Beruflich Dokumente
Kultur Dokumente
INSTALLATION MANUAL
S y s tem Section No. 401-305-0496
INSTALLATION MANUAL
© 1999, C-DOT
Printed in India
C-DOT DSS MAX-XL
INSTALLATION MANUAL
DRAFT 03
AUGUST 1999
BHADRA 2056
THIS C–DOT SYSTEM PRACTICE REFERS TO THE C–DOT DIGITAL SWITCHING SYSTEM
THIS PUBLICATION).
A COMMENT FORM HAS BEEN INCLUDED AT THE END OF THIS PUBLICATION FOR
READER'S COMMENTS. IF THE FORM HAS BEEN USED, COMMENTS MAY BE ADDRESSED
1.1. Introduction....................................................................................................................... 9
Chapter 2. Grouting.................................................................................................................................. 19
2.1. Introduction..................................................................................................................... 19
2.3. Drilling............................................................................................................................. 19
3.1. Introduction..................................................................................................................... 23
4.1. Introduction..................................................................................................................... 47
5.1. Introduction..................................................................................................................... 53
6.1. Introduction..................................................................................................................... 63
7.1. Introduction..................................................................................................................... 78
8.1. Introduction..................................................................................................................... 85
9.1. Introduction..................................................................................................................... 92
10.1. Introduction................................................................................................................... 99
Appendix - II Modifications for Enhanced Subscriber Service Unit (ESU) Equipment......................... 376
Floor Marking
1.1. INTRODUCTION
As a first step towards the installation of Exchange equipment (iron work, IOP-
PDP), the floor should be marked as per the exchange layout. Floor markings are
done in Switch Room where the main switching equipment is placed and IOP Room
where the input output processors with consoles are placed. The main aim of this
marking is to locate the exact position of the grouting holes which are used for
fixing the equipment in the respective rooms. This chapter covers the materials and
tools required and the detailed marking procedure. However, before carrying out
the floor marking, certain standard terms need to be understood and are therefore
defined.
1.2.1. Floor
Floor means the normal floor covered with suitable antistatic material.
A datum line is a straight line drawn through the maximum no. of points
located at a distance, say D, from the wall of the Switch Room/IOP Room.
It is a point on the Switch Room/IOP Room floor to which the datum lines
and subsequent measurements are related. It is also defined as the
intersection point of the two datum lines drawn at right angles to each other.
This is the line drawn parallel to one of the datum line from which the suite
will begin or start growing.
INSTALLATION MANUAL 9
Chapter 1.
These are the lines drawn parallel to the other datum line (one referred in
suite end line) perpendicular to suite end line and coincide with the periphery
of the Base mount Assembly.
These are the lines drawn parallel to one of the datum lines, and coincide
with the periphery of the IOP cabinet.
1. T Square (1 meter) 1
7. Set Square 1
Mark some points along the length of the room at a distance of 600mm from
the wall. Draw a line such that it passes through a maximum number of the
points. To draw the line, soak a silk string of required length in ultra marine
indigo or blue ink. Place it over the points by holding the string tightly at
both the ends. Pull the string from the middle and release it so that it leaves
an impression on the floor. This line is called the first datum line. Refer Fig.
1.1.
Mark a point on the first datum line at a distance of 600mm from the
adjacent wall. This point is called the Reference Point. Fix a brass screw at
the Reference point to mark it permanently. This point is denoted as `X' in
Fig. 1.1.
INSTALLATION MANUAL 11
Chapter 1.
The second datum line should be perpendicular to the first datum line. To
ensure this, the 3-4-5-triangle rule is adopted and the second datum line is
drawn passing through the reference point.
With a steel tape measure a length of 900mm or a multiple of 300mm (say
Nx300mmm) from the reference point and mark a point on the first datum
line. Let us call this point as 'Y'. (Fig. 1.2).
From the reference point 'X' draw an arc at a distance of 1200mm or a
multiple of 400mm (say Nx400 mm) in the direction approximately
perpendicular to the first datum line. To draw an arc use a pen tied to one
end of a string. Draw another arc at a distance of 1500mm or a multiple of
500mm (say Nx500mm) from the point 'Y' on the first datum line such that it
intersects the earlier arc. Let us call the intersection point as 'Z'. Obtain
several points in a similar way. Draw a line from the reference point such
that it passes through maximum number of these points. To draw the line
use the string dipped in ultra marine indigo or blue ink.
Fix some brass screws along the datum lines with a clearance of 2M between
them.
Draw a line parallel to the second datum line at a distance of 1600 mm from
it. This is referred to as the suite end line as shown in Fig. 1.3. Now draw a
line at a distance of 400 mm from and parallel to the first datum line. This is
referred as the suite line. Now other suite lines can be drawn parallel to this
suite line at a distance of 624 mm, 1624 mm, 2248 mm, 3248 mm, 3872 mm,
4872 mm, 5496 mm, 6496 mm and 7120 mm. These suite lines should be of
8590 mm length.
Fig. 1.3 shows a typical switch room grouting hole markings for a five suite
configuration of C-DOT MAX-XL. These holes are used for fixing the iron
work on the floor.
INSTALLATION MANUAL 13
Chapter 1.
Basemount assemblies of the first suite will be placed on the first and second
suite line. Basemount assemblies of the second suite will be placed on the
third and fourth suite line and so on.
A typical MAX-XL switch room layout for a five suite configuration is shown
in Fig. 1.4. It is to be noted that number of suites required depends on the
capacity and configuration of the switch.
A typical TAX-XL switch room layout for a 6K trunk configuration is shown
in Fig. 1.4 (a). For higher capacity (>6K) TAX one more suite will be added
and CM will then be installed in third suite.
INSTALLATION MANUAL 15
Chapter 1.
17
FLOOR MARKING
Chapter 1.
Grouting
2.1. INTRODUCTION
This chapter describes the procedure for preparation of holes used for fixing the iron
work of the multimodule MAX-XL on the floor.
6. Vacuum Cleaner 1
2.3. DRILLING
The marked points ‘+’ (refer Fig. 1.5) serve as the centre point for drilling. An
electrical concrete drilling machine with 32 mm carbide tip spiral bit is used for
drilling on concrete floor. During drilling, care is taken for the hole to be straight
and there is no chipping/cracking of the mosaic tiles.
INSTALLATION MANUAL 19
Chapter 2.
expansion of the grouting bolt. To clear material from the hole a vacuum cleaner is
used.
INSTALLATION MANUAL 21
Chapter 2.
3.1. INTRODUCTION
This chapter describes the procedure and component details for installation of the
iron work which is a structure required for mounting cabinets and cabling C-DOT
MAX-XL.
INSTALLATION MANUAL 23
Chapter 3.
INSTALLATION MANUAL 25
Chapter 3.
(size M16) already fixed on the floor. There are 8 more holes having floating
nut for fixing of cabinets. Before the basemount is placed, it has to be ensured
that the basemount spacer is placed on each grouting bolt to arrest the
movement of grouting bolt. The basemount is now placed in such a way that
all the four grouting bolts are well inserted into the basemount holes. The
fixing is done with M16 nut, spring washer and plain washer. The mounting
procedure is shown in Fig. 3.2. Before fixing the basemount with bolts,
levelling is done using a spirit level. Wherever leveling is to be adjusted,
liner-1, liner-2 and liner-3 which are of different thickness can be used. These
liners can be placed between the floor and the basemount to take care of
uneven levels. After this the bolts can be tightened. The detail of the items
like bolts, washer etc. required for fixing one basemount assembly are given
in Table 3.4.1.
Fig. 3.2 illustrates how the first two and the last two basemount assemblies
in a suite are joined using Base joining-plate. So only two joining plates are
required to assemble all the four basemount assemblies meant for one full
suite. Table 3.4.2 gives the list of fasteners required for fixing one base
joining plate. A gap of 4mm should be maintained between two assemblies
while fixing the joining plates as shown in detail of ‘B’ in Fig.3.2. Similarly a
gap of 17 mm should be ensured between second and third basemount assy
where no joining plate is used. This is shown in detail of `A’ in Fig.3.2.
There are two types of vertical pillar assemblies. One designated as vertical
pillar assembly (Front) is provided with Power Distribution Panel (PDP) for
the suite and is located in the beginning of the suite. The other vertical pillar
assemblies are located at the end of second basemount assembly and the end
of the suite. The locations of these vertical pillar assemblies of the suite are
shown in Fig.3.3. The vertical pillar assemblies should be mounted in such a
way that there is a clearance of 3mm between the edge of the base mount
assembly and the vertical pillar assembly as shown in detail of `A’ in Fig.3.4.
The vertical pillar assemblies are fixed to the basemount assemblies using
M18x60 bolts with washers. Any small dimensional inaccuracies in the pitch
of the holes between pillar and basemount is taken care of by the float nut
arrangement provided in the basemount. A plumb bob is used to check that
the vertical pillars have been mounted in an exactly vertical position. The
vertical pillars are supplied with side covers on both sides. While fixing it on
the basemount assembly, one of the covers is removed to have access to the
fixing holes and the cover is replaced after the installation is completed.
Items required for fixing one vertical pillar assembly is given in Table 3.4.3.
INSTALLATION MANUAL 27
Chapter 3.
INSTALLATION MANUAL 29
Chapter 3.
Having fixed the vertical pillars as described in section 3.3.2. Support box
assembly is required to be fixed on the top of each vertical pillar as shown in
Fig. 3.4 which gives the isometric view. The support box is fixed on the
vertical pillar using M8x50 hexagonal screws with plain washers and spring
washers. The bottom view of the support box after it is placed on the top of
the vertical pillar assy (Front) is clearly shown in Fig.3.4. A cut of 204 mm
has been provided for guiding the support box to rest on the vertical pillar
assembly. Support box has a length of 634 mm. This cut of 204 mm is not in
the centre. A length of 200 mm on left and 230 mm on right is shown. While
fixing this support box care should be taken to ensure that 230 mm portion
falls on right hand side as viewed from front side of the suite. It holds good
for all support boxes.
INSTALLATION MANUAL 31
Chapter 3.
through this section. This raised section divides the child trough in two
portions. The portion towards the front side of the cabinet is used to lay
subscribers and trunk cables coming from mother trough. The other portion
on the rear side of the cabinet is used to lay the Base module to central
module cables. In each child trough assembly, there are two such sections one
on the left hand side and the other on the right hand side of the assembly
namely power trough (left) and power trough (right) respectively. The child
trough assembly is mounted on two support box assemblies of a suite. Six
nos. of bolts of size M8X20 alongwith washer are used for fixing the child
trough assembly with the support box. The fixing procedure is shown in Fig.
3.8 and Fig.3.9. List of materials required for fixing one child trough
assembly to support boxes is given in Table 3.4.6. The alignment of the
vertical pillar is checked with the help of plumb bob and then the nuts, bolts
are tightened. Nut insert covers are used over the nuts to avoid scratches on
cables while laying.
After routing all the cables False panel assembly-2 (trough) and false panel
assembly-3 (trough) are fixed on to the child trough. Each panel is meant for
two cabinets. With this, the cables dropping from child trough to the cabinets
are not visible from the front and from the rear. Each child trough assembly
is fixed with false panel assembly-2 (trough) and false panel assembly-3
(trough) on left and right side of the assembly on both the front and rear side
as shown in Fig.3.14.
The opening formed between the mother trough assembly and child trough
assembly on the support box on the vertical pillar assembly (front) of the last
suite is covered by End plate-2. This is shown in Fig.3.13.
The opening formed between the mother trough assembly and child trough
assembly on the support box on the middle vertical pillar of the last suite is
covered by End plate- 3. (Refer Fig.3.13)
All openings between the mother trough assembly (R) and child trough
assembly on the support boxes on the vertical pillar on Right Side of the
suites, except the last suite, is covered by end plate-5. (Refer Fig.3.13)
The opening between the mother trough assembly (R) and child trough
assembly on the support box of the Vertical pillar on right side of the last
suite is covered by End Plate-I. (Refer Fig.3.13)
The uncovered portion in the support box assembly on the vertical pillar assy
(front) is covered by cover plate (support box). (Refer Fig.3.13)
INSTALLATION MANUAL 33
Chapter 3.
INSTALLATION MANUAL 35
Chapter 3.
INSTALLATION MANUAL 37
Chapter 3.
Fig.3.10 shows the view after placement of eight cabinets on the Basemount
assemblies. It is suggested that the cabinets should be erected on the first
suite before taking up the installation of second suite and subsequent suites.
After the erection of first suite, and cabinet placement, second suite erection
is to be done as shown in Fig. 3.11. It is similar to the first suite. The
interconnecting trough assemblies are different which are clearly shown in
Fig.3.12.
INSTALLATION MANUAL 39
Chapter 3.
INSTALLATION MANUAL 41
Chapter 3.
INSTALLATION MANUAL 43
Chapter 3.
OR (FS ) OR
Table 3.4.4 Support Box Assembly Fixing with Vertical Pillar Assembly
Sl. No. CDOT PART NO. DESCRIPTION QTY.
3. MCW-HESSP006-401 Washer-M8 6
Table 3.4.5 Mother Trough Assy. and Power Trough (end) Fixing with Cable Ladder
(Left Side)
Sl. No. CDOT PART NO. DESCRIPTION QTY.
4. MCW-HESSP006-401 Washer M8 8
INSTALLATION MANUAL 45
Chapter 3.
Table 3.4.6 Child Trough Assy. Fixing with Support Box Assembly
Sl. No. CDOT PART NO. DESCRIPTION QTY.
4.1. INTRODUCTION
The C-DOT DSS MAX-XL utilizes a single supply potential of -48V DC as input for
all its power requirements. All AC and DC potential required for the operation of
the various cards in a frame of any cabinet and operation of VDU and Printers are
derived from this -48V DC source. In order to ensure a reliable and continuous
operation of MAX-XL, DC power distribution is carried out through two distribution
panels - Intermediate Distribution Panel (IDP) located in power room and DC
Distribution Panel (DCDP) in switch room.
2. DC Distribution Panel 2
3. Rawl Bolt 12
4. Drilling Machine 1
5. FBI Cards 2
6. Screws 8
INSTALLATION MANUAL 47
Chapter 4.
The interconnection from switching cubicle to IDP is either through bus bars
or maximum three pairs of PVC insulated cable of conductor cross section 240
sq. mm. crimped with a copper lugs on both the ends.
For extending the power from IDP to DCDP in the Switch Room, PVC
insulated cables of size 240 sq. mm is used. There is a provision for a
maximum of six pairs of cables, each pair used for -48V and -48V GND.
All these cables are explained in Chapter 10 and are connected as shown in
Fig. 10.7 (a).
INSTALLATION MANUAL 49
Chapter 4.
DCDP1 is installed in switch room close to the first suite. The distance
between DCDP1 and first suite should be less than 10 mtrs. The size of the
DCDPs is 700x800x1700 mm. It is to be mounted on the floor by fixing the
bottom frame assembly with four rawl bolts.
If the exchange requires more than 3 suites then DCDP2 is installed in
switch room close to fourth suite as shown in Fig. 1.4 switch room layout.
Internal details of DCDPs are shown in Fig. 4.3.
As shown in Fig. 4.3, FBI card is mounted on each DCDP with four fixing
screws. -48V busbar of DCDP has a provision for DC supply to FBI card. For
sensing of MCB's failures on FBI, shorting stubs W21 to W28 and W31 to
W38 are to be shorted according to the MCB's used.
Cabling is done from IDP to DCDPs and DCDPs to individual suite PDPs,
IOP-PDP, invertors, emergency light etc as shown in Fig. 10.7 (b) and 10.7
(c). The cable assembly details are given in Chapter 10.
INSTALLATION MANUAL 51
Chapter 4.
Cabinet Installation
5.1. INTRODUCTION
This chapter gives details on unpacking, mounting and levelling a cabinet on a
Basemount. The material and tools required for the purpose along with the
procedure for ganging two cabinets is also explained.
2. Pen Knife 1
(MAM-AXCBZ039-401)
7. M6 Nut Driver 1
INSTALLATION MANUAL 53
Chapter 5.
3. Liner 4, MPI-WKSTZ138-401 3
4. Liner 5, MPI-WKSTZ139-401 3
5. Liner 6, MPI-WKSTZ140-401 3
6. Spirit Level 1
4. Ganging Panel 1
(MPM-AXCBZ098-201)
7. Ganging Bracket-2 2
(MPM-AXCBZ097-401)
8. Ganging Bracket – 1 2
(MPM-AXCBZ096-401)
INSTALLATION MANUAL 55
Chapter 5.
INSTALLATION MANUAL 57
Chapter 5.
INSTALLATION MANUAL 59
Chapter 5.
INSTALLATION MANUAL 61
Chapter 5.
MDF Installation
6.1. INTRODUCTION
The MDF for Multi module exchange is quite different from that of SBM RAX
exchange. The SBM RAX MDF is wall mountable and requires little support from
floor. MBM MDF does not require any wall support and is fixed on the floor. This
should be installed near the cable chamber where the underground cables are
coming. A trench is provided in the cable chamber where these cables enter. These
underground cables are jelly filled cables. These cables can be terminated on the
line side of the MDF directly. But care should be taken that they are terminated on
backmount frames from bottom to top. If the jelly filled cables are not to be
terminated directly on the MDF then through a cable joint these cables can be
converted to switch board cables of 100 pair each. This jointing is done in the trench
provided in the cable chamber. The trench portion can then be covered with wooden
planks. This MDF is in the form of verticals having backmount frames on both
sides, one for exchange side and the other for line side. This MDF is supplied in
multiples of 5 verticals. The no. of verticals to be installed depends upon the line
capacity of the exchange. The width of the MDF is fixed whereas length depends
upon the number of verticals supplied.
Note : Installation of C-DOT designed MDF only is explained in brief in this
Chapter. In case it is other than C-DOT design the corresponding MDF
installation manual supplied alongwith the MDF shall be referred for
installation of the MDF.
6.2. MARKING
Suppose 10 verticals are to be installed. Draw a line at a distance of 200 mm from
the holes from where the cables will be leading in for termination on the verticals of
the MDF. The length of this line should be 2498 mm (10 verticals). Mark 4 points
at a distance of 260 mm, 1010 mm, 1509 mm, 2259 mm as shown in Fig. 6.1 (a).
These points are for fixing of expansion bolts.
INSTALLATION MANUAL 63
Chapter 6.
INSTALLATION MANUAL 65
Chapter 6.
Fix Long prop. assy (item 4) on both ends of BTM section Assy-5 (item 1) with the
help of a Hex bolt (item 22) and lock washer (item 23). This is shown in detail C of
fig. 6.3. Now fix cable support assy (item 2) to the long prop. assy (item 4) using Hex
bolt (item 26), lock washer (item 27) Hex nut (item 28), lock washer (item 23) Fig.
6.2 (detail b). Now this support assy (item 3) is to be provided support at both ends.
For this fix leg (item 12) and Angle brace (item 13) with the help of Hex bolt (item
22) lock washer (item 23) and Hex nut (item 24). The brace angle is to be fixed to
the floor also with the help of expansion bolt (M6x65). So mark the drilling points.
Make the holes and fix the expansion bolts after drilling of holes. For this support
assy may have to be removed temporarily for drilling of holes. Refer Fig. 6.2 (detail
a). Short prop. assy (item 5) is to be fixed with BTM section assy - 5 (item 1) using
Hex bolt (item 22) lock washer (item 23) and Hex nut (item 24) as shown in Fig.
6.4 (detail e). Top ends of these three short prop. assy (item 5) are provided a
support by angle section-5 (item 8). This is fixed with long & short prop. assy using
Hex bolt (item 22) lock washer (item 23) and Hex nut (item 24) as shown in fig. 6.4.
Angle long (item 10) is to be fixed with cable support assy (item 2) and support assy
(item 3) using Hex bolt (item 26), lock washer (item 27) and Hex nut (item 28) as
shown in Fig. 6.5.
Cross member assy (item 6) passing through long prop. assy (item 4) is fixed onto
Angle long (item 10) using cheese head screw (item 29) lock washer (item 32) and
Hex nut (item 33).
Similarly cross member assy (item 6) passing through short prop. assy (item 5) is
fixed onto Angle short (item 9) using cheese head screw (item 29) lock washer
(item 32) and Hex nut (item 33). Refer fig. 6.6. Strip-5 (item 11) is to be joined with
cross member assy (item 6) using counter sunk screw. Similarly Horizontal Angle -
5 (item 14) is joined onto cross member assy (item 6) using counter sunk screw.
Refer fig. 6.7 (detail j).
Bent conduit -1 (item 17) and Bent conduit - 2 (item 18) are to be fixed onto conduit
- 4 (item 16) using hex bolt (item 25) and lock washer (item 27). Then this assembly
is joined onto support (item 3) using Hex bolt (item 26) and lock washer (item 27),
Refer Fig. 6.8. Top angle section - 5 (item 21) and clamp (item 20) are to be fixed
onto long prop assy (item 4) using Hex bolt (item 26), lock washer (item 27) and Hex
nut (item 28) as shown in Fig. 6.9.
Backmount frame - 11 is fixed onto Angle short (item 9) and Angle Long (item 10)
using cheese head screw, lock washer and Hex nut. Backmount frame - 9 is fixed
onto horizontal angle - 5 (item 14) with the help of cheese head screw, lock washer
and Hex nut.
For expanding MDF capacity, another similar structure for 5 verticals is to be
added using Fish plate - 1 (item 9) and Fish Plate-2 (item 17).
INSTALLATION MANUAL 67
Chapter 6.
INSTALLATION MANUAL 69
Chapter 6.
INSTALLATION MANUAL 71
Chapter 6.
INSTALLATION MANUAL 73
Chapter 6.
INSTALLATION MANUAL 75
Chapter 6.
INSTALLATION MANUAL 77
Chapter 7.
7.1. INTRODUCTION
IOPs are placed in IOP Room as per the layout discussed in Fig. 1.5. The cabinet of
IOP is not fixed on the floors. The cabinet of IOP is shown in Fig. 7.1 (a). VDU
Terminals are connected to IOP for issuing commands and printer is connected to
IOP for hard copy output.
The alarm display panel is a unit which is connected to the Central Module by
means of HDLC link cable. The system is powered by tapping -48V DC supply from
the IOP Power Distribution Panel (IOP PDP) which is located in the IOP Room.
ADP is placed in Operation and Maintenance Control (OMC) Room at convenient
location (height of eye-level) on a table so that the alarm is audible/visible to the
operator. The alarms can be acknowledged by the operator by pressing the switch
`ACKNOWLEDGE' provided on the front panel of the ADP (Fig. 7.2 (a )).
It is ensured that the floor marking in IOP Room is done as per the Fig. 1.4
for the physical placement of IOP racks. Next, the IOPs are carefully placed
at the marked location.
The top cover of IOP cabinet is removed and check that all internal cables are
terminated at their proper positions. It is also ensured that the connectors
are tight and are latched properly.
Visual check is made of glass fuse and ensure that it is mounted in fuse
holder near shell connector of IOP. The rating of fuse should be 6.3 amps.
The packing material (paper) inserted in the cartridge drive for protection
during transportation is removed and it is ensured that there is no damage to
drives and front panel. The front view and rear view of IOP-VH are shown in
Fig. 7.1 (a) and 7.1 (b) respectively.
IOP basically requires four types of cables to be connected. They are `IOP -
Power Cable', ‘IOP - Terminal Cable’, ‘IOP - Printer Cable’ and IOP-HDLC
link cables. Details on these cables are given in chapter 10, sec 10.5.23,
10.6.5, 10.6.6, 10.6.1 and 10.6.2 respectively.
The panel is taken out of the wooden casing by removing the front cover.
After unpacking of the unit it is carefully examined for any breakage in the
acrylic sheet and LEDs. Check that all the keys mounted on the front panel
of ADP are not damaged i.e. permanently jammed or broken. The RESET and
ON/OFF switch mounted at the rear of the ADP are also checked for proper
functioning. The front view and rear view of MM ADP are shown in Fig. 7.2
(a) and 7.2 (b) respectively.
INSTALLATION MANUAL 79
Chapter 7.
One 11 pair cable from the High Performance Administrative Processor Unit
(HPU) of the Central Module which connects both copies of AP to the ADP is
laid. This cable placement detail is given in Chapter 10, Section 10.6.3. For
terminations at the ADP end, a 25 pin D-Type female connector is used and
at the HPU end it is two 7/2 IDC connector (enclosed in a hood).
For -48V DC supply, a 4 core single cable is connected from IOP PDP through
an MCB of 2A to the rear panel of ADP. 2 Cores of this cable are used for -
48V and 2 cores for ground. Cable details are given in Chapter 10, Section
10.5.24 on cable laying. Use Red and Yellow/Green core for ground and Blue
and Yellow for -48V.
INSTALLATION MANUAL 81
Chapter 7.
INSTALLATION MANUAL 83
Chapter 7.
8.1. INTRODUCTION
Power Distribution Panel (PDP) forms a part of Vertical Pillar Assembly in the Iron
work as shown in Fig. 8.1. PDP is used for further distributing -48V and -48V gnd to
the eight cabinets in the suite. One PDP is present in each suite. -48V is distributed
to cabinets through MCBs/Fuses which are mounted on the PDP. The indication of
the blowing of fuses/tripping of MCBs is given on Fuse Blown Indicator Card (FBI),
which is mounted on PDP. This chapter gives details regarding PDP installation
and mounting of FBI card on PDP and setting of shorting stubs on it.
It is ensured that
• All copper bars are mounted firmly,
• The fuse blocks have screws for mounting the wires,
• All the wire clamps are there,
• All the fuse holder and fuses are there and are properly fixed. The number
of fuses will depend on the configuration of the site.
The distribution of -48 volts supply from DCDP to the cabinets in suite is
done through Fuses/MCBs mounted on the PDP. Each copy of a cabinet gets
supply through an independent Fuse/MCB. The Table 8.1 mentions the
power distribution. Fig. 8.2 shows the Fuse/MCB placement.
INSTALLATION MANUAL 85
Chapter 8.
1. FBI Card 1
2. Shorting stubs 50
3. Screw-driver 1
2. Screws 4
It is ensured that no damage is occurred to LEDs and reset switches are not
stuck.
FBI card is mounted on PDP of each suite as shown in Fig. 8.2 using four
screws.
Details of connections between FBI card pins and various locations from the
suites are described in the FBI card block diagram (Fig. 8.3). From copy 0
and copy 1 of -48V GND busbars two signal cables are connected to J37 and
J39 pins respectively of the FBI card mounted on PDP. Similarly FBI card
gets the -48V in pins J41 and J43 from copy 0 -48V and copy 1 -48V busbars
respectively. Fuses F1, F3, F5, F7, F9, F11, F13 and F15 mounted on suite
PDP are connected with copy 0 -48V busbar. Power cables from F1, F3, F5,
F7, F9, F11, F13 & F15 are connected to the pins J1, J3, J5, J7, J9, J11, J13
& J15 respectively of FBI card. Similarly pins J2, J4, J6, J8 J10, J12, J14 &
J16 of FBI card are to be connected with fuses F2, F4, F6, F8, F10, F12, F14
and F16 respectively, which are connected with copy 1 -48V busbar.
Filter box sensing cables coming from cabinet-1, cabinet-2, .... Cabinet-8 are
to be connected to FBI card pin nos J21, J22 ..... J28 respectively.
FBI cards mounted on suite PDPs, DCDPs and IOP-PDP are daisy-chained to
extend alarm signal generated in the system to OMA panel (Described later
in Section 9.3.3).
TABLE 8.1
Fuse No. Fuse Rating Amps. Equipment Connected
F17 -
F18 -
Note : In case of CM cabinet the Fuse rating (i.e. F5 & F6) is 36 Amps.
For enabling the fuse blow indication some points are to be shorted with help
of shorting stubs. If these points are not shorted then the fuse blown
indication will not come. For indicating blown fuse of -48V supply to the
cabinet (copy 0 & copy 1) and filter boxes of the cabinet, four points have to
be shorted. These points are mentioned on per cabinet basis in the table
below. W`xx' indicates the position of the shorting points on the FBI cards. A
switch of FBI card is provided to enable the extension of blown fuse to
Operation & Maintenance Alarm Box. After installation, this switch should
be kept upwords to enable the OMA alarm. The same steps mentioned above
INSTALLATION MANUAL 87
Chapter 8.
TABLE 8.3
SL. No. W22 W32 W3 W4 STATE
1. Short Short Short Short Fuse F3 sensing enabled Fuse F4 sensing
enabled Filter box fuse sensing enabled for
cabinet no 2.
TABLE 8.4
SL. No. W23 W33 W5 W6 STATE
1. Short Short Short Short Fuse F5 sensing enabled Fuse F6 sensing
enabled Filter box fuse sensing enabled for
cabinet no 3.
TABLE 8.5
SL. No. W24 W34 W7 W8 STATE
TABLE 8.6
SL. No. W25 W35 W9 W10 STATE
1. Short Short Short Short Fuse F9 sensing enabled Fuse F10 sensing
enabled Filter box fuse sensing enabled for
cabinet no. 5
TABLE 8.7
SL. No. W26 W36 W11 W12 STATE
1. Short Short Short Short Fuse F11 sensing enabled Fuse F12 sensing
enabled Filter box fuse sensing enable for
cabinet no 6.
TABLE 8.8
SL. No. W27 W37 W13 W14 STATE
1. Short Short Short Short Fuse F13 sensing enabled Fuse F14 sensing
enabled Filter box fuse sensing enabled for
cabinet no 7.
TABLE 8.9
SL. No. W28 W38 W15 W16 STATE
1. Short Short Short Short Fuse F15 sensing enabled Fuse F16 sensing
enabled Filter box fuse sensing enabled for
cabinet no 8.
Three error cables are coming out from the CM cabinet and are all
terminated on FBI card. They are :
1. Copy 0 filter box and child card daisy chained error cable (coming out
as ER44).
2. Copy 1 filter box and child card daisy chaired error cable (coming out
as ER45).
3. Fan fail error (both copy 0 and copy 1) daisy chained (coming out as
ER46), which is coming from top hat of the cabinet.) (To access we have
to remove the top hat). All the above cables end in mate-n-lock
connectors thus compatible with earlier MAX-L version of connectors
used.
These three error cables are terminated on FBI card. One of them (fan
fail error cable) will go to the usual rack position for third cabinet J23.
Copy 0 filter box and child card daisy chained cable will terminate on
J29 and copy-1 filter box and child card daisy chained cable will
terminate on J30 position of the FBI card. Shorting stubs position
required for enabling alarms from J29 and J30 are given in table 8.10
and 8.11 respectively.
TABLE 8.10
SL. No. W17 W18 W29 W39
TABLE 8.11
SL. No. W19 W20 W30 W40
INSTALLATION MANUAL 89
Chapter 8.
INSTALLATION MANUAL 91
Chapter 9.
9.1. INTRODUCTION
This is a Power Distribution Panel for Input Output Processor (IOP), Alarm Display
Panel (ADP), Operation & Maintenance Alarm (OMA), Smoke Detector etc. The
isometric view of IOP-PDP is given in Fig. 9.1. It has four busbars for -48V, -48V
gnd, Digital ground and Chassis ground as shown in Fig. 9.2. Input to these busbars
is coming from DCDP1 for further distribution. It has 3 shell connectors for
supplying power to two IOPs and one ADP. Supply to these units is given through
MCB as shown in Fig. 9.2. A tag block has been provided to give supply to OMA,
Smoke detector etc. For these supplies, no fuse protection has been provided. A mini
busbar has been provided for distribution to these units. Input for this busbar is
also coming from DCDP. Internally connections have been provided between mini
busbar and the tag block. Similarly internal connections have been provided
between ground busbar and the tag block. On the top of the IOP-PDP, Fuse Blown
Indicator (FBI) card is mounted. The function of this card is to sense the presence
of -48V supply to IOPs and ADP. In case of failure of -48V supply to IOPs and ADP,
alarm signal will be extended by this card to OMA and will be displayed on FBI
card itself through an LED. This FBI card is covered with an acrylic sheet through
which the LEDs are visible.
FBI card is to be mounted on IOP-PDP for sensing fuse failure in IOP and
ADP. This FBI card extends alarm signal to the OMA panel assembly for
audio-visual display in case of any power failure in IOP & ADP. This card is
INSTALLATION MANUAL 92
IOP - PDP AND OMA INSTALLATION
INSTALLATION MANUAL 93
Chapter 9.
in daisy- chain with FBI cards of suite PDPs and DCDP. W21 to W23 and
W31 to W33 are to be shorted on FBI card according to MCBs used.
1. OMA 1
2. Screws 4
3. Wooden Plugs 4
4. Rubber Grommets 4
5. Drilling Machine 1
6. Screw-Driver 1
The OMA panel is wall mountable. The front cover of OMA panel is opened
with the help of four screws provided as shown in Fig. 9.3. Two holes are
provided on the rear side of the panel for fixing on the wall. With the help of
screws and wooden plugs the OMA panel is fixed on the wall. Another two
holes are provided to access mounting screws for tightening the screws from
the front. These holes are plugged with rubber grommets after tightening the
screws.
Whenever any fault occurs in power plant or in any of the inverters or in
switching equipments, it gets -48V GND to raise audio-visual alarm. Cables
coming from the two inverters, power plant room and IOP-PDP (FBI card
J32) are terminated on the terminal block TB1 of OMA panel. Details of
connections in OMA TB1 as per as follows:-
INSTALLATION MANUAL 95
Chapter 9.
INSTALLATION MANUAL 97
Chapter 9.
10.1. INTRODUCTION
In this chapter preparation of various types of cables at site are discussed. Certain
cables are prepared in the factory for which the length is known. Following type of
cables which need to be prepared at site are covered in this chapter :
i) Ground cables,
ii) DC cables,
iii) Signal cables,
iv) MDF cables.
CABLE PART NO. : This number gives the type of cable used.
CABLE MARKER NO. : This number is given to the cable which gives
an identity to the cable.
SOURCE TERMINATION PART NO. : This number gives the detail of the termination
arrangement used at the source point.
DESTINATION TERMINATION PART : This number gives the detail of the termination
NO. arrangement used at the terminating point.
SOURCE PLACEMENT : This gives the place detail from where the cable
will start.
DESTINATION PLACEMENT : This gives the place detail where the cable will
be terminated.
The cables having common parameters are grouped together in Tabular form.
10.4.1.1.
CDOT ASSY NO : ACB-MAXLGXXX-000
Note :
XXX takes different values as depicted in Table 10.1.
Refer Fig. 10.1 (a) for block diagrams.
10.4.1.2.
CDOT ASSY NO. : ACB-MAXLGXXX-000
Note :
XXX takes different values depicted in Table 10.1.
Refer Fig. 10.1 (a) for connections.
TABLE 10.1
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE
No. NO. MARKER
2. ACB-MAXLGDS1-000 FIG. 10.2 Earth Collector Plate DCDP1 digital 240mm2 GDS1
ground bus bar
3. ACB-MAXLGDS2-000 FIG. 10.2 Earth Collector Plate DCDP2 Digital 240mm2 GDS2
ground bus bar
5. *ACB-MAXLGM01-000 FIG. 10.3 Earth Collector Plate MDF (Lines) 25mm2 GMO1
6. ACB-MAXLGM02-000 FIG. 10.3 Earth Collector Plate MDF (Trunks) 25mm2 GMO2
7. ACB-MAXLGMP1-000 FIG. 10.3 Earth Collector Plate MDF (PCM) 25mm2 GMP1
10. ACB-MAXLGCI1-000 FIG. 10.3 Earth Collector Plate IDP chassis 25mm2 GCI1
Note :
# Instead of 240mm2 cables BTC wire (19/1.8mm2) can be used.
* There will be two such cables running between Earth collector plate
and MDF (lines).
10.4.1.3.
CDOT ASSY NO. : ACB-MAXLGA01-000
Note :
1. For earthing the antistatic material a copper strip is fastened/rivetted
on bottom side of antistatic material. This strip is earthed through a
cable with 1M ohm/5W resistor.
2. If IOP and switch room antistatic flooring is not shorted through
copper strip, then two separate cables are required from earth plate for
earthing IOP and switch room floor.
Refer Fig. 10.1 (a) for connections.
10.4.1.4.
CDOT ASSY NO. : ACB-MAXLGCA1-000
10.4.2. Details of Digital & Chassis Ground Cable From DCDP to PDP/IOP-
PDP/DCDP Chassis
CDOT ASSY NO. : ACB-MAXLGXXX-000
Note :
XXX takes values as per Table 10.2.
Refer Fig. 10.1 (a) for connections.
Table 10.2
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE
No. NO. MARKER
1. ACB-MAXLGDP1-000 Fig. 10.6 DCDP1 Digital GND PDP Digital 25mm2 GDP1
Bus Bar GND Bus Bar
(Suite 1)
2. ACB-MAXLGDP2-000 Fig. 10.6 DCDP1 Digital GND PDP Digital 25mm2 GDP2
Bus Bar GND Bus Bar
(Suite 2)
3. ACB-MAXLGDP3-000 Fig. 10.6 DCDP1 Digital GND PDP Digital 25mm2 GDP3
Bus Bar GND Bus Bar
(Suite 3)
5. ACB-MAXLGDP4-000 Fig. 10.6 DCDP2 Digital GND PDP Digital 25mm2 GDP4
Bus Bar GND Bus Bar
(Suite 4)
6. ACB-MAXLGDP5-000 Fig. 10.6 DCDP2 Digital GND PDP Digital 25mm2 GDP5
Bus Bar GND Bus Bar
(Suite 5)
7. ACB-MAXLGCP1-000 Fig. 10.6 DCDP1 Chassis GND PDP Chassis 25mm2 GCP1
Bus Bar GND Bus Bar
(Suite 1)
11. ACB-MAXLGCP4-000 Fig. 10.6 DCDP2 Chassis PDP Chassis 25mm2 GCP4
GND Bus Bar GND Bus Bar
(Suite 4)
12. ACB-MAXLGCP5-000 Fig. 10.6 DCDP2 Chassis PDP Chassis 25mm2 GCP5
GND Bus Bar GND Bus Bar
(Suite 5)
10.5. DC CABLES
Fig. 10.7 (a), Fig. 10.7 (b), Fig. 10.7 (c) and Fig. 10.7 (d) show Block Diagram of DC
Power Cables.
10.5.1. Details of -48V & -48V GND DC Cable from Switching Cubicle to IDP
CDOT ASSY NO. : ACB-MAXLPPSI-000 (Blue)
ACB-MAXLPGSI-000 (Red)
DESTINATION : IDP
Note :
Three such cables (blue) for -48V and three (Red) for -48V GND will run
parallely from switching cubicle to IDP. See Fig. 10.7 (a).
OR
Two bus bars of size 100x10 mm will run parallely from switching cubicle to
IDP, each bus bar is for -48 V and -48 V GND.
Refer Fig. 10.7 (a) for block diagram.
10.5.2. Detail of -48V and -48V GND DC Cables from IDP to DCDP
CDOT ASSY NO. : ACB-MAXLPPDX-000 (Blue)
ACB-MAXLPGDX-000 (Red)
Note :
1. There can be maximum of six such cable pairs going from IDP to
DCDPs. The actual number of cables to be used will depend upon the
number of suites installed.
2. X takes values 1 and 2 for DCDP1 and DCDP2 respectively.
Refer Fig. 10.7 (a) for block diagrams.
Table 10.3
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE COLOUR
No. NO. MARKER
1. ACB-MAXLPPD1-000 Fig. 10.9 IDP -48V busbar DCDP1 -48V 240mm2 PPD1 Blue
busbar
2. ACB-MALPPD2-000 Fig. 10.9 IDP -48V busbar DCDP2 -48V 240mm2 PPD2 Blue
busbar
3. ACB-MAXLPGD1-000 Fig. 10.9 IDP -48V GND DCDP1 -48V 240mm2 PGD1 Red
busbar GND busbar
4. ACB-MAXLPGD2-000 Fig. 10.9 IDP -48V GND DCDP2 -48V 240mm2 PGD2 Red
busbar GND busbar
Note :
There can be maximum of four such cable pairs PPD1 and PGD1 to DCDP1
and PPD2 and PGD2 to DCDP2. The actual number of cables to be used will
depend upon the number of suites installed.
10.5.3. Detail of -48V & -48V GND DC Cables from DCDP1 to IOP PDP
CDOT ASSY NO. : ACB-MAXLPPM1-000 (Blue)
ACB-MAXLPPC1-000 (Blue)
ACB-MAXLPGM1-000 (Red)
Note :
Two such cables will be there - from DCDP1 for keeping redundancy. Refer
Fig. 10.7 (b) for Block Diagram.
Table 10.4
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE COLOUR
No. NO. MARKER
1. ACB-MAXLPPM1-000 Fig. 10.10 -48V DCDP1 -48V busbar 25mm2 PPM1 Blue
IOP-PDP MCB IOP-PDP
2. ACB-MAXLPPM1-000 Fig. 10.10 -48V DCDP1 -48V busbar 25mm2 PPM1 -do-
IOP-PDP MCB IOP PDP
4. ACB-MAXLPGM1-000 Fig. 10.10 -48V GND DCDP1 -48V GND bus 25mm2 PGM1 Red
busbar bar IOP PDP
5. ACB-MAXLPGM1-000 Fig. 10.10 -48V GND DCDP1 -48V GND bus 25mm2 PGM1 -do-
busbar bar IOP PDP
10.5.4. Detail of -48V and -48V GND DC Cables from DCDP to PDP
CDOT ASSY NO. : ACB-MAXLPLXX-000
ACB-MAXLPNXX-000
Note :
XX takes different values as depicted in Table 10.5.
Refer Fig. 10.7 (b) & (c) for Block Diagrams.
TABLE 10.5
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE COLOUR
No. NO. MARKER
10. ACB-MAXLPL10-000 FIG. 10.11 DCDP2 PDP (copy 1) 120mm2 PL10 Blue
-48V MCB -48V busbar
(Suite 5) Suite 5
11. ACB-MAXLPN01-000 FIG. 10.11 DCDP1 PDP (copy 0) 120mm2 PN01 Red
-48V gnd busbar -48V gnd busbar
Suite 1
12. ACB-MAXLPN02-000 FIG. 10.11 DCDP1 PDP (copy 1) 120mm2 PN02 Red
-48V gnd busbar -48V gnd busbar
Suite 1
13. ACB-MAXLPN03-000 FIG. 10.11 DCDP1 PDP (copy 0) 120mm2 PN03 Red
-48V gnd busbar -48V gnd busbar
Suite 2
14. ACB-MAXLPN04-000 FIG. 10.11 DCDP1 PDP (copy 1) 120mm2 PN04 Red
-48V gnd busbar -48V gnd busbar
Suite 2
15. ACB-MAXLPN05-000 FIG. 10.11 DCDP1 PDP (copy 0) 120mm2 PN05 Red
-48V gnd busbar -48V gnd busbar
Suite 3
16. ACB-MAXLPN06-000 FIG. 10.11 DCDP1 PDP (copy 1) 120mm2 PN06 Red
-48V gnd busbar -48V gnd busbar
17. ACB-MAXLPN07-000 FIG. 10.11 DCDP2 PDP (copy 0) 120mm2 PN07 Red
-48V gnd busbar -48V gnd busbar
Suite 4
19. ACB-MAXLPN09-000 FIG. 10.11 DCDP2 PDP (copy 0) 120mm2 PN09 Red
-48V gnd busbar -48V gnd busbar
Suite 5
20. ACB-MAXLPN10-000 FIG. 10.11 DCDP2 PDP (copy 1) 120mm2 PN10 Red
-48V gnd busbar -48V gnd busbar
Suite 5
Note :
-48V GND busbar at DCDPs has provision to terminate cable on both sides,
front as well as back. Copy 0 terminations of PDP are taken from front side
and copy 1 terminations of PDP from back side for each suite.
10.5.5. Detail of -48V and -48V GND DC Cables from DCDPs to Invertor
CDOT ASSY NO. : ACB-MAXLPPIX-000
ACB-MAXLPGIX-000
Note :
X takes different values as depicted in Table 10.6.
Refer Fig. 10.7 (b) and (c) for inverter connections.
TABLE 10.6
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE COLOUR
No. NO. MARKER
Note :
1. XX takes different values as depicted in Table 10.7.
2. Refer Fig. 10.7 (d) for Block Diagram.
TABLE 10.7
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE LENGTH
No. NO. MARKER mm
1. ACB-MAXLPG01-000 FIG. 10.13 PDP GND Cabinet 1 (copy 16mm2 PG01 985
0) Red busbar
2. ACB-MAXLPG03-000 FIG. 10.13 PDP GND Cabinet 2 (copy 16mm2 PG03 2410
0) Red busbar
3. ACB-MAXLPG05-000 FIG. 10.13 PDP GND Cabinet 3 (copy 16mm2 PG05 3410
0) Red busbar
4. ACB-MAXLPG07-000 FIG. 10.13 PDP GND Cabinet 4 (copy 16mm2 PG07 4415
0) Red busbar
5. ACB-MAXLPG09-000 FIG. 10.13 PDP GND Cabinet 5 (copy 16mm2 PG09 5570
0) Red busbar
6. ACB-MAXLPG11-000 FIG. 10.13 PDP GND Cabinet 6 (copy 16mm2 PG11 6700
0) Red busbar
7. ACB-MAXLPG13-000 FIG. 10.13 PDP GND Cabinet 7 (copy 16mm2 PG13 7710
0) Red busbar
8. ACB-MAXLPG15-000 FIG. 10.13 PDP GND Cabinet 8 (copy 16mm2 PG15 8680
0) Red busbar
9. ACB-MAXLPG02-000 FIG. 10.13 PDP GND Cabinet 1 (copy 16mm2 PG02 2410
1) Red busbar
10. ACB-MAXLPG04-000 FIG. 10.13 PDP GND Cabinet 2 (copy 16mm2 PG04 3470
1 ) Red busbar
11. ACB-MAXLPG06-000 FIG. 10.13 PDP GND Cabinet 3 (copy 16mm2 PG06 4430
1) Red busbar
12. ACB-MAXLPG08-000 FIG. 10.13 PDP GND Cabinet 4 (copy 16mm2 PG08 5400
1 ) Red busbar
13. ACB-MAXLPG10-000 FIG. 10.13 PDP GND Cabinet 5 (copy 16mm2 PG10 6755
1) Red busbar
14. ACB-MAXLPG12-000 FIG. 10.13 PDP GND Cabinet 6 (copy 16mm2 PG12 7710
1) Red busbar
15. ACB-MAXLPG14-000 FIG. 10.13 PDP GND Cabinet 7 (copy 16mm2 PG14 8760
1) Red busbar
16. ACB-MAXLPG16-000 FIG. 10.13 PDP GND Cabinet 8 (copy 16mm2 PG16 9560
1) Red busbar
Note :
1. Similar cables for other suites.
10.5.7.(a) Detail of -48V DC Cables from PDP to Cabinets and FBI Card
CDOT ASSY NO. : ACB-MAXLPPXX-000
Note :
XX takes different values as depicted in Table 10.8 (a)
Refer Fig. 10.7 (d) for block diagram.
1. ACB-MAXLPP01-000 FIG. 10.14 (a) PDP fuse Cabinet 1 (copy 16mm2 PP01 1130
F1 0) Blue Busbar
FBI Card J1 1mm2 FP01 1200
2. ACB-MAXLPP03-000 FIG. 10.14 (a) PDP fuse Cabinet 2 (copy 16mm2 PP03 2650
F3 0) Blue Busbar
FBI Card J3 1mm2 FP03 1200
3. ACB-MAXLPP05-000 FIG. 10.14 (a) PDP fuse Cabinet 3 (copy 16mm2 PP05 3680
F5 0) Blue Busbar
FBI Card J5 1mm2 FP05 1200
4. ACB-MAXLPP07- 000 FIG. 10.14 (a) PDP fuse Cabinet 4 (copy 16mm2 PP07 4705
F7 0) Blue Busbar
FBI Card J7 1mm2 FP07 1200
5. ACB-MAXLPP09-000 FIG. 10.14 (a) PDP fuse Cabinet 5 (copy 16mm2 PP09 5870
F9 0) Blue Busbar
FBI Card J9 1mm2 FP09 1200
6. ACB-MAXLPP11-000 FIG. 10.14 (a) PDP fuse Cabinet 6 (copy 16mm2 PP11 6990
F11 0) Blue Busbar
FBI Card J11 1mm2 FP11 1200
7. ACB-MAXLPP13-000 FIG. 10.14 (a) PDP fuse Cabinet 7 (copy 16mm2 PP13 8075
F13 0) Blue Busbar
FBI Card J13 1mm2 FP13 1200
8. ACB-MAXLPP15-000 FIG. 10.14 (a) PDP fuse Cabinet 8 (copy 16mm2 PP15 9055
F15 0) Blue Busbar
FBI Card J15 1mm2 FP15 1200
9. ACB-MAXLPP02-000 FIG. 10.14 (a) PDP fuse Cabinet 1 (copy 16mm2 PP02 2830
F2 1) Blue Busbar
FBI Card J2 1mm2 FP02 1200
10. ACB-MAXLPP04-000 FIG. 10.14 (a) PDP fuse Cabinet 2 (copy 16mm2 PP04 3840
F4 1) Blue Busbar
FBI Card J4 1mm2 FP04 1200
11. ACB-MAXLPP06-000 FIG. 10.14 (a) PDP fuse Cabinet 3 (copy 16mm 2 PP06 4815
F6 1) Blue Busbar
FBI Card J6 1mm 2 FP06 1200
12. ACB-MAXLPP08-000 FIG. 10.14 (a) PDP fuse Cabinet 4 (copy 16mm2 PP08 5830
F8 1) Blue Busbar
FBI Card J8 1mm2 FP08 1200
13. ACB-MAXLPP10-000 FIG. 10.14 (a) PDP fuse Cabinet 5 (copy 16mm2 PP10 7190
F10 1) Blue Busbar
FBI Card J10 1mm2 FP10 1200
14. ACB-MAXLPP12-000 FIG. 10.14 (a) PDP fuse Cabinet 6 (copy 16mm2 PP12 8160
F12 1) Blue Busbar
FBI Card J12 1mm2 FP12 1200
15. ACB-MAXLPP14-000 FIG. 10.14 (a) PDP fuse Cabinet 7 (copy 16mm2 PP14 9245
F14 1) Blue Busbar
FBI Card J14 1mm2 FP14 1200
16. ACB-MAXLPP16-000 FIG. 10.14 (a) PDP fuse Cabinet 8 (copy 16mm2 PP16 10068
F16 1) Blue Busbar
17. ACB-MAXXFP17-000 FIG. 10.14 (b) Copy 0 busbar of FBI card J17 2.5mm2 FP17 3700
CM cabinet
18. ACB-MAXXFP19-000 FIG. 10.14 (b) Copy 0 busbar of FBI card J19 2.5mm2 FP19 3700
CM cabinet
19. ACB-MAXXFP18-000 FIG. 10.14 (b) Copy 1 busbar of FBI card J18 2.5mm2 FP18 4700
CM cabinet
20. ACB-MAXXFP20-000 FIG. 10.14 (b) Copy 1 busbar of FBI card J20 2.5mm2 FP20 4700
CM cabinet
Note :
XX takes values 17 t0 20 shown in Table 10.8 (a).
10.5.7 (c) Detail of Cables from MCBs of DCDP to FBI Card (for Sensing MCB's
Failure)
CDOT ASSY NO. : ACB-MAXLDFXX-000
Note :
XX takes different values as depicted in Table 10.8 (b).
10.5.7 (d) Detail of Cable from IOP-VH to FBI Card (IOP-PDP) (for Sensing
IOP-ERROR)
CDOT ASSY NO. : ACB-MAXLIERX-000
Note :
i) X takes values 0 for IOP-0 1 for IOP-1
ii) In IOP-VH it is to be ensured that the pins C28 and C32 of power
connector are shorted to enable this alarm if already not done.
For DCDP1
10. ACB-MAXLDF20-000 IOP PDP copy 1 FBI card J10 DF20 2800mm
MCB
For DCDP2
Note :
XX takes different values as depicted in Table 10.9.
Refer Fig. 10.1 (b) for block diagram.
TABLE 10.9
SL. C-DOT ASSY NO DRAWING FROM TO SIZE CABLE LENGTH
No. NO. MARKER mm
1. ACB-MAXLPD01-00 FIG. 10.15 PDP (Digital Cabinet 1 (copy 10mm2 PD01 2350
earth) 0) Black Busbar
2. ACB-MAXLPD02-00 FIG. 10.15 PDP (Digital Cabinet 2 (copy 10mm2 PD02 3780
earth) 0) Black Busbar
3. ACB-MAXLPD03-00 FIG. 10.15 PDP (Digital Cabinet 3 (copy 10mm2 PD03 4780
earth) 0) Black Busbar
4. ACB-MAXLPD04-00 FIG. 10.15 PDP (Digital Cabinet 4 (copy 10mm2 PD04 5780
earth) 0) Black Busbar
5. ACB-MAXLPD05-00 FIG. 10.15 PDP (Digital Cabinet 5 (copy 10mm2 PD05 6940
earth) 0) Black Busbar
6. ACB-MAXLPD06-00 FIG. 10.15 PDP (Digital Cabinet 6 (copy 10mm2 PD06 8070
earth) 0) Black Busbar
7. ACB-MAXLPD07-00 FIG. 10.15 PDP (Digital Cabinet 7 (copy 10mm2 PD07 9080
earth) 0) Black Busbar
8. ACB-MAXLPD08-00 FIG. 10.15 PDP (Digital Cabinet 8 (copy 10mm2 PD08 10050
earth) 0) Black Busbar
9. ACB-MAXLPD09-00 FIG. 10.15 PDP (Digital Cabinet 3 (copy 10mm2 PD09 5780
earth) 1) Black Busbar
Note :
1. Similar cables for other suites.
2. Item No. 9 is required in case of CM cabinet only.
Note :
XX takes different values as depicted in Table 10.10.
Refer Fig. 10.1 (b) for block diagram.
TABLE 10.10
SL. C-DOT ASSY NO FROM TO CABLE CABLE
No. MARKER LENGTH
Note :
Similar cables for other suites.
10.5.10. Detail of Cables from Cabinet (Filter box) Copy 0 to FBI Card (for
Sensing Filter box Fuses)
CDOT ASSY NO. : ACB-MAXLFFXX-000
Note :
XX takes different values as depicted in Table 10.11.
TABLE 10.11
SL. C-DOT ASSY NO FROM TO CABLE CABLE
No. MARKER LENGTH
Note :
1. Similar cables (except FF09, FF10) for other suites.
2. FF09 & FF10 cables will come into picture; if CM cabinet comes to the
suit.
3. In the suite, where CM cabinet is installed, the FF03 cable from FBI
card J23 will be terminated to Fan error signal point as mentioned in
Table 10.41. S.No. 44 to 46 (ER44 to ER46).
10.5.11. Detail of Cable from Copy0 Filter Box to Copy1 Filter Box for
Interconnecting Both Copies in a Cabinet
CDOT ASSY NO. : ACB-MAXLFI01-000
ASSEMBLY PROCEDURE : -
Note :
1. Similar cable is used for all the cabinets in all Suites. 8 Cables are
required for each suite except in CM cabinet.
2. Filter box cabling is done by the manufacturer now a days i.e. wired
cabinets are coming, these cabling are not done on site.
10.5.12. Detail of Cable from Copy-1 -48V GND Busbar to Copy1 Filter Box
(Frame 1)
CDOT ASSY NO. : ACB-MAXLFG01-000
ASSEMBLY PROCEDURE : -
Note :
1. Similar cable is used for all the cabinets in all Suites. 8 such cables are
required per suite except CM cabinet.
2. These cablings are done by the manufacturer i.e. wired cabinets are
received from the manufacturer, nothing is to be done on site.
10.5.13. (a) Details of Cable used for Supplying -48V From Suite PDP to FBI
Card
CDOT ASSY NO. : CB-MAXLPPUX-000
Note :
X takes different values as depicted in Table 10.12. (a).
Similar cables are used for all the five suites.
TABLE 10.12 (a)
Sl. No. CDOT Assy. No. From To Cable Marker
10.5.13 (b) Detail of -48V GND Cable from Suite PDP to FBI Card (Suite) (Supply
of FBI Card)
CDOT ASSY NO. : ACB-MAXLPGUX-000
Note :
Similar cables are used in all the five suites.
Refer Fig. 10.7 (d) for connections.
10.5.14. Cable used for Supplying -48V & -48V GND from DCDP to FBI Card
of DCDP
CDOT ASSY NO. : ACB-MAXLDPUX-000
ACB-MAXLDGUX-000
Note :
X takes different values as depicted in Table 10.13.
TABLE 10.13
SL. No. C-DOT ASSY NO FROM TO CABLE COLOUR CABLE
MARKER LENGTH
10.5.15. Details of -48V DC Cables from IOP-PDP to IOP PDP FBI Card
CDOT ASSY NO. : ACB-MAXLPPVX-000
CABLE LENGTH : 75 cm
10.5.16. Details of –48V GND Cables from IOP PDP to IOP PDP FBI Card
CDOT ASSY NO. : ACB-MAXLPGVX-000
CABLE LENGTH : 85 cm
Note :
X takes values as per table 10.14.
Refer Fig. 9.4 for connections.
TABLE 10.14
Sl. No. CDOT Assy. No. From To Cable Marker
Note :
Cable corresponding to DCDP2 is not required if DCDP2 is not used.
10.5.18. (a ) Detail of Cable from FBI Card (Suite PDP) to Suite Alarm
CDOT ASSY NO. : ACB-MAXLPXXX-000
Note
1. The cables are on per suite basis.
2. XXX takes values as per Table 10.15 (a).
TABLE 10.15 (a)
SL. C-DOT ASSY NO FROM TO CABLE UNIT CABLE
No. COLOUR MARKER
10.5.18 (b) Detail of Cable from FBI Card (DCDP) to Suite Alarm
CDOT ASSY NO. : ACB-MAXLDXXX-000
Note
1. XXX takes values as per Table 10.15 (b).
TABLE 10.15 (b)
SL. C-DOT ASSY NO FROM TO CABLE UNIT CABLE
No. COLOUR MARKER
10.5.19. Detail of -48V & -48V GND Cable from IOP-PDP to OMA Panel
CDOT ASSY NO. : ACB-MAXLPMP1-000 (Blue)
ACB-MAXLPMG1-000 (Red)
ASSEMBLY PROCEDURE : -
Refer Fig. 10.1 (c) and 10.7 (e) for block diagram.
ASSEMBLY PROCEDURE : --
ASSEMBLY PROCEDURE : -
Note :
XX can vary from 01 to 03.
TABLE 10.16
S.NO. CDOT ASSY NO. FROM TO CABLE
MARKER
ASSEMBLY PROCEDURE : -
ASSEMBLY PROCEDURE : -
TABLE 10.17
Sl. No. CDOT Assy. No. From To Cable Marker
ASSEMBLY PROCEDURE : -
CONNECTIVITY CONDUCTOR :
ALIGNMENT
Note :
XX takes values as per table 10.18
Refer Fig. 10.32 for block diagram.
TABLE 10.18
Sl. No. CDOT Assy. No. From To Cable
Marker
CONNECTIVITY CONDUCTOR :
ALIGNMENT
SOURCE PLACEMENT :
Note :
1. ZZ takes different values as listed in Table 10.19.
2. If cable length of terminal is exceeding 25 meters then terminal access
will be through ACIA driver/receiver. The part code of ACIA
driver/receiver is ACP-LD08001D-000.
\DESIGN\DSSMAX\MAX-XL\MAX-XLIM\MXI-IPTC
TABLE 10.19
SL. NO. C-DOT ASSY NO FROM TO CABLE
MARKER NO
Note :
X takes different values as depicted in Table 10.20.
TABLE 10.20
SL. NO. C-DOT ASSY NO FROM TO CABLE
MARKER NO.
\DESIGN\DSSMAX\MAX-XL\MAX-XLIM\MXI-IPPC
Note :
YY takes different values as depicted in Table 10.21.
This cable is only for Analog BMs.
Refer Fig. 10.43 for cable routing.
TABLE 10.21
SL. No. C-DOT ASSY NO CABLE FROM TO REMARKS CABLE
MARKER NO. X/P/Q/R/S/T X/P/Q/R/S/T LENGHT
Note :
Connector insertion position indicated as X/P/Q/R/S/T
X = BM number
P = Rack number (1-3)
Q = Frame/Card cage no. (1-6)
R = Slot no. (1-26)
S = Connector row number (A, B)
T = Position on connector (1-4) (Also indicates polarisation tab to be
retained on the connector)
Note : X can take values 1 to 32.
Modification in Test Access Cable routing and placement in case of
Digital Trunk Terminal Unit (DTU/ISTU/CCS7 UNIT) :
a) If principal TU is DTU/CSU then concerned TA cable is not at all
required as there would not be any analog trunks in this ITU.
Also note that test access cable does not get inserted on the 2nd slot of
the motherboard at all if the terminal unit happens to be a Digital
Trunk Unit (DTU/CCS7 UNIT).
b) If principal TU is ISTU, then concerned TA cable has to be put in the
position J1/4 connector.
Note :
1. YY takes different values as depicted in Table 10.22.
2. For each Base Module and its corresponding Line Module, a set of 48
concentration cables TL01 to TL48 will be required.
3. Concentration is not provided in Trunk Base Modules.
Refer Fig. 10.44 (b) for cable routing.
TABLE 10.22
SL. No. C-DOT ASSY NO CABLE FROM TO REMARKS
MARKER NO. X/P/Q/R/S/T X/P/Q/R/S/T
Note :
Connector insertion position indicated as X/P/Q/R/S/T
X = BM number
P = Rack number (1-3)
Q = Frame/Card cage no. (1-6)
R = Slot no. (1-26)
S = Connector row number (A,B)
T = Position on connector (1-4) (Also indicates polarisation tab to be
retained on the connector)
Note :
X takes values from 1 to 32.
TABLE 10.23
BUS0 (BTU0)
Sl. No. Cable No. (BDXX) Source (CM Side) Destination (BM Side)
Frame No. : 1 Frame No. : 6
BM No.
BM No.
Table 10.24
BM-CM CLOCK CABLES
BUS0 (BTU0)
Sl. No. Cable No. (BDXX) Source (CM Side) Destination (BM Side)
Frame No. :1 Frame No. :6
Slot No. : 12
Slot Connector
Connector : B
No. B Tab Position :1
Tab Position
BM No.
1. BC01 5 B3 1
2. BC03 5 B4 2
3. BC05 6 B3 3
4. BC07 6 B4 4
5. BC09 7 B3 5
6. BC11 7 B4 6
7. BC13 8 B3 7
8. BC15 8 B4 8
9. BC17 9 B3 9
10. BC19 9 B4 10
11. BC21 10 B3 11
12. BC23 10 B4 12
13. BC25 11 B3 13
14. BC27 11 B4 14
15. BC29 12 B3 15
16. BC31 12 B4 16
17. BC33 15 B3 17
18. BC35 15 B4 18
19. BC37 16 B3 19
20. BC39 16 B4 20
21. BC41 17 B3 21
22. BC43 17 B4 22
23. BC45 18 B3 23
24. BC47 18 B4 24
25. BC49 19 B3 25
26. BC51 19 B4 26
27. BC53 20 B3 27
28. BC55 20 B4 28
29. BC57 21 B3 29
30. BC59 21 B4 30
31. BC61 22 B3 31
32. BC63 22 B4 32
BUS1 (BTU1)
Sl. No. Cable No. (BDXX) Source (CM Side) Destination (BM Side)
Frame No. :1 Frame No. :6
Slot Connector Slot No. : 12
No. B Connector : B
Tab Position Tab Position :1
BM No.
1. BD02 5 B3 1
2. BD04 5 B4 2
3. BD06 6 B3 3
4. BD08 6 B4 4
5. BD10 7 B3 5
6. BD12 7 B4 6
7. BD14 8 B3 7
8. BD16 8 B4 8
9. BD18 9 B3 9
10. BD20 9 B4 10
11. BD22 10 B3 11
12. BD24 10 B4 12
13. BD26 11 B3 13
14. BD28 11 B4 14
15. BD30 12 B3 15
16. BD32 12 B4 16
17. BD34 15 B3 17
18. BD36 15 B4 18
19. BD38 16 B3 19
20. BD40 16 B4 20
21. BD42 17 B3 21
22. BD44 17 B4 22
23. BD46 18 B3 23
24. BD48 18 B4 24
25. BD50 19 B3 25
26. BD52 19 B4 26
27. BD54 20 B3 27
28. BD56 20 B4 28
29. BD58 21 B3 29
30. BD60 21 B4 30
31. BD62 22 B3 31
32. BD64 22 B4 32
For each RSU, eight digital Trunk cables (4 for bus-0 and 4 for bus-1) are
required on CM-XL side and cables in each bus are tied together as shown in
Fig. 10.47 (a) and 10.47 (b). These cables are required only when RSUs are to
be parented to MAX-XL.
10.6.11.1. Detail of Digital Trunk Cable (For RSU Link)
C-DOT ASSY NO. : ACB-MAXRMDXX-000
Note :
* The exact length of the digital cable from exchange to MDF is site
dependent. Care should be taken so that total length of the cable from
exchange to first repeater position should not exceed more than
hundred metres.
# These parts are required to be connected as shown in Fig. 10.47 (a) &
10.47 (b).
Connections for Digital Trunk Cable CM-XL end (using 4 pair cable)
Table 10.25
Cable No.'s for Different RBM No.'s
RBM No. uu vv xx yy
02 01 02 03 04
04 05 06 07 08
06 09 10 11 12
08 13 14 15 16
10 17 18 19 20
12 21 22 23 24
14 25 26 27 28
16 29 30 31 32
18 33 34 35 36
20 37 38 39 40
22 41 42 43 44
24 45 46 47 48
26 49 50 51 52
28 53 54 55 56
30 57 58 59 60
32 61 62 63 64
Table 10.26
Module No. Pin No. `A' `B' `C'
Note :
i) For the values of uu, vv, xx and yy for different BMs please see table
No. 10.25.
() indicates cable number
[] indicates corresponding cable colour pair
Bl : Blue
O : Orange
G : Green
Br : Brown
2) This cable assembly procedure is given in detail in RSU installation
manual also.
In CM-XL, there can be maximum three Reference Clock input per copy of
NSC. Clock is extended from DTS card (which is connected to a working PCM
stream connected to exchange supply of Reference Clock) and given to each
copy of NSC by splitting at the CM end. Corresponding DTS slots on DTU
mother board should be assembled with shrouds, latch frames and latches at
site.
Detail of Reference Clock Cable
C-DOT ASSY. NO. : ACB-NSCERCKN-000
N VARIES FROM 0 TO 2
\DESIGN\DSSMAX\MAX-XL\MAX-XLIM\MXI-RCC
\DESIGN\DSSMAX\MAX-XL\MAX-XLIM\MXI-RCCC
Note :
See Fig. 10.47 (c) & 10.47 (d)
In this section all the internal cables of CM-XL are briefly covered as
assembly of these cables are done and routed within CM-XL at factory.
Number of cables for each type is given in tables 10.27 to 10.43 and the
routing diagrams for these cables are given in figures 10.48 to 10.62. For
assembly of these CM-XL Internal Cables, Assembly Instructions and
corresponding drawings supplied alongwith system engineering documents
shall be referred.
ADDRESS, DATA & CONTROL BUS CABLE ROUTING
TABLE 10.27
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/
CONNECTOR CONNECTOR
Note :
See Fig. 10.48 for Cable routing.
TABLE 10.28
CHASSIS GND CABLE ROUTING
SL. No. CABLE NO. CABLE PART NUMBER SOURCE DESTINATION LENGTH REMARKS
PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMB POSITION/NUMBER
ER
Note :
CF/1/S/-/03 - Screw 3 of Card frame 1
1/--/FT/-/01 - Fast-on-tab 1 of frame 1
See Fig. 10.49 for Cable routing.
TABLE 10.29
16 MHz CLOCK CABLES ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/SLOT/
CONNECTOR CONNECTOR/
POSITION/NUMBER
TABLE 10.30
DIRECT LINK CABLE ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT IN
FRAME/ FRAME/ CENTI-
CONNECTOR CONNECTOR METERS
TABLE 10.31
EXCHANGE BUS CABLE ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
1 EB01 ACB-CMXLEB01-000 2/05/J/-/03 3/05/J/-/01 30 Cms.
TABLE 10.32
ERROR & CONTROL CABLE ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
1 EC01 ACB-CMXLEC01-000 2/02/A/4/- 1/02/B/2/- 75 Cms. Coding to be
retained
according to
position
marked
2 EC02 ACB-CMXLEC02-000 2/02/A/3/- 1/02/B/1/- 80 Cms.
3 EC03 ACB-CMXLEC03-000 2/02/A/2/- 1/02/A/2/- 89 Cms.
4 EC04 ACB-CMXLEC04-000 2/02/A/1/- 1/02/A/1/- 92 Cms.
5 EC05 ACB-CMXLEC05-000 2/26/A/4/- 1/26/B/4/- 64 Cms.
6 EC06 ACB-CMXLEC06-000 2/26/A/3/- 1/26/B/3/- 66 Cms.
7 EC07 ACB-CMXLEC07-000 2/26/A/2/- 1/26/A/4/- 85 Cms.
8 EC08 ACB-CMXLEC08-000 2/26/A/1/- 1/26/A/3/- 82 Cms.
9 EC09 ACB-CMXLEC09-000 2/02/B/4/- 1/26/A/2/- 144 Cms.
10 EC10 ACB-CMXLEC10-000 2/02/B/3/- 1/26/A/1/- 150 Cms.
11 EC11 ACB-CMXLEC11-000 2/02/B/2/- 1/26/B/2/- 136 Cms.
12 EC12 ACB-CMXLEC12-000 2/02/B/1/- 1/26/B/1/- 142 Cms.
13 EC13 ACB-CMXLEC13-000 2/26/B/4/- 1/02/A/4/- 140 Cms.
14 EC14 ACB-CMXLEC14-000 2/26/B/3/- 1/02/A/3/- 144 Cms.
15 EC15 ACB-CMXLEC15-000 2/26/B/2/- 1/02/B/4/- 132 Cms.
16 EC16 ACB-CMXLEC16-000 2/26/B/1/- 1/02/B/3/- 136 Cms.
17 EC17 ACB-CMXLEC17-000 3/02/A/4/- 4/02/B/2/- 78 Cms.
18 EC18 ACB-CMXLEC18-000 3/02/A/3/- 4/02/B/1/- 80 Cms.
19 EC19 ACB-CMXLEC19-000 3/02/A/2/- 4/02/A/2/- 94 Cms.
20 EC20 ACB-CMXLEC20-000 3/02/A/1/- 4/02/A/1/- 98 Cms.
21 EC21 ACB-CMXLEC21-000 3/26/A/4/- 4/26/B/4/- 62 Cms.
22 EC22 ACB-CMXLEC22-000 3/26/A/3/- 4/26/B/3/- 68 Cms.
23 EC23 ACB-CMXLEC23-000 3/26/A/2/- 4/26/A/4/- 82 Cms.
24 EC24 ACB-CMXLEC24-000 3/26/A/1/- 4/26/A/3/- 84 Cms.
25 EC25 ACB-CMXLEC25-000 3/02/B/4/- 4/26/A/2/- 138 Cms.
26 EC26 ACB-CMXLEC26-000 3/02/B/3/- 4/26/A/1/- 142 Cms.
27 EC27 ACB-CMXLEC27-000 3/02/B/2/- 4/26/B/2/- 130 Cms.
28 EC28 ACB-CMXLEC28-000 3/02/B/1/- 4/26/B/1/- 136 Cms.
29 EC29 ACB-CMXLEC29-000 3/26/B/4/- 4/02/A/4/- 142 Cms.
30 EC30 ACB-CMXLEC30-000 3/26/B/3/- 4/02/A/3/- 146 Cms.
31 EC31 ACB-CMXLEC31-000 3/26/B/2/- 4/02/B/4/- 134 Cms.
32 EC32 ACB-CMXLEC32-000 3/26/B/1/- 4/02/B/3/- 138 Cms.
TABLE 10.33
ERROR CABLE ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
1 ER01 ACB-CMXLER01-000 BUS BAR (RED) 0V FB/01/J/-/02 12 Cms. All three
POSITIVE cables are of
red colour
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
TABLE 10.34
FAN ERROR CABLE ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/SLOT/
CONNECTOR CONNECTOR/
POSITION/NUMBER
1 FE01 ACB-CMXLFE01-000 6/J1 TH/FFB/J/-/01 250 Cms T- Top Flat
Assy.
Route the above cables along the side trough towards the top of the cabinet
and take a bend into the Top Panel. Then terminate the cables as per the
above table.
Note : TH/FFB/J/-/01 - Top hat Fan Failure Board Connector J1.
TABLE 10.35
FAN CABLE ROUTING
SL. No. CABLE NO. ASSEMBLED CABLE SOURCE DESTINATION LENGTH REMARKS
FAN PART NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
1 FN01 ACB-CMXLFN01-000 TH/--/FN/-/01 TH/FFB/J/-/4 30 Cms.
Note :
TH/--/FN/-/01 - Top hat Fan No.1 TH/FFB/J/-/4 - Top hat Fan Failure Board
J4 Connector REFER DOC.NO. DCM-XL0XXX00-000 (AD) UNDER
FUNCTIONAL CATEGORY FAN CABLE FOR ROUTING THE CABLES
For cable routing see Fig. 10.56
TABLE 10.36
BUS0_MUXD BUS CABLE ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/
CONNECTOR CONNECTOR
1 MB01 ACB-CMXLMB01-000 1/J4 2/J8 90 Cms. Copy 0
TABLE 10.37
SIGNAL : MESSAGE CLOCK & DATA CABLE ROUTING
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/
CONNECTOR CONNECTOR
1 MS01 ACB-CMXLMS01-001 6/J16 1/J6 240 Cms
TABLE 10.38
PSU Error Cable
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/
CONNECTOR CONNECTOR
1 PS 01 ACB-CMXLPS01-000 1/J1 1/J37 100 Cms.
TABLE 10.39
POWER CABLE ROUTING
SL. No. CABLE NO. ASSEMBLED CABLE SOURCE DESTINATION LENGTH REMARKS
FAN PART NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
1 PW01 ACB-CMXLPW01-001 FB/01/J/-/01 1/--/M/-/01 25 Cms.
2 PW02 ACB-CMXLPW02-001 FB/02/J/-/01 1/--/M/-/04 115 Cms.
3 PW03 ACB-CMXLPW03-001 FB/03/J/-/01 1/--/M/-/03 25 Cms.
4 PW04 ACB-CMXLPW04-001 FB/04/J/-/01 1/--/M/-/02 115 Cms.
5 PW05 ACB-CMXLPW05-001 FB/05/J/-/01 2/--/M/-/01 25 Cms.
6 PW06 ACB-CMXLPW06-001 FB/06/J/-/01 2/--/M/-/02 35 Cms.
7 PW07 ACB-CMXLPW07-001 FB/07/J/-/01 2/--/M/-/03 25 Cms.
8 PW08 ACB-CMXLPW08-001 FB/08/J/-/01 2/--/M/-/04 35 Cms.
9 PW09 ACB-CMXLPW09-001 FB/09/J/-/01 3/--/M/-/01 25 Cms.
10 PW10 ACB-CMXLPW10-001 FB/10/J/-/01 3/--/M/-/02 35 Cms.
11 PW11 ACB-CMXLPW11-001 FB/11/J/-/01 3/--/M/-/03 25 Cms.
12 PW12 ACB-CMXLPW12-001 FB/12/J/-/01 3/--/M/-/04 35 Cms.
13 PW13 ACB-CMXLPW13-001 FB/13/J/-/01 4/--/M/-/01 25 Cms.
14 PW14 ACB-CMXLPW14-001 FB/14/J/-/01 4/--/M/-/04 115 Cms.
15 PW15 ACB-CMXLPW15-001 FB/15/J/-/01 4/--/M/-/03 25 Cms.
16 PW16 ACB-CMXLPW16-001 FB/16/J/-/01 4/--/M/-/02 115 Cms.
17 PW17 ACB-CMXLPW17-001 FB/17/J/-/01 5/--/M/-/01 25 Cms.
18 PW18 ACB-CMXLPW18-001 FB/18/J/-/01 5/--/M/-/02 35 Cms.
19 PW19 ACB-CMXLPW19-001 FB/19/J/-/01 5/--/M/-/03 25 Cms.
20 PW20 ACB-CMXLPW20-001 FB/20/J/-/01 5/--/M/-/04 35 Cms.
21 PW21 ACB-CMXLPW21-001 FB/21/J/-/01 6/--/M/-/01 25 Cms.
22 PW22 ACB-CMXLPW22-001 FB/22/J/-/01 6/--/M/-/04 115 Cms.
23 PW23 ACB-CMXLPW23-001 FB/23/J/-/01 6/--/M/-/03 25 Cms.
24 PW24 ACB-CMXLPW24-001 FB/24/J/-/01 6/--/M/-/02 115 Cms.
25 PW25 ACB-CMXLPW25-001 C0 BUS BAR TH/FFB/J/-/02 100 Cms.
26 PW26 ACB-CMXLPW26-001 C1 BUS BAR TH/FFB/J/-/25 100 Cms.
Note :
FB/01/J/-/01 - J1 of Filter box 1 1/--/M/-/01 - M1 of Frame 1 (M.B) TH/FFB/J/-
/02 - J2 of Top hat FFB Card REFER DOC.NO. DCM-XL0XXX01-000 (AD)
UNDER FUNCTIONAL CATEGORY POWER CABLE FOR ROUTING THE
CABLES
See Fig. 10.60 (a) for cable routing.
TABLE 10.40
SIGNAL : PROCESSOR BUS CABLE
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/
CONNECTOR CONNECTOR
1 PB01 ACB-CMXLPB01-000 5/J24 2/J6 220 Cms. ADDRESS 0
TABLE 10.41
SWITCHED BUS CABLE ROUTING
SL. No. CABLE NO. ASSEMBLED CABLE SOURCE DESTINATION LENGTH REMARKS
FAN PART NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
1 SB01 ACB-CMXLSB01-000 1/05/J/-/02 2/15/J/-/02 90 Cms.
1/06/J/-/02
SL. No. CABLE NO. ASSEMBLED CABLE SOURCE DESTINATION LENGTH REMARKS
FAN PART NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
Note :
See Figs. 10.61 (a) & 10.61 (b) for Cable routing.
TABLE 10.42
SYNC RELAY CABLE
SL. No. CABLE NO. CABLE PART SOURCE DESTINATION LENGTH REMARKS
NUMBER PLACEMENT PLACEMENT
FRAME/ FRAME/
CONNECTOR CONNECTOR
1 SR01 ACB-CMXLSR01-000 2/J4 1/J16 60 Cms.
TABLE 10-43
SYSTEM SYNC CABLE ROUTING
SL. No. CABLE NO. ASSEMBLED CABLE SOURCE DESTINATION LENGTH REMARKS
FAN PART NUMBER PLACEMENT PLACEMENT
FRAME/SLOT/ FRAME/SLOT/
CONNECTOR/ CONNECTOR/
POSITION/NUMBER POSITION/NUMBER
1 SS01 ACB-CMXLSS01-000 5/J16 2/04/A/J/05 280 Cms.
ASSEMBLY PROCEDURE : --
Note :
1. NN denotes the BM number, it takes value from 1 to 32.
2. XX takes value from 1 to 4.
Note :
1. XX can takes values from 1 to 16.
2. Fig. 10.64 (a) & 10.65 (a) are for EMF cables in TU1.
3. NN denotes the BM number, it takes value from 1 to 32.
Note :
1. XX can take value from 1 to 48.
2. NN denotes the BM number.
Note :
XX can take value 01 to 8.
** The other cable unit Colour is yellow. One 24 pair cable can have two
cable units of colour white and yellow. NN denotes the BM number, it
takes value from 1 to 32.
PLACEMENT : Module 1 : 1
TAB NO. RETAINED Module 2 : 2
CONNECTIVITY CONDUCTOR : -
ALIGNMENT
Note :
1. X/P/Q/R/S/T : BM Number/Cabinet Number/Card Frame No./slot
No./Connector No./position on Connector.
2. In case of Line BM and LM, all TUs have 64 pair cables.
3. NN denotes the BM, it takes values from 1 to 32.
PLACEMENT :
TAB NO. RETAINED
CONNECTIVITY CONDUCTOR :-
ALIGNMENT
Note :
1. X/P/Q/R/S/T : BM Number/Cabinet Number/Card Frame No./slot
No./Connector No./position on Connector
2. NN denotes the BM, it takes values from 1 to 32.
\DESIGN\DSSMAX\MAX-XL\MAX-XLIM\MXI-TTCL
ASSEMBLY PROCEDURE : --
Note :
1. NN denotes the BM number, it takes value from 1 to 32.
2. XX takes value from 1 to 16.
TABLE 10.44
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
1. ACB-MAXXA001-000 A001/NN AA03 White XX/1/1/3/A/1,2
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
PI07 XX/1/1/7/A/1
PI09 XX/1/1/9/A/1
PI11 XX/1/1/11/A/1
PI21 XX/1/1/21/A/1
SL. No C-DOT ASSY NO CABLE No. CABLE UNIT CABLE UNIT SOURCE PLACEMENT
NO. COLOUR O/P/Q/R/S/T
PI23 XX/1/1/23/A/1
PI25 XX/1/1/25/A/1
PI11 XX/1/2/11/A/1
PI21 XX/1/2/21/A/1
PI23 XX/1/2/23/A/1
PI25 XX/1/2/25/A/1
PI07 XX/1/3/7/A/1
PI09 XX/1/3/9/A/1
PI11 XX/1/3/11/A/1
Note :
XX & NN denotes the BM numbers, it takes value from 1 to 32.
to right for each disconnection module and disconnection modules should grow from
bottom to top. One vertical will be able to accommodate 1000 pairs.
Note :
NN denotes BM number. It can take values from 1 to 32.
11.1. INTRODUCTION
This chapter gives the details and placement of the various fuses and MCBs in a
multimodule exchange. In CM, fuses are present in FFB, NSC and PSU-II cards
and the corresponding power line filters. In a BM, fuses are present in TTC, PSU-I,
PSU-II, TUI, TSI cards and in filter boxes of TUs, TSU and BPU. In a LM, fuses are
present in TUI and PSU-I cards and the filter boxes of TUs. In IOP input fuse is
present. In ADP fuse is present only in the power supply card. FBI cards mounted
on DCDPs, IOP-PDP and suite PDPs contain two fuses each. MCBs/HRC fuses are
located in suite PDP, IOP-PDP and DCDPs.
*@ Note
1. 36A HRC fuse will be used in case CM is present in that suite.
IOP-PDP } FBI
DCDPs }
Suite PDP }
6. 1.6 Amp Slow blow fuse BM-XL, CM-XL TSU, FFB TSI, FFB
9. 2 Amp HRC fuse Suite PDP & IOP Suite PDP &
PDP IOP-PDP
Operator Positions
(Information will be provided later)
Invertor Arrangement
13.1. INTRODUCTION
Three 1 KVA inverters are provided to meet uninterrupted AC requirements of the
VDUs (Visual Display Unit) and the printers in IOP room, OMC room and the MDF
room (Test positions). All the three inverters will be in use to meet IOP room, OMC
room and MDF room power requirements. Although no spare inverter has been
provided to handle failure of any of the inverters, the output of the three inverters
has been distributed in such a fashion that in case of failure of any of the inverters,
the other two inverters will be able to handle the total load. In OMC room 4 CRP
terminals and two printer terminals will be provided out of which two terminals
and one printer will be connected to IOP-0 and other two CRP terminals and printer
will be connected to IOP-1. In addition to that two more operator terminals (test
positions) will be provided in MDF room.
very close together such that in case any fault occurs in any inverter, terminals
supply can be tapped from adjacent DB, connected with the other inverter.
When all the three inverters are working, then the distribution of inverters to VDUs
and printers can be given as per the table 13.1. In case of failure of any one of the
inverters, supply can be trapped from the nearest inverter.
Note :
Inverters' output ground should not be extended to DBs. i.e. only line and
neutral are to be connected to VDUs and printers.
Table 13.1
Sign Writing
14.1. INTRODUCTION
A multimodule exchange has different types of cabinets (ex. Base Modules, Line
Modules and Central Module). For the purpose of easy maintenance and trouble
shooting of faults proper identification of cabinets is very much essential. Actually
this identification marking or "SIGN WRITING" has to be put at site to identify a
particular cabinet. The format used for this purpose is explained below. This is also
supported by fig. 14.1 & 14.2.
15.1. INTRODUCTION
This chapter gives details on settings of different parameters of VDU and printer.
In case VDU or printer is not functioning properly, check for these
parameters/switch setting before attempting any repair.
80 columns
Interpret controls
Auto wrap
Jump scroll
Light text, Dark screen
Intensity = 10
Cursor
Block cursor style
Time display
Status line = ON
ii) Special Set-up
/- = /
-/_ = -/_
=/+ = =/+
(x = (x
(/ ) = (/ )
,/, = ,/,
./. = ./.
CR pad off
Edit/Arrow/PF Keys Active
iii) General Set-up
Transmit = 9600
Receive = Transmit
x off at 64
8 bits, no parity
1 stop bit
No local echo
EIA port, data leads only
Disconnect, 2s delay
Limited transmit
v) Printer Set-up
Speed = 9600
Normal print mode
X off
8 bits, no parity
1 stop bit
Print full page
Print National only
No terminator
vi) Keyboard Set-up
Typewriter keys
Caps lock
F1-F5 no lock
Auto Repeat
Key click
Margin bell
Warning bell
Break
Auto Answer Back
Answer Back =
Not concealed
Note :
For tab setting, move the cursor to `Clear All Tabs' and hit `Enter' key. Then
move the cursor to `Set 8 Columns Tabs' and hit `Enter'. The first `T' should
appear at position 9 and the rest should be at intervals of 8.
2-5 UP
2-6 UP
2-7 DOWN
2-8 DOWN
Note : UP means ON
Jumper Settings
16.1. INTRODUCTION
This document describes the types of jumpers used in MAX-XL cards and the
position of required shorts.
Example :
In APC-MSC014/F-S07, W1 and W4 are two pin Jumpers
W1 - To be shorted
W4 - Not to be shorted
3 Pin Jumpers (3P)
In this type of jumper settings, there are 3 pins and the instruction required is
whether the jumper position needs to be shorted or not. If shorting is needed further
instruction should be which 2 pins (out of the total 3 pins) are required to be
shorted.
Example :
In APC-TGA077/T-S02 W1 and W2 are 3 pin jumpers.
W1 - Has to be shorted for position `bc'
W2 - Has to be shorted for position `bc'.
16.3.1. APC-ANN078/T-S03
JUMPER SHORTING POSITION
W1 Horizontal
(Lower Position)
W2 Horizontal
(Lower Position)
W3 Horizontal
(Lower Position)
16.3.2. APC-BPC441/O-S02
JUMPER POSITION REMARKS
W19 b & c or 2 & 3
W20 b & c or 2 & 3
W21 b & c or 2 & 3
W22 to W29 b & c or 2 & 3 For single ended links
16.3.3. APC-BME442/H-S02
16.3.4. APC-TIC002/F-S10
W1 should be shorted for 27C512 in U75
W1 should be left open for 27C256 in U75.
16.3.5. APC-MSC014/F-S07
To be shorted - W1
Not to be shorted - W4
16.3.6. APC-MSD013/F-S06
Grouped Jumpers
JUMPER SHORTING POSITION FIGURE
W11 A Position B A B A
o o
| |
W12 A Position o o o o
W14 BMS
16.3.7. APC-MFC043/F-S08
JUMPER SHORTING POSITION
W5 Top 1-2
W6 Right 2-3
W7 Bottom 2-3
16.3.8. APC-TGA077/T-S02
JUMPER SHORTING POSITION
W1 Horizontal
(b-c)
W2 Horizontal
(b-c)
16.3.9. APC-TSC008/F-S06
JUMPER SHORTING POSITION
W1 Middle
(A-b)
16.3.10. APC-TUI084/T-S03
JUMPER SHORTING POSITION
X = 1, 2, 3, 4
16.3.11. APC-TUC046/T-S03
JUMPER SHORTING POSITION
W2 Bottom
(b-c)
16.3.12. APC-TUB003/T-M04
JUMPER SHORTING FUNCTION
POSITION
C1 C0
W3 W1
W4 W2
16.3.13. APC-BPU438/H-M01
COPY-0
LSB
0 W13 4 W9
1 W14 5 W10
2 W15 6 W11
3 W16 7 W12
MSB
Note :
* The mentioned jumpers should be shorted
* The jumpers not mentioned to be left open
* For RBM (RSU) W12 (i.e. MSB) to be left upon.
16.3.14. APC-BPU439/H-M01
COPY-1
LSB
0 W21 4 W17
1 W22 5 W18
2 W23 6 W19
3 W24 7 W20
MSB
Note :
* The mentioned jumpers should be shorted
* The jumpers not mentioned to be left open
* For RBM (RSU) W20 (i.e. MSB) to be left open.
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\ ICC ID = C2
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
ICC ID = C4
\\\\
\\\\
\\\\
\\\\
\\\\
\\\\
Legend = Open
\\\\ = Short
\\\\
W1o o W9 o o
W2 o o W10 o o
W3 o o W11 o o
W4 o o W12 o o
W5 o o W13 o o
W6 o o W14 o o
W7 o o W15 o o
ICC ITC
16.3.16.1.a) SUM jumper-ID should be 5E (in copy0) and 5F (in copy1). Accordingly
following jumpers are to be put on the SUM motherboard.
7SU Copy0 7SU copy1
W1 Close W13 Open
W2 Open W14 Open
W3 Open W15 Open
W4 Open W16 Open
W5 Open W17 Open
W6 Close W18 Close
W7 Open W19 Open
16.3.16.2. The TUI card jumper setting will be as per the position of the SUM.
Note :
a) At present the SUM should preferably be put in principal TU.
Moreover if SUM is in BM-1, DM2 should not be an RSU.
b) It HPC is used in place of BPC in SUM then BME card jumper setting
to be as follows :
W2 & W3 should be shorted and W1, W4 to be left open.
16.4.1. APC-PSM383/F-S02
16.4.2. APC-BPC441/O-S02
16.4.3. APC-BME442/H-S02
Pin Nos. 1 & 2 of W1 and W4 are to be shorted. For BPU, SCU, HPU and
#7SU with BPC.
W2, W3 jumpers are to be left open.
Pin Nos. 1 & 2 of W2 and W3 are to be shorted for #7SU with HPC. W1 & W4
to be left open.
16.4.4. APC-CBX380/H-S01
16.4.5. APC-CCK381/F-S02
Jumpers W1, W2, W5, W7, W8, W9, W12 are to be shorted
For jumpers W1 & W2 refer figure 16.1.
16.4.11. APC-ESM397/H-S01
2 PIN JUMPERS (In all slots)
Jumpers W11, W21, W22, W24 are to be shorted. Rest of the Jumpers are to
be left open.
16.5.1. APC-VHC358/O-S00
Jumpers W13, W14, W15, W17, W18 are to be shorted. Rest of the jumpers
are to be kept open.
16.5.2. APC-VHI359/F-S00
Power-ON Procedure
17.1. INTRODUCTION
This chapter describes the power on procedure of the C-DOT MAX-XL system. This
procedure is to be followed after installation has been done as per Chapters 1 to 16
of this manual. It should be ensured that no cards are to be inserted in any of the
cabinets at this stage. MCBs or fuses at DCDPs, PDP and IOP-PDP should be in
"OFF" position and power cables should be disconnected from switching cubicle.
This activity can be sub divided into following groups in sequence.
• Visual Inspection
• Electrical Tests
• Opening the ADP back panel, visual checking is to be done on it to see whether
any damage has taken place during transportation.
• Check for the voltages -48V (Voice), - 48V (Load) and -48V(Ring) with respect to
-48V GND at the back plane and check for the polarity also.
• Switch on the supply from MCB for IOP 0 and IOP-1 at IOP- PDP.
• Switch on IOPs and check -48V LED on rear side is glowing and run LED on
front panel is blinking.
• After power-on of the system, yellow LEDs on all FBI cards (suite PDPs, DCDPs
& IOP-PDP) should glow. In suite-PDP FBI card, if any red LED glows check the
filter box daisy-chain connection upto its termination to FBI Card corresponding
to the particular BM or CM or LM. FBI Card jumper setting should be verified.
For CM, FFB on top hat jumper settings should be verified also to detect fan
failure alarm (visual) on suite PDP FBI card to which CM is connected. All fuses
on PDPs are to be checked also.
When all the electrical testings are over, start software loading as per the
procedure given in the "Exchange Operation" manual. Here data cartridge to be
used is "BARE MINIMUM DATA CARTRIDGE" supplied along with the
software deliverables.
• Do all preliminary testing of IOPs as per the "Acceptance Testing" document.
Functional Testing
18.1. INTRODUCTION
This chapter gives the functional testing procedure of the CDOT MAX-XL system.
This procedure is to be followed once installation and power-on have been completed
as per Chapters 1 to 17 of this manual. The detailed testing of MAX-XL is done in
the following order.
Software Installation on IOP
Administrative Module (AM) Testing
Space Switch Controller Unit (SCU) Testing
Bus Termination Unit (BTU) Testing
Space Switch Unit (SSU) Testing
BM Testing through CM
System Initialisation in Different Configurations
Inter BM Testing
Alarm Testing
System Stability
Load Testing
18.3. AM TESTING
18.3.1. AP Downloading
Set up
IOP-0 INS-ACT (inservice active).
Connect VDU Terminals on AP-0 and AP-1 through BP terminal cable
(Refer section 10.6.4 for details on BP terminal cable).
HPU is fully equipped but power is OFF.
ADP is connected.
18.4. AM DIAGNOSTICS
18.4.1. AP Diagnostics
Set up
IOP-0 INS-ACT.
AM is fully initialised and all units are inservice.
ADP is connected.
Set up
Same as in 18.4.1
1. Make AP-0 INS-ACT and AP-1 INS-SBY
2. Give command PUT-SWU-OOS for MU-0, alarm should appear on
ADP for AM.
3. Give command DGN-SWU for MU-0. DGN pass/fail report for MUs will
come on OOD. If DGN passes, bring MU-0 inservice by PUT-SWU-INS
command. If DGN fails take suitable action and run diagnostics again.
There should not be any alarm on ADP for AM.
4. Make MU-1 OOS-OPR
5. Repeat step 3 for MU-1
6. Interchange APs
7. Repeat steps 2 to 5 again for both copies of memories with AP-1 active.
Set up
IOP-0 is INS-ACT
AP completely initialised, its all units are inservice, AP-0 INS-ACT, AP-1
INS-SBY. All HMS cards in HPU are jacked in.
All the cards are equipped in SCU and all four PSUs are switched off
Connect VDU Terminals on both SSC controllers through BP terminal
cable.
Each SSC has links to all the four CMSs (HMSs) but AP has links only to
CMS1 and CMS2. SSC code loading take place through active AP via CMS1
or CMS2. For complete testing of SSC initialisation with active AP all the
different combinations are to be checked.
1. Switch on four PSUs of SCU and check that LEDs of all PSU's are
glowing.
2. Ensure power-on tests for SSC-0 and SSC-1 are successfully
completed.
3. Give reset on SSC-1 and make sure that SSC-0 has started code
loading. Check the message on SSC-0 terminals for both ports enabled,
i.e., it has access to both memories. Message will come as PO-1E on
SSC-0 terminal.
4. Wait for some time so that a few blocks of code is loaded i.e. 0K, 36K,
72K .....
5. Now give a reset on CMS1 card, (Refer Fig. 18.1 for identification of
switch units and corresponding physical cards) SSC-0 terminal will
print LF 66 and will continue down loading through CMS2.
6. Give reset to CMS2 now SSC-0 terminal will print LF 67 but code
loading will continue through CMS1.
7. Give a reset to SSC-0 now SSC-0 link to active AP is broken, SSC-1
will take over code load through CMS1 and CMS2. Check the message
PO-1E on SSC-1 terminal for both memory ports enabled.
8. Repeat steps 4,5,6 for checking SSC-1 down loading with both CMS1
and CMS2.
9. Give a reset to SSC-1 again, SSC-0 will take over code loading and
wait for complete code loading and SCU to come up.
10. Check the status of all units of SCU. All units of CM are SSC-0, SSC-1,
CMS1, CMS2, CMS3, CMS4, SS-0, SS-1, SSBID-0, SSBID-1,
NSC/CLK-0, NSC/CLK-1, MU-0, MU-1. Let SSC-0 be active and SSC-1
standby.
11. Make CMS2 OOS-OPR
12. Give soft start to CM, CM should come up through only available
CMS1.
13. Bring CMS2 inservice
14. Make CMS1 OOS-OPR
15. Give soft start to CM, CM should come up through only available
CMS2.
16. Bring CMS1 inservice
17. Interchange SSC
18. Repeat step 11 to 16
19. Interchange AP
20. Repeat step 3 to 18
Finally all units of AM and CM should be inservice.
Set up
IOP-0 is INS-ACT
AM, CM completely initialised and all units are inservice
1. Make SSC-0 OOS-OPR, SSC-1 INS-ACT
2. Give a command DGN-SWU for SSC-0. If diagnostics are okayed then
bring SSC-0 inservice by PUT-SWU-INS command. If diagnostics are
failed take appropriate action and give diagnostics again.
3. Interchange SSCs
4. Repeat step 1 to 3 for SSC-1.
Set up
IOP-0 is INS-ACT
AM, CM completely initialised and all units are inservice.
Same as in 18.6.1
Set up
1. Make SSC-0 INS-ACT SSC-1 INS-SBY
2. Make CLK-0 OOS-OPR, CLK-1 INS-ACT
3. Give command PUT-SWU-INS for CLK-0, if clock card does not come
up then run diagnostics on CLK-0 and take appropriate action. Run
diagnostics again if diagnostics are okayed then bring CLK-0 inservice
by put-swu-ins command.
4. Make CLK-1 OOS-OPR, CLK-0 INS-ACT
5. Repeat step 3 for CLK-1
6. Interchange SSC
7. Repeat steps 2 to 6 with SSC-1 active.
Set up
Same as in 18.6.1
1. Make SSC-0 INS-ACT, SSC-1 INS-SBY
18.7. BM EQUIPPING
Now create the data for all BMs on one IOP through EQUIP-MOD command by
using standard procedure. Procedure is given in Appendix-1.
Set up
IOP-0 is INS-ACT and data of all BMs created.
BM-CM cables are connected
1. Power on BTU and SSU. Ensure required number of IFC
(PSM/ESM) and SWC (PSS) cards are jacked in.
2. Give code load to system. System will come up with all units of
AM and CM inservice.
3. If any unit is Out Of Service (OOS) then run diagnostics for that
unit and bring it inservice by PUT-SWU-INS command.
Bus Terminal Unit (BTU ) of Central Module Contains local PSM/ESM IFC
cards. Each PSM card caters for two consecutive Base Modules and each
ESM card caters for one local Base Module and one Remote Base Module.
Hence numbers of PSM/ESM cards in BTU depends upon how many Base
Modules (local+Remote) are equipped and what are their positions in the
configuration. If some Base Modules are not equipped then PSM/ESM cards
are not required but at those slots CML cards are put for providing proper
matching of impedances on the Bus for avoiding noise on the Bus. Please
refer Fig. 18.1 for the numbering of PSM/ESM cards in both Buses. Table
18.1 gives the relation between PSM/ESM cards and Base Modules.
Note : Only even numbered BM can be configured as Remote BM.
TABLE 18.1
BASE MODULE NUMBER - PSM/ESM CARD NUMBER
S.No. Bus Frame Nos. Base Module Numbers IFC Number (PSM/ESM) Slot No.
1 0 1 1&2 1 5
2 0 1 3&4 2 6
3 0 1 5&6 3 7
4 0 1 7&8 4 8
5 0 1 9 & 10 5 9
6 0 1 11 & 12 6 10
7 0 1 13 & 14 7 11
8 0 1 15 & 16 8 12
9 0 1 17 & 18 9 15
10 0 1 19 & 20 10 16
11 0 1 21 & 22 11 17
12 0 1 23 & 24 12 18
13 0 1 25 & 26 13 19
14 0 1 27 & 28 14 20
15 0 1 29 & 30 15 21
16 0 1 31 & 32 16 22
17 1 4 1&2 17 5
18 1 4 3&4 18 6
19 1 4 5&6 19 7
20 1 4 7&8 20 8
21 1 4 9 & 10 21 9
22 1 4 11 & 12 22 10
23 1 4 13 & 14 23 11
24 1 4 15 & 16 24 12
25 1 4 17 & 18 25 15
26 1 4 19 & 20 26 16
27 1 4 21 & 22 27 17
28 1 4 23 & 24 28 18
29 1 4 25 & 26 29 19
30 1 4 27 & 28 30 20
31 1 4 29 & 30 31 21
32 1 4 31 & 32 32 22
Note :
Corresponding to RBM, ESM card is required in both cases. (e.g. if BM12 is to
be configured as RBM, ESM cards are to be equipped as IFC6 and IFC22 in
bus-0 and bus-1 of BTUs respectively).
Set up
CM is fully initialised and BM-CM cables are connected.
Set up
CM is fully initialised and BM-CM cables are connected
1 1 0 (0x0) 1 (0x1)
2 2 2 (0x2) 3 (0x3)
3 3 4 (0x4) 5 (0x5)
4 4 6 (0x6) 7 (0x7)
5 5 8 (0x8) 9 (0x9)
6 6 10 (0xA) 11 (0xB)
7 7 12 (0xC) 13 (0xD)
8 8 14 (0xE) 15 (0xF)
9 9 16 (0x10) 17 (0x11)
10 10 18 (0x12) 19 (0x13)
11 11 20 (0x14) 21 (0x15)
12 12 22 (0x16) 23 (0x17)
13 13 24 (0x18) 25 (0x19)
14 14 26 (0x1A) 27 (0x1B)
15 15 28 (0x1C) 29 (0x1D)
16 16 30 (0x1E) 31 (0x1F)
17 17 32 (0x20) 33 (0x21)
18 18 34 (0x22) 35 (0x23)
S.No. Base Module Number Back-Plane id Copy 0 BPU in Back Plane id Copy 1 BPU
Decimal & Hex in Decimal & Hex
19 19 36 (0x24) 37 (0x25)
20 20 38 (0x26) 39 (0x27)
21 21 40 (0x28) 41 (0x29)
22 22 42 (0x2A) 43 (0x2B)
23 23 44 (0x2C) 45 (0x2D)
24 24 46 (0x2E) 47 (0x2F)
25 25 48 (0x30) 49 (0x31)
26 26 50 (0x32) 51 (0x33)
27 27 52 (0x34) 53 (0x35)
28 28 54 (0x36) 55 (0x37)
29 29 56 (0x38) 57 (0x39)
30 30 58 (0x3A) 59 (0x3B)
31 31 60 (0x3C) 61 (0x3D)
32 32 62 (0x3E) 63 (0x3F)
Note :
i) Shorting of Pins at Back Plane represents `0'
ii) Opening of Pins at Back Plane represents `1'
iii) Base Module number (16) Back Planes ids are shown as under.
COPY 1(BPU) COPY 0 (BPU)
LSB LSB
o o W21 o o W17 o--- o W13 o o W9
o o W22 o o W18 o o W14 o---o W10
o o W23 o o W19 o o W15 o---o W11
o o W24 o o W20 o o W16 o---o W12
MSB MSB
3. Jack out the concerned IFC card of bus 1 for that BM.
4. Switch on BPU and TSU of the concerned BM. BM will get path
to CMS1 or CMS2 through TSC-0 or TSC-1 and it will start
Note :
i) Atleast one PHC card should be equipped for code-loading to take
place.
ii) For all the SUM related commands the module should be specified as
SUM only.
Set-up
IOP-0 is INS-ACT
AM/CM/BM is initialized
TSU-TU cables will terminate on slot 14, B connection, tab 1 and 2 and
slot 17, B connection tab 1 and 2. Refer appendix III for details.
Refer page 10-216 for card slot details. Power and error cable terminals
are same as normal TU (ATU)
Since ISTU cannot be concentrated, it may be equipped as principal TU
one, using command equip-frame and FRM-TYP as ITU.
Run DGN on T1XX-0 or T1XX-1 and ICCX-0 or ICCX-1 using standard
procedure. If DGN fails, take appropriate action.
All the controllers should in in-service and interchange should be smooth
Test set details for BRI/PRI are available in Appendix-A of the
maintenance procedure document.
Set up
Both IOPs are inservice (Duplex)
1. Make inter BM calls, they should be successful and check the speech.
2. Make BUS-1 OOS-OPR for BM1 and BM3 i.e. IFC17 and IFC-18
should be OOS-OPR. Now make inter BM calls, calls should be
successful and check speech. Bring IFC17 & IFC18 inservice.
3. Make BUS-0 OOS-OPR for BM1 and BM3 i.e. IFC1 and IFC2 should
be OOS-OPR. Now make inter BM calls, calls should be successful and
check speech. Bring IFC1 and IFC2 inservice.
4. Make BUS-0 OOS-OPR for BM1 and BUS-1 OOS-OPR for BM3 i.e.
IFC1 and IFC18 should be OOS-OPR. Now make inter BM calls, calls
should be successful and check speech. Bring IFC1 and IFC18
inservice.
5. Make BUS-1 OOS-OPR for BM1 and bus-0 OOS-OPR for BM3 i.e.
IFC2 and IFC17 should be OOS-OPR. Now make inter BM calls, calls
should be successful and check speech. Bring IFC2 and IFC17
inservice.
6. Make inter BM calls in all BMs and check voice path.
Set up
A full duplex system
Set up
A full duplex system
3. Switch off PSU (slot 1) plane 0 of SCU, alarm should come indicating
plane 0 PSU faulty in SCU.
4. Switch on the both PSUs back, alarm for PSU in SCU should be
cleared.
5. Make all the units inservice.
6. Repeat step 1 to 5 for PSU cards of plane 1.
Set up
A duplex system
Set up
A duplex system
18.15.1. DGNAPU.COM
Set up
A duplex system
18.15.2. DGNSCU.COM
Set up
A duplex system
18.15.3. DGNBMNN.COM
Set up
A duplex system
This command file covers the diagnostics on all units of Base Module
number NN. We have to make command files for all Base Modules which
are equipped.
18.15.4. TSTTRMNN.COM
Set up
A duplex system
Make command files for all Base Modules covering all lines and trunks
of all types for testing the equipped terminals. NN is the number of
base module equipped.
1. Connect a LTG such that line terminations are coming from different
BMs.
2. Run a load of successful inter BM calls such that total traffic on any
BM should not exceed 6000. All types of calls should be made i.e.
Decadic and MF with two way, E&M & Digital loop backs.
3. Check the stability of the system and call failures. The grade of service
should be 0.0003 i.e. three call failures out of 1000 call attempts.
BM Equipage Procedure
This Appendix explains the procedure for equipping a Base Module in MAX-XL.
Please follow the procedure in this sequence.
Note
For expansion of existing exchanges, please refer to C-DOT DSS MAX-XL exchange
operation Document.
PROCEDURE TO EQUIP A BM :
1. Take the one IOP [say IOP-0] to Warm start level using init-iop command.
2. IOPXX) cd /u/admn/cmdfile
3. Invoke utility conv_cmd with physical bm no. in a command line parameter
e.g. to equip BM No. 5 give :
IOPxx ) sh conv_cmd l
The following are the input parameters.
Configuration : xl
BM Number [1 to 32] : 5
Normal/Remote [N/R] : N
4. Invoke crp
5. Execute the following crp commands at crp prompt.
< exec-cmd-file:aemod.cmdo;
< exec-cmd-file:aefrm.cmdo;
< exec-cmd-file:amslm.cmdo;
< exec-cmd-file:aesrv.cmdo;
< exec-cmd-file:amtam.cmdo;
< exec-cmd-file:aemfc.cmdo;
Warning : After each step come out of crp and check the log.
6. If it is a Digital BM (i.e., all TUs are DTUs), unequip TTC by uneq-srv-card
command.
7. Repeat steps 3 to 7 to equip all other BMs.
8. Invoke crp and (exec.cmd file : amlpr.cmd;
9. Shut down and Boot the IOP-0 after all BMs are equipped.
10. Bring IOP-1 to warmstart level if it is inservice.
11. Bring IOP-0 to INS level by giving command INIT-IOP:5,1;
12. Give part-init to the system.
Now that the BM equipping part is over, the actual exchange data generation
can be done.
PROCEDURE TO BE FOLLOWED FOR PREPARATION OF DATA :
13. Invoke crp (Refer note 1 below for information about the following command
files).
crp
Create the command files through CRE-CMD-FILE command Execute them
one by one using the commands given below in the order given.
* (exec-cmd-file:fil-nam=aefrm.cmd,break=y;
(exec-cmd-file:fil-nam=aetrm.cmd,break=y;
(exec-cmd-file:fil-nam=aemfc.cmd,break=y;
(exec-cmd-file:fil-nam=aesrv.cmd,break=y;
(exec-cmd-file:fil-nam=amxcd.cmd,break=y;
(exec-cmd-file:fil-nam=amans.cmd,break=y;
(exec-cmd-file:fil-nam=actgp.cmd,break=y;
(exec-cmd-file:fil-nam=acsub.cmd,break=y;
(exec-cmd-file:fil-nam=acrut.cmd,break=y;
! (exec-cmd-file:fil-nam=achgp.cmd,break=y;
(exec-cmd-file:fil-nam=amdty.cmd,break=y;
! (exec-cmd-file:fil-nam=acsgp.cmd,break=y;
(exec-cmd-file:fil-nam=acsrt.cmd,break=y;
(exec-cmd-file:fil-nam=acslv.cmd,break=y;
(exec-cmd-file:fil-nam=amsdr.cmd,break=y;
! (exec-cmd-file:fil-nam=afabs.cmd,break=y;
! (exec-cmd-file:fil-nam=afsal.cmd,break=y;
! (exec-cmd-file:fil-nam=afdiv.cmd,break=y;
! (exec-cmd-file:fil-nam=afhil.cmd,break=y;
! (exec-cmd-file:fil-nam=afsog.cmd,break=y;
! (exec-cmd-file:fil-nam=afqng.cmd,break=y;
LEGEND :
* If some more frames are to be equipped as in the case of concentration.
! These command files are optional i.e., these are to be used if some hunt
groups or service groups are to be created or if some extra features are
to be granted to subscribers.
WARNINGS :
The given order of command file execution is to be STRICTLY followed.
After execution of each command file ensure its successful completion by
looking at the log files.
Execution of amdty.cmd is COMPULSORY. During generation of bare
minimum data the current day's type did not get modified.
Only on execution of the command file, (i.e., amdty.cmd) will the day type get
modified.
14. Since the log files occupy space unnecessarily they should be deleted as soon
as the data is prepared.
cd \u\admn\cmdfile
rm -f *.log
16. If required, IOPs can be brought into duplex at this stage.
Note : 1
aefrm.cmd - command file for equipping frames
aetrm.cmd - command file for equipping terminal cards
aemfc.cmd - command file for equipping service cards
amxcd.cmd - command file for creating & modifying exchange
code
amans.cmd - command file for modifying answering circuit
numbers
actgp.cmd - command file for creating trunk groups
acsub.cmd - command file for creating subscribers
acrut.cmd - command file for creating routes
achgp.cmd - command file for creating hunt groups
amdty.cmd - command file for modifying day type
acsgp.cmd - command file for creating service group
acsrt.cmd - command file for creating special routes
acslv.cmd - command file for making a lvn supervisor
amsdr.cmd - command file for modifying system directory
number
afabs.cmd - command file for granting absentee facility
afsal.cmd - command file for granting Semi-Automatic Alarm
afdiv.cmd - command file for granting diversion facility
afhil.cmd - command file for granting hold line facility
afsog.cmd - command file for granting subscriber controlled
O/G call Restriction
afqng.cmd - command file for granting subscriber queueing
facility
Note : 2
For ILT Exchange :
MOD-SYS-PARAM:PAR-NAM=OWN-STD-LEN,PAR-VAL= (Length of the
ILT code)
CRE-SPL-ROUT:RUT-COD-mmm.RUT-FLG=1-CNB-NA-GA, CRG-RTN=1-8,
ILT=Y;
mmm = Exchange code appended to ILT code.
For eg, if the ILT code is 01793 and exchange code is 2 then the commands to
be given are :
MOD-SYS-PARM:PAR-NAM=OWN-STD-LEN,PAR-VAL=5;
CRE-SPL-ROUT:RUT-COD=017932,RUT-FLG=1-CNB-NA-GA,CRG-RTN=
1-8, ILT=Y;
Note : 3
For Satellite Exchange :
Routes may be created in a similar manner.
For eg, if the ILT code is 01793 and Satellite exchange code is 81 then the
commands to be given are :
MOD-SYS-PARAM:PAR-NAM=OWN-LEN, PAR-VAL=5;
CRE-SPL-ROUT:RUT-COD=0179381, RUT-FLG=1-CNB-NA-GA,
CRG-RTN=1-8, ILT=Y;
Port 3 C7 AII.2
S7 AII.3
Port 4 C6 AII.2
S6 AII.3
Port 5 C5 S5 AII.2
AII.3
Port 7 C2 S2 AII.2
AII.3
Port 8 C1 S1 AII.2
AII.3
X/P/Q/R/S/T X/P/Q/R/S/T
X/P/Q/13/A/1 X/P/Q/14/B/1
X/P/Q/13/A/2 X/P/Q/14/B/2
X/P/Q/14/A/1 X/P/Q/17/B/1
X/P/Q/14/A/2 X/P/Q/17/B/2
Changes to done in EPC DTS066/T-S04. Two layer card strap list for NSC clock
driving
Mount IC 26LS31 (2 Nos. ) on U104 and U113 with Pin no.1 towards the connector.
Do the following straps.
S1 Connect AC10 to U113/1 S12 Connect U104/7 to U113/15