Parameter Unit Value Min Max

AVR ID - 0000 - -
Activation T2 - T2 on - -
Active Desired Volt. Level - DVL 1 - -
Analog Val. Tap Pos Max % 100,0 0 100
Analog Val. Tap Pos Min % 10,0 0 100
Analog Val. Volt.Lev. Max % 100,0 0 100
Analog Val. Volt.Level Min % 20,0 0 100
Bandwidth % 0,70 0,5 9
Baud Rate - 57.6 kBaud - -
Blocking Overcurr. I> - Off - -
Blocking Overvolt. U> - Off - -
Blocking Undercurr. I< - Off - -
Blocking Undervolt. U< - On - -
Blocking lower Tap - 0 -128 128
Blocking upper Tap - 20 -128 128
CAN Address - 0 0 16
CT Terminal - 1A - -
Characteristics T1 - T1 linear - -
Circ. Current Blocking % 15,0 0,5 40
Circ. Current Sensitivity % 10,0 0 100
Compensation Method - LDC - -
Delay Parallel Failure s 10 1 99
Delay Time T1 s 12 0 600
Delay Time T2 s 10,0 1 10
Delay Time U< s 10,0 0 20
Desired Voltage Level 1 kV 500,00 222,73 636,36
Desired Voltage Level 2 kV 500,00 222,73 636,36
Desired Voltage Level 3 kV 500,00 222,73 636,36
Display % / A - A - -
Display Dimming - On - -
Display kV / V - kV - -
Foll. Tapping w/o Umeas - Off - -
Follower Tapping Direction - Standard - -
Function Monitoring - Off - -
GPI 1 - X4:13 - Off - -
GPI 2 - X4:14 - Off - -
GPI 3 - X4:15 - Off - -
GPI 4 - X4:16 - Quick Tap - -
GPI 5 - X4:17 - DVL 2 - -
GPI 6 - X4:18 - DVL 3 - -
GPI 7 - X6:1 - ParGroup1 - -
GPI 8 - X6:2 - ParGroup2 - -
GPO 1 - X4:9 - Off - -
GPO 2 - X4:12 - Off - -
GPO 3 - X5:9 - ParState - -
GPO 4 - X5:12 - ParError - -
GPO 5 - X5:18 - Undervolt. - -
GPO 6 - X5:21 - Overvolt. - -
GPO 7 - X5:24 - Overcurr. - -
Key Lock - On - -
LED 1 - GPI 1 - -
LED 2 - GPI 2 - -
LED 3 green - Off - -
LED 3 yellow - Off - -
LED 4 red - Off - -
LED 4 yellow - Off - -
Language - English - -
Line Drop Compensation Ur V 2,1 -25 25
Line Drop Compensation Ux V 25,0 -25 25
Local / Remote - Local - -
Manual / Auto - Auto - -
Master/Foll. Curr. Block. - Blocking - -
Max. Tap Difference - 2 1 4
Meas.Transformer Circuit - 0 1PH - -
Motor Runtime s 10,0 0 30
Neg. Act. Pow. Block. - Off - -
Normset Activation - Off - -
Operation Counter - 0 0 99999999
Overcurrent I> [%] % 110 50 210
Overvoltage U> [%] % 110 100 140
Parallel Control Enable - On - -
Parallel Operation Method - Master - -
Paralleling Group - Group 1 - -
Primary Current A 2000 0 10000
Primary Voltage kV 500 0 9999
Pulse Time s 1,5 0 10
Remote Volt. Level Setting - Off - -
Secondary Voltage V 110,0 57 123
Stand-alone Blocking - On - -
Tap Pos Limit Block Mode - Off - -
Tap Position Lower Value - 1 -40 40
Tap Position Upper Value - 17 -40 40
Tap pos. indication - Off - -
U< Below 30V - Off - -
Undercurrent I< [%] % 20 0 210
Undervoltage U< [%] % 90 60 100
Voltage Level Lower Val. V 90,0 0 140
Voltage Level Upper Val. V 110,0 0 140
Z - Comp. Limit % 10,0 0 15
Z - Comp. Volt Rise % 10,0 0 15