For indoor BTS3900,we defined 7 alarms for BTS and 3 alarms for DG
1 2 3 4 5 6 7 8 9 10 11
Ac mains Rectifier BLVD door fire High water DG DG run Low fuel OB light
fail fail alarm alarm Temp fail
NC NC NC NC NC NC NC NC NC NC
Test method:
1. AC mains fail
Turn off the supply power switch on power cabinet, which is a product of
Huawei (equal to Eltek of swap site), to simulate the Main Alarm
Turn on the switch to eliminate the Main Alarm
Notice:
When you simulate this alarm, Rectifier module failure alarm will appear
at the same time.
Other method: 文backup,we’d better use the first method文
- At Relay test mode on Power cabinet, press Relay 3 to simulate AC Main
fail alarm
- Press Relay 3 again to clear this alarm
2. Rectifier alarm
Take out the Rectifier module board from power cabinet to simulate the
2013-11-8 文文文文文文文文文文文文文 文 1 文, 文 7 文
文文文文 文文文文文
alarm
Insert the Rectifier board to eliminate the alarm
2013-11-8 文文文文文文文文文文文文文 文 2 文, 文 7 文
文文文文 文文文文文
2013-11-8 文文文文文文文文文文文文文 文 3 文, 文 7 文
文文文文 文文文文文
2013-11-8 文文文文文文文文文文文文文 文 4 文, 文 7 文
文文文文 文文文文文
- Select Clear Robbery Alarm tab and then click Apply button
2013-11-8 文文文文文文文文文文文文文 文 5 文, 文 7 文
文文文文 文文文文文
6. Fire alarm
The testing is the same swap site, blow the smoke into smoke sensor box to
simulate Fire alarm (Smog alarm)
Implement the same clear Door open alarm but choosing Clear smoke tab
before clich Apply button
2013-11-8 文文文文文文文文文文文文文 文 6 文, 文 7 文
文文文文 文文文文文
Take out the water sensor from the can of water to eliminate this alarm
8. Over Temperature alarm
Turn off power supply for Air-conditional and then to dry in fire the temperate
sensor to simulate Over temperature alarm
Stop dry in fire the temperature sensor and turn on the Air-Conditional, and
then waiting the temperature decrease.
Other Method: 文backup,we’d better use the first method文
- Implement shorting circuit the cables connect to Temperature sensor box to
simulate Over Temperature alarm