Engineers Newsletter
volume 47–2

HVAC-related changes in
ASHRAE Standard 90.1-2016
down in a digital document (ironically 2013 version. This is the energy
Jurisdictions have begun to adopt
ASHRAE 90.1-2013. We now look to the
noted in this three-column document). consumed by the entire building,
2016 version for ideas on how to save And due to overwhelming hue and cry, including equipment not regulated by
energy over the 2013 version—for italics that were removed in the 2013 90.1.
participating in above-code programs, version have been restored. Words in
preparing for the future, or simply as a The mechanical-related changes include:
italics are defined in Chapter 3 of the
design preference for energy and energy
cost saving. This Engineers Newsletter standard. You'll also find that digital • New climate zone assignments from
describes important changes affecting versions have hyperlinks and cross- ASHRAE Standard 169-2013
HVAC systems and related equipment. references. There is also a new
interactive tool for 90.1 available on the • Replacement equipment to follow
ASHRAE website. some mandatory and prescriptive
Since 1975, ANSI/ASHRAE/IES
requirements (other than just
Standard 90.1 (hereafter referred to as
Purchase a copy of Standard 90.1, and efficiency)
90.1 for brevity) has been the basis of
the accompanying User’s Manual to
many energy codes, and continues to • New coverage in equipment classes
better understand the requirements as
be adopted directly or by reference in such as DOAS, CRAC and pool
they apply to specific systems, climates,
the International Energy Conservation dehumidifiers
buildings and design applications.
Code (IECC). It is also the basis for
• Upgraded efficiency in packaged DX
determining compliance with the
rooftops, PTAC and VRF
Energy Policy Act of 1992.
• Economizer fault detection in
While harmony is desired and 2016 HVAC Changes packaged DX equipment
attempted between 90.1 and IECC,
• Variable airflow exhaust- and return-
some requirements diverge. This 121 addenda were incorporated in 2016.
fan VFD control for building pressure
newsletter identifies some of the areas Of those, only 23 had energy savings
control
and sections with the most differences which could be captured in any of the
between the two model codes, to help nearly 600 energy models created by the • VFD threshold reductions (towers,
designers select a preferred path when U.S. Department of Energy to determine pumps, fans)
there is a choice. energy saving impacts. Some types of
• Fan system control 5 hp threshold
equipment are not used in any of the
Look for this icon throughout this moved to subsections
prototype buildings, some changed the
newsletter to indicate significant optional performance path only, and • Chilled-water plant monitoring
differences between 90.1-2016 and others simply added clarity to previous • 15°F minimum design delta T for
IECC-2018. requirements. cooling coil selections
The most obvious change is the new According to these models, the 23 • Chilled water reset alternative to
formatting, which is better suited for addenda save 34 percent energy versus pump pressure reset
digital use. More columns in the old the 2004 version, or 6.8 percent
version lead to more scrolling up and (weighted average) compared to the Let's review these changes in more
detail.

©2018 Trane. All rights reserved. 1


Revised climate classifications. Figure 1. ASHRAE climate zone map.
ASHRAE 90.1-2016 updated to the
climate classifications published in
ASHRAE Standard 169-2013 (Figure1).
The methods and data used to develop
the classifications are sufficiently
arcane that this newsletter will only
summarize and illustrate the
significance of this change.

Some areas were quite affected


(Figure 2). For example, 75 percent of
the population of Wisconsin "moved"
from climate 6A to 5A and 3 percent
moved from 7 to 6A. Other states
heavily reclassified are West Virginia
(47%), North Carolina (43%), North
Dakota (37%), Tennessee (36%),
Indiana (30%) and Texas (24%). A few
states reclassified as colder, such as
Oklahoma (9% from 3A to 4A), New
Hampshire (6% from 5A to 6A) and
Washington (4% from 4C to 5C).
Portions of 169 have been reprinted in
the appendices of 90.1 for ease of
reference.

These changes have ripple effects Figure 2. Counties where climate zone classification has changed.
throughout the Standard. For example,
requirements for insulation, glazing,
the economizer tradeoff and high limit
controls may change, all with potential
impacts on energy savings
calculations.

Climate zone 1 has been divided to


include a new climate zone 0, to allow
for more discerning requirements and
their justifications for even hotter
locations. Several areas outside of
North America have begun to use 90.1
as the basis of their own energy RED counties moved to
codes—some of which are in climate milder zones
zone 0. Source:
GREEN counties moved to
colder zones

2 Trane Engineers Newsletter volume 47-2 providing insights for today’s HVAC system designer
Mandatory Section (6.4) stringency. The table is quite large due to Prescriptive Section (6.5)
Changes many different temperature conditions for Changes
the various cooling and heating sources.
Requirements in this section are Prescriptive requirements may be traded
mandatory, meaning they cannot be Chiller-plant monitoring and reporting. off using one of the performance or
traded off using any of the other Another mandatory requirement is for new alternative compliance paths. If you have a
compliance paths. All paths include the chiller plants to have efficiency and energy situation where you can't or don't wish to
mandatory sections. use measurement and reporting. This comply with a prescriptive requirement,
requirement is invoked based on climate you may switch to the performance path
and chiller-plant size (Table 1). (Chapter 11) or the new Energy-Cost-
Replacement equipment. Previously,
like-for-like replacement equipment only Budget (Appendix G) based compliance
Table 1. Chiller-plant monitoring requirements
had to meet the minimum efficiency option.
Climate zone Water-cooled Air-cooled
requirements, and not all other
plant plant
prescriptive and mandatory Replacement equipment
requirements. In the new version, 3C,4C,5,6,7,8 >1500 tons >860 tons prescriptions. In addition to the
replacement equipment is now obliged previously mentioned mandatory
to also meet several mandatory (as well 0,1,2,3A,3B, >1000 tons >570 tons requirements, the following prescriptive
as prescriptive) requirements. This 4A,4B requirements must also be met when
includes off-hour controls, demand- replacing like-for-like equipment.
controlled ventilation for single-zone
• Economizers (outdoor units)
systems, and setpoint controls. Other The data must be recorded and trended
prescriptive requirements for every 15 minutes and graphically displayed • Integrated economizer control
replacement equipment will be to include hourly, daily, monthly and annual • Economizer heating impact
discussed later. information. The data must be maintained
for at least three years. • Fan efficiency
DOAS equipment. A new class of • Fan airflow control
product has been added for direct- Economizer fault detection and • Ventilation optimization (multiple-zone
expansion (DX), dedicated outdoor air diagnostics. This mandatory requirement VAV systems)
systems (DOAS). This includes a applies to packaged unitary DX air-
reference to the recently created AHRI conditioners and heat pumps, regardless of • Parallel, fan-powered VAV controls
Standard 920, which reflects the condensing type, if they have an air • Fractional horsepower fan motors
different conditions a 100 percent economizer. The purpose is to identify
outdoor-air unit is expected to when sensors and controls on the • Fan speed control (heat rejection
experience. The rating is based on equipment are not economizing (bringing in equipment)
moisture removal efficiency (MRE) with more than minimum outdoor air) when • Chiller and boiler isolation
an off-design rating of ISMRE for cooling outdoor conditions are favorable, or
and/or ISCOP for heating. Standard 920 • Boiler turndown
conversely if the economizer is active when
and its use by 90.1 was the subject of a conditions are unfavorable. Permanent
previous Engineers Newsletter. sensors, economizer status, fault Chilled-water reset. This is a new
detection, reporting and provisions for test alternative to pump-pressure reset based
Pool dehumidifiers and CRAC units modes are specified by 90.1. This on critical valve position. You may now
are newly covered in the scope of requirement has been in place for several choose to reset chilled-water temperatures
90.1. The scope of 90.1 is written so years in California; manufacturers have to keep one valve nearly wide open or until
that coverage for new equipment can be already developed equipment options that equipment limits are reached. Or, you may
added over time. In this case, pool meet the requirements (Figure 3). continue to use pump-pressure reset
dehumidifiers and CRAC units now have based on critical valve. Exceptions are
minimum efficiency requirements. provided for district cooling, thermal
Figure 3. Automatic fault detection implemented storage and process cooling. The Trane
in a rooftop unit controller
ENL in 2015 included a table comparing the
VRF equipment. The 2013 version had
energy performance of the two options.
the first efficiency requirements for VRF
Generally speaking, pump-pressure reset
systems with a corresponding AHRI
saves more energy at higher load (flow)
certification program and test
conditions, or when constant-speed
procedure. The 2016 version changes
chillers are used, and when system design
some of the part-load requirements,
delta T is less than 15º F. You can also
effective either January of 2017 or 2018,
choose to do both resets in sequence. That
depending on the product. Part of this is
is, do one until it reaches a limit and then
due to a change in the test procedures
the other.
and part from an actual improvement in

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–2 3
Table 2. Updated requirements for pump VFD control
Chilled-water pumps Heating-water pumps Nameplate hp
0, 1, 2B no requirement ≥ 2 hp
2A, 3B no requirement ≥ 3 hp
3A, 3C, 4A, 4B 7,8 ≥ 5 hp
4C, 5, 6 3C, 5A, 5C, 6B ≥ 7.5 hp
4A, 4C, 5B ≥ 10 hp
7,8 4B ≥ 15 hp
2, 3A, 3B ≥ 25 hp
1B ≥ 100 hp
0, 1A ≥ 200 hp

Pump VFD control by climate zone, Waterside economizer for induction Two changes were made. The word "fan"
now includes heating. During the and/or fan-free systems. Aggregating was struck from the threshold, as
evaluation of lowering the chilled-water coil capacity rather than looking at the sometimes these units do not have a fan.
pump VFD threshold, it was discovered fan-plus-coil terminal size is something Then, when their total cooling load is
that the existing requirements were not that's new and starting to affect more large enough, an economizer is required.
universally cost justified. The result of codes, but not 90.1. Thresholds based on "Large enough" varies by climate zone.
this evaluation prompted a new table, terminal size were used so that chilled-
which also creates VFD requirements The new requirement applies to chilled-
water systems were not disadvantaged
on heating-water pumps in many water cooling systems without a fan or
compared to other small-terminal DX
climate zones. Unsurprisingly, hot that use induced airflow when the sum of
systems, such as PTACs or VRF. Small
climates use drives on smaller pumps the cooling loads not served by another
units (<54,000 Btu/h) have traditionally
in their cooling system and cold type of economizer is
been exempt from economizers and still
climates use drives on smaller pumps are. However, chilled-beam and induction • ≥ 1,000,000 Btu/h (83 tons) in
in their heating systems (Table 2). units now are not. When multiple chilled- climates 0, 1B, 2, 3, and 4
water terminals are connected to the
• ≥ 1,400,000 Btu/h (116 tons) in
same chiller, especially sensible-cooling-
climates 5-8
only terminals using relatively warm
water, it's difficult to ignore the potential • Any size in climate 1A
savings by using the water-economizer
cycle.

Water economizer requirement in IECC.


Unlike 90.1, the IECC now has a system size aggregation (not just for induction units but for all chilled-water coils) when water economizers
are required. The equipment performance exception may be used instead in climates 2A/B, 3A/B and 4A/B (Table 3).

Table 3. Minimum chilled-water system cooling capacity for determining economizer cooling requirements

Total chilled-water system capacity less capacity of cooling units with air economizers
Climate zone
Local water-cooled chilled-water systems Air-cooled chilled-water systems or district chilled-water systems

1A Economizer not required Economizer not required

1B, 2A, 2B ≥ 960,000 Btu/h ≥ 1,250,000 Btu/h

3A, 3B, 3C, 4A, 4B, 4C ≥ 720,000 Btu/h ≥ 960,000 Btu/h

5A, 5B, 5C, 6A, 6B, 7,8 ≥ 1,320,000 Btu/h ≥ 1,720,000 Btu/h

4 Trane Engineers Newsletter volume 47-2 providing insights for today’s HVAC system designer
Ventilation optimization despite Parallel-flow, fan-powered VAV Compliance requires two things: control
ERV. The 2010 standard introduced the (PFPVAV) air termination control. This and capability. The return/relief fan control
requirement for ventilation optimization new requirement specifies the method of must either directly manage building
in multiple-zone VAV systems. It was controlling the fan in a parallel, fan- pressure control or indirectly through
thought that systems required to use powered VAV terminal. The fan is only supply-return airflow tracking. The second
exhaust air energy recovery should be permitted to run during heating mode, or part of the requirement is for VFDs on
exempt from this requirement. if required for ventilation, and as the first fans ½ hp and larger or at least four
However, energy use increased with this stage of heat before any heating coil is stages of control.
exception, so it has been removed. All activated. Additionally, during warmup or
multiple-zone VAV systems must use during setback the controller must either Fan system control threshold moved to
ventilation optimization unless their stop the primary air or reverse the logic subsections. Previous versions only
exhaust is too high (>70%) relative to so that when the primary air is warmer required compliance with all of Section
outdoor-air intake, or if zone-to-zone rather than colder than the zone, the 6.5.3 Air System Design and Control once
transfer fans are used, as in fan-powered damper actuates to open (for more heat) the total system motor nameplate
VAV systems. The first exception is rather than close to its minimum as it exceeds 5 hp. This meant that
because less turndown of outdoor air is does in cooling mode when the zone is requirements such as the system fan-
available, and the second exception is being overcooled. power limit effectively did not apply to
because the ventilation effectiveness of
small, unitary packaged equipment.
systems meeting that exception cannot Variable airflow exhaust- and return- Requirements specifically addressing
be easily determined. fan controls. Building pressurization is products below the threshold (such as fan
critical for conserving energy, not to control down to 65,000 Btu/h, supply- air-
Ventilation design. This new mention moisture control. When exhaust temperature reset, VAV setpoint sensing)
requirement sets an upper limit on fans are out of sync with the ventilation perversely did not apply in some cases
ventilation of 135 percent of the system, buildings don't perform well. anyway. The system size threshold was
minimum outdoor airflow rate using the This can lead to doors that stand open replaced with individual thresholds within
prescriptive path. If additional ventilation (positive pressure) or to moisture the specific requirements
is part of the design, the building would intruding into the envelope (negative (Table 4).
have to comply using one of the pressure). Moisture in the insulation layer
performance options. reduces its effectiveness at reducing heat
gains or losses across the envelope.
Limits on reheating in dedicated Buildings with poor pressurization control
outdoor-air systems (DOAS). When are also more likely to have operators
zones demand cooling, it doesn't make who disable or limit airside economizer
sense for the DOAS to reheat operation.
dehumidified air to space neutral dry-
bulb temperatures, because zone
cooling and fan energy increase. This Table 4. Size thresholds for Section 6.5.3.
requirement sets a limit of no higher Section Name Threshold
than 60°F supply air from the DOAS 6.5.3.1 Fan System Power and Efficiency > 5 hp
when a majority of the zones are in 6.5.3.1.3 Fan Efficiency All, with exceptions
cooling mode. Any energy (even site-
6.5.3.2 Fan Control DX >= 65,000 Btu/h
sourced or recovered energy) is
chilled water >= 1/4 hp
prohibited from being used for this
6.5.3.2.2 VAV Static Pressure Sensor Location All or meet 6.5.3.2.3 instead
purpose. This implies system-level
coordination: the DOAS is operated 6.5.3.2.3 VAV Setpoint Reset > 5 hp and DDC
differently, depending on the mode 6.5.3.2.4 Return and Relief Fan Control >1/2 hp in total (exception) or 4+ stages
(heating or cooling) of the majority of the 6.5.3.3 Multiple-zone VAV Ventilation Optimization All, with exceptions
zones served by the other cooling/ 6.5.3.4 Parallel-flow, Fan-powered VAV Control (new All
heating systems. A previous Trane requirement)
Engineers Newsletter and application 6.5.3.5 Supply-Air-Temperature Reset All, with exceptions for climate zones 0, 1A, 2A,
guide (SYS-APG001-EN) discuss the 3A (and other cases
merits of non-neutral DOAS air delivery 6.5.3.6 Fractional Horsepower Fan Motors 1/12 to 1/2 hp motors, exception for heating-only
in more detail. fans, others
6.5.3.7 Ventilation Design (new requirement) All

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–2 5
Economizer comfort cooling efficiency Minimum 15°F delta T chilled-water
tradeoff. This requirement is not new, cooling coil selections. Chilled-water Where to Learn More
but many locations may have switched coils now must be selected for at least a
climate zones. The option compares the 15°F delta T with at least a 57°F leaving ASHRAE 90.1-2016 incorporated many
efficiency of compressor-bearing coil water temperature. Exceptions changes in this cycle. This newsletter
equipment to the minimum requirements include: summarized only the HVAC-related
for that same equipment in Section 6.4.1. mandatory and prescriptive changes. In
• Sensible-only cooling coils,
If the unit meets the full-load efficiency 2017, ASHRAE launched a 90.1 portal which
required in Section 6.4.1 and its rated • Fan-cooling units with 5000 cfm or you may find useful for learning more about
part-load efficiency is better than the less, these and other changes. It brings together
minimum requirement by the fraction in the Standard, the Users' Manual, and a
• Constant volume systems,
the tradeoff table (Table 5), an redline version that shows changes from
economizer is not required. • Coils selected at 50°F or higher one version to the next. Visit https://
entering water or 65°F or higher 901portal.ashrae.org.
This option is quite different in IECC- entering air temperatures, or coils
2018, where it is less stringent but only selected at the maximum The International Code Council (ICC) has
covers six climates: 2A/B, 3A/B, 4A/B. temperature difference allowed by also provided free online view-only access
The "A" climates are new in the 2018 the chiller. to the IECC Model Code. Chapter 4
version (Table 6). (commercial) can be viewed at https://
An extensive analysis was submitted to codes.iccsafe.org/public/document/
90.1 showing system energy iecc2018/chapter-4-ce-commercial-energy-
Table 5. Eliminate required economizer for consumption and first costs are reduced efficiency.
comfort cooling by increasing cooling when chilled-water coils are selected for
efficiency (90.1) higher delta Ts (lower water flow rates).
climate efficiency The analysis included the impacts on fan,
zone improvement pump and chiller energy and costs. The By Susanna Hanson, Trane. To subscribe or view
previous issues of the Engineers Newsletter visit
2A 17% rationale is explained in detail in a new trane.com/EN. Send comments to ENL@trane.com.
2B 21% course, ""Fundamentals of Design and
3A 27%
Control of Central Chilled-Water Plants,"
from the ASHRAE Learning Institute.
3B 32%
3C 65%
4A 42% Table 6. Table C403.5 (2) Equipment Efficiency
4B 49% Performance Exception for Economizers (IECC)
4C 64% cooling equipment
climate
performance improvement
5A 49% zones
(EER or IPLV)
5B 59%
2A, 2B 10% efficiency improvement
5C 74%
3A, 3B 15% efficiency improvement
6A 56%
4A, 4B 20% efficiency improvement
6B 65%
7 72%
8 77%

6 Trane Engineers Newsletter volume 47-2 providing insights for today’s HVAC system designer
A New Level of Building Design Accuracy
References
Announcing TRACE® 3D Plus!
[1] American Society of Heating, Refrigerating,
and Air-Conditioning Engineers. 2013 ANSI/
ASHRAE/IESNA Standard 90.1-2013: Energy
Standard for Buildings Except Low-Rise
Residential Buildings. Atlanta, GA: ASHRAE.

[2] American Society of Heating, Refrigerating,


and Air-Conditioning Engineers. 2016. ANSI/
ASHRAE/IESNA Standard 90.1-2016: Energy
Standard for Buildings Except Low-Rise
Residential Buildings. Atlanta, GA: ASHRAE.

[3] ASHRAE Standard 90.1-2016 User’s Manual.


Atlanta, GA: ASHRAE. Available at TRACE 3D Plus is a next generation building design and analysis software
www.ashrae.org/bookstore. program that delivers faster, more accurate results through a seamless
workflow that closely aligns with today's building process. The latest
[4] 2018 International Energy Conservation Code.
HVAC systems and controls can be modeled quickly, precisely and with
International Code Council, Washington, D.C.
IECC. 2018. the intricacies of today's many building applications. TRACE 3D Plus is
built on the U.S. Department of Energy's EnergyPlus® engine and
[5] Murphy, J., AHRI 920 "Rating Standard for enhanced with Trane's industry leading expertise to help designers
Dedicated Outdoor Air Units," Trane Engineers validate and interpret projects with confidence and clarity. All of these
Newsletter, vol. 45-4. ADM-APN060-EN. Trane
2016
new features plus a more robust support experience to get you up and
running quickly.
[6] Hanson, S., M. Patterson and J. Harshaw,
"Chilled-Water System Design Trends." Trane
For details or to download a trial version visit Trane.com/TRACE3DPlus
Engineers Newsletter LIVE. APP-CMC056-EN.
Trane. 2015.

[7] Trane. Dedicated Outdoor Air Systems: Trane


DX Outdoor Air Unit Application Guide. SYS-
APG001-EN. 2012.

[8] Taylor, Steven T, "Fundamentals of Design and


Control of Central Chilled-Water Plants",
ASHRAE Learning Institute, 2017.

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 47–2 7
Join your local Trane office for the 2018 Engineers Newsletter LIVE!
Mark your calendar!
Demand-Controlled Ventilation. The mobility of a building’s occupants poses a
ventilation challenge: To bring enough outdoor air into the building to help ensure
good indoor air quality without wasting energy by bringing in (and conditioning) too
much. This ENL will discuss various methods used to vary outdoor airflow based on
actual demand. It also reviews the related requirements for compliance with
ASHRAE Standards 62.1 and 90.1. (November)

Contact your local Trane office for dates and details.

Earn PDH credit - no charge and on-demand!


NEW Online Courses Available!
View all courses under Training/Continuing Education at www.trane.com

Cooling Towers and Condenser-Water System Design and Operation


Sometimes overlooked, the cooling towers and condenser water loop play and
important role in the first cost, function, and efficiency of the chilled-water
systems. A fundamental understanding of how the cooling tower affects chiller
performance can provide opportunities to reduce both capital cost and operating
expense. (Recorded 2005)

Chilled-water System Design Trends This program reviews recent advancements


in technology and trends due to these developments, system strategies that can
take advantage of the latest technology and when various system strategies
should be used. Consideration will be given to: variable primary, primary
secondary, constant flow, series chillers, chilled water reset, pump pressure
optimization, flow rates and turndown, heat exchanger types, and the components
of air- and water-cooled systems.

Trane, the Circle Logo, and TRACE are trademarks of Trane in the United States and other countries. ASHRAE is a regis-
tered trademark of the American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc. Trane is a brand
of Ingersoll Rand, a world leader in creating comfortable, sustainable and efficient environments. Ingersoll Rand's family
of brands includes Club Car®, Ingersoll Rand®, Thermo King® and Trane®.

Trane, This newsletter is for informational purposes only and does not constitute legal advice.
A business of Ingersoll Rand Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
For more information, contact your local Trane
the material presented.
office or e-mail us at comfort@trane.com

8 Trane Engineers Newsletter volume 47–2 ADM-APN066-EN (June 2018)