Sie sind auf Seite 1von 4

- Test report -

- Cover -

Customer
Name: Location:
Test job
Description:
Executed on: 6/9/2018 3:14:44 PM by: Administrator
Plant
Name:
Voltage level:
Bay:
Device under test
Designation: Distance RElay Order number: 421
Manufacturer: KoCoS Messtechnik AG Description:
Type series/Model:
Serial number:
Specification:
Test system
Name: ARTES 560 (ARTES 560) Serial number: 32901000255
Last adjustment: 10/26/2017 4:18:17 PM

created on: 6/9/2018 3:15:06 PM


ITTEHAD ELECTRIC CO. created by: Administrator
Signature:
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2017-11-17 19:42

Installation Location
Plant: Voltage level:
Bay:
Test object data
Designation: Distance RElay Serial number:
Manufacturer: KoCoS Messtechnik AG Build date: 14.11.2017
Type series/Model: HW-Version:
Specification: FW-Version:
Rated values: 1.000 A 63.500 V 50.000 Hz

IO-Interfaces
Analog inputs
Connection Signal Settings Ratio
Line current L1 (primary) 4.000 In 750.00 A/1.00 A
Line current L2 (primary) 4.000 In 750.00 A/1.00 A
Line current L3 (primary) 4.000 In 750.00 A/1.00 A
Line current L1 (secondary) 4.000 In 1600.00 A/1.00 A
Line current L2 (secondary) 4.000 In 1600.00 A/1.00 A
Line current L3 (secondary) 4.000 In 1600.00 A/1.00 A
Binary outputs
Connection Signal Settings
Differential general trip command Normally open contact (NO)
Current transformer - Primary energy system
Vendor/Type: Ratio: 750.00 A / 1.00 A
Serial number: Power/Precision class: 0.000 VA / 0
Build date:
Current transformer - Secondary energy system
Vendor/Type: Ratio: 1600.00 A / 1.00 A
Serial number: Power/Precision class: 0.000 VA / 0
Build date:

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 6/9/2018 3:14:44 PM Administrator
Created: 6/9/2018 3:15:06 PM Administrator
Page: 2/4
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2017-11-17 19:42

Scheme Settings
Primary transformer current
Vendor/Type:
Serial number:
Build date:
Ratio: 750.00 A / 1.00 A
Power/Precision class: 0.000 VA / 0
Secondary transformer current
Vendor/Type:
Serial number:
Build date:
Ratio: 1600.00 A / 1.00 A
Power/Precision class: 0.000 VA / 0

Transformer settings
Role Vector group Phase shift Rated apperent power Rated current Rated voltage
Primary winding Y 0.000 ° 250.000 MVA 662.707 A 217.800 kV
Secondary y0 0.000 ° 250.000 MVA 1.093 kA 132.000 kV
winding

Settings DIFF monitor


Calculation basis:

Reference: Rated current protection object


Tripping values
Idiff > : 0.250 In tdiff > : 0.030 s
Idiff >> : 10.000 In tdiff >> : 0.030 s

Differential protection harmonic test


Duration: 00:22.861 Start time: 6/9/2018 3:14:19 PM
Comments before testing:

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 6/9/2018 3:14:44 PM Administrator
Created: 6/9/2018 3:15:07 PM Administrator
Page: 3/4
Plant: Bay:
Device under test: Overall Differential Relay T-3 Specification:
Job: 5 harmonics test
th

Comments before testing:

Comments after testing:

DIFF monitor test points

Fault Loop Hamonic Ixf Idiff Start angle Tripping time


index Reference Actual Deviation
L1-L2-L3 5 0.351 0.959 In 0.00 ° 0.030 s 0.029 s -4.58 %
L1-L2-L3 5 0.456 0.959 In 0.00 ° n.t. n.t. 0.00 %

Tested by Witnessed by Witnessed by Witnessed by


TSG NTDC Asset Management NTDC EHV NTDC Contractor