Product brochure

Transformer OIP bushing


Products Group Insulation & Components
ABB Hefei Transformer Co., LTD.
Address: 3318 Lianhua Road, Hefei Economic
& Techological Development Zone
Hefei, Anhui, P.R.China
Postal code: 230601
Tel +86 551 6227 3762

www.abb.com/transformercomponents
1ZKM9121-G, Rev.5, 2017-11-3 © Copyright 2017 ABB All rights reserved

Scan to access eStore

Note: We reserve the right to make technical changes or


modify the contents of this document without prior notice.
With regard to purchase orders, the agreed particulars shall
prevail. ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this
document.
2 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 3

— —
Our company Brief introduction of OIP bushings
and Features

ABB Hefei Transformer Co., Ltd was the first Our main products are: On-load tap-changer, ABB has more than 100 years history of bushing ABB Hefei Product Group Insulation & Components
power transformer joint venture set up by the ABB Transformer bushings (RIP, OIP), Oil treatment manufacture technology up to now, and has (PGIC), belongs to ABB Hefei transformer Co., Ltd
group in China in 1992 with the total investment plants, Measurement and safety devices. Among developed into one of the key market leaders introduced advanced technique and production
up to 30 million USD. It became a wholly owned them, On-load Tap-changers, OIP Bushings were providing a comprehensive range of high voltage echnologies of OIP bushings from ABB
company by ABB in May, 2005 with more than 400 technique transferred and authorized by ABB bushings and high grade service to meet the Components, Sweden in 2007, including design,
employees. At present, the company is organized Insulation and Components in Sweden. RIP Dry- demands of all applications. Oil-impregnated equipment, production processes, core materials,
into two product groups: Product Group Insulation type Bushings and Oil treatment plants were paper (OIP) bushings of the ABB group have a long test equipment etc. Localized parts are tested and
& Components and Distribution transformers. technique transferred and authorized by ABB and successful history, especially on extra and approved by ABB’s material test laboratory in
(Micafil) Co., Ltd in Switzerland. ultra high voltage levels wher e service experience Sweden. The performance of bushings produced
ABB Hefei Product Group Insulation & Components and mature technology is most crucial. In 2008, by Hefei is equal to bushings produced by ABB
(PGIC) is an independent unit of ABB Hefei As one of the most comprehensive range of ABB 1100 kV OIP condenser bushings were Components in Sweden, completely satisfying
Transformer Co., Ltd, and a manufacture and transformer components production and supply successfully used in China’s first UHV 1000 kV requirements from the Chinese market.
supply centre in China and Asia-Pacific region, center of ABB group, ABB Hefei PGIC has become project line, Jindongnan-Nanyang-Jingmen. As the
established by ABB group to serve the local one of the main suppliers providing high quality world’s largest bushing manufacturer, ABB group Range of OIP bushings in ABB Hefei:
market. transformer components in both domestic and owns bushing manufacturing units located all 52 kV to 550 kV Transformer OIP bushings
overseas market. around the world, including Sweden, Switzerland,
Russia, America, Brazil, India and China.

High dielectric reliability High mechanical strength


Ÿ Partial discharge <5Pc at Um. Ÿ Withstand cantilever operating load: heavy load
Ÿ Lower dielectric losses over the bushing’s entire of level II.
service life. Ÿ Withstand high seismic stress: ZPA 0.3 g.
Ÿ Uniform electric field distribution, simulating
electric field distribution by finite element Reliable sealing system
method. Ÿ Excellent sealing structure, oil and heat resistant
Ÿ External insulation with good pollution gaskets with -40°C brittleness point.
performance. Ÿ Strict quality and process control to verify the
tightness of all parts individually, as well as the
Perfect thermal stability complete system during the final testing, no
Ÿ Hot spots in the condenser core are calculated sign of leakage is allowed.
by Finite Element Method, to select conductor Ÿ An adequate press force on the sealing structure
size correctly. assures permanent sealing during all service
Ÿ The finest quality paper with low dielectric conditions.
dissipation factor is used to assure long life.
Ÿ Advanced equipment and process for winding
machine assure low dielectric losses.
4 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 5


Transformer bushings, type TOB


Transformer bushing type TOB Common applications

Application Transformer
Classification Oil impregnated paper, capacitance graded, outer door-immersed bushing
1
Ambient temperature +40°C to~-40°C
Altitude of side <2000 m
Level of rain and humidity 1-2 mm/min horizontally and vertically, as per IEC 60060-1
3 Pollution level SPS class e, according to IEC 60815
2a
2b 4 Type of immersion medium Transformer oil. Maximum daily mean oil temperature 90°C
Maximum temporary oil temperature 115°C
5
Oil level below Bushing flange Max. 30 mm
Max. pressure of medium 100 kPa overpressure
Marking IEC 60137, GB/T 4109 and IEEE Std C57. 19. 00*
6

7

Electrical data

Type Rating Routine test


8 Rated Highest Phase-to- Lighting Wet power Dry power
9
current voltage for earth impulse frequency frequency
equipment voltage
Ir Um Uy BIL AC 1 min, 50 Hz
A kV, RMS kV, RMS kV, peak kV, RMS kV, RMS
10
TOB(2) 350-800 800 72.5 42 350 140 160
2c
TOB(2) 350-1250 1250 72.5 42 350 140 160
TOB(2) 350-2000 2000 72.5 42 350 140 155
11
TOB(2) 350-3150 3150 72.5 42 350 140 160
TOB(2) 550-800 800 126 73 550 230 260
TOB(2) 550-1250 1250 126 73 550 230 260
TOB(2) 550-2000 2000 126 73 550 230 260
12
TOB(2) 650-630 630 145 145 650 275 310
13
TOB(2) 650-1250 1250 145 145 650 275 310
TOB(2) 750-630 630 170 170 750 325 365
TOB(2) 750-1250 1250 170 170 750 325 365
1 Outer terminal 6 Air side porcelain insulator TOB 325-800 800 72.5 72.5 325 140 155
2 Oil level gauge 7 Condenser body TOB 325-1250 1250 72.5 72.5 325 140 155
a Single prism glasses (TOB 325, TOB(2) 350) 8 Test tap TOB 550-800 800 126 73 550 230 255
b Double prism glasses (TOB 550) 9 Mounting flange TOB 550-1250 1250 126 73 550 230 255
c Magnetic oil level indicator (TOB 550, TOB(2) 550) 10 Flange extension TOB 550-1600 1600 126 73 550 230 255
3 Sealing plug 11 Oil side porcelain insulator TOB 550-2000 2000 126 73 550 230 255
4 Top chamber 12 Bottom nut
5 Insulation oil 13 End shield
6 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 7


Type TOB
Dimension and technical data

L4 (Draw lead length)


M12 R2 R2
Oil level
D8

indicator Earthing D9

R2
D4

hole

D1
4xΦ14 T=25

D5
H2
D11

Φ14(2x)

L5

L5
L10

40

L5
L9

20

L9
40

L9
R1 60
T1 D2
R1 R1 80
L7 T2 L6 D6 D10 D10 D10
D7 D3 D3
L2 L1 D3
L
800 A, 1250 A 2000 A 3150 A

Type Cat. No. Rated Min. normal Space Oil level Net Dimensions mm Creepage Cantilever
current specific c.d. for C.T indicator mass distance test load
60 s
A mm/kV mm kg L L1 L2 L4 L5 L6 L7 L9 L10 D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 T1 T2 R1 R2 H2 mm N
TOB(2) 350-800-4-0 1ZKJ810001-BP 800 31 0 Prism glass 52 1430 330 1020 912 90 5 680 35 / 119 34 115 190 150 280 330 250 18(6X) 83 30 22 70 10 8 80 2285 2000
TOB(2) 350-800-4-0.3 1ZKJ810001-BM 300 57 1710 610 285
TOB(2) 350-800-4-0.5 1ZKJ810001-BR 500 61 1910 810 485
TOB(2) 350-800-4-0.65 1ZKJ810001-BX 650 63 2060 960 635
TOB(2) 350-1250-4-0 1ZKJ810001-BS 1250 31 0 Prism glass 59 1420 330 1010 941 90 5 680 35 / 134 48 134 190 160 280 330 265 18(6X) 100 30 22 70 10 8 80 2285 2000
TOB(2) 350-1250-4-0.3 1ZKJ810001-BT 300 66 1700 610 285
TOB(2) 350-1250-4-0.5 1ZKJ810001-BN 500 69 1900 810 485
TOB(2) 350-1250-4-0.65 1ZKJ810001-BY 650 72 2050 960 635
TOB(2) 350-2000-4-0 1ZKJ810001-BU 2000 31 0 Prism glass 102 1630 510 1020 / 220 5 680 76 45 152 / 152 175 160 350 400 282 24(6X) 128 60 22 70 9 9 100 2285 3150
TOB(2) 350-2000-4-0.3 1ZKJ810001-BV 300 111 1870 750 245
TOB(2) 350-2000-4-0.5 1ZKJ810001-BW 500 122 2070 950 445
TOB(2) 350-3150-4-0.55 1ZKJ810001-DB 3150 31 550 Magnetic 150 2348 1027 1196 / 260 550 700 92 / 185 / 210 290 210 350 400 344 24(6X) 165 60 23 115 16 16 125 2430 4000
TOB(2) 550-800-4-0.1 1ZKJ810106-FM 800 31 100 Magnetic 99 2080 520 1480 1372 110 95 1050 50 / 144 34 128 210 175 350 400 285 24(6X) 83 30 22 70 18 15 80 3980 3150
TOB(2) 550-800-4-0.4 1ZKJ810105-FM 400 106 2370 810 385
TOB(2) 550-800-4-0.5 1ZKJ810107-FM 500 109 2470 910 485
TOB(2) 550-800-4-0.55 1ZKJ810108-FM 550 110 2520 960 535
TOB(2) 550-1250-4-0.1 1ZKJ810116-FM 1250 31 100 Magnetic 111 2070 520 1470 1401 110 95 1050 50 / 159 48 150 210 190 350 400 300 24(6X) 100 30 22 70 18 15 80 3980 3150
TOB(2) 550-1250-4-0.4 1ZKJ810115-FM 400 119 2360 810 385
TOB(2) 550-1250-4-0.5 1ZKJ810117-FM 500 122 2460 910 485
TOB(2) 550-1250-4-0.58 1ZKJ810118-FM 580 125 2540 990 565
TOB(2) 550-2000-4-0.1 1ZKJ810125-FM 2000 31 100 Magnetic 180 2210 630 1480 / 220 95 1050 74 45 190 / 182 230 218 350 400 340 24(6X) 142 60 22 70 15 15 100 3980 4000
TOB(2) 550-2000-4-0.4 1ZKJ810126-FM 400 197 2500 920 385 74 45
TOB(2) 550-2000-4-0.5 1ZKJ810127-FM 500 203 2600 1020 485 74 45
TOB(2) 550-2000-4-0.67 1ZKJ810128-FM 670 215 2770 1190 655 72 40
8 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 9


Type TOB
Dimension and technical data

L4 (Draw lead length)


M12
Oil level R2
indicator
D8
Earthing D9
D4

R2
hole

D1
D5
H2
D11

Φ14(2x)

L5

L5
45
L9
R1

L9
60
T1 D2
L7 T2 L6 D6 D10 R1
D10
D7 D3
L2 L1
D3
L
630A, 800 A, 1250 A 1600 A, 2000 A

Type Cat. No. Rated Min. normal Space Oil level Net Dimensions mm Creepage Cantilever
current specific c.d. for C.T indicator mass distance test load
60 s
A mm/kV mm kg L L1 L2 L4 L5 L6 L7 L9 D1 D2 D3 D4 D5 D6 D7 D8 D9 D10 D11 T1 T2 R1 R2 H2 mm N
*TOB 325-800-4-0.4 1ZKJ810001-BK 800 31 400 Prism glass 67 1945 700 1165 1057 60 345 825 15 124 36 120 155 140 280 320 254 18(6x) 84 30 22 70 12 8 80 3010 2000
*TOB 325-1250-4-0.5 1ZKJ810001-BL 1250 500 92 2185 920 1086 110 525 55 152 60 150 175 165 350 400 282 24(6x) 110 40 10 100 3010 2000
*TOB 550-800-4-0.4 1ZKJ810104-FM 800 31 400 Magnetic 141 2620 810 1730 1622 60 420 1300 15 168 36 120 210 197 350 400 303 24(8x) 84 30 22 70 12 8 80 4680 3150
*TOB 550-1250-4-0.5 1ZKJ810114-FM 1250 500 174 2770 940 1651 110 510 55 194 60 150 230 225 400 450 330 110 30 12 10 80 4680 3150
*TOB 550-2000-4-0.5 1ZKJ810124-FM 2000 500 221 2875 1045 / 220 510 74 194 / 182 230 225 400 450 330 142 60 15 15 100 4680 4000
TOB 550-1600-4-0.1 1ZKJ810150-FM 1600 31 100 Magnetic 176 2210 630 1480 / 220 95 1050 74 190 / 182 230 225 400 450 340 24(8x) 142 40 22 70 15 15 100 3980 3150
TOB 550-1600-4-0.4 1ZKJ810151-FM 400 192 2500 920 385
TOB 550-1600-4-0.5 1ZKJ810152-FM 500 197 2600 1020 485
TOB 550-1600-4-0.6 1ZKJ810153-FM 600 203 2700 1120 585
TOB(2) 650-630-4-0.15 1ZKJ810160-AAC 630 31 150 Prism glass 129 2293 580 1590 1500 100 120 1250 20 160 34 140 265 190 290 335 305 16(12x) 90 30 20 60 15 15 125 4600 3150
TOB(2) 650-630-4-0.3 1ZKJ810161-AAC 300 135 2453 740 280
TOB(2) 650-630-4-0.5 1ZKJ810162-AAC 500 146 2653 940 480
TOB(2) 650-1250-4-0.15 1ZKJ810160-AAD 1250 150 Prism glass 144 2293 580 1590 / 100 120 1250 20 160 34 140 265 190 290 335 305 16(12x) 90 30 20 60 15 15 125 4600 3150
TOB(2) 650-1250-4-0.3 1ZKJ810161-AAD 300 151 2453 740 280
TOB(2) 650-1250-4-0.5 1ZKJ810162-AAD 500 163 2653 940 480
TOB(2) 750-630-4-0.2 1ZKJ810170-AAC 630 31 200 Prism glass 237 2718 685 1910 1820 100 165 1460 20 184 34 140 265 184 290 335 350 16(12x) 90 30 20 60 15 15 125 5420 3150
TOB(2) 750-630-4-0.3 1ZKJ810171-AAC 300 240 2833 800 280
TOB(2) 750-630-4-0.5 1ZKJ810172-AAC 500 243 3033 1000 480
TOB(2) 750-1250-4-0.2 1ZKJ810170-AAD 1250 31 200 Prism glass 255 2718 685 1910 / 100 165 1460 20 184 34 140 265 184 290 335 350 16(12x) 90 30 20 60 15 15 125 5420 3150
TOB(2) 750-1250-4-0.3 1ZKJ810171-AAD 300 259 2833 800 280
TOB(2) 750-1250-4-0.5 1ZKJ810172-AAD 500 263 3033 1000 480

*High altitude bushing


10 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 11


Transformer bushings, type TOM


Transformer bushing type TOM Common applications

1 Application Transformer
Classification Oil impregnated paper, capacitance graded, outer door-immersed bushing
Ambient temperature +40°C to~-40°C
2b 3 2a
4 Altitude of side <2000 m
5
Level of rain and humidity 1-2 mm/min horizontally and vertically, as per IEC 60060-1
Pollution level SPS class d, e, according to IEC 60815
6 Type of immersion medium Transformer oil. Maximum daily mean oil temperature 90°C
Maximum temporary oil temperature 115°C
Oil level below Bushing flange Max. 30 mm
Max. pressure of medium 100 kPa overpressure

7 Marking IEC 60137, GB/T 4109


Electrical data

Type Rating Routine test Design data


Rated Highest Phase-to- Lighting Wet power Dry power Switching
current voltage for earth impulse frequency frequency impulse
equipment voltage 1 min, Dry or Wet
Ir Um Uy BIL AC 50/60 Hz SIL
A kV, RMS kV, RMS kV, peak kV, RMS kV, RMS kV, peak
10 9 11 TOM 1050-800 800 252 146 1050 460 505 750
12 TOM 1050-1250 1250 252 146 1050 460 505 750
TOM 1050-1600 1600 252 146 1050 460 505 750
TOM 1050-3150 3150 252 146 1050 460 505 850
13

14
15

1 Outer terminal 8 Condenser body


2 Oil level gauge 9 Test tap
a Double prism glasses 10 Ball valve
b Magnetic oil level indicator 11 Mounting flange
3 Sealing plug 12 Flange extension
4 Top chamber 13 Oil side porcelain insulator
5 Set of springs 14 Bottom nut
6 Insulation oil 15 End shield
7 Air side porcelain insulator
12 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 13


Type TOM 1050-800/1250/1600
Dimension and technical data

L4 (Draw lead length)

75
Oil level
indicator M12(2X)
25
Earthing
D8

hole
H2
D4

D1

R2
Φ24(12X) D2
Φ14(2X)

R2

45

L5
D11

L5

L9
L9
L7 L6 R1
Φ500

R1
D10 D10
L2 L1
Φ550 D3 D3
L
800 A, 1250 A 1600 A

Type Cat. No. Rated Min. normal Space Net Net mass Oil level Dimensions mm Creepage Cantilever
current specific c.d. for C.T indicator distance test load
60 s
A mm/kV mm kg L L1 L2 L3 L4 L5 L6 L9 D1 D2 D3 D4 D8 D10 D11 R1 R2 H2 mm N
TOM 1050-800-4-0 1ZKJ810210-FM 800 31 - 357 Magnetic oil level indicator 3580 745 2735 2250 2656 120 5 75 232 48 168 358 380 115 30 12 12 100 8507 4000
TOM 1050-800-4-0.3 1ZKJ810211-FM 300 370 (Option: double prism glasses) 3880 1045 305
TOM 1050-800-4-0.4 1ZKJ810212-FM 400 374 3980 1145 405
TOM 1050-800-4-0.6 1ZKJ810213-FM 600 383 4180 1345 605
TOM 1050-800-4-0.8 L 1ZKJ810214-FM 800 416 4717 1880 805
TOM 1050-1250-4-0 1ZKJ810220-FM 1250 31 - 393 Magnetic oil level indicator 3580 745 2735 2250 2656 120 5 75 252 60 185 378 400 134 40 12 12 100 8507 4000
TOM 1050-1250-4-0.3 1ZKJ810221-FM 300 408 (Option: double prism glasses) 3880 1045 305
TOM 1050-1250-4-0.4 1ZKJ810222-FM 400 413 3980 1145 405
TOM 1050-1250-4-0.6 1ZKJ810223-FM 600 423 4180 1345 605
TOM 1050-1600-4-0 1ZKJ810230-FM 1600 31 - 441 Magnetic oil level indicator 3700 865 2735 2250 / 240 5 110 252 / 235 378 400 135 40 25 25 100 8507 4000
TOM 1050-1600-4-0.3 1ZKJ810231-FM 300 460 (Option: double prism glasses) 4000 1165 305
TOM 1050-1600-4-0.4 1ZKJ810232-FM 400 467 4100 1265 405
TOM 1050-1600-4-0.6 1ZKJ810233-FM 600 479 4300 1465 605
14 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 15


Type TOM 1050-3150
Dimension and technical data

Magnetic oil level indicator


Φ450

M12 R30
Φ24(12X) T=25

D8

Φ270
Φ60 Φ14(4X)

320
125

120
40

40

20
L3 24 Φ500 80

Φ550 R30 Φ170


196 L6

L1 Outer terminal Φ264


L2

Type Cat. No. Rated Min. normal Space Net Net mass Oil level Dimensions mm Creepage Cantilever
current specific c.d. for C.T indicator distance test load
60 s
A mm/kV mm kg L L1 L2 L3 L6 D8 mm N
TOM 1050-3150-4-0.6 1ZKJ810240-FM 3150 31 605 678 Magnetic oil level indicator 4751 1550 3076 2400 605 419 8860 5000
16 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 17


Transformer bushings, type GOE Fig.1 Shed profile GOE

Fig.2 Shed profile GOE 2


GOE features
A set of concentric tubes are pre stressed and
inclination can be obtained on request. The
current shall be reduced for horizontal mounting
serve as springs which hold the main bushing and up to 15°from horizontal.
components together and provide adequate
pressure on the gaskets in all expected The top housing is made of aluminum alloy and
temperature and load conditions. has expansion space for the oil, sufficient for
temperature variations in the bushing between -
Transformer bushing type GOE The annular space formed between the tubes 40°C and +80°C. Variations in the length of the
makes an efficient cooling duct for dissipation of centre tube and the housing are compensated by a
the heat, thus improving the current-carrying flexible connection inside the top housing.
1 capacity and thermal stability of the bushing.
2
The upper insulator on bushings GOE 1050 and
3
The bushing is designed to be mounted at an larger are equipped with retaining rings mounted
4
angle of up to 30° to 60° from the vertical. A higher with stainless steel details.
5

6
7
8 Shed profile The shed profile is designed according to IEC
The shed profile for all GOE bushings is of the anti- 60815.For each pair of sheds, the ratio between
fog type with alternating long and short sheds. nominal creepage distance and the axial length is
9 4.0. This shed profile is developed and tested
specially for heavy
pollution.

65 72
45 52
10
R7 R5.5 R8 R5
11
12 R9 R10

12° 27 12° 29
18° 18°
R7 65 R8 70
R9.5 R5.5 R10 R5
13
12° 12°
18° 18°

— —
Fig.1 Fig.2


14 Common applications
For conditions exceeding the standard specification below, please consult ABB.

Application Transformer
Classification Oil impregnated paper, capacitance graded, outer door-immersed bushing
1 Top end nut 8 Transformer oil Ambient temperature +40°C~-40°C
2 Sealing plug 9 Condenser core Altitude of side <1000 m
3 Flexible connection 10 Clamping ring Level of rain and humidity 1-2 mm/min horizontally and vertically, as per IEC 60060-1
4 Top housing 11 Mounting flange Pollution level According to specified creepage distance and IEC 60815
5 Oil level gauge 12 Extension for current transformers Type of immersion medium Transformer oil. Maximum daily mean oil temperature 90°C
6 Porcelain insulator, air side 13 Porcelain insulator, oil side Maximum temporary oil temperature 115°C
7 Pre-stressed tubes 14 Bottom end nut Oil level below Bushing flange Max. 30 mm
Max. pressure of medium 100 kPa overpressure
Marking IEC 60137, GB/T 4109 and IEEE
18 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 19


Type GOE 250—GOE 650
Dimension and technical data
L5 L2

L1
Position of oil
sample valve Earthing hole
L3 115 130
A2

Φ60
A1

D6

125 Position of test tap


D1

Mounting hole D9
D3 D2 25 D4 D5

Type Catalog Flenge extension Creepage distance D1 L1 L2 L3 L5±5 Net mass D2 D3 D4 D5 D6 A1 A2 D9


number mm mm mm mm mm mm mm kg mm mm mm mm mm ° ° mm

GOE 250-210-3150-0.3 1ZKJ820052-ABB 300 2955±80 48 825±20 1331±25 305 685 240 224 350 386 350 300 60 60 20(6X)
GOE 250-210-3150-0.6 1ZKJ820052-ABA 600 2955±80 48 825±20 1331±25 605 985 250 224 350 386 350 300 60 60 20(6X)
GOE 250-210-5000-0.3 1ZKJ820052-AAB 300 2955±80 38 825±20 1331±25 305 685 270 224 350 386 350 300 60 60 20(6X)
GOE 250-210-5000-0.6 LF 121051-CZ 600 1425±40 38 550±20 1060±25 605 985 245 224 350 386 350 300 60 60 20(6X)
GOE 380-300-3150-0.3 1ZKJ820072-ABB 300 2955±80 48 825±20 1331±25 305 685 240 224 350 386 350 300 60 60 20(6X)
GOE 380-300-3150-0.6 LF 121052-AZ 600 2955±80 48 825±20 1331±25 605 985 250 224 350 386 350 300 60 60 20(6X)
GOE 380-300-5000-0.3 1ZKJ820072-AAB 300 2955±80 38 825±20 1331±25 305 685 270 224 350 386 350 300 60 60 20(6X)
GOE 450-400-3150-0.6 LF 121053-AZ 600 3355±90 48 1120±20 1630±25 605 985 275 224 350 386 350 300 60 60 20(6X)
GOE 650-500-3150-0.3 1ZKJ820145-ABB 300 4775±125 48 1300±27 1806±33 305 835 330 264 400 386 350 350 45 90 20(8X)
GOE 650-500-3150-0.6 LF 121054-AZ 600 4775±125 48 1300±27 1806±33 605 1135 350 264 400 386 350 350 45 90 20(8X)

Type Catalog Rated Rated Phase-to-earth Lighting Wet Wet power Dry power Dry Nominal capacitance Max.test load 60 s
Max permitted load(N)
number current voltage votage impulse switching frequency frequency switching between conductor acc.to IEC 60137
in operation at mounting angle
Ir Um Uy BIL impulse AC 1 min, 50/60 Hz impulse and test tap(C1)
A kV, RMS kV, RMS kV, peak kV, peak kV, RMS kV, RMS kV, peak C1±10%(pF) (N) 0° 30° 60°
GOE 250-210-3150-0.3 1ZKJ820052-ABB 3150 52 30 250 210 120 120 400 448 5700 2800 2300 1700
GOE 250-210-3150-0.6 1ZKJ820052-ABA 3150 52 30 250 210 120 120 400 574 5700 2800 2300 1700
GOE 250-210-5000-0.3 1ZKJ820052-AAB 5000 52 30 250 210 120 120 400 448 5700 2800 2300 1700
GOE 250-210-5000-0.6 LF 121051-CZ 5000 52 30 250 210 120 120 400 782 5700 2800 2300 1700
GOE 380-300-3150-0.3 1ZKJ820072-ABB 3150 72.5 42 380 300 170 185 550 448 5700 2800 2300 1700
GOE 380-300-3150-0.6 LF 121052-AZ 3150 72.5 42 450 300 170 185 550 574 5700 2800 2300 1700
GOE 380-300-5000-0.3 1ZKJ820072-AAB 5000 72.5 42 380 300 170 185 550 448 5700 2800 2300 1700
GOE 450-400-3150-0.6 LF 121053-AZ 3150 123 (126) 71 (73) 550 400 240 260 650 543 5700 2800 2300 1700
GOE 650-500-3150-0.3 1ZKJ820145-ABB 3150 145 84 650 500 315 325 650 392 5000 2500 2000 1500
GOE 650-500-3150-0.6 LF 121054-AZ 3150 145 84 650 500 315 325 650 498 5000 2500 2000 1500
20 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 21


Type GOE 1050—GOE 1800
Dimension and technical data
L5 L2

L1
Position of oil
sample valve 90° Earthing hole
L3 196 150

Φ60
A1

D6
Position of test tap
125
D1
Mounting hole D9

D3 D2 28 D4 D5

Type Catalog Flenge extension Creepage distance D1 L1 L2 L3 L5±5 Net mass D2 D3 D4 D5 D6 A1 D9


number mm mm mm mm mm mm mm kg mm mm mm mm mm ° mm

GOE 1050-750-2500-0.3 1ZKJ820245-ABB 300 8900±210 48 2230±55 3070±60 305 1035 765 330 480 495 500 430 45 20(8X)
GOE 1050-750-2500-0.6 1ZKJ820245-ABA 600 8900±210 48 2230±55 3070±60 605 1335 785 330 480 495 500 430 45 20(8X)
GOE 1050-750-5000-0.6 LF 121063-BDZ 600 8900±210 38 2230±55 3070±60 605 1335 860 330 480 495 500 430 45 20(8X)
GOE 1175-850-2500-0.3 1ZKJ820362-AAA 300 9120±240 48 2470±55 3311±60 305 1035 825 330 480 485 500 430 45 20(8X)
GOE 1175-850-2500-0.6 1ZKJ820362-AAB 600 9120±240 48 2470±55 3311±60 605 1335 845 330 480 485 500 430 45 20(8X)
GOE 1300-1150-2500-0.6 LF 121071-CZ 600 13745±355 48 3620±56 4460±61 605 1335 1095 330 480 485 500 430 45 20(8X)
GOE 1425-1150-2500-0.6 1ZKJ820420-BAB 600 13745±355 48 3620±55 4460±61 605 1335 1095 330 480 485 500 430 45 20(8X)
GOE 1675-1300-2500-0.3 1ZKJ820550-ABB 300 18755±505 48 4710±55 5751±61 305 1285 1995 428 720 579 600 660 30 24(12X)
GOE 1675-1300-2500-0.6 LF 121076-GZ 600 18020±470 48 4710±55 5751±61 605 1585 2030 428 720 565 600 660 30 24(12X)
GOE 1675-1300-2500-0.6 LF 121076-HZ 600 19250±505 48 4710±55 5751±61 605 1585 2200 428 720 565 600 660 30 24(12X)
GOE 1675-1300-1600-0.94 LF 121076-PZA 940 18755±505 48 4710±55 5751±61 945 1925 2070 428 720 579 600 660 30 24(12X)
GOE 1675-1300-2500-0.94 LF 121076-PZ 940 18755±505 48 4710±55 5751±61 945 1925 2070 428 720 579 600 660 30 24(12X)
GOE 1800-1360-2500-0.6 LF 121076-BAZ 600 18020±470 48 4710±55 5751±61 605 1585 2030 428 720 565 600 660 30 24(12X)

Type Catalog Rated Rated Phase-to-earth Lighting Wet Wet power Dry power Dry Nominal capacitance Max.test load 60 s
Max permitted load(N)
number current voltage votage impulse switching frequency frequency switching between conductor acc.to IEC 60137
in operation at mounting angle
Ir Um Uy BIL impulse AC 1 min, 50/60 Hz impulse and test tap(C1)
A kV, RMS kV, RMS kV, peak kV, peak kV, RMS kV, RMS kV, peak C1±10%(pF) (N) 0° 30° 60°
GOE 1050-750-2500-0.3 1ZKJ820245-ABB 2500 245(252) 141(146) 1050 750 480 505 960 352 13000 6500 4300 3100
GOE 1050-750-2500-0.6 1ZKJ820245-ABA 2500 245(252) 141(146) 1050 750 480 505 960 405 13000 6500 4300 3100
GOE 1050-750-5000-0.6 LF 121063-BDZ 5000 245(252) 141(146) 1050 750 480 505 960 405 13000 6500 4300 3100
GOE 1175-850-2500-0.3 1ZKJ820362-AAA 2500 362 209 1175 850 540 530 950 420 12000 6000 4300 3100
GOE 1175-850-2500-0.6 1ZKJ820362-AAB 2500 362 209 1175 850 540 530 950 490 12000 6000 4300 3100
GOE 1300-1150-2500-0.6 LF 121071-CZ 2500 420 242 1425 1175 695 695 1265 528 9000 4500 2500 /
GOE 1425-1150-2500-0.6 1ZKJ820420-BAB 2500 420 242 1425 1175 695 695 1265 528 9000 4500 2500 /
GOE 1675-1300-2500-0.3 1ZKJ820550-ABB 2500 550 318 1675 1300 870 750 1430 460 13000 6500 4300 1500
GOE 1675-1300-2500-0.6 LF 121076-GZ 2500 550 318 1675 1300 870 750 1430 456 13000 6500 4300 1500
GOE 1675-1300-2500-0.6 LF 121076-HZ 2500 550 318 1675 1300 870 750 1430 456 13000 6500 4300 1500
GOE 1675-1300-1600-0.94 LF 121076-PZA 1600 550 318 1675 1300 870 750 1430 515 13000 6500 4300 1500
GOE 1675-1300-2500-0.94 LF 121076-PZ 2500 550 318 1675 1300 870 750 1430 515 13000 6500 4300 1500
GOE 1800-1360-2500-0.6 LF 121076-BAZ 2500 550 318 1800 1360 870 870 1500 456 13000 6500 4300 1500
22 Transformer OIP bushing Product manual Transformer OIP bushing Product manual 23

— —
Bushing on-line monitor and adapter Terminal plate

GOE bushings are designed with voltage tap, TOB and TOM
bushings are designed with test tap, both can be used for Type A Type B
online bushing monitoring.

110
The voltage tap can be used for measurement of partial 80 50 THK12
discharge, dissipation factor, and capacitance values. It can 40 THK15

40
For rated current Ir<= 800 A
also provide a voltage source while the bushing is in

40 20
1ZKJ195001-A, Type A, Cu/Sn Φ18(4X)

130
operation. The max. power-frequency voltage withstand test

50
80
Φ14(4x)
1ZKJ195001-D, Type A, Cu/Ag

185
with tap to earth is 20 kV, one minute, 50 Hz.

155
1ZKJ195001-E-1, Type B, Cu/Sn
1ZKJ195001-E-2, Type B, Cu/Ag

60

60
If needed, customer can select TOB(2)/TOM bushings with
specially designed voltage tap. These kind of bushings have
Φ30 Φ30
C1 conducting layer and C2 conducting layer in condenser
core. The voltage tap is internally connected to C1 conducting
layer whereas the C2 conducting layer is permanently
connected to mounting flange. Under online bushing 110
100
50
monitoring, C2 conducting layer is always grounded via 50 THK20 THK16

earthed mounting flange.

40
25
For rated current Ir<= 1600 A

100
50

130
Φ18(4x) Φ18(4x)

50
1ZKJ195001-B, Type A, Cu/Ag

205
195
161 1ZKJ195001-F-1, Type B, Cu/Sn

1 2 3 4 5 6 1ZKJ195001-F-2, Type B, Cu/Ag

80

80
Φ40 Φ40
M30×2-6g

110
Φ38

Φ24
Φ8

125 50
THK16

32.5
60 THK20

40
M20×1.5
cable glanf For rated current Ir<= 2500 A

50
180
Φ18(6x)

60
6 Φ18(4x)

125
1ZKJ195001-C, Type A, Cu/Ag

50
275
13 12 11 10 9 8 7 1ZKJ195001-G-1, Type B, Cu/Sn

240
1ZKJ195001-G-2, Type B, Cu/Ag

100

100
1 5CNI300000 HNBR O ring 28×2.65-G-N-GB/T3452.1
Φ60 Φ60
2 5CNI600004 Resistor
3 5CNI200004 CAP for adaptor
4 5CNI600007 Nameplate label 160
50 50
5 5CNI200008 M4 Nut S.S.A2 GB/T 6170 THK16

50 50 40
6 5401620000 M20×1.5 cable gland
7 5CNI200005 Conduction rod For rated current Ir<= 5000 A Φ18(9x)

195
8 5CNI600005 Ground lead
1ZKJ195001-H-1, Type B, Cu/Sn

305
9 5CNI200007 SCREW M4×6 GB/T822 S.S.A2
1ZKJ195001-H-2, Type B, Cu/Ag
10 5CNI600006 Insulated tube

115
11 5CNI200003 Foundation for adaptor
12 5CNI200006 Check ring D=17.3GB/T893.1
Φ60
13 5CNI300001 HNBR O ring 30×1.8-G-N-GB/T3452.1

Note: 1. Mount the foundation item 11 on the test tap thread M30 in bushing fange.
2. Disconnect cable item 8 from conduction rod item 7, then connect foundation item 11 to the ground.