For indoor BTS3900,we defined 7 alarms for BTS and 3 alarms for DG

Alarm name list:

DC Power alarm Sensor DG

1 2 3 4 5 6 7 8 9 10 11

Ac mains Rectifier BLVD door fire High water DG DG run Low fuel OB light
fail fail alarm alarm Temp fail

NC NC NC NC NC NC NC NC NC NC

Test method:

1. AC mains fail

Turn off the supply power switch on power cabinet, which is a product of
Huawei (equal to Eltek of swap site), to simulate the Main Alarm
Turn on the switch to eliminate the Main Alarm

Notice:
When you simulate this alarm, Rectifier module failure alarm will appear
at the same time.
Other method: 文backup,we’d better use the first method文
- At Relay test mode on Power cabinet, press Relay 3 to simulate AC Main
fail alarm
- Press Relay 3 again to clear this alarm

2. Rectifier alarm

Take out the Rectifier module board from power cabinet to simulate the

2013-11-8 文文文文文文文文文文文文文 文 1 文, 文 7 文
文文文文 文文文文文

alarm
Insert the Rectifier board to eliminate the alarm

Other method: 文backup,we’d better use the first method文


- At Relay Test mode on Power cabinet, press Relay 5 to simulate
Rectifier larm.
- Press Relay 5 again to clear this alarm
3. Low battery alarm

In the eltek cabinet,choose twice to enter “user option”,then press

,choose LVBD information,press “sel.”,change the value to a high

one,then we can see the alarm on M2000

Recover the value to the default one to eliminate the alarm

Other method: 文backup,we’d better use the first method


1.At Relay Test mode, press Relay 6 to simulate Low battery alarm
Press Relay 6 again to clear this alarm
2.- Take off the cover of EPAC-AG box, then implement shorting circuit the
fourth pair cable from left to right direction to simular Low battery alarm

2013-11-8 文文文文文文文文文文文文文 文 2 文, 文 7 文
文文文文 文文文文文

- Uncorvered this once to clear Low Battery alarm


Notice: 4 pair cables connected from power cabinet to EPAC-AG must connect
to 3XS1 slab of EPAC-AG box.

4. Low voltage alarm

In the eltek cabinet,choose twice to enter “user option”,then press

,choose LVLD information,press “sel.”,change the value to a high

one,then we can see the alarm on M2000

Recover the value to the default one to eliminate the alarm


Other method: 文backup,we’d better use the first method文
At Relay Test mode, press Relay 4 to simulate Low battery alarm
Press Relay 4 again to clear this alarm
- Take off the cover of EPAC-AG box, then implement shorting circuit the
second pair cable from left to right direction to simular Low VOLT alarm

2013-11-8 文文文文文文文文文文文文文 文 3 文, 文 7 文
文文文文 文文文文文

- Uncorvered this once to clear Low VOLT alarm

5. Door open alarm


Open the door of of the BTS room to simulate the alarm
Close the door and implement as follow to eliminate the alarm.
- Right click mouse on site icon on LMT

2013-11-8 文文文文文文文文文文文文文 文 4 文, 文 7 文
文文文文 文文文文文

- Choosing Monitor environment tab and then a box will appear

- Select Clear Robbery Alarm tab and then click Apply button

2013-11-8 文文文文文文文文文文文文文 文 5 文, 文 7 文
文文文文 文文文文文

6. Fire alarm
The testing is the same swap site, blow the smoke into smoke sensor box to
simulate Fire alarm (Smog alarm)
Implement the same clear Door open alarm but choosing Clear smoke tab
before clich Apply button

7. Water immersed alarm


Lift and put the water sensor into a can of water to simulate Water
immersed alarm.

2013-11-8 文文文文文文文文文文文文文 文 6 文, 文 7 文
文文文文 文文文文文

Take out the water sensor from the can of water to eliminate this alarm
8. Over Temperature alarm
Turn off power supply for Air-conditional and then to dry in fire the temperate
sensor to simulate Over temperature alarm
Stop dry in fire the temperature sensor and turn on the Air-Conditional, and
then waiting the temperature decrease.
Other Method: 文backup,we’d better use the first method文
- Implement shorting circuit the cables connect to Temperature sensor box to
simulate Over Temperature alarm

- Open circuit again to clear this alarm