9 ELECTRICAL INSTALLATION MDB-II
9.2 Flush mounting distribution board, SDB-II-
1/2/3/4/5/6/7/8 in sheet steel enclosure with
lockable door, and with phase neutral and earth
bus-bars 100A rating, and consisting of
1 pc main RCCB of 63A/3P , COUPLED WITH
DIGITAL KWHM
1 pc surge arrestor of 63A/3P,
11 pcs RCCB of 10A/1P
14pcs RCCB of 16A/1P
3pcs RCCB of 20A/1P
1pc RCCB of 6A/1P
1pc PHOTO CELL SWITCH of 10A/1P
25% reserve pitches NO. 1.00 -

LIGHT POINTS
9.3 Flush mounted light points fed through HEAVY
DUTY PVC insulated conductors of 3 x 2.5 mm²
inside PVC conduits of 20mm diameter, coupler,
including junction boxes with covers insulating
screw cap connectors. Including Incidence
Work. NO 90.00 -

LIGHTING CONTROL DEVICES


(TYPE LEGRAND SUNO OR EQUIVALENT)
9.4 Flush mounting single switch, 7740 01 + 77 40
41 NO 4.00 -

9.5 Flush mounting 2 gang single switch, 7740 05 +


77 40 41 NO 10.00 -

9.6 Flush mounting two-way switch, 7740 06 + 77


40 41 NO 17.00 -

9.7 Flush mounting dimmer switch NO 6.00 -

SOCKET OUTLET POINTS


9.8 10/16A / 1P flush mounted twin socket outlets
fed through heavy duty PVC insulated
conductors of 3 x 2.5 sq.mm inside PVC
conduits of 25mm diameter including junction
boxes with covers and insulating screw cap
connectors. Including Incidence Work. NO 27.00 -

9.9 ditto but for single socket outlet NO 21.00 -


9.10 20A / 1P wall mounted single socket outlets fed
through heavy duty PVC insulated conductors of
3 x 4 sq.mm inside PVC conduits of 25mm
diameter including junction boxes with covers
and insulating screw cap connectors. Including
Incidence Work for STOVE. NO 1.00

9.11 10/16A / 1P Flush mounted socket outlets fed


through heavy duty PVC insulated conductors of
3 x 2.5 sq.mm inside PVC conduits of 16mm
diameter including water proof metallic floor box
with cover, junction boxes with covers and
insulating screw cap connectors. Including
Incidence Work for water heater. NO 3.00 -

9.12 20A / 1P FLUSH/surface/floor mounted socket


outlets fed through heavy duty PVC insulated
conductors of 3 x 4 sq.mm inside PVC conduits
of 25mm diameter including water proof metallic
floor box with cover , junction boxes with covers
and insulating screw cap connectors. Including
Incidence stove/steam/cold room including
socket outlet with isolator switch. NO 1.00 -

9.12.1 Extra Over socket outlets For : -


(TYPE LEGRAND SUNO OR EQUIVALENT)
1.00 Flush mounting socket outlet of 10-16A/1P,
7740 20 + 77 40 41. NO 21.00 -

2.00 Flush mounting socket outlet of 10-16A/1P twin,


7740 25 NO 27.00 -

3.00 Ditto, but with switch for water heaters. NO 3.00 -

4.00 Flush mounting socket outlet of20A/1P with


switch for stove NO 2.00 -

Feeder Cables
PVC Sheathed PVC Insulated power cable type
NYY 0.6/1KV or equivalent to be drawn inside
cement or PVC conduit (measured elsewhere)
and of.
9.13 2(3X120/70+1x50)mm² from CMDB-II&IV TO
MDB-II M 26.00 -

9.14 3x25/16+1x16mm² from MDB-II TO SDB-II-1 M 55.75 -

9.15 3x25/16+1x16mm² from MDB-II TO SDB-II-2 M 48.75 -

9.16 3x25/16+1x16mm² from MDB-II TO SDB-II-3 M 37.00 -

9.17 3x25/16+1x16mm² from MDB-II TO SDB-II-4 M 28.25 -


CONDUITS & PIPES

9.18 UPVC pipe of 110mm diameter PN16 OR BS


3505. M 52.00 -

9.19 UPVC pipe of 70mm diameter PN16 OR BS


3505. M 169.75 -

INTERIOR LIGHTING

Light fittings and lamps (specified type or


equivalent)

9.20 TYPE 2 NO 3.00 -


9.21 TYPE 3 NO 12.00 -
9.22 TYPE 5 NO 19.00 -
9.23 TYPE 6 NO 2.00 -
9.24 TYPE 7 NO 2.00 -
9.25 TYPE 8 NO 7.00 -
9.26 TYPE 8' NO 4.00 -
9.27 TYPE 10 NO 4.00 -
9.28 TYPE 11 NO 4.00 -
9.29 TYPE 11' NO 2.00 -
9.30 TYPE 13 NO 18.00 -
9.31 TYPE 13' NO 5.00 -
9.32 TYPE 14 NO 4.00 -
9.33 TYPE 15 NO 1.00 -
9.34 TYPE 20 NO 1.00 -
9.35 TYPE 12 NO 6.00 -

DATA /TELECOM POINTS / WI-FI OUTLETS


9.36 Telephone, DATA AND WI-FI points fed
through twisted pair category 6E UTP cable
inside heavy duty rigid PVC conduit of 25mm
diameter Including Incidence Work NO 17.00 -

9.37 RJ 45 outlet type LEGRAND


(774038+774041)category 6E with 8 contacts
complete with clip on support frame. NO 17.00 -

9.38 cisco switch catalyst 2950 24ports No 1.00 -

9.39 RJ-45 to RJ-6 chord 1m No 17.00 -

9.40 patch panel 24 port No 1.00 -

9.41 Linksys WAP54G, Wireless-G Access Point No 4.00 -


9.42 9U Patch panel in 19'' (400mm depth) steel
enclosure with lockable door, including screen,
label holder, all fixing and cabling accessories
and consisting of:
1pc of organizer 1pc schucko outlet block with 6
socket outlet reserve space for future addition
of switch No 1.00 -

MATV SYSTEM NOTE: use modular back box


GEWISS (GW24232) for concrete & masonry
wall and GEWISS (24234) for light weight or
gypsum wall
9.43 MATV points indoor coaxial cable of RG6 double
shielded, 75ohm, inside heavy duty rigid PVC
conduit of 20mm diameter from, taps to TV
outlet at shown on drawings, including back box No 5.00 -

9.44 MATV out door coaxial cable of RG11 double


shielded, 75ohm, for external use and from
splitter / amplifier to splitter as shown on the
drawing M 62.50 -

9.45 TV-FM socket outlet GEWISS Eco 60 range


cloud white range or approved equivalent flush
mounted with appropriate cover plate frame and
box, frequency range TV: % to 862MHz, FM: 5
to 862MHz No 5.00 -

9.53 Distribution amplifier, frequency range 47-


862MHz gain adjustable 20dB, attenuation 0-
20dB, power supply 220V, 7.5W No 1.00 -

9.54 Splitter, frequency range 5-1000MHz outputs 2,


insertion loss 4.5dB, F-type No 1.00 -

9.55 Tap, frequency range 5-1000MHz, output 2,


insertion loss 4.5dB, tap loss 8dB, F-type No 3.00 -

BELL CALL SYSTEM

9.56 Bell call point fed through PVC insulated cable


of 2x1.0sq.mm inside heavy duty rigid PVC
conduit of 16mm diameter. No 1.00 -

9.57 Digital bell call panel with buzzer No 1.00 -


9.58 Power to bell call panel fed through PVC
insulated wire of 3X2.5mm² inside heavy duty
rigid conduit of 20mm diameter including
incident works No 1.00 -

9.59 Illuminated push button Legrand or equivalent No 1.00 -

FIRE ALARM SYSTEM ( Including Incidence


Work) Intelligent fire alarm equipment, supplied,
installed connected, tested and commissioned
including fire rated cables, heavy duty conduits
and all necessary accessories, complete as
manufactured by notifier/siemens or approved
equivalent and /or shown on the drawings;
9.60 Intelligent photoelectric smoke detector sensor
type HF,Siemens,Notifier FSP -851 or
equivalent which all necessary mounting
accessories for both surface/flush mounted NO 17.00 -

9.61 Intelligent photoelectric heat detector sensor


type HF,Siemens,Notifier FSP -851 or
equivalent which all necessary mounting
accessories for both surface/flush mounted NO 7.00 -

9.62 Addressable manual push switch station type


HF,Siemens Notifier NBG - 12LX or equivalent
which all necessary accessories surface/flush
mounted. NO 3.00 -

9.63 Wall mounted speaker / strobe type system


sensor SP2R2430 (Red) which all necessary
mounting accessories for both surface / flush
on loop with relay base. NO 3.00 -

9.65 Smoke /heat detector points fed through fire


resistance cable of 2-core 2.5 mm² inside heavy
duty PVC conduit of 20mm diameter including all
necessary accessories NO 24.00 -

9.66 Fire alarm speaker / strobe points fed through


fire resistance cable of 2 - core 2.5 mm² inside
heavy duty PVC conduit of 20mm diameter
including all necessary accessories NO 3.00 -

9.67 Manual call points fed through fire resistance


cable of 2 - core 2.5 mm² inside heavy duty PVC
conduit of 20mm diameter including all
necessary accessories NO 3.00 -
MDB-II
1.1 Note: LVSG MDB-II shall be supplied,
installed commissioned.Floor stand low
voltage switch gear,LVSG (MDB-II -IP65)
with hard drawn conductivity copper bus
bars of 800A rating, 150KA for 1sec.
including all controlling and other necessary
accessories with ample reserve space, all
tested and wired to relevant standard IEC
standard & consists of:
1 pc main RCCB of 400A/3P, coupled with
digitak Kwhm
1 pc surge arrestor of 400A/3P,
10 pcs RCCB of 63A/3P
1 pc RCCCB of 50A/3P
3 pcs Pilot lamps
high performance ventillation
25% reserve pitches NO. 1.00 -

LIGHTING CONTROL DEVICES


(TYPE LEGRAND SUNO OR
EQUIVALENT)
1.2 20A / 1P wall mounted single socket
outlets fed through heavy duty PVC
insulated conductors of 3 x 4 sq.mm inside
PVC conduits of 25mm diameter including
junction boxes with covers and insulating
screw cap connectors.Including Incidence
Work for STOVE. NO 1.00 -

MATV SYSTEM NOTE: use modular back box


GEWISS (GW24232) for concrete & masonr wall
and GEWISS (24234) for light weight or gypsum
wall
1.3 VHF aerial 13 elements, gain 11.55dB,
front to back ratio > 24dB, wind load 120N,
aluminum channel 5-12 horizontal
mounting,including mass bracket support
boom and all necessary accessories No 1.00 -

1.4 UHF aerial 66 elements, gain 17.0dB, front


to back ratio > 27dB, wind load 150N,
aluminum channel 21-50 horizontal
mounting,including mass bracket support
boom and all necessary accessories. No 1.00 -
1.5 Dish, 2400mm diameter, light gray, gain
40.0 dB, band width 10.75 - 12.75GHz,
wind load 1000N, material galvanized steel
with polyester power coat finish thickness
2mm 4ports quad with offset feedhome
LNBs and plastic LNB's holder including
Hot dip zink treated fixed support base,
ground stand to withstand wind velocity of
90Km/H and all necessary accessories. No 3.00 -

1.6 19'' cabinet with glass door and back board


for MATV headends 1100x650x450
(HxWxD) including fan operate with 220V,
protection grid from fan, 19" shelf for
satellite receiver and all necessary
accessories. No 1.00 -

1.7 Main unit for digital head end, controller,


remote/ local operating mode by connecting
a PC directly to the head end or by using
an external modem connected the phone
line, maximum number of device 254, contrl
bus of RS 485 3lines, trasmission rate of
9600bps, output frequency 47-862 MHz,
including software, power supply unit,
hybrid amplifier, connectors, mounting rail,
modem,rack frame 19" blank plate and all
necessary accessories No 1.00 -

1.8 Head end power supply from the nearest


distribuition board (refer distribution board
schedule) in heavy rigid PVC conduit of
20mm diameter fed PVC conductor of
3x2.5mm² No 1.00 -

FIRE ALARM SYSTEM ( Including


Incidence Work) Intelligent fire alarm
equipment, supplied, installed connected,
tested and commissioned including fire
rated cables,heavy duty conduits and all
necessary accessories, complete as
manufactured by notifier/siemens or
approved equivalent and /or shown on the
drawings;

1.9 Intelligent addressable fire alarm control


and dicated panel type NO 1.00 -
Notifier NFS-640 or approved equivalent
including notification appliance circuit
modules, control relay Module, contact and
under mention specification:
.. Input power 220VAC, 50Hz
.. Capable of networked connection
.. Programable internal hard ware and out
put circuits
.. Programable soft ware zones
..Accessories for out put connection for
telephone circuits
.. Sealed battery capable supply to all
equipments at least 72 hrs
.. Intelligent signaling line circuit
.. PA system interface
.. Trouble aknowledge and alarm silence
switch
.. Visual and audiable troouble alarm zone
..Manual acknowledge function
.. Minimum of 10 Zones digital
..LCD display (80 characters)
.. Program key pad
.. LED indicators
.. Two relay outputs
.. 7loops
.. Compatable devices
.. Compatable intelligent device with all
necessary accesssories
as BSNE 54 standard to make the system
1.1 Testing and commissioning LS 1.00 -
1.00 ELECTRICAL INSTALLATION COMMON
ITEMS
MDB-IV
1.10 Note: LVSG MDB-IV shall be supplied, installed
commissioned.Floor stand low voltage switch
gear,LVSG (MDB-II -IP65) with hard drawn
conductivity copper bus bars of 800A rating,
150KA for 1sec.including all controlling and
other necessary accessories with ample reserve
space, all tested and wired to relevant standard
IEC standard & consists of:
1 pc main RCCB of 400A/3P, coupled with
digitak Kwhm
1 pc surge arrestor of 400A/3P,
11 pcs RCCB of 63A/3P
3 pcs Pilot lamps
high performance ventillation
25% reserve pitches NO. 1.00 -
SOCKET OUTLET POINTS
1.20 20A / 1P wall mounted single socket outlets fed
through heavy duty PVC insulated conductors of
3 x 4 sq.mm inside PVC conduits of 25mm
diameter including junction boxes with covers
and insulating screw cap connectors.Including
Incidence Work for STOVE NO 1.00 -

MATV SYSTEM NOTE: use modular back box


GEWISS (GW24232) for concrete & masonry
wall and GEWISS (24234) for light weight or
gypsum wall
1.30 VHF aerial 13 elements, gain 11.55dB, front to
back ratio > 24dB, wind load 120N, aluminum
channel 5-12 horizontal mounting,including
mass bracket support boom and all necessary
accessories No 1.00 -

1.40 UHF aerial 66 elements, gain 17.0dB, front to


back ratio > 27dB, wind load 150N, aluminum
channel 21-50 horizontal mounting,including
mass bracket support boom and all necessary
accessories No 1.00 -

1.50 Dish, 2400mm diameter, light gray, gain 40.0


dB, band width 10.75 - 12.75GHz, wind load
1000N, material galvanized steel with polyester
power coat finish thickness 2mm 4ports quad
with offset feedhome LNBs and plastic LNB's
holder including Hot dip zink treated fixed
support base, ground stand to withstand wind
velocity of 90Km/H and all necessary
accessories No 3.00 -

1.60 19'' cabinet with glass door and back board for
MATV headends 1100x650x450 (HxWxD)
including fan operate with 220V, protection
grid from fan, 19" shelf for satellite receiver
and all necessary accessories No 1.00 -

1.70 Main unit for digital head end, controller, remote/


local operating mode by connecting a PC
directly to the head end or by using an external
modem connected the phone line, maximum
number of device 254, contrl bus of RS 485
3lines, trasmission rate of 9600bps, output
frequency 47-862 MHz, including software,
power supply unit, hybrid amplifier, connectors,
mounting rail, modem,rack frame 19" blank
plate and all necessary accessories No 1.00 -
1.80 Head end power supply from the nearest
distribuition board (refer distribution board
schedule) in heavy rigid PVC conduit of 20mm
diameter fed PVC conductor of 3x2.5mm² No 1.00 -

FIRE ALARM SYSTEM ( Including Incidence


Work)Intelligent fire alarm equipment, supplied,
installed connected, tested and commissioned
including fire rated cables,heavy duty conduits
and all necessary accessories, complete as
manufactured by notifier/siemens or approved
equivalent and /or shown on the drawings;
1.90 Intelligent addressable fire alarm control and
dicated panel type Notifier NFS-640 or
approved equivalent including notification
appliance circuit modules, control relay
Module, contact and under mention
specification: NO 1.00 -

.. Input power 220VAC, 50Hz


.. Capable of networked connection
.. Programable internal hard ware and out put
circuits
.. Programable soft ware zones
..Accessories for out put connection for
telephone circuits
.. Sealed battery capable supply to all
equipments at least 72 hrs
.. Intelligent signaling line circuit
.. PA system interface
.. Trouble aknowledge and alarm silence switch

.. Visual and audiable troouble alarm zone


..Manual acknowledge function
.. Minimum of 10 Zones digital
..LCD display (80 characters)
.. Program key pad
.. LED indicators
.. Two relay outputs
.. 7loops
.. Compatable devices
.. Compatable intelligent device with all
necessary accesssories as BSNE 54 standard
to make the system

1.10 Testing and commissioning LS 1.00 -


SUB TOTAL -
9.00 ELECTRICAL INSTALLATION
MDB-IV
9.2 Flush mounting distribution board, SDB-IV-
1/2/3/4/5/6/7/8 in sheet steel enclosure with
lockable door, and with phase neutral and earth
bus-bars 100A rating, and consisting of :-
1 pc main RCCB of 63A/3P , COUPLED WITH
DIGITAL KWHM
1 pc surge arrestor of 63A/3P,
10 pcs RCCB of 10A/1P
15pcs RCCB of 16A/1P
3pcs RCCB of 20A/1P
1pc RCCB of 6A/1P
1pc PHOTO CELL SWITCH of 10A/1P
25% reserve pitches NO. 1.00 -

LIGHT POINTS
9.3 Flush mounted light points fed through HEAVY
DUTY PVC insulated conductors of 3 x 2.5 mm²
inside PVC conduits of 20mm diameter, coupler,
including junction boxes with covers insulating
screw cap connectors. Including Incidence Work NO 81.00 -

LIGHTING CONTROL DEVICES


(TYPE LEGRAND SUNO OR EQUIVALENT)
9.4 Flush mounting single switch, 7740 01 + 77 40
41 NO 8.00 -

9.5 Flush mounting 2 gang single switch, 7740 05 +


77 40 41 NO 12.00 -

9.6 Flush mounting two-way switch, 7740 06 + 77


40 41 NO 17.00 -

9.7 Flush mounting dimmer switch NO 8.00 -

9.8 Flush mounting intermediate single switch, 7740


05 + 77 40 41 NO 2.00 -

SOCKET OUTLET POINTS


9.9 10/16A / 1P flush mounted twin socket outlets
fed through heavy duty PVC insulated
conductors of 3 x 2.5 sq.mm inside PVC
conduits of 25mm diameter including junction
boxes with covers and insulating screw cap
connectors. Including Incidence Work NO 20.00 -

9.10 ditto but for single socket outlet NO 29.00 -


9.11 20A / 1P wall mounted single socket outlets fed
through heavy duty PVC insulated conductors of
3 x 4 sq.mm inside PVC conduits of 25mm
diameter including junction boxes with covers
and insulating screw cap connectors. Including
Incidence Work for STOVE NO 1.00 -

9.12 10/16A / 1P Flush mounted socket outlets fed


through heavy duty PVC insulated conductors of
3 x 2.5 sq.mm inside PVC conduits of 16mm
diameter including water proof metallic floor box
with cover , junction boxes with covers and
insulating screw cap connectors. Including
Incidence Work for water heater NO 4.00 -

9.13 20A / 1P FLUSH/surface/floor mounted socket


outlets fed through heavy duty PVC insulated
conductors of 3 x 4 sq.mm inside PVC conduits
of 25mm diameter including water proof metallic
floor box with cover , junction boxes with covers
and insulating screw cap connectors. Including
Incidence stove/steam/cold room including
socket outlet with isolator switch NO 2.00 -

9.13.1 Extra Over socket outlets For : -


(TYPE LEGRAND SUNO OR EQUIVALENT)
1.00 Flush mounting socket outlet of 10-16A/1P,
7740 20 + 77 40 41. NO 8.00 -

2.00 Flush mounting socket outlet of 10-16A/1P,


7740 20 + 77 40 41.water proof NO 12.00 -

3.00 Flush mounting socket outlet of 10-16A/1P twin,


7740 25 NO 27.00 -

4.00 Ditto, but with switch for water heaters. NO 4.00 -

5.00 Flush mounting socket outlet of20A/1P with


switch for stove NO 2.00 -
Feeder Cables
PVC Sheathed PVC Insulated power cable type
NYY 0.6/1KV or equivalent to be drawn inside
cement or PVC conduit (measured elsewhere)
and of.
9.14 2(3X120/70+1x50)mm² from CMDB-II&IV TO
MDB-Iv M 2.50 -

9.15 3x25/16+1x16mm² from MDB-II TO SDB-IV-1 M 43.25 -


9.16 3x25/16+1x16mm² from MDB-II TO SDB-IV-2 M 35.50 -

9.17 3x25/16+1x16mm² from MDB-II TO SDB-IV-3 M 17.25 -

9.18 3x25/16+1x16mm² from MDB-II TO SDB-IV-4 M 8.75 -

CONDUITS & PIPES


9.19 UPVC pipe of 110mm diameter PN16 OR BS
3505. M 5.00 -

9.20 UPVC pipe of 70mm diameter PN16 OR BS


3505. M 104.75 -
INTERIOR LIGHTING
Light fittings and lamps (Specified type or
equivalent)
9.21 TYPE 2 NO 4.00 -
9.22 TYPE 3 NO 4.00 -
9.23 TYPE 3' NO 1.00 -
9.24 TYPE 5 NO 13.00 -
9.25 TYPE 6 NO 2.00 -
9.26 TYPE 7 NO 1.00 -
9.27 TYPE 8 NO 10.00 -
9.28 TYPE 9 NO 1.00 -
9.29 TYPE 10 NO 5.00 -
9.30 TYPE 11 NO 10.00 -
9.31 TYPE 11' NO 1.00 -
9.32 TYPE 13 NO 15.00 -
9.33 TYPE 13' NO 1.00 -
9.34 TYPE 15 NO 10.00 -
9.35 TYPE 20 NO 1.00 -
9.36 TYPE 12 NO 4.00 -

DATA /TELECOM POINTS / WI-FI OUTLETS


9.37 Telephone, DATA AND WI-FI points fed
through twisted pair category 6E UTP cable
inside heavy duty rigid PVC conduit of 25mm
diameter Including Incidence Work NO 16.00 -

9.38 RJ 45 outlet type LEGRAND


(774038+774041)category 6E with 8 contacts
complete with clip on support frame. NO 16.00 -

9.39 cisco switch catalyst 2950 24ports No 1.00 -

9.40 RJ-45 to RJ-6 chord 1m No 16.00 -

9.41 patch panel 24 port No 1.00 -


9.42 Linksys WAP54G, Wireless-G Access Point No 4.00 -

9.43 9U Patch panel in 19'' (400mm depth) steel


enclosure with lockable door, including screen,
label holder, all fixing and cabling accessories
and consisting of:
1pc of organizer
1pc schucko outlet block with 6 socket outlet
reserve space for future addition of switch No 1.00 -

MATV SYSTEM NOTE: use modular back box


GEWISS (GW24232) for concrete & masonry
wall and GEWISS (24234) for light weight or
gypsum wall.
9.44 MATV points indoor coaxial cable of RG6 double
shielded, 75ohm, inside heavy duty rigid PVC
conduit of 20mm diameter from, taps to TV
outlet at shown on drawings, including back box No 5.00 -

9.45 MATV out door coaxial cable of RG11 double


shielded, 75ohm, for external use and from
splitter / amplifier to splitter as shown on the
drawing M 62.50 -

9.46 TV-FM socket outlet GEWISS Eco 60 range


cloud white range or approved equivalent flush
mounted with appropriate cover plate frame and
box, frequency range TV: % to 862MHz, FM: 5
to 862MHz No 5.00 -
- -

9.54 Distribution amplifier, frequency range 47-


862MHz gain adjustable 20dB, attenuation 0-
20dB, power supply 220V, 7.5W No 1.00 -

9.55 Splitter, frequency range 5-1000MHz outputs 2,


insertion loss 4.5dB, F-type No 1.00 -

9.56 Tap, frequency range 5-1000MHz, output 2,


insertion loss 4.5dB, tap loss 8dB, F-type No 3.00 -

BELL CALL SYSTEM


BELL CALL
9.57 Bell call point fed through PVC insulated cable
of 2x1.0sq.mm inside heavy duty rigid PVC
conduit of 16mm diameter. No 1.00 -

9.58 Digital bell call panel with buzzer No 1.00 -


9.59 Power to bell call panel fed through PVC
insulated wire of 3X2.5mm² inside heavy duty
rigid conduit of 20mm diameter including
incident works No 1.00 -

9.60 Illuminated push button Legrand or equivalent No 1.00 -

FIRE ALARM SYSTEM ( Including Incidence


Work)Intelligent fire alarm equipment, supplied,
installed connected, tested and commissioned
including fire rated cables, heavy duty conduits
and all necessary accessories, complete as
manufactured by notifier/siemens or approved
equivalent and /or shown on the drawings;
9.61 Intelligent photoelectric smoke detector sensor
type HF,Siemens,Notifier FSP -851 or
equivalent which all necessary mounting
accessories for both surface/flush mounted NO 12.00 -

9.62 Intelligent photoelectric heat detector sensor


type HF,Siemens,Notifier FSP -851 or
equivalent which all necessary mounting
accessories for both surface/flush mounted NO 7.00 -

9.63 Addressable manual push switch station type


HF,Siemens Notifier NBG - 12LX or equivalent
which all necessary accessories surface/flush
mounted. NO 4.00 -

9.64 Wall mounted speaker / strobe type system


sensor SP2R2430 (Red) which all necessary
mounting accessories for both surface / flush
on loop with relay base. NO 4.00 -

9.66 Smoke /heat detector points fed through fire


resistance cable of 2-core 2.5 mm² inside heavy
duty PVC conduit of 20mm diameter including all
necessary accessories NO 28.00 -

9.67 Fire alarm speaker / strobe points fed through


fire resistance cable of 2 - core 2.5 mm² inside
heavy duty PVC conduit of 20mm diameter
including all necessary accessories NO 4.00 -

9.68 Manual call points fed through fire resistance


cable of 2 - core 2.5 mm² inside heavy duty PVC
conduit of 20mm diameter including all
necessary accessories NO 4.00 -

SUB TOTAL -