diverting the transient current and limiting the voltage
throughout the duration of the overvoltage surge. Repair and maintenance
Protection of operating personnel and the system is not The transfer characteristics of the devices remain stable over
ensured if the product is not used in accordance with its long periods of time. This eliminates the need for regular
intended use. adjustment. Maintenance is not required.
Intrinsic safety circuits that were operated with circuits of other
Fault elimination
Accessories

types of protection may not be used as intrinsically safe


circuits afterwards. No changes can be made to devices that are operated in
hazardous areas. Repairs on the device are not allowed.
Application
Surge Protection Barriers themselves can be installed within
Ambient conditions
the hazardous area of Zone 1. They can be used for Ambient temperature
intrinsically safe circuits up to Ex ia IIC. The ignition protection
class is determined by the connected intrinsically safe circuit -30 °C to 60 °C (-22 °F to 140 °F) for Ex application, please
11/2010

of the corresponding electrical equipment. observe EC-Type Examination Certificate

Surge Protection Barriers must not be installed in Storage temperature


908837 (US) / 208599 (EU)

dust Ex-zones. -30 °C to 80 °C (-22 °F to 176 °F)


Relative humidity
max. 75 % without moisture condensation
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


496 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description

Safety Information for P-LB-*.*.* Installation and commissioning in


plug-in modules connection with hazardous areas
Commissioning and installation must be performed only by
The corresponding data sheets, the Declaration of
specialists who are trained specifically for this purpose.
Conformity, the EC-Type Examination Certificate and

Surge Protection
applicable certificates (see data sheet) are an integral part of The quality of the ground is a significant precondition for
this document. problem-free overvoltage protection. Short connections and
large cable cross-sections are basic requirements for effective
Intended use protection. These requirements can be fulfilled through the
use of appropriate accessories (see data sheets).
Laws and regulations applicable to the usage or planned
Plug-in terminal modules are designed in the IP20 protection
purpose of usage must be observed. Devices are only
class in accordance with EN 60529 and must be accordingly
approved for proper usage in accordance with intended use.
protected against adverse environmental conditions such as
Improper handling will result in voiding of any warrantee or
splashed water or dirt beyond pollution degree 2.
manufacturer's responsibility.
Plug-in terminal modules can be installed inside the
Plug-in terminal modules are used as modules positioned
hazardous area of Zone 2/Div. 2. Since plug-in terminal
upstream in the circuit from the corresponding electrical

DIN Rail Mount


modules are always used in combination with devices of the
equipment. They make it possible to protect against
K-System, the devices of the K-System must, in this case, be

Modules
overvoltages originating from various causes (lightning
suitable for use in Zone 2/Div. 2. The devices of the K-System
strikes, switching processes, etc.). This is achieved by
must then be installed only in Zone 2/Div. 2 if a corresponding
diverting the transient current and limiting the voltage
Declaration of Conformity for a named location or a
throughout the duration of the overvoltage surge. Various
manufacturer's Declaration of Conformity is present. For
modules are available for protecting 2, 3, 4 or 6 conductors.
information on whether this condition has been met, please
The assignment of input connections of plug-in terminal
refer to the data sheets for the devices of the K-System. The
modules/intrinsically safe equipment (binary or analog
instruction manual, the Declaration of Conformity of a named
signals) corresponds to that of the following related
location or the manufacturer's Declaration of Conformity of

Field Mount
equipment (see the corresponding data sheets). Plug-in

Modules
devices of the K-System and the information in them must be
terminal modules should only be used in combination with a
followed.
device of the K-System.
Depending on the ignition protection class, the circuits of
Protection of operating personnel and the system is not
plug-in terminal modules may be directed in Zone 1 or 0.
ensured if the product is not used in accordance with its
Special attention must be paid to a secure separation from all
intended use.
non-intrinsically safe circuits in this context. A shortest path
Intrinsic safety circuits that were operated with circuits of other distance of at least 50 mm must be maintained between
types of protection may not be used as intrinsically safe intrinsically safe and non-intrinsically safe conducting terminal
circuits afterwards. blocks during assembly. The ignition protection class is

Modules
Plug-In
determined by the connected intrinsically safe circuit of the
Application corresponding electrical equipment.
Plug-in terminal modules can be installed within the The installation of the intrinsically safe circuits is to be
hazardous area of Zone 2/Div. 2. They can be used for conducted in accordance with the relevant installation
intrinsically safe circuits up to Ex ia IIC. The ignition protection regulations.
class is determined by the connected intrinsically safe circuit The respective maximum values of the field device, the
of the corresponding electrical equipment. plug-in terminal modules and the corresponding electrical

Accessories
Plug-in terminal modules are not used to separate intrinsically equipment as defined by explosion protection must be
safe circuits from non-intrinsically safe circuits. observed for interconnecting with intrinsically safe electrical
equipment (proof of intrinsic safety). EN 60079-14/
Plug-in terminal modules must not be installed in
IEC 60079-14 must be observed (where appropriate).
dust Ex-zones.
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 497
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection

The EC-Type Examination Certificates or standard Isolation coordinates for devices with
certificates/approvals should be observed. It is especially
Ex-certificate in accordance with EN 50020
important to observe the "special conditions" if these are
included in the certificates. and EN 60079-11
The terminal modules must be installed in such a way that The devices are assessed for pollution degree 2 and
Surge Protection

they are protected from electrostatic charge. overvoltage category II according to EN 50178.

The use of this device must not change the ignition protection
Ambient conditions
category of the supplying circuit. Thus, for example, ib circuits
must not enter Zone 0, even if they are controlled via this Ambient temperature
device – unless otherwise stated in the related approval.
-20 °C to 60 °C (-4 °F to 140 °F)
Repair and maintenance Storage temperature
The transfer characteristics of the devices remain stable over -30 °C to 80 °C (-22 °F to 176 °F)
long periods of time. This eliminates the need for regular
Relative humidity
adjustment. Maintenance is not required.
max. 75 % without moisture condensation
DIN Rail Mount

Fault elimination
Modules

No changes can be made to devices that are operated in Technical data


hazardous areas. Repairs on the device are not allowed.
For additional details, see data sheets.
Field Mount
Modules
Modules
Plug-In
Accessories

11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


498 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Selection Tables
DIN Rail Mount Modules

Model Number Page

Rated Voltage (V)

Surge Protection
Grounded
Channels
K-LB-1.30 1 30 501

K-LB-2.30 2 30 502

K-LB-1.6 1 6 503

K-LB-2.6 2 6 504

K-LB-1.30G 1 30  505

DIN Rail Mount


K-LB-2.30G 2 30  506

Modules
K-LB-1.6G 1 6  507

K-LB-2.6G 2 6  508

Field Mount Modules

Field Mount
Model Number Page

Modules
Rated Voltage (V)
Channels

Thread
FN-LB-I 1 48 ½ NPT 509

Modules
Plug-In
FS-LB-I 1 48 M20 x 1.5 510

FP-LB-I 1 48 PG13.5 511

Accessories
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 499
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Selection Tables Surge Protection

Plug-In Modules

Model Number Page

Rated Voltage (V)


Surge Protection

For Terminals
Channels
P-LB-1.A.13 1 30 1, 3 512

P-LB-2.A.1346 2 30 1, 3; 4, 6 513

P-LB-1.B.12 1 30 1, 2 514

P-LB-2.B.1245 2 30 1, 2; 4, 5 515

P-LB-1.C.123 1 30 1, 2, 3 516
DIN Rail Mount

P-LB-2.D.123456 2 30 1, 2, 3; 4, 5, 6 517
Modules

P-LB-1.E.23 1 30 2, 3 518

P-LB-2.C.2356 2 30 2, 3; 5, 6 519

P-LB-1.D.1234 1 30 1, 2, 3, 4 520

P-LB-1.F.1236 1 30 1, 2, 3, 6 521
Field Mount

Accessories for DIN Rail Mount Modules


Modules

Model Number Description Page

NS 35/7.5 35 mm DIN Rail 523

USLKG5 Terminal Block 523

ZH-ES/LB Insertion Strip 523

ZH-Z.BT Label Carrier 523


Modules
Plug-In

Accessories for Plug-in Modules

Model Number Description Page

ZH-Z.AB/SS Mounting Block 523

ZH-Z.AK16 Connector 523


Accessories

ZH-Z.AR.85 Spacing Roller 523

ZH-Z.NLS-Cu3/10 Grounding Rail 523


11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


500 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.30

Technical data Features


Supply • 1-channel
Connection terminals 7, 8; 1, 2
• DIN rail mount module
Rated voltage ≤ 30 V
• For 30 V IS or Non-IS applications

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA • Protects field or control circuit
On-state voltage ≤ 45 V inputs
Ground insulation 500 V breakdown voltage • Surge protection up to 10 kA
Ambient conditions • Provides 500 V DC of isolation
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Uninterruptable operation
observe EC-Type Examination Certificate
(auto reset)
Mechanical specifications
Protection degree IP20
Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters
induced transients of different origin (e. g.
with Ex-areas

DIN Rail Mount


lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X
This is achieved by diverting the transient

Modules
Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
temperature classification current to ground and limiting the signal
CSA approval line voltage to a safe level for the duration
Control drawing 116-0187 (cCSAus) of the surge.
This barrier provides low 45 V line-to-line
and 500 V line-to-ground clamping
voltage for the protected instruments. It
also protects instruments that have more

Field Mount
than 500 V isolation-to-ground, such as

Modules
intrinsic safety isolated barriers, signal
conditioners and most field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is

Modules
protecting. The ground system must

Plug-In
comply with all applicable regulations.

Accessories
Diagrams

Front view

Terminals
not protected
K-LB-1.30

1 2
3 4

Tag holder
11/2010

1
7

2
908837 (US) / 208599 (EU)

5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-1.30

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 501
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.30 Surge Protection Barrier

Features Technical data


• 2-channel Supply
Connection terminals 1, 2; 7, 8/3, 4; 5, 6
• DIN rail mount module
Rated voltage ≤ 30 V
• For 30 V IS or Non-IS applications
Surge Protection

Rated current ≤ 250 mA


• Protects field or control circuit Leakage current ≤ 5 μA
inputs On-state voltage ≤ 45 V
• Surge protection up to 10 kA Ground insulation 500 V breakdown voltage
• Provides 500 V DC of isolation Ambient conditions
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Uninterruptable operation
observe EC-Type Examination Certificate
(auto reset)
Mechanical specifications
Protection degree IP20
Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters
induced transients of different origin (e. g.
with Ex-areas
DIN Rail Mount

lightning stroke, switching impulse, etc.).


EC-Type Examination Certificate PTB 00 ATEX 2176X
This is achieved by diverting the transient
Modules

Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6


current to ground and limiting the signal temperature classification
line voltage to a safe level for the duration CSA approval
of the surge. Control drawing 116-0187 (cCSAus)
This barrier provides low 45 V line-to-line
and 500 V line-to-ground clamping
voltage for the protected instruments. It
also protects instruments that have more
Field Mount

than 500 V isolation-to-ground, such as


Modules

intrinsic safety isolated barriers, signal


conditioners and most field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules

protecting. The ground system must


Plug-In

comply with all applicable regulations.


Accessories

Diagrams

Front view

Terminals
not protected
K-LB-2.30

1 2
3 4

Tag holder
1
7
11/2010

2 8
908837 (US) / 208599 (EU)

3
5

4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-2.30

502 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.6

Technical data Features


Supply • 1-channel
Connection terminals 7, 8; 1, 2
• DIN rail mount module
Rated voltage ≤6 V
• For 6 V IS or Non-IS applications

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 10 μA • Protects field or control circuit
On-state voltage ≤ 12 V inputs
Ground insulation 500 V breakdown voltage • Surge protection up to 10 kA
Ambient conditions • Provides 500 V DC of isolation
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Uninterruptable operation
observe EC-Type Examination Certificate
(auto reset)
Mechanical specifications
Protection degree IP20
Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters
induced transients of different origin (e. g.
with Ex-areas

DIN Rail Mount


lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X
This is achieved by diverting the transient

Modules
Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
temperature classification current to ground and limiting the signal
CSA approval line voltage to a safe level for the duration
Control drawing 116-0187 (cCSAus) of the surge.
This barrier provides low 12 V line-to-line
and 500 V line-to-ground clamping
voltage for the protected instruments. It
also protects instruments that have more

Field Mount
than 500 V isolation-to-ground, such as

Modules
intrinsic safety isolated barriers, signal
conditioners and most field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is

Modules
protecting. The ground system must

Plug-In
comply with all applicable regulations.

Accessories
Diagrams

Front view

Terminals
not protected
K-LB-1.6

1 2
3 4

Tag holder
11/2010

1
7

2
908837 (US) / 208599 (EU)

5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-1.6

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 503
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.6 Surge Protection Barrier

Features Technical data


• 2-channel Supply
Connection terminals 1, 2; 7, 8/3, 4; 5, 6
• DIN rail mount module
Rated voltage ≤6 V
• For 6 V IS or Non-IS applications
Surge Protection

Rated current ≤ 250 mA


• Protects field or control circuit Leakage current ≤ 10 μA
inputs On-state voltage ≤ 12 V
• Surge protection up to 10 kA Ground insulation 500 V breakdown voltage
• Provides 500 V DC of isolation Ambient conditions
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Uninterruptable operation
observe EC-Type Examination Certificate
(auto reset)
Mechanical specifications
Protection degree IP20
Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters
induced transients of different origin (e. g.
with Ex-areas
DIN Rail Mount

lightning stroke, switching impulse, etc.).


EC-Type Examination Certificate PTB 00 ATEX 2176X
This is achieved by diverting the transient
Modules

Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6


current to ground and limiting the signal temperature classification
line voltage to a safe level for the duration CSA approval
of the surge. Control drawing 116-0187 (cCSAus)
This barrier provides low 12 V line-to-line
and 500 V line-to-ground clamping
voltage for the protected instruments. It
also protects instruments that have more
Field Mount

than 500 V isolation-to-ground, such as


Modules

intrinsic safety isolated barriers, signal


conditioners and most field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules

protecting. The ground system must


Plug-In

comply with all applicable regulations.


Accessories

Diagrams

Front view

Terminals
not protected
K-LB-2.6

1 2
3 4

Tag holder
1
7
11/2010

2 8
908837 (US) / 208599 (EU)

3
5

4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-2.6

504 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.30G

Technical data Features


Supply • 1-channel
Connection terminals 7, 8; 1, 2
• DIN rail mount module
Rated voltage ≤ 30 V
• For 30 V IS or Non-IS applications

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA • Protects field or control circuit
On-state voltage ≤ 45 V inputs
Ambient conditions • Surge protection up to 10 kA
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please • Uninterruptable operation
observe EC-Type Examination Certificate (auto reset)
Mechanical specifications
Protection degree IP20 Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in) This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters induced transients of different origin (e. g.
with Ex-areas
lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X

DIN Rail Mount


This is achieved by diverting the transient
Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
current to ground and limiting the signal

Modules
temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some

Field Mount
Modules
field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.

Modules
Plug-In
Accessories
Diagrams

Front view

Terminals
not protected
K-LB-1.30G

1 2
3 4

Tag holder
11/2010

1
7

2
908837 (US) / 208599 (EU)

5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-1.30G

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 505
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.30G Surge Protection Barrier

Features Technical data


• 2-channel Supply
Connection terminals 1, 2; 7, 8/3, 4; 5, 6
• DIN rail mount module
Rated voltage ≤ 30 V
• For 30 V IS or Non-IS applications
Surge Protection

Rated current ≤ 250 mA


• Protects field or control circuit Leakage current ≤ 5 μA
inputs On-state voltage ≤ 45 V
• Surge protection up to 10 kA Ambient conditions
• Uninterruptable operation Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
(auto reset) observe EC-Type Examination Certificate
Mechanical specifications
Function Protection degree IP20
Mass approx. 100 g
This Surge Protection Barrier limits Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
induced transients of different origin (e. g. Data for application in connection see page 522 for entity parameters
with Ex-areas
lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X
DIN Rail Mount

This is achieved by diverting the transient


Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
current to ground and limiting the signal
Modules

temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some
Field Mount
Modules

field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.
Modules
Plug-In
Accessories

Diagrams

Front view

Terminals
not protected
K-LB-2.30G

1 2
3 4

Tag holder
1
7
11/2010

2 8
908837 (US) / 208599 (EU)

3
5

4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-2.30G

506 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.6G

Technical data Features


Supply • 1-channel
Connection terminals 7, 8; 1, 2
• DIN rail mount module
Rated voltage ≤6 V
• For 6 V IS or Non-IS applications

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA • Protects field or control circuit
On-state voltage ≤ 12 V inputs
Ambient conditions • Surge protection up to 10 kA
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please • Uninterruptable operation
observe EC-Type Examination Certificate (auto reset)
Mechanical specifications
Protection degree IP20 Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in) This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters induced transients of different origin (e. g.
with Ex-areas
lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X

DIN Rail Mount


This is achieved by diverting the transient
Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
current to ground and limiting the signal

Modules
temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some

Field Mount
Modules
field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.

Modules
Plug-In
Accessories
Diagrams

Front view

Terminals
not protected
K-LB-1.6G

1 2
3 4

Tag holder
11/2010

1
7

2
908837 (US) / 208599 (EU)

5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-1.6G

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 507
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.6G Surge Protection Barrier

Features Technical data


• 2-channel Supply
Connection terminals 1, 2; 7, 8/3, 4; 5, 6
• DIN rail mount module
Rated voltage ≤6 V
• For 6 V IS or Non-IS applications
Surge Protection

Rated current ≤ 250 mA


• Protects field or control circuit Leakage current ≤ 5 μA
inputs On-state voltage ≤ 12 V
• Surge protection up to 10 kA Ambient conditions
• Uninterruptable operation Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
(auto reset) observe EC-Type Examination Certificate
Mechanical specifications
Function Protection degree IP20
Mass approx. 100 g
This Surge Protection Barrier limits Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
induced transients of different origin (e. g. Data for application in connection see page 522 for entity parameters
with Ex-areas
lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X
DIN Rail Mount

This is achieved by diverting the transient


Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
current to ground and limiting the signal
Modules

temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some
Field Mount
Modules

field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.
Modules
Plug-In
Accessories

Diagrams

Front view

Terminals
not protected
K-LB-2.6G

1 2
3 4

Tag holder
1
7
11/2010

2 8
908837 (US) / 208599 (EU)

3
5

4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-LB-2.6G

508 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier FN-LB-I

Technical data Features


Supply • 1-channel
Rated voltage ≤ 48 V
• Field mount module
Rated current ≤ 250 mA
• ½ NPT thread

Surge Protection
Leakage current ≤ 5 μA
On-state voltage ≤ 85 V • Stainless steel housing
Ground insulation ≥ 500 V breakdown voltage • Discharge current 10 kA
Ambient conditions • 500 V isolation from earth
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Suitable for hazardous area
observe EC-Type Examination Certificate
Mechanical specifications
Function
Housing material stainless steel 1.4401 (AISI 316)
surface all over polished
This Surge Protection Barrier limits
Protection degree IP20
induced transients of different origin (e. g.
Cable
lightning stroke, switching impulse, etc.).
Length L 0.4 m
This is achieved by diverting the transient
Mass approx. 200 g

DIN Rail Mount


current to ground and limiting the signal
Dimensions AF22 x 77 mm (0.9 x 3 in)
line voltage to a safe level for the duration

Modules
Mounting ½ NPT thread
of the surge.
Data for application in connection see page 522 for entity parameters
with Ex-areas This barrier provides 85 V line-to-line and
EC-Type Examination Certificate PTB 00 ATEX 2175 500 V line-to-ground clamping voltage for
Group, category, type of protection, ¬ II 2G EEx ia IIC T6 the protected instruments. It also protects
temperature classification instruments that have less than 500 V
CSA approval isolation-to-ground.
Control drawing 116-0187 (cCSAus)
It is installed in an available conduit or

Field Mount
cable gland opening like those found on

Modules
most process transmitters.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must

Modules
Plug-In
comply with all applicable regulations.

Accessories
Diagrams
1/2" NPT

rd FN-LB-I
11/2010

GND gn/ye
bk
908837 (US) / 208599 (EU)

Zone 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


FN-LB-I

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 509
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
FS-LB-I Surge Protection Barrier

Features Technical data


• 1-channel Supply
Rated voltage ≤ 48 V
• Field mount module
Rated current ≤ 250 mA
• M20 x 1.5 thread
Surge Protection

Leakage current ≤ 5 μA
• Stainless steel housing On-state voltage ≤ 85 V
• Discharge current 10 kA Ground insulation ≥ 500 V breakdown voltage
• 500 V isolation from earth Ambient conditions
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Suitable for hazardous area
observe EC-Type Examination Certificate
Mechanical specifications
Function
Housing material stainless steel 1.4401 (AISI 316)
surface all over polished
This Surge Protection Barrier limits
Protection degree IP20
induced transients of different origin (e. g.
Cable
lightning stroke, switching impulse, etc.).
Length L 0.4 m
This is achieved by diverting the transient
Mass approx. 200 g
DIN Rail Mount

current to ground and limiting the signal


Dimensions AF22 x 77 mm (0.9 x 3 in)
line voltage to a safe level for the duration
Modules

Mounting M20 x 1.5 thread


of the surge.
Data for application in connection see page 522 for entity parameters
This barrier provides 85 V line-to-line and with Ex-areas
500 V line-to-ground clamping voltage for EC-Type Examination Certificate PTB 00 ATEX 2175
the protected instruments. It also protects Group, category, type of protection, ¬ II 2G EEx ia IIC T6
instruments that have less than 500 V temperature classification
isolation-to-ground. CSA approval
Control drawing 116-0187 (cCSAus)
It is installed in an available conduit or
Field Mount

cable gland opening like those found on


Modules

most process transmitters.


For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
Modules
Plug-In

comply with all applicable regulations.


Accessories

Diagrams
M20x15

FS-LB-I rd
11/2010

GND gn/ye
bk
908837 (US) / 208599 (EU)

Zone 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


FS-LB-I

510 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier FP-LB-I

Technical data Features


Supply • 1-channel
Rated voltage ≤ 48 V
• Field mount module
Rated current ≤ 250 mA
• PG13.5 thread

Surge Protection
Leakage current ≤ 5 μA
On-state voltage ≤ 85 V • Stainless steel housing
Ground insulation ≥ 500 V breakdown voltage • Discharge current 10 kA
Ambient conditions • 500 V isolation from earth
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Suitable for hazardous area
observe EC-Type Examination Certificate
Mechanical specifications
Function
Housing material stainless steel 1.4401 (AISI 316)
surface all over polished
This Surge Protection Barrier limits
Protection degree IP20
induced transients of different origin (e. g.
Cable
lightning stroke, switching impulse, etc.).
Length L 0.4 m
This is achieved by diverting the transient
Mass approx. 200 g

DIN Rail Mount


current to ground and limiting the signal
Dimensions AF22 x 77 mm (0.9 x 3 in)
line voltage to a safe level for the duration

Modules
Mounting PG13.5 thread
of the surge.
Data for application in connection see page 522 for entity parameters
with Ex-areas This barrier provides 85 V line-to-line and
EC-Type Examination Certificate PTB 00 ATEX 2175 500 V line-to-ground clamping voltage for
Group, category, type of protection, ¬ II 2G EEx ia IIC T6 the protected instruments. It also protects
temperature classification instruments that have less than 500 V
CSA approval isolation-to-ground.
Control drawing 116-0187 (cCSAus)
It is installed in an available conduit or

Field Mount
cable gland opening like those found on

Modules
most process transmitters.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must

Modules
Plug-In
comply with all applicable regulations.

Accessories
Diagrams
Pg 13,5

rd FP-LB-I
11/2010

GND gn/ye
bk
908837 (US) / 208599 (EU)

Zone 1, 2
Div. 1, 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


FP-LB-I

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 511
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.A.13 Surge Protection Barrier

Features Technical data


• 1-channel Signal lines
Connection terminals 1, 3
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules
Surge Protection

Rated current ≤ 250 mA


• Analog or digital signal inputs Leakage current ≤ 5 μA
• Surge protection up to 10 kA On-state voltage ≤ 45 V
• Protects leads 1 and 3 of KF modules Ground insulation ≤ 500 V breakdown voltage
• Uninterruptable operation Ambient conditions
(auto reset) Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Function Protection degree IP20
Mass approx. 70 g
This Surge Protection Barrier is designed Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
for use with K-System (KF modules). Data for application in connection see page 522 for entity parameters
with Ex-areas
By simply snapping the barriers into a
EC-Type Examination Certificate PTB 02 ATEX 2044
DIN Rail Mount

standard KF module, the modules are


Group, category, type of protection ¬ II (1)G [EEx ia] IIC
safely protected against voltage surges of
Modules

CSA approval
different origin (e. g. lightning stroke,
Control drawing 116-0187 (cCSAus)
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
The end digits of the model designation
Field Mount

correspond to the protected terminals of


Modules

the respective KF module.


For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
Modules

comply with all applicable regulations.


Plug-In
Accessories

Diagrams

Front view

Connection to earth

P-LB-1.A.13
Removable terminal
blue, not protected
11/2010

1 (1)

3 (3)
908837 (US) / 208599 (EU)

Terminals Zone 0, 1, 2 Zone 2


protected Div. 1, 2 Div. 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-1.A.13

512 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.A.1346

Technical data Features


Signal lines • 2-channel
Connection terminals 1, 3; 4, 6
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 3, 4 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044

DIN Rail Mount


By simply snapping the barriers into a
Group, category, type of protection ¬ II (1)G [EEx ia] IIC
standard KF module, the modules are

Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.

Field Mount
The end digits of the model designation

Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is

Modules
protecting. The ground system must

Plug-In
comply with all applicable regulations.

Accessories
Diagrams

Front view

Connection to earth

P-LB-2.A.1346
Removable terminals
blue, not protected
11/2010

1 (1)

3 (3)
908837 (US) / 208599 (EU)

4 (4)

6 (6)

Zone 0, 1, 2 Zone 2 Terminals


Div. 1, 2 Div. 2 protected
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-2.A.1346

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 513
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.B.12 Surge Protection Barrier

Features Technical data


• 1-channel Signal lines
Connection terminals 1, 2
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules
Surge Protection

Rated current ≤ 250 mA


• Analog or digital signal inputs Leakage current ≤ 5 μA
• Surge protection up to 10 kA On-state voltage ≤ 45 V
• Protects leads 1 and 2 of KF modules Ground insulation ≤ 500 V breakdown voltage
• Uninterruptable operation Ambient conditions
(auto reset) Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Function Protection degree IP20
Mass approx. 70 g
This Surge Protection Barrier is designed Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
for use with K-System (KF modules). Data for application in connection see page 522 for entity parameters
with Ex-areas
By simply snapping the barriers into a
EC-Type Examination Certificate PTB 02 ATEX 2044
DIN Rail Mount

standard KF module, the modules are


Group, category, type of protection ¬ II (1)G [EEx ia] IIC
safely protected against voltage surges of
Modules

CSA approval
different origin (e. g. lightning stroke,
Control drawing 116-0187 (cCSAus)
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
The end digits of the model designation
Field Mount

correspond to the protected terminals of


Modules

the respective KF module.


For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
Modules

comply with all applicable regulations.


Plug-In
Accessories

Diagrams

Front view

Connection to earth

P-LB-1.B.12
Removable terminal
blue, not protected
11/2010

1 (1)

2 (2)
908837 (US) / 208599 (EU)

Terminals Zone 0, 1, 2 Zone 2


protected Div. 1, 2 Div. 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-1.B.12

514 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.B.1245

Technical data Features


Signal lines • 2-channel
Connection terminals 1, 2; 4, 5
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 2, 4 and 5 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044

DIN Rail Mount


By simply snapping the barriers into a
Group, category, type of protection ¬ II (1)G [EEx ia] IIC
standard KF module, the modules are

Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.

Field Mount
The end digits of the model designation

Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is

Modules
protecting. The ground system must

Plug-In
comply with all applicable regulations.

Accessories
Diagrams

Front view

Connection to earth

P-LB-2.B.1245
Removable terminals
blue, not protected
11/2010

1 (1)

2 (2)
908837 (US) / 208599 (EU)

4 (4)

5 (5)

Zone 0, 1, 2 Zone 2 Terminals


Div. 1, 2 Div. 2 protected
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-2.B.1245

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 515
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.C.123 Surge Protection Barrier

Features Technical data


• 1-channel Signal lines
Connection terminals 1, 2, 3
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules
Surge Protection

Rated current ≤ 250 mA


• Analog or digital signal inputs Leakage current ≤ 5 μA
• Surge protection up to 10 kA On-state voltage ≤ 45 V
• Protects leads 1, 2 and 3 of Ground insulation ≤ 500 V breakdown voltage
KF modules Ambient conditions
• Uninterruptable operation Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
(auto reset) Mechanical specifications
Protection degree IP20
Function Mass approx. 70 g
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
This Surge Protection Barrier is designed Data for application in connection see page 522 for entity parameters
for use with K-System (KF modules). with Ex-areas
EC-Type Examination Certificate PTB 02 ATEX 2044
DIN Rail Mount

By simply snapping the barriers into a


Group, category, type of protection ¬ II (1)G [EEx ia] IIC
standard KF module, the modules are
Modules

CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount

The end digits of the model designation


Modules

correspond to the protected terminals of


the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules

protecting. The ground system must


Plug-In

comply with all applicable regulations.


Accessories

Diagrams

Front view

Connection to earth

P-LB-1.C.123
Removable terminal
blue, not protected
11/2010

1 (1)

2 (2)
908837 (US) / 208599 (EU)

3 (3)

Terminals Zone 0, 1, 2 Zone 2


protected Div. 1, 2 Div. 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-1.C.123

516 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.D.123456

Technical data Features


Signal lines • 2-channel
Connection terminals 1, 2, 3; 4, 5, 6
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 2, 3, 4, 5 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044

DIN Rail Mount


By simply snapping the barriers into a
Group, category, type of protection ¬ II (1)G [EEx ia] IIC
standard KF module, the modules are

Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.

Field Mount
The end digits of the model designation

Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is

Modules
protecting. The ground system must

Plug-In
comply with all applicable regulations.

Accessories
Diagrams

Front view

Connection to earth

P-LB-2.D.123456
Removable terminals
blue, not protected

1 (1)
11/2010

2 (2)

3 (3)
908837 (US) / 208599 (EU)

4 (4)

5 (5)

6 (6)

Zone 0, 1, 2 Zone 2 Terminals


Div. 1, 2 Div. 2 protected
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-
2.D.12345
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 517
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.E.23 Surge Protection Barrier

Features Technical data


• 1-channel Signal lines
Connection terminals 2, 3
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules
Surge Protection

Rated current ≤ 250 mA


• Analog or digital signal inputs Leakage current ≤ 5 μA
• Surge protection up to 10 kA On-state voltage ≤ 45 V
• Protects leads 2 and 3 of KF modules Ground insulation ≤ 500 V breakdown voltage
• Uninterruptable operation Ambient conditions
(auto reset) Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Function Protection degree IP20
Mass approx. 70 g
This Surge Protection Barrier is designed Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
for use with K-System (KF modules). Data for application in connection see page 522 for entity parameters
with Ex-areas
By simply snapping the barriers into a
EC-Type Examination Certificate PTB 02 ATEX 2044
DIN Rail Mount

standard KF module, the modules are


Group, category, type of protection ¬ II (1)G [EEx ia] IIC
safely protected against voltage surges of
Modules

CSA approval
different origin (e. g. lightning stroke,
Control drawing 116-0187 (cCSAus)
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
The end digits of the model designation
Field Mount

correspond to the protected terminals of


Modules

the respective KF module.


For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
Modules

comply with all applicable regulations.


Plug-In
Accessories

Diagrams

Front view

Connection to earth

P-LB-1.E.23
Removable terminal
blue, not protected
11/2010

2 (2)

3 (3)
908837 (US) / 208599 (EU)

Terminals Zone 0, 1, 2 Zone 2


protected Div. 1, 2 Div. 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-1.E.23

518 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.C.2356

Technical data Features


Signal lines • 2-channel
Connection Terminals 2, 3; 5, 6
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 2, 3, 5 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044

DIN Rail Mount


By simply snapping the barriers into a
Group, category, type of protection ¬ II (1)G [EEx ia] IIC
standard KF module, the modules are

Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.

Field Mount
The end digits of the model designation

Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is

Modules
protecting. The ground system must

Plug-In
comply with all applicable regulations.

Accessories
Diagrams

Front view

Connection to earth

P-LB-2.C.2356
Removable terminals
blue, not protected
11/2010

2 (2)

3 (3)
908837 (US) / 208599 (EU)

5 (5)

6 (6)

Zone 0, 1, 2 Zone 2 Terminals


Div. 1, 2 Div. 2 protected
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-2.C.2356

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 519
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.D.1234 Surge Protection Barrier

Features Technical data


• 1-channel Signal lines
Connection terminals 1, 2, 3, 4
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules
Surge Protection

Rated current ≤ 250 mA


• Analog or digital signal inputs Leakage current ≤ 5 μA
• Surge protection up to 10 kA On-state voltage ≤ 45 V
• Protects leads 1, 2, 3 and 4 of Ground insulation ≤ 500 V breakdown voltage
KF modules Ambient conditions
• Uninterruptable operation Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
(auto reset) Mechanical specifications
Protection degree IP20
Function Mass approx. 70 g
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
This Surge Protection Barrier is designed Data for application in connection see page 522 for entity parameters
for use with K-System (KF modules). with Ex-areas
EC-Type Examination Certificate PTB 02 ATEX 2044
DIN Rail Mount

By simply snapping the barriers into a


Group, category, type of protection ¬ II (1)G [EEx ia] IIC
standard KF module, the modules are
Modules

CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount

The end digits of the model designation


Modules

correspond to the protected terminals of


the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules

protecting. The ground system must


Plug-In

comply with all applicable regulations.


Accessories

Diagrams

Front view

Connection to earth

P-LB-1.D.1234
Removable terminal
blue, not protected
11/2010

1 (1)

2 (2)
908837 (US) / 208599 (EU)

3 (3)

4 (4)

Terminals Zone 0, 1, 2 Zone 2


protected Div. 1, 2 Div. 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-1.D.1234

520 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-1.F.1236

Technical data Features


Signal lines • 1-channel
Connection terminals 1, 2, 3, 6
• Plugs directly in to field side of
Rated voltage ≤ 30 V
KF modules

Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 2, 3 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044

DIN Rail Mount


By simply snapping the barriers into a
Group, category, type of protection ¬ II (1)G [EEx ia] IIC
standard KF module, the modules are

Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.

Field Mount
The end digits of the model designation

Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is

Modules
protecting. The ground system must

Plug-In
comply with all applicable regulations.

Accessories
Diagrams

Front view

Connection to earth

P-LB-1.F.1236
Removable terminal
blue, not protected
11/2010

1 (1)

2 (2)
908837 (US) / 208599 (EU)

3 (3)

6 (6)

Zone 0, 1, 2 Zone 2 Terminals


Div. 1, 2 Div. 2 protected
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


P-LB-1.F.1236

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 521
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Entity Parameters Surge Protection

ATEX Entity Parameters

Model Number Terminals Ui (V) Ii (mA)


K-LB-1.30 1, 2 30 250
Surge Protection

K-LB-2.30 1, 2; 3, 4 30 250
K-LB-1.6 1, 2 6 250
K-LB-2.6 1, 2; 3, 4 6 250
K-LB-1.30G 1, 2 30 250
K-LB-2.30G 1, 2; 3, 4 30 250
K-LB-1.6G 1, 2 6 250
K-LB-2.6G 1, 2; 3, 4 6 250
FN-LB-I red, black 50 –
FP-LB-I red, black 50 –
FS-LB-I red, black 50 –
P-LB-1.A.13 1, 3 30 250
DIN Rail Mount

P-LB-2.A.1346 1, 3; 4, 6 30 250
Modules

P-LB-1.B.12 1, 2 30 250
P-LB-2.B.1245 1, 2; 4, 5 30 250
P-LB-1.C.123 1, 2, 3 30 250
P-LB-2.D.123456 1, 2, 3; 4, 5, 6 30 250
P-LB-1.E.23 2, 3 30 250
P-LB-2.C.2356 2, 3; 5, 6 30 250
P-LB-1.D.1234 1, 2, 3, 4 30 250
P-LB-1.F.1236 1, 2, 3, 6 30 250
Field Mount
Modules

CSA Entity Parameters

Model Number Terminals Vmax (V) Imax (mA)


K-LB-1.30 1, 2 40 250
K-LB-2.30 1, 2; 3, 4 40 250
Modules

K-LB-1.6 1, 2 40 250
Plug-In

K-LB-2.6 1, 2; 3, 4 40 250
K-LB-1.30G 1, 2 40 250
K-LB-2.30G 1, 2; 3, 4 40 250
K-LB-1.6G 1, 2 40 250
K-LB-2.6G 1, 2; 3, 4 40 250
FN-LB-I red, black 48 250
FP-LB-I red, black 48 250
Accessories

FS-LB-I red, black 48 250


P-LB-1.A.13 1, 3 40 250
P-LB-2.A.1346 1, 3; 4, 6 40 250
P-LB-1.B.12 1, 2 40 250
P-LB-2.B.1245 1, 2; 4, 5 40 250
P-LB-1.C.123 1, 2, 3 40 250
P-LB-2.D.123456 1, 2, 3; 4, 5, 6 40 250
P-LB-1.E.23 2, 3 40 250
11/2010

P-LB-2.C.2356 2, 3; 5, 6 40 250
P-LB-1.D.1234 1, 2, 3, 4 40 250
908837 (US) / 208599 (EU)

P-LB-1.F.1236 1, 2, 3, 6 40 250
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


522 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Accessories

35 mm DIN Rail Insertion strip


NS 35/7.5 ZH-ES/LB

Insertion Strip
Label carrier
ZH-ES/LB ZH-Z.BT

Surge Protection
Label Carrier DIN rail NS 35/7.5
ZH-Z.BT 35 mm standard rail
to DIN EN 60715
Terminal Block
USLKG5
Function
DIN rail mount module grounding
Terminal block
USLKG5

DIN Rail Mount


Modules
Mounting Block
ZH-Z.AB/SS
Connector
ZH-Z.AK16
Spacing Roller

Field Mount
ZH-Z.AR.85

Modules
Grounding Rail
ZH-Z.NLS-Cu3/10 Connection terminal
1
ZH-Z.AK16

15 mm (0.59'')
Function
Plug-in module grounding

Mounting block

Modules
2

Plug-In
ZH-Z.AB/SS

'')
57
(4.
6 mm
11

Spacing roller Grounding rail


3 4

Accessories
ZH-Z.AK.85 ZH-Z.NLS-Cu3/10

Notes
When mounting on 35 mm DIN rail:
• installation height 15 mm: spacing roller ZH-Z.AR.85
• installation height 7.5 mm: no spacing roller necessary
Keep the drilling distance of 116 mm between center DIN rail and center
grounding bar.
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs