Abstract – This work presents a new 12kW high power factor A parallel connection of three six-pulse bridge rectifier
three-phase rectifier based on a Y-connected differential is used to obtain 18-pulse uncontrolled converter. Usually,
autotransformer with reduced kVA and 18-pulse input an Interphase Transformer (IPT) connected on the DC
current followed by three DC-DC boost converters. The sides of the three bridge rectifiers is required to absorb the
topology provides a regulated output voltage and natural
instantaneous voltage differences between the bridges.
three-phase input power factor correction. The lowest input
current harmonic components are the 17th and the 19th. Three When a non-isolated transformer is used, two IPT are
boost converters, with constant input currents and regulated needed: one connected to the positive outputs, and another
parallel connected output voltages are used to process 4kW connected to the negative outputs. The size, the loss and
each one. the cost of the IPT are, therefore, increased.
Analytical results from Fourier analyses of winding Figure 1 shows the basic diagram for a non-isolated 18-
currents and the vector diagram of winding voltages are pulse converter using two conventional IPT to improve
presented. Experimental results to verify the proposed parallel connection on the DC sides.
concept is shown in the paper. This work proposes a new 18-pulse converter using a Y-
connected differential autotransformer. The
I. INTRODUCTION
autotransformer is designed to feed three six-pulse bridge
rectifiers displaced in phase by 20o. The autotransformer
In telecommunication systems, conventional input
power rate is only 22% of the output kVA and the lowest
stage of power supplies is widely realized as voltage DC-
order harmonics are the 17th and the 19th.
link converters. In many cases, the AC supply voltage is
In order to provide parallel-connected [04] and regulated
connected to a DC link voltage by a diode rectifier with
output voltages, without an IPT, three boost converters
output filter capacitor. A high-frequency DC-DC
with additional diodes were proposed.
converter, with regulated output voltage, is then connected
Six small size high-frequency boost inductors, as shown
in series with the DC-link voltage.
in figure 2, replace the large interphase transformers. The
Motivated by high efficiency, high power density, low
continuous conduction mode and output regulated voltage
cost and robustness, an uncontrolled three-phase bridge
are guaranteed by basic and simple control strategy of the
directly connected to the AC supply has been used.
boost converter. The inductor currents of each converter
However, this concept shows, as disadvantage, high low-
are kept constant with a little high frequency ripple.
frequency current harmonics, due to the output capacitor, Io /3
which leads to a distortion of the AC supply voltage. I o /3 Io
Va Io /3
Various international standards like IEEE-519 and IEC- Bridge 1
IPT1
1000-3-2, were proposed to maintain the THD (Total
Harmonic Distortion) and the Power Factor (PF) at Non-isolated
Vb 18-pulse
acceptable levels. This is especially important for transformer Load
Bridge 2
guaranteeing universal applicability of telecommunication Vc
rectifiers. IPT2
Furthermore, the conventional power supplies are being
replaced more and more by three-phase modular rectifier Bridge 3
systems, due to the advantages of the latter concerning Fig. 1. 18-Pulse converter with conventional IPT
operational behavior, system technology, and costs [01].
Io /3
In the same way that the great number of works
developed for power factor correction in single-phase Va
systems, the techniques for three phase systems to operate Io /3
Vb
with power factor correction are growing, either through
Vc
converters with one or more associated switches, or by N Load
using specially connected transformers. In general, the Io /3
Vc I ic
Ian
I bn
Were, VLan, VLbn and VLcn are the magnitude of the
I cn
Lb
N
Ic
voltages across the secondary windings Lan, Lbn and Lcn,
Ib La1
La2 Lc
Lcn I o /3
respectively.
Lbn
Lc1 Lb2 I b1
Ic1
The winding turns-ratio to ensure 88% from primary
I a1
voltage (n1), without displacement, is given by.
Fig. 3. A simplified circuit of proposed topology for analysis V 1
n1 = a = = 8.29 (11)
VLan 0.1206
This result shows that this secondary turns is 8.29 times Ian(t)
Va (t)
Io/3
lower than the primary turns.
The magnitude voltages for these secondary terminals, 0
o
with respect to the virtual neutral point N, are obtained as 30 150
o
follows. T/2 T t
Van = 0.8794 . Va (12) 0 0.01 0.02 0.03
Fig. 5. Primary reference voltage and secondary current to phase
Vbn = 0.8794 . Vb (13) indexed by “a”
Vcn = 0.8794 . Vc (14)
140π
∑ k . cos k. 6 .sin k. ωt − 180 (22)
4 Io 1 1
I b2 (t) = . .
B. Analysis of the Winding Currents π 3 k
The technique to eliminate harmonic of current in the
20π
∑ k . cos k. 6 .sin k. ωt − 180
4 Io 1 1
multiple pulse converters requires current-mode operation I c2 (t) = . . (23)
to the load. π 3 k
In this case, the 18-pulse converter, formed by three- The primary winding currents (Ia, Ib and Ic) can be
bridge rectifier, each converter conducts 1/3 of the load obtained by considering the currents of the three secondary
current (Io/3). The currents in the secondary windings are winding coupled to the same limb core and by turns-ratio
the same to the input currents of each bridge. (n1=8.29 and n2=2.88). As mentioned bottom, winding
The waveform of the input Va and the current through with the same index (a, b or c) are coupled in the same
one secondary winding (Lan) are shown in figure 5. These limb.
waveforms are adopted as angular reference to represent
I ( t ) + I a 2 ( t ) I an ( t )
the other ones. I a ( t ) = a1 − (24)
The waveform of Ian can be decomposed in Fourier n2 n 1
series by the conventional way. By the way, when I ( t ) + I b 2 ( t ) I bn ( t )
discontinuous function is considered, the series terms can I b ( t ) = b1 − (25)
be obtained by inspection. We can observe that this n2 n 1
waveform presents alternate symmetry, the negative half I ( t ) + I c 2 ( t ) I cn ( t )
I c ( t ) = c1 − (26)
n 1
cycle is an inverted reproduction of the positive half cycle.
Thus, the even harmonic are zero and there are not terms in n2
cosines. The average value is also zero. Figure 6 shows the primary current (Ia). It is obtained by
We can observed that this winding (Lan) conducts the composition of equation (24) from (04), (11), (15), (18)
current Io/3 during 120o (2π/3), starting from 30o (π/6). and (21). This solution is easily found and plotted through
Thus, for k=1, 3, 5, ...,the expression of the current results: MathCad program.
1
∑
4 I 1
I an ( t ) = . o . . cos k. .sin (k.ωt ) (15) C. Analysis of the Line-Input Currents
π 3 k k 6 The input currents Iia, Iib and Iic are obtained by
The waveforms of all currents through the secondary summing all currents through windings at same node as
windings are the same, only with a 20o phase-shift among shown in figure 3. So, the follow equations can be written.
each three-phase system. The other currents are I ia ( t ) = I a ( t ) + I an ( t ) + I b1 ( t ) + I c 2 ( t ) (27)
represented by the same equation of Ian as shown below.
I ib ( t ) = I b ( t ) + I bn ( t ) + I c1 ( t ) + I a 2 ( t ) (28)
Therefore, all phases are adjusted.
I ic ( t ) = I c ( t ) + I cn ( t ) + I a1 ( t ) + I b 2 ( t ) (29)
1 2π
∑
4 I 1
I bn ( t ) = . o . . cos k. .sin k. ωt + (16) Figure 7 shows the phase currents that are obtained by
π 3 k k 6 3 composition of equation (27) to (29) from (15) to (26).
2π
∑ k . cos k. 6 .sin k. ωt −
4 Io 1 1
I cn ( t ) = . . (17) Io /6
π 3
Ia (t)
k
3
In the other secondary three-phase system, the currents 0
are expressed by:
1 100π
∑
4 I 1 t
I a1 ( t ) = . o . . cos k. .sin k. ωt − (18) 0 0.01 0.02 0.03
π 3 k k 6 180
Fig. 6. Primary current waveform
1 20π
∑
4 Io 1
I b1 ( t ) = . . . cos k. .sin k. ωt + (19) Iia (t) Iib (t) Iic (t)
π 3 k
k 6 180
140π
∑ k . cos k. 6 .sin k. ωt + 180
Io /3
4 Io 1 1
I c1 ( t ) = . . (20) 0
π 3 k
To the last system, the currents are expressed by:
1 100π
∑
4 I 1 t
I a 2 (t ) = . o . . cos k. .sin k. ωt + (21) 0 0.01 0.02 0.03
π 3 k k 6 180 Fig. 7. Three-phase input currents
D. Harmonic Analysis for Input Phase Current The voltage across secondary windings with phase shift
Total Harmonic Distortion (THD) is calculated by of 20o in relation to primary ones, La1, La2, Lb1, Lb2, Lc1 and
relationship between rms values of the fundamental Lc2, are reduced by turns ratio n2. Therefore, the
components and all phase current harmonics. In these relationship between these voltages are expressed for (01),
calculations MathCad program has considered the first (02) and (03).
1000 harmonic components (k=1,3,5 ...999). Expression (36) and (37) give the average voltage from
The total rms value for all harmonics of the phase output of the rectifier.
∫ ( )
current Iia and the rms current for fundamental component 6 2π
Iia1 (for k=1), are calculated through (30) and (31): Vo = . 2 3 . 0.8794 . Va . sin (ωt ) dωt (36)
2π 0
2π
∫
1 Vo = 2.057 . Va (37)
I ia = . I ia ( t ) 2 .dωt (30)
2π 0 The secondary power rate VA is obtained by summing
of the product of voltage and current of each secondary
1 2π
I ia1 =
2π
.
0 ∫
I ia1 ( t ) 2 .dωt (31) winding, as shown in (38).
S2 = 0.323 . Po (38)
Where, Iia(t) is solved by (27) for k=1,3,5,... and The primary power rate VA is obtained by summing of
Iia1(t) is solved by (27) for k=1. the product of voltage and current of each primary
From (30) and (31), the THD is easily obtained by (32). winding, as shown in (39).
S1 = 0.114 . Po (39)
I ia − I ia1
2 2
THD = 2
= 10.7% (32) Where
I ia1 P o = Vo . I o (40)
The Power Factor (PF) is calculated by (33). The Thus, the autotransformer power rate is given by average
displacement between the phase current and the phase value between S1 and S2. Then,
voltage is negligible. S = 0.218 . Po (41)
1
PF = = 0.994 (33) III. PROPOSED BOOST CONVERTER STRATEGY
1 + THD 2
Figure 8 shows the frequency spectrum of the input The boost converter is chosen because it provides a
phase current Iia(t). We can observe that 18-pulse converter simple regulated output voltage and regulated inductor
presents only harmonic orders X.(18±1), for X=1,2,3,.... current. Furthermore, it is very easy to obtain three parallel
The lowest harmonic orders are the 17th and the 19th. connected boost converters [04], as shown in figure 2.
The conventional boost converter can not be used
E. Power Rate of the Autotransformer because when two or more switches are closed, the current
The shape of all secondary winding currents are equal, flowing through the first boost returns through the second
but each one is shifted in phase to generate the three-phase one. One diode that is added in the conventional boost can
systems. Anyway, all rms value of secondary currents are solve this problem.
the same. Then, they can be calculated through (34). Another problem occurs when all switches are
2π 2 simultaneously open. The current flows through the first
I an ( t )
∫
1
I an = I o . . .dωt Ian = 0.272 . Io (34) boost, through the load and returns through the second one.
2π 0 Io This problem is solved by division of each boost inductor
The primary winding currents have the same rms value in two series connected inductors, as shown in figure 2.
and can be expressed by (35). After the switch turn-off, the lower inductor forces the
2 current from upper one to comes back through it. In this
1 2π I a (t )
Ia = Io .
.
2π 0 I o ∫
.dωt Ia = 0.078 . Io (35) way, the lower inductors are necessary.
This connection is very important to the operating of the
Where, Ian(t) and Ia(t) are the secondary and the primary circuit. It improves an independent operation mode among
winding currents, respectively. Other currents are the boost converters.
calculated with the same way.
The voltage across secondary windings with the same A. Command Circuit for Regulated Boost Converter
phase than primary ones, Lan, Lbn and Lcn, are reduced by To improve regulated current in boost inductor and
turns ratio n1. Therefore, the relationship between these regulated output voltage, various command circuits such as
voltages is expressed for (08) to (10). constant hysteresis and average current-mode control were
6
%Iia
investigated. The simplest strategy to promote both
5 regulated voltage and regulated current is shown in block
4 diagram in figure 9.
3 This is a conventional scheme to control each boost
2 Harmonic converter. The output voltage error amplifier is used as
orders
1 reference by the current regulator and the output current
0 error amplifier is connected to PWM controller at constant
0 18 36 54 72 90 108 126 144 162 180
Fig. 8. Frequency spectrum for input phase currents
Boost inductors = 1mH (60 turns on core E65-26)
Boost diodes = HFA15TB60
Snubber diodes = HFA15TB60
Snubber inductor Ls = 2µH (4 turns on core E30-7)
PWM Controller
and Gate-drive Snubber capacitor Cs = 47ηF
Kc Kv Output capacitors Co = 470 µF
Current error
amplifier Current sensor = LA-25PN
I ref Voltage error
- Vref PWM circuit = LM 3524
- + amplifier + Operational amplifier = LM 324
Fig. 9. Command strategy for one boost converter
Optocoupler = HP 2211
frequency. Anyway, all boost converters operate Figure 11 shows a detail of the main switch turn-on
independently and decoupled. Therefore, the synchronism transition with the snubber circuit installed.
among them is not necessary. Figure 12 shows the most important result of this work.
In order to connect all boost converters in parallel, only It shows the waveforms for input current and input voltage
one voltage regulator is necessary. Fortunately, the in the same phase. We can observed the shape of input
command circuit becomes simpler, as shown in figure 10. current between experimental result (fig. 12) and
mathematical results (fig. 7) are the same. The input PF
IV. EXPERIMENTAL RESULTS and the THD of the input current measured are equal to
0.99 and 8.8%, respectively.
A prototype rated at 12kW, input line voltage equal to Figure 13 shows the three currents displaced by 20o in
380V and DC output voltage equal to 600V has been built phase. With this figure we can visualise one phase of each
and tested in the laboratory. The implemented circuit is three-phase systems (Ia1, Ian and Ia2).
shown in figure 10. The boost inductor regulated currents are shown in
To reduce the stress current due the recovery diode and figure 14.
to reduce the turn-on losses on IGBT, a regenerative Figure 15 shows the efficiency of the converter – boost,
snubber circuit (Ls, Ds1, Ds2 and Cs) [05] is used. autotransformer and total.
The more relevance components and the main
specifications are reported as follows. V. CONCLUSION
Primary windings N(La, Lb, Lc) = 330 turns with
20AWG wire In this paper we presented a three-phase high input
Secondary windings N(Lan, Lbn, Lcn) = 40 turns with power factor rectifier, intended to be used in the design of
15AWG wire a 12kW rectifier unity for telecommunications.
Secondary windings N(La1, Lb1, Lc1) = 114 turns with The converter is composed of a 18-pulse rectifier based
15AWG wire on a differential Y-connected autotransformer and three
Secondary windings N(La2, Lb2, Lc2) = 114 turns with six-pulse diode bridge, and three boost DC-DC converters.
15AWG wire From the studies reported in this paper, we draw the
Central area of the “EI” three-Limb core = 27cm2 conclusion as follows:
Three-phase bridge = SKD 30/08 A1 (Semikron) 9 The proposed circuit works according to the predicted
Active switch = IGBT (IRG4PC30W) models;
5 Ls Db1
Cs
+Vcc
S1
Ds1 Ds2 Snubber 199k
+Vcc Gate
Co Ro
100u 1k
1k Source Db2
+ -
LA-25PN
M
Va Drive +Vdd 27
139 +Vcc
10k 1k Gate
Vb HP2211
2222
15V
1 3 15 2 8 15V
7 2907 Source
470p 3 5 6
Vc N +Vcc
13
12
2907
120p
LM3524 1k 4.7V 10u
11
100k 62k
14
9 10k
2
33u 16
3.3V
7
6 10n
2.2k
10 8 5 4
Autotransformer BOOST 1
33p
BOOST 2 100k 100n
47k
-
10k +Vcc
+
LM324
5k
BOOST 3 +Vcc
Is L1
Fig. 11. Detail of the main switch turn-on transition Fig. 14. Boost inductor currents
(200ηs/Div, 100V/Div, 5A/Div) (200µs/Div, 5A/Div)
100
Efficiency (%)
I ia Boost
98
Autotransformer
96
Total
94
Va 92
Output (kW)
90
2 3 4 5 6 7 8 9 10 11 12
Fig. 15. Efficiency
Figure 12: Input current and voltage 9 It employs three active switches that make this
(2.5ms/Div, 100V/Div, 10A/Div) rectifier simpler and more reliable than the rectifier
with six active switches.
9 It is controlled by very simple PWM dedicated
I Lb1 +20o integrated circuit, not requiring multipliers.
I Lan 0o It is the author’s opinion that the proposed rectifier is a
good candidate for 12 kW power supply design for
I Lc2 -20o
telecommunications, with many advantages over the
topologies presently being used in these applications.
VI. REFERENCES
[01] J. W. Kolar, F. C. Zach “A Novel Three-Phase Utility
Interface Minimizing Line Current Harmonics of High-Power
Telecommunications Rectifier Modules”, IEEE Trans. on
Industrial Electronics, Vol. 44, pp. 456-467 Aug. 1997.
[02] Paice, Derek A. "Power Electronic Converter Harmonic
Multipulse Methods for Clean Power", N.Y., IEEE Press,
1996.
Fig. 13. Bridge input currents displaced by 20o in phase [03] S. Choi, P. N. Enjeti, I. J. Pitel "Polyphase Transformer
(2.5ms/Div, 5A/Div) Arrangements with Reduced kVA Capacities for Harmonic
Current Reduction in Rectifier-Type Utility Interface", IEEE
9 The input power factor and current THD are equal to Trans. on Power Electronics, Vol. 11, pp. 680-690, Set. 1996.
0.99 and 8.8%, respectively; [04] G. Spiazzi, F. C. Lee “Implementation of Single-Phase Boost
9 The low frequency 18-pulse autotransformer is rated
Power-Factor-Correction Circuits in Three-Phase
Applications” IEEE Trans. on Industrial Electronics, Vol. 44,
at 22% of the output power. Therefore, the weight and pp. 365-370 Jun. 1997.
volume are compatible with the telecommunication [05] A. Pietkiewicz and D. Tollik “Snubber circuit and Mosfet
power supply specifications. Paralleling Considerations for High Power Boost-Based
Power-Factor Correctors” Proceedings of INTELEC’95, pp.
41-45, 1995.