APPENDIX A SECTION 6
INSTRUMENTATION SPECIFICATION
Qatar General Electricity & Water Corporation
Tender No. GTC 626/2014
Construction of Mega Reservoirs PRPSs
(Package A, B, C, D & E)
6 INSTRUMENTATION WORKS
6.1 GENERAL REQUIREMENT
Unless otherwise stated in the Project Documentation, the Contractor shall comply with
every requirement of the Qatar Construction Specification (QCS) that is relevant to the
type of work forming any part of the Contract and shall adopt whichever permissible
option or alternative is best suited to the needs of the work being undertaken.
6.2.1 General
This covers the requirements of the Control and Instrument Cables as listed but
not limited to the following main process components of the PRPS:
Main Pumps (Corridor Pumps and Transmission Pumps);
Recirculation and Drain/Scour Pumps;
Surge Suppression System (Surge Vessels, Compressed Air Systems, etc.);
Disinfection System;
Tanker Filling Pumps; and
Potable Water, Irrigation and Fire Fighting Pumps.
Power cables shall be in accordance with Clause 7.4.3 of Appendix A7.
B. Electric Cables
The CONTRACTOR shall also note that it is not the intent of this specification
to deviate from good engineering practices. The absence of specifications
shall imply that the best engineering practices shall prevail, utilising first quality
materials and workmanship.
The CONTRACTOR shall seek clarification from KAHRAMA/ENGINEER of
any confusing or conflicting information contained in this specification and the
accompanying documents.
Any deviation from this specification shall be indicated by the
CONTRACTOR/VENDOR along with his bid. Otherwise
KAHRAMA/ENGINEER shall assume full compliance with this specification
while accepting the bid.
C. Units
The instrumentation cables specifications and signals shall be according to
the international system of units (SI).
K. Cable Identification:
PE/MS/PVC/LS/PVC/SWA/PVC
Size: 1.0mm2 for Analogue
1.5mm2 for Digital
L. End Sealing
After completion of the Factory Tests, the ends of the cable shall be sealed
to prevent ingress of moisture.
M. Marking of Supplies
The external surface of the over sheath shall be embossed and/or printed
with:
Manufacturer's Name;
Year of Manufacture;
Size and Type of cable; and
Length marking.
This identification is to be repeated at intervals of not more than 1 meter.
The minimum character size shall be 3mm. The accuracy of the length
marking shall be within the limits of + 1%. The colour of the initial printed
marking shall be white. In case of a defective initial marking, the cable shall
be remarked in yellow.
Cable Type
RTD Cable - 1
Type PE-MS-PVC-SWA-PVC
Conductor insulation PE
Ripcord N/A
Type PE-MS-PVC-SWA-PVC
Conductor insulation PE
Ripcord Required
6.3.1 General
This covers the requirements of the Instruments as listed but not limited to the
following main process components of the PRPS:
Main Pumps (Corridor Pumps and Transmission Pumps)
Recirculation and Drain/Scour Pumps
Surge Suppression System (Surge Vessels, Compressed Air Systems, etc.)
Disinfection System
Tanker Filling Pumps
Potable Water, Irrigation and Fire Fighting Pumps
1. General
Electromagnetic flow meters shall be of a robust construction;
generally with the requirements of BS EN ISO 6817. Materials of
construction shall have a high level of corrosion resistance, be
durable and where normally exposed, be resistant to degradation by
sunlight and high temperatures.
The flow meter shall comprise of a flow sensor and a transmitter unit.
The transmitter shall be supplied as remotely mounted from the flow
sensor, subject to KAHRAMA/ENGINEER approval unless otherwise
specified on the Instrument Datasheet.
The flow meter shall be of the electromagnetic type utilizing pulsed
DC excitation and shall be microprocessor based.
The flow meter dimensions shall be in metric units. The flow meter
shall be calibrated at the factory to its actual flow range in m³/hr as
specified in the data sheets. A factory calibration certificate shall be
provided with the meter.
Accuracy shall be equal or better than ±0.2% of reading (actual flow
rate) at flow velocity >1 m/s with repeatability within ±0.1% of flow
rate.
The flow meter shall have on-site validation capability for sensor and
transmitter. This shall either come through built-in feature within the
meter’s advanced electronics or by a dedicated field portable
validator connected to the meter under test with or without cable.
The pipes on the upstream or downstream side of all flow meters
shall be provided with 2” NPT(F) threaded boss connection facility for
insertion of portable insertion type magnetic flow meter for verification
of the inline unit.
2. Flow Sensor
Construction shall comply with the following:
Sensor tube - stainless steel
Sensor tube lining - inert plastic material approved for use in
contact with potable water dosed with Chlorine and Chlorine
Dioxide disinfectants.
Flanges - carbon steel drilled to suit pipe flanges and coated with
an approved corrosion protection
Terminal Box: Aluminium
Ambient Temperature Limits: 70 Deg C
Process Temperature Limits: 70 Deg C
Electrode Material: SS 316L
The flow sensor tube shall be manufactured from AISI 316 stainless
steel with a non-conductive liner to withstand process temperatures
up to 70 ºC. The liner material shall be abrasive resistant and
approved for KAHRAMA potable water use by WR-UK or equivalent
internationally recognized authority.
The flow sensor lining has to be WRAS listed for water applications.
The cable has to be armoured, fitted and potted to the sensor prior to
shipping from the manufacturer's location. The electrical connection
4. Connection
The gauges shall have a bottom connection as specified. Connection
size shall preferably be ½ inch NPT (M).
5. Pointer Movement
The movement shall be of corrosion and wear-resisting material e.g.
stainless steel. Pressure gauges shall have zero adjustment facility
externally without the necessity for opening the case or draining the fill
fluid.
6. Pointer and Dial
A stainless steel flexible pointer stop on the dial shall be provided.
7. Safety Factor
Pressure containing parts shall be designed with a safety factor of 4 to 1.
8. Accuracy
Accuracy of the gauge shall be better than +1% of f.s.d.
9. Accessories
Each gauge shall be supplied with a gauge cock and a sample cock
which shall be fitted between the gauge and the discharge pipe
according to the approved primary connection diagram. Also a pulsation
damper / snubbers shall be supplied with each gauge if mounted in
highly pulsating process and discharge side of pumps. Diaphragm seals
shall be provided where the process media is unsuitable for direct
connection of gauge such as chlorine service.
A. Pressure Switches
The pressure-sensing element may be of the Bourbon tube, spiral,
helical, bellows or diaphragm type, depending upon the application
requirements. The pressure sensing element shall be of AISI 316
SS. Pressure switches shall withstand the maximum pressure of the
system to which it is connected. In addition, over range protection,
(at least 1.3 times the maximum scale reading), shall be included for
all instruments. Gauge protectors shall be included wherever
required to withstand maximum surge pressure. The Vendor shall
indicate the proof pressure for the proposed model in the material
submittal.
Set point for pressure switches shall be adjustable throughout the
operating range.
Pressure switches shall have ½" NPT (M) process connection.
Pressure switches generally be used for "ON-OFF" applications with
an adjustable set point and a differential gap with a reference or
calibrated scale. The switch type shall be snap action DPDT, rated
for 5 A at 240V AC or 1 A 30V DC. The switch shall also be
hermetically sealed with gold plated contacts. Degree of protection
shall be IP65 or better.
B. Pressure Transmitters
Pressure transmitters shall be of the direct sensing type with the
sensing element as per manufacturer's standard. The diaphragm
shall be hermetically welded to the measuring element assembly,
which shall be suitable for the operating temperature limits of 0 to 55
ºC unless otherwise specified.
The outputs shall be programmable through the keypad and the input,
outputs and power supply shall be electrically isolated from one
another.
The transmitter has to be mounted away from the sensor and shall be
housed in GRP boxes (double enclosure type) sunshades to protect
them against direct sun radiation.
The following outputs shall be available and configurable by the user:
i. 4 Nos. programmable Digital Output contacts as back-up level
reference.
ii. Analogue, 4-20 mA signal proportional to level
iii. HART communication port as required by the SCADA
Communication System.
The unit shall operate on a power supply of 240 V AC.
5. Materials
Sensor Horn : AISI 316L Stainless Steel
Flange : AISI 316L Stainless Steel
The following quality analysers shall be provided at the main inlets and the
main outlets of the PRPS:
Chlorine
Chlorine Dioxide
ORP
pH
Turbidity
Conductivity
Temperature
Residual Chlorine All the above sensors shall be flow cell type (except
Temperature which shall be Thermowell type) installed on Analyser Racks
located in the Water Quality Analyser rooms located near in the Chlorine
Plant. the sampling points. Sampled water shall be drawn from the locations
as shown on the drawings and routed via sampling pipes to the Water Quality
Analyser room.s.
The following quality analysers shall be provided at the inlets and the outlets
of all the cells of each reservoir:
Chlorine
Chlorine Dioxide
All the above sensors shall be flow cell type installed on Analyser Racks
located in the Water Quality Analyser rooms located near the sampling points
in the reservoir area.
It shall be noted that for the reservoirs, the sampling points are below ground
level at the inlet and outlet pipes. These locations will provide sufficient
sample pressure to the analysers. However, when water levels in the
reservoir drop below ground level (during emergency supply), sufficient
pressure will not be available to push water to the analysers located above
ground level in the Water Quality Analyser rooms. As such, sample pumps
shall be provided at the sampling points which shall come into operation
during these times. The starting and stopping of the sampling pumps shall be
determined by the flow sensor in the Chlorine Flow Cell and Chlorine Dioxide
Flow Cell.
The sensors shall be mounted on a Water Quality Analyser Rack at the
following locations:
Pumping Station discharge pipelines to Corridor and Transmission Mains
(Residual Chlorine, pH & ORP)
The Water Quality Analyser Rack for the pumping station discharge shall be
located in the Analyser Room which is part of the Chlorine Building.
All sensor transmitters for the reservoirs shall be located near the sensors on
ground level. The sensors shall be installed in the valve chambers which are
located below ground level. Sufficient sensor cable lengths shall be provided
to allow connection of sensors to transmitters.
B. Water Quality Analyser Transmitters
The unit shall be microprocessor based and of modular construction. The
operation shall be based on intelligent software to allow conversion of the
sensor signals, temperature (where required) to accurate readings.
The transmitter enclosure shall be certified to IP67 of IEC-60529.
The unit shall be provided with a keypad on the front panel to be used for
configuration purposes together with an illuminated LCD display and bar graph
segment display for level in steps of 10% or better.
Configurations shall be carried out by the use of standard operating matrix and
the time required for starting minimized by the use of pre-set operating
parameter values. Data storage shall be in EEPROM non-volatile memory to
avoid requirement of battery backup. A keypad locking facility to prevent
unauthorised access to program changes shall be provided.
D. Chlorine Dioxide
The analyser unit shall consists of flow cells, sensors, transmitter, associated
pipework, valves, cabling, etc. all factory pre-fitted on a stainless steel back
panel. The sensor shall measure Chlorine Dioxide.
The sensor shall be a three electrode amperometric type whereby the anode
is split into two parts to provide stable measurement and longer electrode life.
The measuring electrode shall be gold, the reference electrode shall be silver
with silver halide and the counter electrode shall be stainless steel. The
method of measurement shall be reagent-free and continuous in accordance
with US EPA Method 327.0.
The sensors shall be digital type which allows plug and play capability
whereby they can be calibrated in the lab and plugged into the controllers at
the analyser racks without any additional calibration, settings, software
configurations, etc.
A non-contacting sample flow sensor shall be incorporated to provide alarm
for insufficient flow. All warning shall be easily configurable.
The sensor characteristics shall be as follow:
Measurement range: 0 to 210ppm
Lower limit of detection: 90ppb
Resolution: 0.001ppm
Accuracy: ±510%
E. Conductivity
The measuring principle of the sensor shall be based on induction and
conduction. An alternating magnetic field generated in a primary coil shall
induce a current in the process media. Whereby, the strength of the induced
current will be proportional to the ion concentration and thus the conductivity
of the media. The current flow in the media shall generate another magnetic
field in a secondary coil which is then measured to determine the conductivity.
The sensors shall be retractable insertion type at the following locations:
Upstream of Reservoir Distribution Chambers
Inlet to Reservoirs
Outlet of Reservoirs
At the above listed locations, the sensors shall be installed into the pipelines
using a stainless steel retractable assembly. The retractable assembly shall
allow insertion and retraction of sensor without the need to isolate or interrupt
the main pipeline flow. This shall be achieved by isolation valves on the
retractable assembly which shall allow the sensor to be retracted without
allowing the medium in the pipeline to escape.
The retractable assembly shall be installed on the pipeline in such a way as to
allow accurate measurement and shall be able to sustain the maximum
pressure rating of the process.
The sensor characteristics shall be as follow:
Measurement range: 50 µS/cm to 500 mµS/cm
Accuracy: ±0.5%
F. pH Analyser
The sensor shall have an electrode with a glass membrane which supplies
an electrochemical potential dependent upon the pH value of the medium.
This potential shall be generated by the selective penetration of positive
hydrogen ions (H+) through the outer layer of the membrane which causes
an electrochemical boundary layer with an electrical potential. The measured
value of the electrical potential gives a measure of the pH. A reference
electrode shall be provided as well.
The sensors shall be retractable insertion type at the following locations:
Upstream of Reservoir Distribution Chambers
Inlet to Reservoirs
Outlet of Reservoirs
At the above listed locations, the sensors shall be installed into the pipelines
using a stainless steel retractable assembly. The retractable assembly shall
allow insertion and retraction of sensor without the need to isolate or interrupt
the main pipeline flow. This shall be achieved by isolation valves on the
retractable assembly which shall allow the sensor to be retracted without
allowing the medium in the pipeline to escape.
The retractable assembly shall be installed on the pipeline in such a way as
to allow accurate measurement and shall be able to sustain the maximum
pressure rating of the process.
The sensors shall be fitted into a flow cell mounted on a Water Quality
Analyser Rack at the following locations:
Pumping Station discharge pipelines to Corridor and Transmission Mains
The sensor characteristics shall be as follow:
Measurement range: 0pH to 14 pH
Accuracy: ±0.5%
G. Turbidity
The turbidity measurement shall be based on the measurement of light
scattered by suspended particles when a light beam is shone through the
medium. The amount of scatter gives a measurement of the turbidity of the
medium.
The sensors shall use a dual-beam infrared/scattered light photometer to
measure turbidity. An LED light source shall transmit a beam of infrared light
into the medium at an angle to the probe face. The scattered light shall be
detected by a pair of photoreceptors in the sensor face.
A backscatter photoreceptor shall be provided to accurately measure
suspended particles.
The sensors shall be insertion type installed into the pipelines using a
stainless steel retractable assembly. The retractable assembly shall allow
insertion and retraction of sensor without the need to isolate or interrupt the
main pipeline flow. This shall be achieved by isolation valves on the retractable
assembly which shall allow the sensor to be retracted without allowing the
medium in the pipeline to escape.
sheath material shall be provided. Terminals shall be suitable for solid wires
or wire pins of maximum 1.2 mm diameter.
RTD elements shall be offered in 3-wire duplex configuration. For 3-wire
configuration the lead wire terminals shall be colour coded red, red, and
white.
The sheath shall have a nominal outside diameter of 6 mm ±0.1 mm.
Sensing element shall be annealed platinum, sheath shall be austenitic
stainless steel or high nickel alloy tubing, grade determined subject to the
limit of the operating temperatures.
Insulating material within the sheath shall be compatible with the platinum
resistance thermometer operating temperature. Hermetically sealing
compound shall be compatible with the environmental conditions specified in
the purchase order. Connecting wire joining materials shall withstand the
RTD maximum operating temperature.
The platinum resistance thermometer performance shall be in accordance
with the requirements of IEC 60751, Pt 100 elements, having a resistance of
100 ohms at 0 ºC and a temperature coefficient of 0.003851 ºC-1.
The resistance tolerance shall comply with Class A according to IEC 60751,
where Class A tolerance (ºC) is 0.15 + 0.002 [t]. Where [t] = modulus of
temperature in degrees Celsius without regard to sign.
The insulation resistance of the compacted ceramic material shall have a
minimum resistance of 100 MΏ at ambient temperature (15-35 ºC) and a
relative humidity of minimum 80%, with an applied 10 to 100V DC voltage in
accordance with IEC 60751. Any decrease in insulation resistance at
elevated temperatures shall be in accordance with IEC 60751.
The RTD elements shall be supplied with thermowells of 316 SS. The
thermowells shall be drilled from barstock. Insertion length shall be to suit
the application requirements. Thermowell Test Pressure shall be 100barg.
The transmitter shall be of a smart type with modular design and compatible
with 3-wire RTD sensor. The transmitter shall be attached directly to the
sensor assembly.
The transmitter housing material shall be made of die-cast aluminium.
Enclosure class shall be according to IP67 of IEC 60529, as a minimum.
The electrical signal cable entry connection shall be M20 x 1.5 metric, unless
otherwise specified in the data sheet. Unused electrical connections shall be
plugged off with a recessed head screw in compliance with the specified
electrical safety requirements. The screw material shall be of stainless steel
for stainless steel enclosures. The signal cable termination points shall of the
screw type.
The following outputs shall be available and configurable by the user:
iii. Analogue, 4-20 mA signal proportional to level
iv. HART communication port as required by the SCADA Communication
System.
The unit shall operate on a power supply of 24 V DC.
The transmitter electronics shall be microprocessor based. Printed circuit
board(s) should be of replaceable modular construction, shall be
hermetically sealed or protected by a corrosion-resistant coating
The nameplates shall be fixed to the mounting plate, the mounting bracket or
the junction boxes door/cover with industrial glue, stainless steel (type AISI
316), M4 bolts and nuts, self-tapping screws or pop-rivets, subject to
KAHRAMA/ENGINEER approval.
Note: Fixing arrangements for nameplates installed on junction boxes
provided with protection', for e.g. Type IP65, shall not adversely affect the
type of protection.
The CONTRACTOR shall design and requisition mounting brackets for
instruments and/or components such as manual-operated switches,
displacer-type level instruments and those for temperature measurements,
etc. which are not installed on a mounting plate.
6.4.1 Earthing
Common Plant Earth Grid shall be provided as per the standards and all
instrument housing and cable armoring shall be connected to this earth only.