Beruflich Dokumente
Kultur Dokumente
for
CONTENTS
Page
1. Scope 2
2. System Parameters 2
3. Service Conditions 2
4. Applicable Standards 2
5. Basic Features 3
6. Quality Assurance 7
7. Additional Requirements 7
9. Sample 10
12. Annexure 11
1
CEB STANDARD 067:1998
1.0 SCOPE
This Specification covers the general requirements of the design, manufacture and testing
of Static (Electronic) Three Phase Energy Meters of Accuracy Class 0.2 and 0.5.
The equipment and components supplied shall be in accordance with the latest
editions/amendments of the Standards specified below.
2
CEB STANDARD 067:1998
The Three Phase Static Energy Meters shall consist of an Integrating Static Kilowatt-hour
(kWh) Meter of Accuracy Class 0.2 / 0.5 and a Static Maximum Demand Indicator (MDI).
Specified accuracy should remain for full power factor range in all quadrants. The burden
of the meters shall not be more than 1VA. The meters shall be of the surface mounting
type and shall have bottom terminals.
a) The meters shall be of the programmable type suitable for recording active energy
consumption in kilowatt-hour (kWh) and the maximum demand (KVA).
c) The meters shall record the cumulative consumption of kWh every thirty days
(monthly consumption), and the maximum of average KVA demand over a demand
integration period of fifteen (15) minutes. Facilities shall be provided to reset the
maximum demand indication. (generally every 30 days)
d) The meters shall have facilities to display the kWh consumption and the Maximum
Demand, to store a minimum of four months data and to display the necessary
data when required.
e) The meters shall be programmable via a hand held programming unit or function
keys with facilities for down loading of readings to a data logger/PC (IBM
Compatible).
3
CEB STANDARD 067:1998
v) Frequency 50Hz
g) The meters shall display the stored cumulative consumption of kWh, maximum
demand and the maximum demand reset count when required ;
h) The meters shall preferably record accurately irrespective of the phase sequence
of supply.
i) The meter shall operate normally, even in the absence of neutral & when any two
voltage leads are connected.
a) 110 Volts, three phase, three wire (two element) system when used at
33KV & 11KV system.
b) 400 Volt, three phase, four Wire system when used at low voltage system.
The Meters shall be suitable for operation on standard rated currents of 1 Amp and 5
Amps and the maximum current shall be 20% of the standard rating
The meter shall be designed and constructed in such a way as to avoid introducing any
danger in normal use and under normal working conditions, so as to ensure especially ;
All parts which are subject to corrosion shall be suitably protected and any protective
coating shall not be liable to damage by normal handling.
4
CEB STANDARD 067:1998
The meter shall have an insulated case which shall be sealed in such a way that the
internal parts of the meter are not accessible to unauthorised persons.
Any non-permanent deformation of the case shall not affect the satisfactory performance
of the meter.
The window shall be of transparent material which cannot be removed undamaged without
breaking seals.
The Insulating material of which the terminal block is made shall be capable of passing the
test stipulated in ISO 75 for a temperature of 135°C. and a pressure of 1.8 MPa.
The bore of the terminals shall be adequate enough to accommodate two numbers 2.5
mm² copper cables and each terminal shall have two screws for effectively clamping
cables.
The wiring terminals shall be protected by a sealable terminal cover and the terminal cover
shall be made of an insulating material.
The terminal covers shall be of extended type with easily breakable knock-outs. Provision
shall be made to seal the meter cover and terminal cover separately.
The terminal block,the terminal cover and the meter case shall not ignite by thermic
overload of live parts in contact with them
The Metering equipment shall be suitable for outdoor use and conform to the degree of
protection of IP51 as per IEC 529.
The meters shall be provided with a clear Electronic Display under a viewing panel to
ensure that the meter retains its IP 65 ratings and the dimensions of figures shall not be
less than 4 mm (Height) and 4 mm (Width). Minimum number of digits shall be 6 including
a decimal.
5
CEB STANDARD 067:1998
The meters shall have non-volatile memory type electronic display. The non-volatile
memory shall have a minimum retention time of four months.
The Meters shall have a test output device accessible from the front and capable of being
monitored with a testing equipment. It shall provide an error message when the meter is
faulty. An operation indicator shall be provided and it shall be visible from the front.
Every meter shall be provided with a Name - plate incorporating the information as per
IEC 687 and the meter terminals shall also be marked.
Every meter shall be indelibly marked with a diagram of connections and this diagram shall
also show the phase sequence for which the meter is intended.
a) Temperature Range
The operating Temperature range of the Meters shall conform to the table 5 of IEC 1036
for outdoor meters.
b) Relative Humidity
The meters shall be suitable for outdoor operation in a humid tropical climatic condition
with the relative humidity as stipulated in clause 3.0 above.
The active and apparent power consumption in the current and voltage circuits of the
meters at a reference voltage, frequency, temperature and rated current shall not be more
than that stipulated in table 6 of IEC 687.
a) Voltage Range
The normal operating voltage range of the meters shall be as stipulated in Table 7 of IEC
687 and the permissible error due to voltage variation shall conform to the table 11 of IEC
687.
6
CEB STANDARD 067:1998
Voltage interruptions shall not produce a change in the readings as stipulated in Clause
4.4.2.2 of IEC 687. When the voltage is restored, the meters shall not have suffered
degradation of the metrological characteristics.
The meters shall be able to carry for 0.5 sec. a current equal to 20 times the rated current
without damage and the variation of error at rated current and unity PF shall not exceed
0.05%
The variation of error due to self-heating shall not exceed the value given in Table 8 of IEC
687.
The temperature rise at any point of the external surface of the meters shall not exceed
25K with the ambient temperature at 40°C. Under normal operating condition the electrical
circuits and insulation shall not reach a temperature which might affect the operation of the
meters.
5.4.5 Insulation
The insulation of the meters shall withstand an impulse voltage of 6kV peak. and power
frequency withstand voltage as stipulated in table 13 of IEC 687.
The meters shall be designed in such a way that conducted or radiated electromagnetic
disturbance as well as electrostatic discharge do not damage or influence the meter.
The meters shall not generate conducted or radiated noise which could interfere with other
equipment.
7
CEB STANDARD 067:1998
The meters shall be of accuracy Class 0.2 / 0.5 as specified and shall be suitable for
operation within the accuracy class limits specified in a tropical climate and service
conditions as given in Clause 3.0.
The percentage errors shall not exceed the limits for the relevant accuracy class given in
tables 9 and 10 of IEC 687.
The additional percentage error due to the change of influence quantities shall not exceed
the limit for the reference accuracy class given in table 11 of IEC 687.
The limits of error shall not exceed the limits given in table 12 of IEC 687.
The meter shall be fully functional within 5 seconds after the voltage is applied to the meter
terminals.
When the voltage is applied with no current flowing in the current circuit, the test output of
the meter shall not produce more than one pulse.
The meter shall start and continue to register at 0.0001 In and unity power factor.
e) Meter Constant
Necessary number of pulses to ensure a measuring accuracy of at least 1/10 of the class
of the meter at the different test point shall be indicated in the offer .
The manufacturer shall have obtained Quality assurance certification conforming to ISO
9001 for the manufacturer of Static Three phase Kilowatt-hour (kWh) Meters and
Maximum Demand Indicators (MDI). Bidders shall furnish documentary evidence to prove
this with the offer.
8
CEB STANDARD 067:1998
b) The Meters shall be rugged construction, proven design and reliable so that the
Meter shall operate within the stipulated error limits for a period of 10 years.
c) The manufacturer shall have supplied static 3 phase energy meters to a minimum
of five Electricity Authorities/Utilities out of which at least 3 are from outside the
country of manufacture. The manufacture shall furnish list of Authorities/Utilities to
whom meters were supplied in the past five years indicating their names and
addresses clearly.
a) Catalogues describing the equipment and indicating the type and model number.
b) Literature describing the operational feature of the equipment.
c) Constructional features, materials used for components and relevant technical
literature.
d) Complete dimensional drawings.
e) Manufacturing Experience and Performance certificate as stipulated in clause 7.1
and 7.2 above.
f) The details of the information that will be indicated on the Name Plate of the Meter
as stipulated in Clause 5.2.8 above.
g) Completed Schedule of Particulars (ANNEXURE - A).
h) Quality assurance certification conforming to ISO 9001.
i) The following Type Test Certificates conforming to IEC 687 from a recognised
testing authority acceptable to the Purchaser shall be furnished;
9
CEB STANDARD 067:1998
c) Vibration Test
d) Test of resistance to heat and fire
e) Tests of protection against penetration of dust and water
10
CEB STANDARD 067:1998
The Type Test shall be performed at a reference voltage of 110V / 415 V at a reference
frequency of 50 Hz.
The Type Test Certificates shall be submitted in complete form as furnished by the testing
Authority. Incomplete Type Test Certificates or parts of Certificates will not be considered.
Failure to furnish the above particulars in full, and sample Meters as stipulated in
clause 10.0 will result in the offer being rejected.
9.0 SAMPLE
One sample meter with manufacturer's seals shall be handed over to the Purchaser if and
when required. The sample of the successful Bidder will be retained and set-off from the
quantity to be supplied by him and the samples of the unsuccessful bidders will be
returned once the award is made.
10.1 Inspection
The selected Bidder shall make necessary arrangements for inspection by an Engineer
appointed by the Purchaser and to carry out in his presence necessary sample /
acceptance tests on the Meters offered.
The following test as per IEC 687 and IEC 1358 shall be witnessed by the representative
of the Purchaser.
11
CEB STANDARD 067:1998
i) Vibration test
ii) Shock test
iii) Spring hammer test
iv) Tests of protection against penetration of dust and water
v) Test of resistance to heat and fire
Extra copies of these Test Certificates shall also be supplied with the Metering Equipment.
Each consignment of equipment shall accompany one set of test results recorded in
tabular form to conform to the above.
If the test results are recorded in separate sheets all such sheets pertaining to each
consignment shall be bound together as one volume.
12
CEB STANDARD 067:1998
12.0 ANNEXURE
ANNEXURE - A
Bidders shall complete and submit with the Bid the schedule of technical particulars given below
for each rating.
4) Applicable Standards -
13
CEB STANDARD 067:1998
21) Whether the following Type Test certificate As per IEC 687
furnished in complete form, from Recognized Testing Authority,
indicate the deviations if any.
14
CEB STANDARD 067:1998
28) Indicate the extra facilities available with the meters. Attach separate sheet
29) Whether the Acceptance/Sample Tests as per
Clause 10.2 will be carried out by the
Manufacturer Yes/No -
15
CEB STANDARD 067:1998
..........................................................
Seal and Signature of the Manufacturer/ Date
TEST-PPM
16