Beruflich Dokumente
Kultur Dokumente
NEC ®, NFPA 70®, NFPA 70E® and National Electrical I dedicate this book to the
Code ® are registered trademarks of the National Fire Lord Jesus Christ,
Protection Association. my mentor and teacher.
Proverbs 16:3
This logo is a registered trademark of Mike
Holt Enterprises, Inc.
•
ARTICLE
Part I. General
690.1 Scope
Figure 690–23
Author’s Comment:
n Listing means that the equipment is in a list published by a
testing laboratory acceptable to the authority having jurisdic-
tion [Article 100].
Figure 690–26
WARNING: ELECTRIC SHOCK HAZARD—IF A GROUND (D) Energy Storage or Backup Power. Stand-alone PV systems aren’t
FAULT IS INDICATED, NORMALLY GROUNDED CONDUCTORS required to have energy storage power supplies.
MAY BE UNGROUNDED AND ENERGIZED
(E) Backfed Circuit Breakers. Circuit breakers that are back-fed Author’s Comment:
must be secured in place by a fastener that requires other than a n The purpose of the breaker fastener is to prevent the cir-
pull to release the breaker from the panelboard, if they’re fed from a
cuit breaker from being accidentally removed from the
stand-alone or multimode inverter output in a stand-alone system. Cir-
panelboard while energized, thereby exposing persons to
cuit breakers marked “line” and “load” aren’t suitable for backfeed or
dangerous voltage.
reverse current. Figures 690–57 and 690–58
Figure 690–57
Figure 690–66
(1) The inverter dc input circuit disconnect must be within sight of and
not more than 50 ft away from the inverter.
(2) The inverter ac output circuit disconnect must be within sight of the
inverter and not more than 50 ft away from the inverter.
(3) A disconnect for the inverter dc input circuit must be located either
outside the building, or inside nearest the point of dc input circuit
conductor entry at a readily accessible location [690.13(A)].
Author’s Comment: Where the output circuit fuse disconnect is located more than 6 ft from
the fuses, a directory showing the location of each PV output circuit fuse
n Tilt-out fuse holders meet the requirement for de-
disconnect must be installed at the fuse location.
energizing the fuse as long as a load break switch is avail-
able at the PV source circuit combiner in accordance with Non-load-break-rated fuse disconnecting means must be marked “Do
690.15(C). not open under load.” Figure 690–74
(B) PV Output Circuit Fuse Disconnect. Where fuses for output cir-
cuits can’t be isolated from energized circuits, a disconnect that
complies with 690.17 must be located within sight of, or integral with,
the PV output circuit fuse holder. Figure 690–73
Note: Devices marked with “line” and “load” aren’t suitable for backfeed
or reverse current.
Figure 690–76
Figure 690–77
Figure 690–80
Author’s Comment:
n Micro-inverters, mini-inverters, and ac modules are the most
common applications where plug connectors are used as the
required disconnecting means for both dc and ac conductors.
Figure 690–78
Figure 690–84
Figure 690–83
Author’s Comment:
n Wiring that’s part of a listed system includes the wiring har-
ness of a micro- or mini-inverter.
Note: PV wire raceway fill is based on the actual area of the conductor
(see manufacturer’s specifications) in conjunction with Table 1 of Chap-
ter 9, see 300.17.
(4) Grouping. Where the conductors of more than one PV system Author’s Comment:
occupy the same junction box or raceway with a removable cover, n TC-ER cable is tray cable (TC) that’s listed for use in exposed
the ac and dc conductors of each system must be grouped separately runs (ER). The product standards require better crush and
by cable ties, and then grouped at intervals not to exceed 6 ft. Figure impact performance for a cable that contains the ER rating.
690–88
Ex: Grouping isn’t required if the PV circuit enters from a cable or race-
way unique to the circuit that makes the grouping obvious.
(E) Flexible Cords and Cables. Flexible cords used to connect the (2) Flexible Wiring Methods. Flexible metal conduit smaller than
moving parts of tracking PV modules must be identified as a hard ser- trade size ¾ or Type MC Cable smaller than 1 in. in diameter contain-
vice cord or portable power cable suitable for extra-hard usage, listed ing PV dc circuit conductors installed across ceilings or floor joists
for outdoor use, water resistant, sunlight resistant, and comply Article must be protected by substantial guard strips that are at least as high
400. as the wiring method.
Figure 690–90
Figure 690–89
WARNING: PHOTOVOLTAIC POWER SOURCE
Ex: Listed switchgear for bipolar systems rated for the maximum
voltage between circuits with a physical barrier separating the dis-
connecting means for each monopole subarray can be used instead of
disconnecting means in separate enclosures.
(I) Bipolar Photovoltaic Systems. Where the sum, without consid- (1) Maximum rated power-point current (Imp x number of combined
eration of polarity, of the PV system voltages of the two monopole paralleled source circuits).*
subarrays exceeds the rating of the conductors and connected equip- (2) Maximum rated power-point voltage (Vpm x number of modules in
ment, monopole subarrays must be physically separated, and the each source circuit).*
electrical output circuits from each monopole subarray must be
installed in separate raceways until connected to the inverter. The (3) Maximum rated system voltage (Voc).*
disconnecting means and overcurrent devices for each monopole sub-
array output must be in separate enclosures. Bipolar PV systems must
(4) Maximum rated circuit current (Isc* x 1.25). (4) Maximum Circuit Current (Isc x 1.25), 690.8(A)(1)
Isc = Module Isc × 1.25 × Number of Strings in Parallel
Note: See 690.8(A)(1) for maximum rated circuit current calculation.
Isc = (8.90A × 1.25) × 2
*The maximum rated power-point current (Imp), power-point voltage Isc = 11.13A × 2
(Vpm), open circuit voltage (Voc), and short-circuit current (Isc) are Isc = 22.26A
contained in the manufacturer’s specifications sheet for the modules
used.
(5) Maximum rated output current of the charge controller (if installed) 690.54 Interactive System
PV dc Power Source Label The point of connection of the PV system to other systems must be
marked at an accessible location at the ac disconnecting means with
Example: Determine the information needed for the PV dc power the inverter ac output current and nominal ac voltage. Figure 690–120
source label for an array that consists of two source circuits
(strings) of ten 250W modules, each rated 8.40 Imp, 29.80 Vpm,
38.30 Voc (at -7°C), 8.90 Isc. The manufacturer’s temperature
690.56 Identification of Power Sources
coefficient is -0.36%/ºC.
(1) Maximum Power-Point Current (Imp), Information from (A) Facilities with Stand-Alone Systems. Any building with a stand-
manufacturer alone PV system (not connected to a utility power source) must have
a permanent plaque placed on the exterior of the building at a read-
Imp = Module Rated Imp × Number of Strings in Parallel
ily visible location that’s acceptable to the authority having jurisdiction.
Imp = 8.40A × 2 The plaque must indicate the location of the stand-alone PV system
Imp = 16.80A disconnecting means and that the structure contains a stand-alone
electrical power system. Figure 690–121
Figure 690–121
Part I. General
705.1 Scope
705.2 Definitions
Figure 705–1
Power Production Equipment. The generating source, and all associ-
ated distribution equipment, that generates electricity from a source
other than a utility supplied service. Figure 705–2
Figure 705–2
Author’s Comment:
n For this textbook, the power production equipment is a Solar
PV system. The “other” source is the electric utility.
Figure 705–4
Scan this QR code for a video of this Code rule. See page xxiii
for information on how to use the QR codes.
(a) The feeder conductor on the load side of the inverter ac output
connection must have an ampacity not less than the feeder over-
current protection device, plus 125 percent of the inverter output
ac circuit current rating. Figure 705–12
Figure 705–10
(2) Feeder Conductor and Panelboard Bus Ampere Rating. Figure 705–12
(2) Feeder Tap Ampere Rating. Feeder tap conductors between the
Feeder Tap—25-foot Rule
feeder overcurrent protection device and the inverter ac output pro-
tection device, must have an ampacity not less than the feeder Example: What size feeder tap conductor (longer than 10 ft but
overcurrent protection device, plus 125 percent of the inverter output not over 25 ft) will be required for a tap to a 100A overcurrent
ac circuit current rating in accordance with 240.21(B). device made between a feeder overcurrent protection device
rated 200A and an inverter with ac output current rated 160A?
Author’s Comment: Figure 705–15
n According to 240.2, a tap conductor is a conductor, other (a) 112A (b) 133A (c) 150A (d) 182A
than a service conductor, that has overcurrent protection
Answer: (b) 133A. Feeder tap conductors must have an ampac-
rated more than the ampacity of a conductor.
ity no less than 1⁄3 the ampacity of the 200A feeder protection
and 160A inverter ac output current rating, 200A + (160A x
1.25) = 400A x 0.3333 = 133A [240.21(B)(2)(1)], and not less
Feeder Tap—10-foot Rule than the rating of the termination of the tap overcurrent protec-
tion device of 100A [240.21(B)(2)(1)].
Example: What size feeder tap conductor (not longer than 10
ft) will be required for a tap to a 100A overcurrent device made
between a feeder overcurrent protection device rated 200A and (3) Panelboard Busbar Ampere Rating. The ampacity of the panel-
an inverter with ac output current rated 160A? Figure 705–14 board busbar must comply with one of the following:
(a) 100A (b) 120A (c) 160A (d) 200A
Author’s Comment:
Answer: (a) 100A. Feeder tap conductors must have an ampacity
n Only one of the four methods (a) through (d) is used to deter-
no less than 1⁄10 the ampacity of the 200A feeder protection and
160A inverter ac output current rating, 200A + (160A x 1.25) mine the busbar ampacity based on the specific condition.
= 400A x 0.10 = 40A [240.21(B)(2)(1)], and not less than the
rating of the termination of the tap overcurrent protection device
of 100A [240.21(B)(1)(4)].
(a) If the inverter ac output circuit breaker(s) aren’t located at the (b) If the inverter ac output circuit breaker(s) are located at the oppo-
opposite end of the feeder terminal on the panelboard, the ampere site end of the feeder termination on the panelboard busbar, the
rating of the panelboard busbar must not be less than the ampere ampere rating of the overcurrent device protecting the panelboard
rating of the overcurrent device protecting the panelboard busbar, busbar, plus 125% of the inverter output ac current rating must
plus 125% of the inverter ac output current ratings. Figures not exceed 120% of the ampere rating of the panelboard busbar.
705–16 and 705–17 Figure 705–18
Example 1: What’s the minimum busbar ampere rating for a Example 2: What’s the minimum busbar ampere rating for a
panelboard containing two 30A, two-pole, 240V circuit breakers panelboard containing six 30A, two-pole, 240V circuit breakers
and six 20A, 240V two-pole circuit breaker? Figure 705–23 and one 20A, 120V one-pole circuit breaker? Figure 705–24
(a) 180A (b) 240A (c) 320A (d) 400A (a) 120A (b) 180A (c) 200A (d) 220A
Figure 705–24
Figure 705–26
Figure 705–25
Note: Fused disconnects are suitable for backfeeding, unless otherwise Author’s Comment:
marked.
n Once the dedicated ac inverter circuit breaker has been
removed from the panelboard, the listed interactive inverter
(5) Fastening. Circuit breakers for utility-interactive inverters that are
automatically powers down and turns off output ac power
backfed aren’t required to be secured in place by an additional fas-
generation from the inverter.
tener as required by 408.36(D). Figure 705–28
Author’s Comment:
n This rule applies to micro-inverters.
Figure 705–28
This DVD program is an insightful guide to the sweeping changes in the NEC ® as they relate to the installation of PV systems
of any size. The program explores the safety aspects of installation and the maintenance of PV systems. If you are a PV
Installer, Electrician, Inspector or Engineer, this book will be an eye-opener to the complexity of Solar Photovoltaic Systems
and the importance of understanding those NEC ® Rules that govern their installation.
Get your Copy for 20% off list price – use discount code PVPDF14
“...as for me and my house, we will serve the Lord.” [Joshua 24:15]
TM
MIKE HOLT Enterprises, Inc.