Sie sind auf Seite 1von 26

Copeland 4-1309

4-1309

Application Engineering Bulletin Issued February, 2000


AE-1309

APPLICATION GUIDELINES FOR


SHL1/SHM1 & SHL2/SHM2
SEMI-HERMETIC SCREW COMPRESSORS

Table of Contents

1. General ....................................................... 2 4.3 Additional Cooling by Direct


Refrigerant Injection ............................... 9
2. Design and Functions ............................... 2 4.4 Start Unloading ...................................... 9
2.1 Construction Features ............................ 2 4.5 Capacity Regulation ............................. 10
2.2 Compression Procedure - 4.6 Parallel Operation ................................ 10
Automatic Vi – Control ............................ 2 4.7 Economizer Operation ......................... 12
2.3 Capacity Control / Start Unloading ......... 3 4.8 Two-Stage Systems ............................. 12
2.4 Mounting the Compressor ...................... 4
2.5 Oil Circulation ........................................ 5 5. Electrical ................................................... 13
2.6 Oil Cooling ............................................. 6 5.1 Motor Design ....................................... 13
5.2 Selection of Electrical Components ..... 13
3. Lubricants .................................................. 7 5.3 Protection Devices ............................... 14
3.1 Table of Lubricants ................................. 7
3.2 Mixing Of Lubricants, Oil Changes ......... 8 6. Selection of Compressor ........................ 14
6.1 Compressor Summary ......................... 14
4. Incorporation into the 6.2 Technical Data ..................................... 14
Refrigeration Circuit .................................. 8 6.3 Application Ranges .............................. 15
4.1 General Design Recommendations/ 6.4 Screw Compressor Accessories .......... 16
Pipe Layout ............................................ 8 6.5 Dimensional Drawings .................... 17-25
4.2 Guide Lines for Special System
Considerations ....................................... 9

©2000 Copeland Corporation 1


Printed in U.S.A.
Copeland 4-1309
1. General The compressor is driven by a three-phase
asynchronous motor that is build into the extended
The SHL & SHM series of screw compressors from compressor housing. The motor rotor is located on
Copeland once again set the standards in the shaft of the male screw rotor. Cooling is achieved
technology and performance. This advanced series by cold refrigerant vapor that mainly flows across
is the result of intensive research based on many the motor rotor, in addition to providing
years experience manufacturing small and medium cooling, this design also functions simultaneously
capacity screw compressors. as a centrifugal liquid separator.
Features:
• High capacity and efficiency due to
- Unique rotor design
- High motor efficiency
- Ease of economized operation
- Automatic Vi Control
- Precise machining process
• Simple and robust design and construction
Side View
• Oversized bearings
• Efficient capacity control (unloaded start)
• Integrated discharge check valve
• Internal pressure relief valve
• ESC 200 electronic control module
• Motor protection device
• Discharge gas temperature protection
• Electronic oil flow switch
• Fine mesh oil filter (10 µ )
• Compatible with R22, R134a, R404A and R507
- Other refrigerants upon request Top View
• Low noise and vibration levels
• Small installed space requirement Figure 1
• Complete line of accessories (E.I. oil separa- Semi Hermetic Screw Compressor
tors, oil filters etc.) 1. Male Rotor
2. Female Rotor
2. Design and Function 3. Rolling Contact Bearing
4. Check Valve
2.1 Construction Features 5. Capacity Control / Start Unloading Pistons
The Contour screw compressors are of 6. Automatic V1 Control
two-shaft rotary displacement design with 7. Internal Pressure Relief Valve
specifically developed profile geometry (lobe ratio 8. Oil Injection
5:6 or 5:7). The main parts of these 9. Discharge Gas Temperature Sensor ( PTC )
compressors are the two rotors (male and 10. Motor
female) which are fitted into a closed housing. The 11. Terminal Box
rotors are precisely located at both ends by roller 12. Motor Protective Device
bearings (radial and axial) which, in conjunction with 2.2 Compression Procedure - Automatic VI
the generously sized oil supply chambers, provides Control
optimum operating characteristics.
Owing to the specific design this type of The compression in a screw compressor takes place
compressor does not require any working valves. in one direction (linear compression). The meshing
To protect against reverse running when the rotors enclose a working space whose volume is
compressor is switched off (expansion continuously reduced as it moves in the axial direc-
operation) a check valve is incorporated in the tion. Refrigerant vapor is drawn in on the suction
discharge chamber (this valve does not side and subsequently compressed by the mesh-
however replace any check valves required by the ing action of the rotors in the enclosed working vol-
system design). Internal differential pressure relief ume. As soon as this working volume is opened to
valves are fitted as over pressure protection. the discharge port, the vapor is discharged to the
high-pressure side and flows to the oil separator.

©2000 Copeland Corporation 2


Printed in U.S.A.
Copeland 4-1309
Caution: Screw compressors may only be 2.3 Capacity Control / Start Unloading
operated in one direction of rotation (reverse
rotation will cause severe damage)! For the Contour Screw Compressors a new form
of regulating system has been developed. The
The very small gap (a few µ) between the rotors basic principle corresponds to that of a control slide
themselves and the housing is dynamically sealed of large industrial compressors, a part of the
with oil, the oil is directly injected into the profile transported vapor flows back to the suction side of
spaces, and to the roller bearings. the rotor chamber. In contrast to larger capacity
compressors the control unit is designed so that it
The size and geometry of the discharge port does not reduce the stability of the compressor hous-
determine the so-called “built-in volume ration (Vi)” ing. The gap between the rotors and the
of the compressor. This ratio must be in a defined housing thus remains within tight tolerances, even
relationship to the operating pressure ratio in order with high operating temperatures and pressures.
to avoid losses in efficiency due to over or under This is an important stage of development and
compression. For this reason screw compressors ensures good overall efficiency of smaller screw com-
are manufactured with different discharge port pressors, due to the higher precision and
configurations specific to the application. tolerance demands.

With the Contour semi – hermetic screw Part Load Operation/Start Unloading Full Load Operation
compressors a newly developed system for fully au-
tomatic Vi-control has been incorporated. The Control Piston

discharge port is automatically optimized for the


nominal operating conditions (pressure ratio). With
a lower pressure ratio in the system a part of the
compressed gas flows directly to the discharge
chamber via a valve mechanism in the rotor
housing (by-passing the discharge port). The flow Solenoid Coil
Solenoid Coil (De-energized) Control Oil
volume remaining in the profiles is thus reduced, (Energized)

the corresponding pressure is reduced and over Figure 3


compression is avoided. This self-regulating Capacity Control System Details
system achieves a high efficiency over a wide
application range. The control system consists of hydraulically
activated pistons for the male and female rotor, which
are flush with the end wall/housing during full load
P oc 2 1 Compression behavior operation. The same efficiencies/characteristics are
2 Losses due to over-compression therefore guaranteed as with a compressor without
P2 3 3 Compression with Vi Control capacity control. Typical losses as with slider sys-
tems are avoided. During part load operation the
pistons move to the rear position and open
1 generously sized ports to the suction side. A
portion of the volume of gas compressed is thereby
P1 V1 transported back to the suction side. The system is
Voc V1
designed for 3 stages of regulation (100, 75, &
50 %). By the use of intermittent switching an
Figure 2
almost stepless characteristic can be achieved.
Compressor Cyle
Control
Control is accomplished electrically via the
solenoid valves located on the discharge flange.

©2000 Copeland Corporation 3


Printed in U.S.A.
Copeland 4-1309
Capacity Control

Compressor Model Full Load Step 1 Step 2 Start Unloading


(100%) (approx.75%)* (approx. 50%)*
SHM1-3000/3500/4000 CR=l
l CR=mm CR=m
m
SHL1-2000/2500/3000
SHM2-3000/3500/4000 CR1=l CR1=m CR1=m CR1=m
SHL2-2000/2500/3000 CR2=l CR2=l CR2=m CR2=m
SHM1-5000/6000 CR1=l CR1=m CR1=m CR1=m
SHL1-4000/5000 CR2=l CR2=l CR2=m CR2=m
SHM1-7000/8000/9000 CR1=l CR1=l CR1=m CR1=m
SHL1-6000/7000/7500 CR2=l CR2=m CR2=m CR2=m
* Effective capacity stages are dependent on operating conditions
l = Solenoid valve energized
m = Solenoid valve de-energized

CR CR2 CR1

Figure 4a Figure 4b
Location of Capacity Control Solenoids Location of Capacity Control Solenoids
SHM1 3000, 3500, 4000 SHM1 5000, 6000, 7000, 8000, 9000
SHL1 2000, 2500, 3000 SHL1 4000, 5000, 6000, 7000, 7500

2.4 Mounting the Compressor

The Contour Screw Compressor itself is provided


as a motor/compressor unit. It is only necessary to
mount the complete unit correctly and to make the
electrical and pipe connections.

The compressor must be installed horizontally. The


use of anti-vibration mounting pads is recommended
to reduce the transmission of noise or vibrations.
The anti-vibration mounting pads are packed
separately from the compressor.

Figure 4c With direct mounting on water-cooled condensers


Location of Capacity Control Solenoids the use of anti-vibration mounting is essential in
SHM2 3000, 3500, 4000 order to prevent possible stress fracturing of the heat
SHL2 2000, 2500, 3000 exchanger tubes.

The installation of the anti-vibration mounting pads


is shown in Figure 5. The bolts should only be
tightened so that deformation of the upper rubber
disc is just visible.
©2000 Copeland Corporation 4
Printed in U.S.A.
Copeland 4-1309
compressor. The oil is then transported together with
the refrigerant vapor in the direction of
5
/8”
compression, where in addition to lubrication it also
forms a dynamic seal between the rotors and the
compressor housing and the rotors, to the
separator/reservoir. The oil and vapor are separated
in the upper portion of this vessel. The oil flow
downward to the reservoir section of the vessel
9
/16”

where it again flow to the compressor. The vapor


exits the top of the vessel and flow to the condenser.
Depending on operating conditions the circulating
Figure 5 oil will need to be cooled in an oil cooler. Under
Mounting Pad Installation certain conditions direct refrigerant injection can be
used to achieve the required oil cooling.

2.5 Oil Circulation The standard accessory kit of the Contour Screw
compressor includes the necessary items for the oil
The compressor oil is obtained from the external oil injection line (oil filter, oil flow switch, oil solenoid
separator that also serves as the oil reservoir. Due valve, sight glass and misc. fittings). In addition a
to the pressure difference between the separator/ line of oil separators is also available. Oil cooling by
reservoir and the injection point, an exactly thermosyphon or Jet Kool principal is also
measured quantity of oil is injected into the available but require individual design and
compression chamber and the bearings of the component selection.

12 13 1/4" ∅
1. Compressor
2. Oil filter
3. Oil flow switch
11 4. Oil solenoid valve
1 5. Oil sight glass
6. Oil separator/receiver
7. Oil level control
8. Oil thermostat
4 5 6 9. Oil heater
10. Oil cooler
(if required)
3 11. Check valve
FZ
12. Solenoid valve
(Off cycle by-pass)
2 7 13. Isolation valve

10 9 8

Figure 6
Oil Circuit

©2000 Copeland Corporation 5


Printed in U.S.A.
Copeland 4-1309
2.6 Oil Cooling

In systems with higher thermal loading, oil cooling is required. The following operating conditions must be
considered:

• Minimum evaporating temperature


• Maximum suction gas superheat temperature
• Maximum condensing temperature
• System operation (capacity control, economizer operation, etc.)

Types of Oil Cooling

Figure 7a Figure 7b
Water-cooled oil cooling Air-cooled oil cooling

ECO

Figure 7c Figure 7d
Thermosyphon oil cooling Direct refrigerant Injection oil cooling

General Recommendations for Oil Coolers

• The oil cooler should be installed in close • The oil flow solenoid valve should be installed
proximity to the compressor. as close as possible to the compressor to limit
• The piping should be designed so that no vapor the amount of oil draining to the compressor
accumulations can occur and to eliminate the during shut down periods (eliminate the
possibility of the oil charge draining back to the possibility of flooding the compressor with oil).
oil separator during shut down periods. • A full port ball valve should be installed in the oil
Preferably the oil cooler should be located be- line after the oil cooler to facilitate servicing.
low the compressor/oil separator. • The oil cooler must be thermostatically
• Pressure drop on the oil side of the oil cooler controlled (see table)
should be less than 7 psig during normal
operation.
©2000 Copeland Corporation 6
Printed in U.S.A.
Copeland 4-1309

Sensor Location Refrigerant Temperature Setting


Nominal Maximum

R-22 54° above condensing 176°F


Temperature temperature
regulator for Discharge Gas Line
oil cooler 100° above condensing
R-134a 203°F
temperature
54° above condensing 176°F
R-22
temperature
Bypass valve Discharge Gas Line
100° above condensing
R-134a 185°F
temperature

• To facilitate the heating of the oil circuit and to to 10% of the compressors refrigerating
reduce the pressure drop with cold oil an oil by- capacity due to the dilution of the oil at higher
pass (or possibly heating of the oil cooler during injection ratios.
off cycle) is required under the following condi- • Only specially designed expansion valves that
tions: regulate by discharge gas temperature are
- When the oil temperature in the oil cooler suitable (Danfoss TEAT20, Sporlan Y1037, Alco
can drop below 68°F during a long off cycle. series 935) with a temperature setting of 195°F.
- When the volume of oil in the oil cooler and • The sensing bulb must be installed on the
associated piping is greater than 7 gal. discharge line approximately 8 inches from the
compressor. The pipe should be cleaned to a
“bright metal” and coated with heat transfer paste
Note: The oil bypass valve should have a
and held in place with pipe clamps.
modulating control function. The use of solenoid
• To ensure bubble free liquid to the expansion
valves (intermittent control) requires a control
valve, the connection to the main liquid line
thermostat with high sensitivity and minimum switch-
should be in a horizontal run and slope down
ing differential (temperature fluctuation) of 20°.
away from the main liquid line.
• Additional items required to be installed in the
Water Cooled Oil Cooler injection line include; solenoid valve (wired in
parallel to the compressor motor), fine mesh
Temperature control by the use of a thermostatic filter and liquid sight glass.
water regulator (temperature range up to 212°F) is
recommended. Thermosyphon Cooling

Air Cooled Oil Cooler Design and technical information available on


request for specific applications.
Temperature control by the use of a thermostatic
switch to turn on and off cooler fans or stepless 3. Lubricants
speed control of the fan motors is recommended
(temperature range up to 212°F). In addition to lubrication oil also provides the
dynamic sealing of the rotors. Special demands
Direct Refrigerant Injection result from this with regard to viscosity, solubility and
foaming characteristics. Only approved oils may
therefore be used.
• This method of oil cooling is limited to an oil
cooling capacity (oil cooler load) that equivalent

3.1 Table of Lubricants


Evaporating Condensing Viscosity Discharge
Refrigerant Temperature Temperature Oil type cSt @ 40 °F Temperature Manufacturer
HFC -4 to 70 °F 160 °F Solest 170 170 Approximately CPI
140 °F
Maximum
R22 -60 to 55 °F 140 °F CP-4214-150 150 CPI
212°F

©2000 Copeland Corporation 7


Printed in U.S.A.
Copeland 4-1309
Important Considerations compressors. Only the oil circuit will differ. Piping
should be designed in compliance with accepted
The operating limits of the compressors must be criteria especially in regard to flow velocities (oil
adhered to (refer to section 5.3). return). The pipe layout and the system
construction must be designed so that the
• The lower limit value indicated for the discharge compressor cannot be flooded with oil or liquid
gas temperature shown is only a reference refrigerant during shutdown periods. A simple
value. The discharge gas temperature must be safeguard against this is to first pipe the discharge
at least 54°F above the condensing and suction lines downward from the compressor.
temperature. As an additional precaution (also provides simple
• The sensor of the oil cooler temperature protection against liquid slugging during starting)
controller must be installed on the discharge line for systems with direct expansion either a
of the compressor approximately 8 inches from gooseneck after the evaporator or installation of the
the compressor. The thermostat or compressor above the level of the evaporator is
regulator should be adjusted to maintain an oil required (not essential with “pump down”
temperature that is 54°F above the condensing system). A solenoid valve should also be installed
temperature. in the liquid line directly before the expansion valve.
• Ester oils such as Solest 170 are extremely hy-
groscopic and careful handling is required. The use of flooded evaporators with HCFC/HFC
Moisture is chemically bonded with these oils refrigerants require a separate oil return from the
and cannot, or only insignificantly, be removed evaporator or low pressure receiver. TH e bleed
by evacuation. Dispose of waste oil in an point (preferably several) should be located in the
ecologically beneficial way (chloritic oil is oil rich liquid phase. The oil should be returned to
pollutive waste). the suction of the compressor, but only after the
• A revised design may be necessary for liquid refrigerant has been evaporated. In systems
direct-expansion evaporators with finned tubes with widely varying liquid levels, such as liquid over
on the refrigerant side (consultation with cooler feed systems, a bleed point from the lowest point
manufacturer). after the circulating pump should be used.

The above information is intended as a guide for Further Recommendations for Unit Construction
general possible applications only. This information and Pipe Layouts
does not have the purpose of confirming certain oil
characteristics or their suitability for a particular use. Due to the low level of vibration and discharge gas
pulsation, the suction and discharge lines can
3.2 Mixing Of Lubricants Oil Changes usually be installed without flexible connections or
mufflers. The piping must however be sufficiently
flexible and must not exert any strain on the
Different lubricants may not be mixed without compressor. Pipe runs parallel to the compressor
agreement from Copeland Corp. Especially in the are preferred. The distance from the compressor
case of an oil change, this is however only axis should be kept as small as possible and the
necessary in exceptional cases for systems with parallel section of piping should be at least as long
screw compressors using HCFC and HFC as the compressor.
refrigerants (acid formation, contaminated oil).
An oil heater is installed in the sump section of the
4. Incorporation into the Refrigeration Circuit oil separator to prevent high concentrations of re-
frigerant diluting the oil during shutdown periods.
Semi hermetic screw compressors, SHM/SHL An adjustable thermostat that should be set at
series, can be used for all refrigeration systems from approximately 160°F. controls the heater. In
air conditioning to low temperature addition, an off cycle by-pass that reduces the
applications. The capacity range can be easily pressure in the oil separator to suction pressure
expanded due to the simple and economic Cope- and reduces the refrigerant saturation of the oil,
land compound technology. can also be installed. An added benefit to this is to
additional reduce the start loading of the
4.1 General Design Recommendation / Pipe Lay- compressor. A check valve after the oil separator,
out and a ¼” Ø equalizing line, with a solenoid valve,
between the oil separator and the suction of the
The screw compressors can be incorporated into compressor must be installed. The solenoid can only
the system in a similar way to reciprocating be opened when all the compressors in the system
are off.
©2000 Copeland Corporation 8
Printed in U.S.A.
Copeland 4-1309
A generously sized good quality liquid line filter drier is recommended. A suction accumulator should be
is required to provide the system with a high degree installed to protect against liquid slugging. To avoid
of dehydration and help maintain the chemical increased oil carry-over, due to a rapid reduction of
stability of the system. pressure in the oil separator, it is necessary to
maintain the oil temperature is at least 54 to 72°F
The installation of a suction filter (25 µ) is above the condensing temperature, during the
recommended to protect the compressor from change over. In addition the installation of a
damage due to dirt or debris especially during the pressure regulator directly after the oil separator is
initial start of the system. recommended to limit the reduction in pressure. Un-
der certain circumstances it is also possible to stop
the compressor shortly before the change over pro-
6 mm (1/4")
5 cedure and then to start it again after a pressure
1 7
PRV
equalization has taken place. The compressor must
6
be operating with the necessary minimum pressure
differential within 30 seconds (see application limits,
FZ
TC
LZ TC
section 6.3).
3 2

8
4 4.3 Condenser Pressure Regulation
PC
9
In order to guarantee consistent good quality oil
supply to the compressor and to maintain oil
separator efficiency a closely stepped or stepless
condenser pressure regulation is required. Rapid
Figure 8 depressurization of the oil separator can lead to
Typical Application excessive foaming, oil migration and possible shut
down by the oil level sensor. Insufficient oil supply
4.2 Guide Lines for Special System Consider- and corresponding shutdown can also occur with
ations insufficient of delayed build up of condenser
pressure. An additional pressure regulator in the
In installations where the system is exposed to low discharge line, after the oil separator, may be
ambient temperatures or the high pressure side is necessary with the following operating conditions:
exposed to high temperatures (heat pumps),
additional insulation of the oil separator is required. • Extreme part load conditions and/or long shut
down periods with outdoor installation of the
In systems where the where the compressor or the condenser in low ambient areas.
suction line/accumulator can reach a lower • High suction pressure during start up in
temperature than the evaporator a pump down cycle conjunction with low temperatures of the heat
must be employed. transfer fluid on the high-pressure side, critical
start conditions.
For systems with multi-circuit condensers and/or • Hot gas defrost, reverse cycle operation.
evaporators additional safeguards are necessary. • Booster applications, low pressure differention
When individual circuits are turned off, liquid from suction to discharge.
refrigerant will migrate to the evaporator/ condenser
(temperature and pressure equalization is not 4.4 Start Unloading
possible), the installation of an additional check valve
in the discharge line and an automatic sequential
switching arrangement for the compressor are Due to the compression characteristics of screw
required. The same also applies for plants with compressors, high suction pressure during start up
individual circuits where temperature and pressure can lead to high mechanical loading and insufficient
equalization cannot occur during long shutdown oil supply. Effective unloading is therefore
periods. In some cases it may be necessary to necessary. In addition, compressors of this size and
install a suction accumulator or utilize a pump down capacity usually require a means to reduce the
circuit. starting current, such as part winding starting.

Systems with reverse cycling or hot gas defrost Start unloading can be achieved by the following
require individually designed safeguards to protect methods:
the compressor against liquid slugging and increased
oil carry-over. In addition a complete system review • Integrated start unloading, see section 2.3.
Standard on all SHM & SHL compressors.
©2000 Copeland Corporation 9
Printed in U.S.A.
Copeland 4-1309
• Limited start unloading is possible by the use 4.6 Parallel operation
of an off cycle by-pass, see General
Recommendations section 4.1, with low The Copeland Contour SHM & SHL series
temperature operation in conjunction with a compressors are particularly suitable for parallel op-
pressure limiting TX-valve or a crankcase eration due to the use of the external oil
pressure regulator. This method is however separator/receiver.
limited to single compressor systems of
specifically designed parallel compressor Important advantages of the Copeland Contour
systems. compound technology:

NOTE: An external start unloading bypass as is • Extension to the limited capacity provided by a
typically used with reciprocating compressors single compressor, up to six (6) compressors
cannot be utilized with screw compressors due to can be compounded.
possible damage of the compressor. • Compounding compressors of similar or
differing capacities.
4.5 Capacity Regulation • Possible to compound systems with differing
suction temperatures.
• Extended capacity regulation.
The requirement for capacity regulation is
• Simple oil distribution with single oil separator/
dependent on the system design and requirements.
receiver.
The following methods are available:
• Higher degree of operational safety, not
dependent on a single compressor.
• Integrated capacity regulation, see section 2.3. • Simple and economical installation.
Standard on all SHM & SHL compressors
• Frequency Inverter
• Parallel operation, see section 4.6, possibly Oil separators and other accessories are available
combined with any of the above methods. that allow up to six (6) compressors in a single cir-
cuit.

2 1

FZ FZ FZ 3 FZ

PRV
4
6 7

LZ TC

TC
8

Figure 9
Parallel compounding with a common oil separator and a water-cooled oil

©2000 Copeland Corporation 10


Printed in U.S.A.
Copeland 4-1309

1
2

FZ FZ FZ 3 FZ

PRV
4 7
6

LZ TC
ϑ

10

12

Figure 10
Parallel compounding with a common oil separator and a air-cooled oil cooler

t0 < t0 >
5

2 1

FZ FZ FZ 3 FZ

PRV
4 7
6

LZ TC

TC TC
8

Figure 11
Parallel compounding for varying suction temperatures

©2000 Copeland Corporation 11


Printed in U.S.A.
Copeland 4-1309

2 1

FZ FZ FZ 3 FZ

4
6

LZ TC

11

TC TC
8 12

Figure 12
Parallel compounding with common oil separator, water-cooled oil cooler and oil pump

Legend
1 – Compressor 7 – Condensing Pressure Regulator (if required)
2 – Oil Solenoid Valve 8 – Water Cooled Oil Cooler
3 – Oil Flow Switch 9 – Condenser
4 – Oil Filter 10 – Air Cooled Oil Cooler
5 – Off Cycle By-pass 11 – Oil Pump
6 – Oil Separator with Heater & level control 12 – Mixing Valve

4.7 Economizer Operation temperatures, low and medium temperatures as an


example, or for systems that require especially low
Copeland Contour compressors are equipped with evaporating temperatures.
an additional inlet connection for Economizer
Operation. Economizing can be accomplished by Typical applications would include large flooded
either utilizing a subcooling circuit or two stage central systems with low pressure receivers and
refrigerant expansion. This mode of operation pumped circulation, blast freezers which may
increases the refrigeration capacity as well as the operate as a single stage system during the initial
ef ficiency of the system. The higher the phase, relatively high evaporating temperatures, but
compression ratios the greater the benefits of this must also provide high capacity and efficiency at low
mode of operation will be. evaporating temperatures, final phase.

Compressor Design
4.8 Two-Stage Systems
• High pressure stage: SHM series
• Low pressure stage: SHL series
Although screw compressors can be efficiently used • Special booster design
with high compression ratios, there are a number of • Operation without an oil pump requires a
applications where two-stage compression can be minimum differential pressure of 36 psi with a
beneficial. This type of system is particularly maximum pressure drop in the oil line from the
beneficial for systems with different suction separator to the compressor of 5 psi
©2000 Copeland Corporation 12
Printed in U.S.A.
Copeland 4-1309

PRV 2 1
LP HP
3
FZ FZ FZ

PRV
4 7
6

LZ TC LZ TC
PC

9
TC
8

11

Figure 13
Two stage system with independent low and high pressure compressors

5. Electrical The following current values appear in the part


windings:
5.1 Motor Design PW1 PW2
50% 50%
The compressors are supplied as standard with part
winding motors (“PW”). Both of the contactors should be selected for at least
60% of the maximum operating current.
Starting methods (connections according to Fig. 14):

• Part winding start to reduce the starting cur- Part - Winding Start Direct – On – Line Start
rent
• Direct on-line start (DOL) PW2 PW2

T1 T1
5.2 Selection of Electrical Components 7
L1
When selecting cables, contactors and fuses the 1 1
maximum operating current / maximum motor power 8 L1 L1
must be used (see section 6.2). L2
2 2
Note: Nominal power is not the same as maximum 9 L2 L2
motor power. L3
3 3
L3 L3

T2 T2

Figure 14
Motor Connections
©2000 Copeland Corporation 13
Printed in U.S.A.
Copeland 4-1309
5.3 Protection Devices Semi-Hermetic Screw Compressors

The Copeland Contour screw compressors uses the Medium Low


ESC-200 protection device, see form no. 99-19 for Temperature Temperature Displacement
features, installation and operating instructions. Applications Applications CFH
SHM1-3000 SHL1-2000 3,567
6. Selection of Compressor SHM2-3000 SHL2-2000 3,567
SHM1-3500 SHL1-2500 4,273
SHM2-3500 SHL2-2500 4,273
6.1 Compressor Summary SHM1-4000 SHL1-3000 5,015
SHM2-4000 SHL2-3000 5,015
Copeland at present offers 16 different semi hermetic SHM1-5000 SHL1-4000 5,933
screw compressors and thereby covers an exten- SHM1-6000 SHL1-5000 6,992
sive range of applications. With the ability of parallel SHM1-7000 SHL1-6000 8,193
compounding of up to 6 compressors on a single SHM1-8000 SHL1-7000 9,394
SHM1-9000 SHL1-7500 10,665
circuit, the capacity range can be significantly ex-
tended and a high operational reliability and the best
efficiency under part load conditions can be achieved

6.2 Technical Data

Compressor Capacity Connection Sizes Dimensions


Model No. Motor H.P. Control Weight Suction Discharge LxWxH
SHM1-3000 30 100%, 75% 375 1 5/8” 2 1/8” 29.8 x 17.05 x 16.93
SHL1-2000 20 366
SHM2-3000 30 100% 375 1 5/8” 2 1/8” 29.8 x 17.05 x 16.93
SHL2-2000 20 75%, 50% 366
SHM1-3500 35 100%, 75% 385 1 5/8” 2 1/8” 29.8 x 17.23 x 16.93
SHL1-2500 25 374
SHM2-3500 35 100% 385 1 5/8” 2 1/8” 29.8 x 17.23 x 16.93
SHL2-2500 25 75%, 50% 374
SHM1-4000 40 100%, 75% 400 1 5/8” 2 1/8” 29.8 x 17.23 x 16.93
SHL1-3000 30 392
SHM2-4000 40 100% 400 1 5/8” 2 1/8” 29.8 x 17.23 x 16.93
SHL2-3000 30 75%, 50% 392
SHM1-5000 50 100% 524 1 5/8” 2 1/8” 35.98 x 20.00 x 17.13
SHL1-4000 40 75%, 50% 515
SHM1-6000 60 100% 541 1 5/8” 2 1/8” 35.98 x 20.00 x 17.13
SHL1-5000 50 75%, 50% 524
SHM1-7000 70 100% 671 2 1/8” 3 1/8” 40.20 x 20.59 x 16.62
SHL1-6000 60 75%, 50% 653
SHM1-8000 80 100% 691 2 1/8” 3 1/8” 40.20 x 20.59 x 16.62
SHL1-7000 70 75%, 50% 682
SHM1-9000 90 100% 739 2 1/8” 3 1/8” 43.03 x 20.59 x 16.62
SHL1-7500 75 75%, 50% 717 41.06 x 20.59 x 16.62

©2000 Copeland Corporation 14


Printed in U.S.A.
Copeland 4-1309
Electrical Ratings
Low Temperature Applications Medium Temperature Applications
Compressor Voltage LRA RLA MCC MCC Compressor Voltage LRA RLA MCC MCC
Model No. R-22 R-404A Model No. R-22 R-404A
SHL1-2000 208/230 492 81 114 SHM1-3000 208/230 436 92 106 130
460 246 41 57 460 218 46 53 65
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL2-2000 208/230 492 81 114 SHM2-3000 208/230 436 92 106 130
460 246 41 57 460 218 46 53 65
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL1-2500 208/230 436 85 120 SHM1-3500 208/230 532 121 138 170
460 218 42 60 460 266 60 69 85
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL2-2500 208/230 436 85 120 SHM2-3500 208/230 532 121 138 170
460 218 42 60 460 266 60 69 85
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL1-3000 208/230 532 104 146 SHM1-4000 208/230 622 130 156 182
460 266 52 73 460 311 65 78 91
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL2-3000 208/230 532 104 146 SHM2-4000 208/230 622 130 156 182
460 266 52 73 460 311 65 78 91
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL1-4000 208/230 655 136 228 SHM1-5000 208/230 743 165 215 258
460 313 65 109 460 355 79 103.6 124
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL1-5000 208/230 743 165 240 SHM1-6000 208/230 939 205 278 334
460 355 79 115 460 449 98 133 160
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL1-6000 208/230 939 186 247 SHM1-7000 208/230 1015 251 280 295
460 449 89 118 460 485 120 134 141
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL1-7000 208/230 1015 215 299 SHM1-8000 208/230 1224 263 293 343
460 485 103 143 460 585 126 140 164
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A
SHL1-7500 208/230 1224 249 314 SHM1-9000 208/230 1435 305 341 358
460 585 119 150 460 686 146 163 171
575 N/A N/A N/A N/A 575 N/A N/A N/A N/A

6.3 Application Ranges

R-22 Operating Envelope R-404A/R-507 Operating Envelope


140 140
SCT[°F] SCT [°F]
120 120
SHM SHM
SHL SHL
100 100

80 80

60 60
SH=40°F SH=40°F

40 40
-60 -40 -20 0 20 SST40 [°F] 60 -60 -40 -20 0 20 SST 40 [°F] 60

©2000 Copeland Corporation 15


Printed in U.S.A.
Copeland 4-1309

6.4 Screw Compressor Accessories

Compressor Applications Kit (one required per compressor)

Kit includes: oil filter housing, oil filter element, flow switch, solenoid valve & coil, sight glass, rotation switch
with vibration damper, fittings and O-rings.

SHM SHL 115 volt 230 volt


Series 1 30/35/40 HP Series 1 20/25/30 HP 560-0001-01 560-0001-00
Series 2 30/35/40 HP Series 2 20/25/30 HP 560-0001-06 560-0001-07
Series 1 50/60 HP Series 1 40/50 HP 560-0001-03 560-0001-02
Series 1 70/80/90 HP Series 1 60/70/75 HP 560-0001-05 560-0001-04

Electronic Module (one required per compressor)

ESC200 Standard Module 560-0002-00


ESC200E Eschelon Module 560-0002-01

Oil Separator Kit (one required per pack)


Oil Separator 115 volt 230 volt
18 liter low profile (1-2 compressors) 560-0003-00 560-0003-01
18 liter top outlet (1-2 compressors) 560-0003-02 560-0003-03
40 liter top outlet (up to 3 compressors) 560-0003-04 560-0003-05
90 liter top outlet (up to 6 compressors) 560-0003-06 560-0003-07
140 liter top outlet (up to 6 compressors) 560-0003-08 560-0003-09

Oil Separator Kit (one required per pack)


Size Low Temperature Medium Temperature
Maximum CFH Maximum CFH
18 Liter 10,600 CFH 7,770 CFH
40 liter 23,300 CFH 15,540 CFH
90 liter 46,615 CFH 31,080 CFH
140 liter 46,615 CFH 46,615 CFH

Compressors listed in U.L. File No. SA 7129


The following models require a Furnas 958 Overload Relay;
• SHL1-4000/5000/6000/7000/7500
• SHM1-5000/6000/7000/8000/9000

©2000 Copeland Corporation 16


Printed in U.S.A.
Copeland 4-1309
6.5 Dimensional Drawings

©2000 Copeland Corporation 17


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 18


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 19


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 20


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 21


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 22


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 23


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 24


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 25


Printed in U.S.A.
Copeland 4-1309

©2000 Copeland Corporation 26 Copeland Corporaton


Printed in U.S.A. Sidney, Ohio 45365-0669

Das könnte Ihnen auch gefallen