Daylighting Credit - LEED v4 Option 2

The credit is based on demonstrating through computer modeling that illuminance levels will be between 300 lux and 3,000 lux
for 9 a.m. and 3 p.m., both on a clear-sky day at the equinox. If 90% of floor area meets the requirement then 2 credits are
awarded, otherwise if 75% of floor area meets the requirements then 1 credit is awarded. Calculations are based on regularly
occupied floor area.

The results below were calculated using the Radiance simulation engine which provides a detailed multi-zone physics-based
calculation of illumination levels on the working planes of the building.

Daylighting data
C:\Users\VivA\Documents\1812 Concurso Vivienda
Project file
sostenible productiva BTA\VivRural_01.dsb
Report generation time 7/01/2019 2:50:30 p. m.
Sky model *** CIE clear day ***
Time 1 9:00, 21 Sep/Mar
Time 2 15:00, 21 Sep/Mar
Location _Bogota
Working plane height (m) 0.760
Max Grid Size (m) 0.300
Min Grid Size (m) 0.300
Illuminance lower threshold (lux) 300.000
Illuminance upper threshold (lux) 3000.000

Summary Results
Total area (m2) 32.132
Total area meeting requirements (m2) 26.922
% Area within illuminance threshold limits 83.8
LEED v4 Option 2 Credits 1

Eligible zones for daylighting, worst case values for 9:00 and 15:00
Working plane
Min Illumination
Zone Block Floor area (m2) area within
(lux)
Limits (%)
Zone 1 al 8.177 410.8 87.7
Zone 1 Block 2 8.177 456.8 87.7
Zone 1 Block 3 3.887 696.2 80.6
Zone 1 zs 8.004 246.6 79.0
Zone 1 Block 5 3.887 646.8 80.6
Total 32.132 246.6 83.8