Table of Contents
Introduction..................................................................................................................................................... 4
Cautions........................................................................................................................................................... 5
Special Attentions............................................................................................................................................ 6
Chapter 1 Safety Rules and Precautions of Gas Generator Set........................................................................7
1.1 —Safety introduction - danger classes...................................................................................................... 7
1.2 Safety rules................................................................................................................................................ 8
1.3 General safety precautions.......................................................................................................................13
Chapter 2 Overview....................................................................................................................................... 19
2.1 Description of gas generator set...............................................................................................................19
2.2 Performance characteristics of gas generator set..................................................................................... 20
Chapter 3 Main Parts of Gas Generator Set and Characteristics................................................................ 21
3.1 Introduction of gas engine....................................................................................................................... 21
3.2 Engine operating principle.......................................................................................................................23
3.3 Installation and connection requirements of gas generator set................................................................ 24
3.4 Engine diagram........................................................................................................................................27
Chapter 4 Circuit System...............................................................................................................................31
4.1 Starting system.........................................................................................................................................31
4.2 Electronic ignition system....................................................................................................................... 36
4.3 Electronic speed governing system..........................................................................................................38
4.4 Process of air/fuel rate control system..................................................................................................... 42
Chapter 5 Lubrication System....................................................................................................................... 43
5.1Engine oil pump........................................................................................................................................43
5.2 Engine oil filter........................................................................................................................................ 43
5.3 Engine oil cooler......................................................................................................................................44
5.4 Oil pan..................................................................................................................................................... 44
5.5 Lubricating system flow chart................................................................................................................. 46
Chapter 6 Cooling System............................................................................................................................. 49
6.1 Water pump..............................................................................................................................................50
6.2 Radiator................................................................................................................................................... 50
6.3 Fan........................................................................................................................................................... 51
6.4 Thermostat............................................................................................................................................... 51
6.5 Cooling system flow chart....................................................................................................................... 53
Chapter 7 Air Intake and Exhaust System..................................................................................................... 54
7.1 Air intake system..................................................................................................................................... 54
7.2 Air intake system flow chart.................................................................................................................... 57
7.3 Air exhaust system................................................................................................................................... 58
Chapter 8 Operation Instructions for the Control System..............................................................................60
8.1 Cautions................................................................................................................................................... 60
8.2 Overview................................................................................................................................................. 60
8.3 Outer appearance of the control system...................................................................................................62
Operation Manual of Gas Generator Set
Introduction
Thank you for using our gas generator set. This manual is formulated to enable you to properly
use and maintain your generator set so as it can serve you reliably.
This document mainly describes the technical specifications, use, calibration and maintenance of
the general models of gas generator set. With the development of the market, we will make
continuous improvements of the existing products and develop new models while revising the
The gas generator set is made by combining the gas engine we develop with the generator set.
Technical improvements and innovations are made to the structure of the engine to adapt it to the
performance of the gas generator, including our proprietary technology. The gas engine drives the
LEROY-SOMER generator on the same chassis, and form a gas generator set together with a
As improper installation, maintenance or part placement will cause serious injury and even death,
operation and maintenance staff of devices must receive and pass professional training before they
are allowed to operate the set and install the electrical and mechanical components.
4
Operation Manual of Gas Generator Set
Cautions
Read carefully the use and maintenance manual of gas generator set before using the product to
learn the structural features and the operation methods of the gas generator set.
Engine oil specific to engines is used for the generator set (at the grade of 15W40 CD or above) at
the general ambient temperature, and lubricant must be clean to make the engine oil waterproof. In
changing to a different type of engine oil, wash the lubricating system before adding the new
To use the generator set in a cold environment (at an ambient temperature of below 5℃), the
antifreeze liquid with a condensation point suitable for the ambient temperature should be chosen
(generally, with a freezing point of 10℃ lower than the lowest temperature in the place of use ).
Alternatively, add hot water before the set is started up and discharge the water once the set is
stopped.
All failures and losses caused due to overload and over-speed of the gas generator set are not
Once a set is stopped because of any fault, switch off the gas valves, leave the set stopped for
several minutes until the fault is removed. After operating the jigger for several times, switch on
The gas valves on the gas pipe must be switched off when the generator set is in a stand-by status
After several attempts of start, switch off the gas valves first and start the set. The residual gas
In case of a gas leak in the generator room, cut off the gas valves and never start the set. Open the
door and ventilator to exhaust the inflammable gas from the room. All working equipment in the
generator room are explosion-proof. Do not smoke or light a fire inside and around the generator
room.
Learn the section "Safety Rules and Precautions of Engine", especially the parts marked with
"Danger" or "Warning" before reading the instruction of gas engine in order to prevent the engine
5
Operation Manual of Gas Generator Set
Special Attentions
☆ Hang a board with such words as "Staff Only" outside the generator room.
☆ Check if there is leakage of the gas pipe regularly and keep the generator room well ventilated.
☆ Following the operation code to avoid causing economic losses and even casualty.
☆ Prepare complete operation records and assign dedicated staff for maintaining the set.
☆ Keep clean within and outside the generator room and the set under good working conditions.
6
Operation Manual of Gas Generator Set
The danger class legends used in this document are also applied to our H-series generator set
products. Such legends cover all the dangers mentioned in this document.
Danger it indicates a danger with a high risk. Ignoring such danger will cause death or grievous
bodily harm.
Warning it indicates a danger with a medium risk. Ignoring such danger may result in death or
Caution it indicates a danger with a low risk. Ignoring such danger may result in minor or
moderate injuries.
protection. Ignoring such tip may result in failure of the machine or physical losses.
7
Operation Manual of Gas Generator Set
Before using the generator, read the operation manual and get familiar with your equipment. The
equipment will only run safely and effectively under correct operation and maintenance. Many
accidental injuries are resulted in incompliance with the general and safety rules. The following
symbols in this document are used to warn the operation and maintenance staff of potential
dangerous conditions:
☆ The gas pipe must have an adequate safety guarantee without leakage. It must be firmly
☆ Ensure that all the inlet pipes of fuel gas are provided with control valves.
☆ Do not smoke when checking and repairing batteries. Lead-acid batteries will generate
hydrogen which will explode in contact with an electric arc or a flame of cigarette.
is leakage in the exhaust system and follow the maintenance schedule. Ensure the exhaust pipes
are installed and fixed. Do not use the exhausted waste gases to warm the room. Make sure the
☆ Keep all parts safe. Check if they are fastened, supports and pipe clips are positioned, and
protective covers of turning parts such as belts and fans are closed.
☆ Do not approach parts that may turn or work on electric equipment wearing loose clothes or
metal ornaments as the loose clothes may be drawn into the turning parts and metal ornaments
☆ When the set is running and needs calibrating, stay away from the hot or turning parts.
8
Operation Manual of Gas Generator Set
☆ Keep hands, clothes and metal ornaments far away from turning parts and eclectic equipment.
☆ When checking and maintaining the generator set before start, disconnect the battery cables to
☆ Keep all parts safe. Check if they are fastened, supports and pipe clips are positioned , and
protective covers of turning parts such as belts and fans are closed.
☆ Place dry wooden plates on the metal or reinforced floor around the electric equipment, and
☆ Do not attempt to solve an electric fault wearing wet clothes and shoes, or non-insulating
☆ A voltage of above 36V may result in personal injury or even death. Do not change any
☆ A prominent label should be affixed onto a switch which is off to prevent other people's
☆ The generator set must be connected to the mains via a parallel control system instead of
directly. Otherwise the equipment and the electric power system will be damaged or burned.
☆ Leave the relevant place immediately. Go outdoor to have fresh air immediately.
☆ Close the safe gas plugs outside the generator room and the dangerous zone, and take
9
Operation Manual of Gas Generator Set
☆ Do not re-enter the related areas except in the following circumstance: with the help of the fire
brigade, the danger, failure or damage has been removed, all space has been ventilated
thoroughly, and the safety system re-sends a signal allowing entry into relevant areas.
☆ Note: as the environment and use conditions vary with devices, an emergency plan must be
made to take into account the specific environment and use conditions before any worker
operates on a device containing toxic gases. And pay attention to the provisions of applicable
laws. Every person operating the equipment must confirm that he has understood the
emergency plan.
10
Operation Manual of Gas Generator Set
Personal Protection
☆ Only professionals who have received related electric or mechanical training can run or
☆ Only such people (professionals) can enter the generator room and they must have read and
☆ Under all circumstances, follow the instructions of prohibition, danger, indicative and warning
signs. Ignoring such signs may result in personal injuries or equipment damages.
☆ Wear protection equipment for the body, head, eyes, ears and respiratory system that is
accepted by relevant authorities. Do not wear loose clothes, jewelry or wear long hair loose
☆ Standard protection kits required for entering the generator room, or approaching or operating
the equipment outside the generator room, include goggles, protective suit, gloves and safety
shoes.
☆ Use hearing protective earplugs, helmet, fall-arrest system, mask or other person protection
kits based on the operation status, environment conditions, working method or place.
☆ Use your good judgment to avoid danger and wear applicable personal protection kits.
☆ Anyone drunk or under the effect of drug is not allowed in the generator room, since he may
☆ You must comply with applicable local safety rules and regulations. JAP
☆ Injuries may be caused dependent upon the operation status or operation of equipment, so
The example below is for reference only. when the equipment is running,
☆ Put up earplugs for hearing protection, goggles, protection suit, safety shoes and protection
gloves!
☆ Note: Many parts of the equipment and engine are heavy. There is a potential risk of being
injured for the weight of such parts. Put up your safety shoes, protection suit and gloves!
11
Operation Manual of Gas Generator Set
and obstacles.
☆ Pipelines and containers with pressure: Such media as cooling water and lubricating oil are of
☆ Operation exposed to dust: Change the air filter regularly, keep clean and change activated
carbon......
☆ Using acids, starter batteries, detergents, engine oil, antifreezer and antiseptic, or chemicals:
personal fall-arrest system composed of safety belt and relevant kits (safety rope, spring
12
Operation Manual of Gas Generator Set
1) Prior observation
When receiving an engine of a gas generator set, read carefully the safety rules in the operation
and maintenance manual. Keep the manual properly for use when maintaining the engine. Where
the service network is appropriate, we adopt the standard rules for gas generator set and provide
test and maintenance services. Original parts are preferred to keep the machine running well when
the parts need replacing after the machine run for a period of time. Such parts are under strict
2) Fume discharge
Gases emitted from internal combustion engines contain toxins which can cause injury and even
death if being inhaled by accident. That is why an exhaust pipe is installed along with the engine
to exhaust the fume out of the engine. Any concealed space should be adequately ventilated with
3) Engine fuel
If the engine cannot be started after three attempts or more or it stops automatically, turn off the air
supply valve and then try to start the engine again until all the unfired gases left in the cylinders
are exhausted. Otherwise the gases may be fired to cause explosion when the engine is started.
As the engine fuel is inflammable and likely to cause explosion, it must go through a good piping
system without any leakage or crack. In addition, it must be designed to stand the break due to
shock. Maintain the natural ventilation in the generator room to prevent explosion caused by gas
leak.
All installed engines must have a safe and reliable emergency device that can cut off the fuel
output. The inlet pipes with a pressure for fuels such as natural gas or liquefied gas must be
provided with a manually controlled system to cut off air supply (a manual or automatic valve).
The system must be separated from the mixer or the gas control system.
Operators are fully responsible for ensuring that there is no gas leak or residual gases in the engine,
5) Protection devices
13
Operation Manual of Gas Generator Set
Safety protection devices should be installed along with the internal combustion engine to protect
the safety of persons and articles, especially the items close to the turning or engine parts.
6) Blowby gas
All gas engines include a crankcase breather and an exhaust pipe to mitigate the pressure
cumulating in the crankcase as the solid gas flows into the piston ring. Check whether the
crankcase breather and the pipe are installed at the right positions and not blocked.
When an engine is running or the water temperature is high, do not loosen the pressure cap. If the
cap is released by accident, the hot water will come out to cause serious burn since the pressure in
the cooling system is very high. Do not release the cap from the heat exchanger, thermometer box,
evaporator or radiator until the engine and the water are cooled. And regularly replace problematic
8) Ignition system
The ignition system is charged. Avoid direct contact with the system and circuits.
If the discharge capacitor of the electronic ignition module is still running, the spark plug is likely
to be fired as the electricity from the capacitor will activate the spark plug and the spark may light
up the residual gas in the cylinder to result in serious injury and an accident.
Switch off the power when rewiring the electric ignition module.
Protect the spark plug, coils and cables from storm and snow.
9) Generator
When operating a generator, avoid touching its electric power system as its voltage can cause
serious injury or even death of operators. Before the operation, make sure the power system is
properly grounded. Be more careful if the surroundings of the generator room is humid. When
maintaining the power system or connecting wires, do cut off the main power supply. When
In case of electric shock in an emergency, switch off the generator immediately. If it is impossible
to turn of the generator, remove the injured from the closed circuit with a dry board or stick or an
14
Operation Manual of Gas Generator Set
insulating tool instead of by hand. If the victim is unconscious, perform necessary first aid on him.
Keep the surroundings of the generator room neat and clean. A good work environment helps
reduce accidents.
When doing the above jobs, do power off the engine and keep all control switches to the off
☆ Do not operate the engine if the any fan blade is found bent, missing, replaced or damaged;
☆ Do not operate the engine if the fan is found in touch with any part of the engine or the center
of the radiator;
☆ Do not attempt to repair or balance the blades, and consult the fan supplier if necessary;
☆ Check carefully if all the bolts are tightened using the torque suggested by the supplier;
☆ Install the fan at the right position and align it to the radiator exactly;
☆ Do not alter or change any part of the engine, particularly make alternations that will
accelerate the engine without content from the technical department for gas generator set;
☆ Do not install any fan unless it is necessary for the engine; And install the specified driving
☆ If the fan or fan rotor contains any plastic part, and the fan was or was working at a super-high
temperature (higher than 120 degrees centigrade), only authorized qualified technicians are
☆ For fans that can turn reversely or with adjustable screw torque strength, do make sure that the
blade positions are right before starting the engine. And check if there is any unmelted ice or
dust or earth on the fan before starting the engine which can cause imbalance of the fan;
☆ Ensure that all the fans, drives and belts are provided with sufficient protection devices.
15
Operation Manual of Gas Generator Set
Take precautions against fire in accordance with local regulations. Place qualified fire
extinguishers at accessible points. All emergency lamps and fire exits should conform to the fire
protection requirements.
14) Detergent
Use appropriate detergents and place them in a ventilated place. Do not breath in the smell of
detergents as it may cause injury to human body. Do not use gasoline and highly inflammable
A broken welding cylinder may cause explosion to result in great damages. Thus such cylinders
must be stored in an appropriate place in accordance with the safety production instructions. If
ethyne is used for welding or cutting, install the fixed valve between the controller and the plastic
hose to keep the controller and fuel tank from the backlash flames which may cause the fuel tank
to explode. Keep the objects of high oil content away from oxygen-contained valves and hoses as
oxygen can cause violent burning as soon as mixed with such objects.
If electric welding is required for the engine, lay the grounding wire close to the welding spot. If
the wire is too far, the electric arc may be produced on a shaft to ignite the engine oil.
Ensure that all tools have been grounded. Use eye protection. Do not operate in a humid place.
The tools should perform well and with protection. Unplug the cable from the power supply
18) Batteries
When using the battery on the engine or its device, remove the grounding wires from the battery to
19) Pay attention to the followings when starting the engine if batteries and auxiliary cables (for
Do not use icebound batteries to start engine since they may cause explosion and breaking. If you
suspect that the batteries are icebound, check all the filler plugs. If any icebound mark is found or
16
Operation Manual of Gas Generator Set
the electrolyte is invisible, do not use such auxiliary batteries or cables to start the engine. Take
The steps below help reduce the risk of causing flames and explosion by connecting one charged
☆ Put down the battery, remove the battery cover, cover the upper part of the battery with a wet
cloth; keep in mind that the voltage of the auxiliary battery is the same as of the uncharged
one;
☆ The anode is marked by a '+' , usually in red, and larger than the cathode in diameter; the
Never use compressed air or fuel gas to clean clothes or the body. Under a high pressure, a drop of
Any one or any staff under the effect of excessive alcohol or drug will endanger other people.
It is common to use acidoids to clean casting or parts of equipment. Pay attention to the followings
☆ Stay away from inflammable sources, sparks and flames in the derusting process;
☆ Do not let acid liquor flow onto cement floor as it will erodes the lime in cement. If the acid
liquor is poured onto the cement by accident, neutralize it with alkali liquor, or rinse the floor
with water;
☆ Acid liquor will react with some metals to produce smell. Generally speaking, the acid in
contact with lime and rusty metal will produce carbon dioxide, though this is harmless. If,
however, the acid contacts with aluminum, zinc, cadmium, tin, sulfur, arsenic and krypton,
toxic and explosive gas will be produced. When using acid in a concealed place, maintain
☆ Seal the bottle cap and place the acid liquor in an appropriate place;
☆ Ensure that the components or containers cleaned by acid are free of damages and leaks since
17
Operation Manual of Gas Generator Set
such damages and leaks will allow the acid liquor to flow to the reverse positions on the
components. In this case, use a lot of water to rinse the reverse positions;
☆ When mixing acid with water, always add acid into water, and never add water into acid;
☆ After using acid, always use alkali for post rinsing and treatment to neutralize the acid and
☆ If possible, remove all the irrelevant metal objects before using the acid for cleaning to avoid
☆ Be careful not to allow the sling to touch the sensitive components of the engine;
☆ Check all points of strength to ensure that there is no poor welding, loose bolt, etc.;
☆ Check all relevant structures to ensure that all supports or equipment can process a weight
☆ When the engine is lifted, ensure that all the equipment is balanced and kept horizontal;
18
Operation Manual of Gas Generator Set
Chapter 2 Overview
A gas generator set includes a gas engine, generator, control cabinet, generator controller, ignition
control module, electronic speed governor, charging generator, common base and engine
mounting.
The diesel engine is redesigned and produced with the gas engine concept based on the world
famous brands of diesel engines and taking into account the burning characteristics of gas in the
cylinder and the control features. Its key parts of the main body are manufactured in accordance
with the advanced international standards for materials, process and accuracy. The special design
The gantry cylinder is made of high-strength cast iron and molded after a number of processes,
with sufficient mechanical strength and rigidity. This improves the stability of the machine as a
whole, facilitates its maintenance, extends its maintenance interval and useful life and saves
The crankshaft is forged in high-strength alloy steel which increases its holistic strength and
rigidity. The crankshaft has a long useful life and high coaxility to keep the machine running
stably.
The electronic mixer developed by our company is adaptive to various gases with a methane
concentration of 30%-50%. The optimal air/fuel ratio is achieved through the automatic electronic
adjustment after the air and the gas are mixed up. Together with the distinctive design of the
combustion chamber, it allows the gas to burn fully, hence reducing the gas consumption,
improving the thermal efficiency of the engine, reducing the emitted NOx hazardous gases and
The electronic ignition system jointly developed by Camda and specialized local manufacturers
comprises a Hall sensor designed for the gas generator set, and dedicated ignition modules,
ignition coils, and high-voltage wires, featuring accurate ignition timing and high ignition energy.
In addition, the spark plug has a long lifetime, improving the starting performance, lowering the
The high-accuracy speed governor for the gas generator set has the strengths of high accuracy
and fast recovery time, and can better adapt to different loads.
19
Operation Manual of Gas Generator Set
The set has a generator of the most famous brand in the world, which has good matching
performance no matter evaluated by the electric, torque, mechanical fit structural features or
(1) Adaptability to various environment, especially harsh environment like coal bed methane,
(2) Optimized winding design ensures better performance of the engine. Regardless of 50Hz or
60Hz, a range of winding forms can adapt to the voltage requirement in different applications. The
standard design of the generator stator winding can perform well under distortion load.
(3) High electric efficiency ensures higher power output of the set.
(5) Reliable AVR can ensure qualified voltage regulating rate to be delivered even under the
20
Operation Manual of Gas Generator Set
All the gas engines manufactured by Camda are designed based on diesel engines by the
principles of gas engine. The special-purpose parts to be altered are produced by specialized
manufacturers and assembled on the same line with that of the original diesel engines. The
ex-factory test is performed with biogas. Such products are not made merely by modifying
finished diesel engines, as a result, unmatched by modified engines regardless of the balance of
moving parts or resistance to thermal load (they are made of better materials than the diesel engine
or redesigned, capable of standing higher exhaust air temperature compared with the diesel engine.
Gas engines feature high temperature of exhaust air mostly due to their low combustion speed.
Engine cylinder
The gas engine is a four-stroke, spark ignition, water-cooled high-speed engine, and of the V type.
There is a cast-iron oil pan under the cylinder, a piston connecting rod for bowl combustion
chamber in the cylinder. The wheel-shaped combined crankshaft with main rolling bearing is
installed in the engine main bearing hole. The camshaft and gas distribution system are provided
internally on the right side facing the flywheel. The transmission gear is arranged in the front gear
housing of the engine. On the left, there are the ignition system, electronic governor system and
inlet system. On the right, there are the exhaust pipe, engine oil filter, engine oil cooler, start motor
and charged engine. The water pump is installed in the front and the oil pump in the front of the
21
Operation Manual of Gas Generator Set
1) Our gas engines are designed and produced with the gas engine concept based on the world
famous brands of diesel engines and taking into account the burning characteristics of gas in the
cylinder and the control features. Its key parts of the main body are manufactured in accordance
with the advanced international standards for materials, process and accuracy. The special design
2) The gantry cylinder is made of high-strength cast iron and molded after a number of processes,
with sufficient mechanical strength and rigidity. This improves the stability of the machine as a
whole, facilitates its maintenance, extends its maintenance interval and useful life and saves
3) The crankshaft is molded by high-strength alloy steel as a whole to improve its holistic strength
4) The Venturi electronic mixer developed by our company is adaptive to various gases with a
methane concentration of 30%-50%. The optimal air/fuel ratio is achieved through the automatic
electronic adjustment after the air and the gas are mixed up. Together with the distinctive design of
the combustion chamber, it allows the gas to burn fully, hence reducing the gas consumption,
improving the thermal efficiency of the engine, reducing the emitted NOx hazardous gases and
Fig.1-3 Mixer
5) The ignition system comprises the ignition control module, ignition coils, high-voltage line and
spark plug. The ALTRONIC ignition system adopted in our gas engines feature high ignition
power, accurate ignition time and easily adjustable ignition time to extend the useful life of the
spark plug, improve the engine's starting performance, lower significantly the knocking risk and
(6) The high-accuracy speed governor for the gas engine has the strengths of high accuracy and
22
Operation Manual of Gas Generator Set
Satisfactory results can only be achieved after you have full understood the engine operating
principle in operating our gas engine. Any part of the engine will affect the operation of the other
The operating process of the gas engine is divided into four strokes: intake stroke, compression
In this stroke, the connecting rod leads the piston to go down, the inlet valve opens and the outlet
valve closes. After the air filtered by the air filter and the fuel gas are mixed evenly in the mixer,
the mixture is suctioned into the cylinder. As the downgoing piston gets to the bottom dead center,
The crankshaft is turned under the inertia effect of the flywheel and moves from the bottom dead
center to the top dead center as the connecting rod pushes the piston. At the same time, the inlet
As the piston gets to the top dead center, the spark plug produces sparks under the high-voltage
current produced by the ignition coils and the ignition signal generator to fire the inflammable gas
inside the cylinder. The high-temperature, high-pressure gas produced during the combustion
pushes the piston to go down, and output power and transmit torque as the connecting rod leads
As the piston moves from the bottom dead center to the top dead center, the exhaust valve opens
and the inlet valve closes. The waste gas in the cylinder after the combustion is pushed out by the
23
Operation Manual of Gas Generator Set
Refer to relevant professional installation standards for the installation and connection
requirements of the gas generator set. This document only describes the installation and
There are 4 mounting brackets on both side of the engine gear housing and flywheel housing.
Each brackets takes four or two holes and can be mounted to the foundation with proper bolts. The
foundation of the land stationary engine has a structure varying with the application condition.
Generally, it is made of reinforced concrete. The foundation for stationing the engine should be
reliable as evidenced by inspection. Its bearing surface should be even. Use adjusting gaskets to
stabilize the engine mounting brackets on the foundation. If the conditions are suitable, install the
leveling guide rails on the foundation, in which case the engine brackets and the foundation are
3.3.2 Hoisting
There are 4 rings on each engine capable of bearing the whole weight of the engine. Use the chain
block or other lifting tools for hoisting. Pay attention: do not let the chain under force press any
parts with thin housing or instruments (try to prevent the rings from bearing bending moment).
Lift the engine mildly to keep it at a horizontal position. Place the engine on a special base or
stable block during the handling and hoisting to prevent the oil pan from directly bearing the
Generally, there is an air filter on the inlet pipe. When an extended inlet pipe is used, ensure that it
has an adequate inlet section and it is preferably not too long or has any abrupt bent. Otherwise,
the inlet resistance will increase to affect the performance of the engine. In addition, pay attention
to the air tightness of the inlet pipe. Otherwise, the engine will be quickly worn.
There is a connecting flange at the outlet of the exhaust pipe. The exhaust connecting pipe outside
the engine generally leads to outdoor or the underground pipe. It is preferably not too long and has
no more than 3 elbows. The inside diameter of the connecting pipe generally is no less than
100mm to prevent from increasing the exhaust back pressure and reducing the output power. The
24
Operation Manual of Gas Generator Set
exhaust back pressure is generally no more than 3kPa. Provide bellows, exhaust pipe supports and
connectors for measuring exhaust air temperature, etc. at proper positions on the outside
connecting pipe. Moreover, do not let the engine exhaust pipe bear the weight of the outside
connecting pipe. Take fireproof, thermal insulation and rainproof measures for the exhaust pipe
The power is output from the flywheel of the gas engine to drive the alternator. Do no install the
horizontal pulley dragging device directly on the flywheel. Do not make the crankshaft and main
25
Operation Manual of Gas Generator Set
LSA 49.1 S4
The LSA49.1generator is designed for multiple typical power supply applications, e.g. standby
power supply, main power supply, regenerative power generation, power for ships, lease and
telecommunication, etc.
The LSA49.1generator complies with the following international standards and rules: IEC 60034,
NEMA MG1.22, ISO 8528, CSA, CSA/UL, and relevant classification society rules. It can be
used for CEc certified generator sets. The LSA49.1 generator is designed, manufactured and
☆ Class H insulation
☆ Voltage range:
☆ The module R791complies with the (CE labeled) EN55011 GROUP 1 CALSS B in Europe.
26
Operation Manual of Gas Generator Set
The figure below shows the positions of main external parts of the engine, filter and other
maintenance points.
Front view
27
Operation Manual of Gas Generator Set
Back view
9. Sealing ring
28
Operation Manual of Gas Generator Set
12. Oil pan land cover 24. Inter-cooler water outlet pipe
29
Operation Manual of Gas Generator Set
Top view
30
Operation Manual of Gas Generator Set
In the standard configuration, the starting system of gas engine starts at 24V direct current.
The most common starting approach applied to the engine is by motor, which is characterized by
compact structure, economy and reliability and applicable for long-distance operation and
automatic operation. Its disadvantage is slow power complement of its storage battery. The
battery's discharge capability is highly dependent upon the ambient temperature. In cold areas, if
no proper measures are taken, the engine can hardly be started and even cannot be started.
The motor starting system includes a motor, storage battery, rotary charger and start switch. The
Starting motor
The batteries should be able to supply the starting current required by the technical specifications
of the engine. Lead batteries are an option. The batteries are exclusively for starting purpose.
Our gas engines have a engine-driven charge generator with automatic voltage adjustment to
The emergency gas engine should be equipped with a charger powered by mains to ensure that the
Generally, the standard provides the longest charging time for the battery. The charging current is
calculated as follows:
31
Operation Manual of Gas Generator Set
In cold areas where batteries may be frozen, a battery heater is required to keep the battery
temperature to above10°C.
The battery capacity is determined by the expected minimum average temperature of the starting
environment.
The batteries should be placed for easy inspection of the liquid level, solution adding and cleaning,
and as close as to the starting motor to reduce the voltage drop in the circuit. At the same time,
keep the battery insulated as possible as you can to ensure that its capacity is enough for starting
the diesel engine. However, the battery temperature is preferably no more than 32°C .
Generally, the battery can be charged by the charge generator of the gas engine. In winter, the start
of the engine and the output capacity of batteries are affected by low temperature. The capacity at
-18℃ is approximately 46% of that at 27℃. Additionally, the increased viscosity of engine oil due
to low temperature results in increased power required for the engine to start (normally increased
by 2.5 times. That is why the engine oil should be appropriate in winter to ensure adequate battery
capacity.
Dependent upon the voltage and capacity of the battery, the battery can be connected in series
or parallel to meet the starting requirements. The typical connections are as follows:
Parallel connection
32
Operation Manual of Gas Generator Set
Series connection
33
Operation Manual of Gas Generator Set
There are various general-purpose battery chargers available. The type of chargers selected
depends on other electric devices on the gas engine. Most battery chargers are in one of the
following types:
On a standby engine, if the charge generator is not available to charge the battery, a full-load
repetitive charger will be needed. With a high charge rate (3-30A charging current), this type can
be operated either manually or automatically. However, it may overcharge or heat the battery to
Complementary charger
A complementary charger can be used on a standby engine. This type can maintain the battery
capacity at a less than 2A current when the charge generator goes wrong.
Automatic charger
This charger has an adjustable strong charging function at a charging current of 6-10A, 6-20A or
6-30A) when the battery capacity is insufficient, and a function of maintaining the battery capacity
at trickle current (0.2-1A or 0.5-2A) when the battery has been charged.
Charger
Pay attention to the followings when considering the connection of the electric starting circuit:
Try to reduce the resistance of the circuit, for example, by selecting the wires with suitable section
size and as short as possible to reduce loss from voltage drop. The maximum allowable resistance
for the starting circuit is listed on the performance data sheet of each engine.
34
Operation Manual of Gas Generator Set
Mark the wires for circuit connection separately or use colored wires.
Minimize the number of connections on the circuit. Connections should be firm. The wire joints
must be soldered. Soldering with acidic flux may cause deterioration of joints. Use rosin flux
instead.
The operating voltage of the engine is 24V. Connect the starting battery in series or parallel
When the starting electromagnetic switch is connected into the starting motor circuit, the voltage
drop caused by the total current through the starting motor coils should be more than 2V in the
24V system. If it is more than 2V, when the battery power decreases in winter, the engine may be
hardly started. To maintain the voltage drop within the required limit in the control circuit of the
starting motor, preferably keep the circuit resistance between the battery and the electromagnetic
switch in the 24V system below 0.030 ohms. For this purpose, choose a suitable type of wire to
A standard engine is equipped with an on-line battery box and connecting cable.
The voltage drop of the connecting cable between the battery pack and starting motor in the 12V
system should be lower than 1V; in the 24V system, lower than 2V.
35
Operation Manual of Gas Generator Set
The world's most advanced electronic ignition system produced by Altronic is adopted,
comprising the ignition signal generator, ignition amplification module, ignition coil, high-voltage
line and spark plug. According to the requirements for each cylinder of the engine to work, the
signal generator produces a voltage pulse signal corresponding to the crankshaft position. The
ignition amplification module connects or disconnects the primary circuit of the ignition coil in
time according to the voltage pulse signal to activate the coil to produce a high voltage. Through
the high-voltage line, the spark plug produces sparks in the combustion chamber and fires the gas
mixture. This makes the engine to fire at an optimal angle and output the maximum power at the
Once the power is on through the control center, the indicator begins to flash at an even interval.
After the engine starts, it flashes regularly according to the rotating speed. The flash point is the
ignition point of cylinder 1. Both off and solid on indicates the ignition signal generator center is
problematic. After the spark plug is working for a period of time, tighten the torque to fasten it
36
Operation Manual of Gas Generator Set
High-voltage line
Spark plug
(1) Do not conduct the cylinder fuel-cut test when the machine is running. Never take off the
high-voltage line when the machine is running. Otherwise, it may endanger people and the
machine.
(2) Keep clean the high-voltage parts such as high-voltage transformer, high-voltage line and
high-voltage cap to prevent them from discharging high voltage to the ground to cause the
machine on fire.
37
Operation Manual of Gas Generator Set
The electronic speed governor has such functions as speed control, maximum current limitation
and protection, adjustable steady governor rate, high-low speed switch, and automatic parallel.
control.
发动机 Engine
执行器 Acturator
速度传感器 Speed sensor
控制器 Controller
电源 Power supply
Control
The control generally serve to test the engine speed, actuator drive and rack position to adjust the
engine speed.
Speed sensor
Speed sensor
The speed sensor is a single-coil electromagnetic sensor and fixed on the engine flywheel ring
gear or the outside edge of gear. The turning gear cuts the magnetic lines to produce electric pulse
signals. Whenever the turning engine passes a tooth, a pulse signal is generated.
38
Operation Manual of Gas Generator Set
Electromagnetic actuator
Electromagnetic actuator
The control analyzes the engine status data collected by the speed sensor and sends corresponding
current signals to the actuator. By moving the draw bar controlling the opening of the butterfly
valve through the actuator, it adjusts the working status of the engine. The draw bar is stabilized at
different positions according to the current to control different air inlet volumes. After the power is
cut off, the electromagnetic force disappears, the draw bar returns to the original position, the
1)Speed control
The speed control by the close-loop method can accurately adjust the engine speed. The stability
The dynamic status can be adjusted by the internal gain and differential potentiometer。
The high-low speed switch generally performs switches of low-speed control and rated speed
control. The external speed fine tuning potentiometer can fine tune
the speed deviation and display the battery voltage and speed by setting the number of teeth for
39
Operation Manual of Gas Generator Set
3) Auto-stop protection
When the speed sensor goes wrong, the speed feedback signal disappears or the power supply fails,
Overspeed protection
In the case of overspeed of the set for various reasons, the control system can make the actuator
lose power to stop the engine. The speed for overspeed protection is set to 1650rpm.
Parallel
The speed governor receives input signals from the load distribution device, automatic
synchronizer and other auxiliary devices of the speed governor system to fulfill the parallel
function.
Other potentiometers and switches on the speed governor have been set by the manufacturer and
40
Operation Manual of Gas Generator Set
grid connection .
41
Operation Manual of Gas Generator Set
42
Operation Manual of Gas Generator Set
pressure and splash. The pressure lubricating oil is provided by the gear engine oil pump (engine
oil pump). The lubricating oil pump is on one side of the engine.
The engine oil pump is connected by an oil pipe connecting with the oil pan. An oil screen in the
oil pan filters the engine oil. The engine oil is suctioned out from the oil pan by the oil pump and
flows back into the cylinder through a full-flow or compound oil cooler. The oil filter can be
installed below the oil cooler or in a far distance. Then the engine oil flows into the main oil
A pressure control valve inside the lubricating oil pump enables control over the oil pressure.
When replacing or reinstalling parts, measure the gap between the end surface and cover of the oil
pump gear. If necessary, make adjustments with a gasket made of pergamyn paper. After it is
assembled, turn the driving shaft by hand. The shaft should be turned freely. Otherwise re-align
The lubricating system has an oil filter to remove foreign matters in the
circulating engine oil and avoid damaging shaft or part matching surfaces.
The filter performance has direct effect on the performance and useful life
of the engine. There is a by-pass valve on the head of the full-flow oil
filter to provide insurance when the oil passage is blocked by dirt or the
43
Operation Manual of Gas Generator Set
The oil cooler for the Camda gas engines is of the water-cooled type.
The oil cooler is in a cylinder shape. There is a core inside composed of radiating fins and distance
pieces. Water flows in the tube of the core; oil flows in the interlayer between the core and the
shell.
Clean the oil cooler periodically. When re-assembling the filter, keep the sealing ring balanced and
at the right position. Replace the aged or sticky sealing ring. Otherwise, the oil and the water may
mix up to cause engine failure. When maintaining the cooler, check whether there is any missing
solder or damage to the cooler core. If necessary, make up the solder or cover the apertures at both
ends of some pipes and then continue the use. If the cooling copper pipe is damaged seriously,
When using the engine in a cold area or in winter, drain the cooling water in the engine after it
For all Camda gas engines, the wet oil pan is applied for storing engine oil. When the engine is
working, the working status of the lubricating system is monitored by the oil thermometer,
pressure gauge and dipstick. Oil drain taps are provided on one side of the oil pan and on the
Oil pan
44
Operation Manual of Gas Generator Set
45
Operation Manual of Gas Generator Set
46
Operation Manual of Gas Generator Set
4. Idler wheel
47
Operation Manual of Gas Generator Set
1. Oil supply up to oil filter base 9. Piston cooling oil passage (outside)
2. Engine oil back to oil pan 10. Piston cooling nozzle (outside)
48
Operation Manual of Gas Generator Set
cooling system, by which the coolant circulation is completed by the dedicated cooling water
The so-called closed circulation indicates that the engine cooling system contains a complete
The closed water-cooled engine drives the cooling pump to produce a circulation power which
enables the coolant in the cylinder and cylinder head pipe to continuously circulate and dissipate
heat, and the engine cooling pump and radiator (or heat exchanger) form a closed power
circulation cooling system. The most common cooling system is the radiator and the cooling fan
directly driven by the engine. The alternative is the heat exchanger, far-placed radiator or
Correct design and installation of the cooling system is essential to the performance and useful life
of the engine:
(1) The whole cooling system should be designed and installed to keep the temperature of the
water radiator upper tank no higher than the limit specified on the performance data sheet for the
particular engine.
(2) The cooling system should be able to exhaust surplus air within the time specified on the
engine performance data sheet. Once the empty cooling system is filled up with cooling water for
(3) Expansion space equivalent to approximately 5% of the gross capacity of the cooling system
should be provided in the water radiator upper tank (or expansion water tank).
(4) A venting system should be provided in the cooling system, which enables the cooling system
to be filled up with cooling water at the specified minimum speed within the longest water filling
(5) When the engine with the water radiator is running at a high idle speed or the filling cover of
the cooling system is removed and the cooling water temperature is 82-88°C, the pressure at the
water inlet of the water pump should be higher than the atmospheric pressure, i.e. a positive
pressure.
49
Operation Manual of Gas Generator Set
The water pump of the Camda gas engine is of the centrifugal type and installed on the front part
of the engine. When installing the water pump impeller, check the axial gap between the impeller
When the engine is running for 400-500h, fill an appropriate of grease with an oil gun from the
After the engine working at a low temperature stops, open the drain valve on the water pump
immediately to drain the water left in the pump to prevent it from frost cracking.
6.2 Radiator
The radiator, or commonly known as water tank, is used to dissipate heat by the coolant of the
engine. Use radiators of the same model but with different cooling areas based on the rated power
The radiator is composed of the tube-and-fin radiating core, upper and lower water sinks, air
director and supports. Water radiators require regular maintenance to ensure the heat exchange
between coolant and air. Generally, every 500h of running of the engine, clean the outside and
inside of the radiator. To get rid of the deposits and settled impurities, drain the water in the
radiator, then fill clean water with a certain pressure into the radiator core until the outflow water
50
Operation Manual of Gas Generator Set
is clean.
After the radiator is used for a period of time, repair any leak with solder. Before starting the
engine, inject the coolant into the empty cooling system at an appropriate speed. After filling it up,
stop and waiting for two minutes to allow the air in the system come out and fill the coolant again,
After the engine working at a low temperature stops, open the drain valve immediately to drain the
When installing the radiator, mount rubber shockproof pads provided or special-purpose vibration
absorber between the mounting supports and the common base bearing surface to mitigate the
6.3 Fan
The piercing riveting fan used in the Camda gas engine serves to create forced blowing for cooling
the air-cooled cooling water tank. Use fans of different specifications based on the model and
Check regularly whether the fan is firmly mounted and whether there is any visible deformation of
the blades. If any, make a replacement immediately. Adjust regularly the tightness of the triangular
rubber belt. Too tight belt may results in excessive wear of the bearing; too loose belt may reduce
the air volume of the fan and affect the cooling performance. Inject an appropriate amount of
6.4 Thermostat
The thermostat is used in the Camda gas engine to adjust the operating temperature of the engine
coolant. When the engine starts working, the coolant temperature going through the thermostat is
lower than its starting temperature. When the outlet valve of the thermostat closes, all the coolant
in the engine flows back to the inlet of the water pump for further circulation so as to heighten the
water temperature in the engine. When the coolant temperature going through the thermostat
reaches about 70℃, the outlet valve of the thermostat opens and some coolant in the engine flows
to the radiator through the outlet valve, and the remaining coolant still flows back to the water
51
Operation Manual of Gas Generator Set
pump inlet. When the coolant temperature going through the thermostat reaches about 85℃, the
outlet valve of the thermostat opens fully, the by-pass valve closes fully, and the coolant in the
engine flows to the radiator through the outlet valve. When the outlet valve closes, the air is
thermostat.
are within the specified range when the outlet valve of the
Thermostat
52
Operation Manual of Gas Generator Set
Thermostat housing
53
Operation Manual of Gas Generator Set
The air intake system of the gas engine works to mix the fresh air and qualified inflammable gas
clarified and purified and direct the gas mixture into the cylinder to supply the air and fuel
The gas supply system comprises the air filter, mixer, relief valve and the gas pressure stabilizer
mounted outside the engine. Make sure that the direction of the relief valve is not reverse.
The control valve at the mixer outlet is connected with the speed governor to control the intake air
The main parts of the engine air intake system are described below.
The relief valve is a main part of the pressure stabilization system. As shown in figure 5-1, it
comprises the spring 6, diaphragm set 4, upper housing 5, lower housing 1, lever set 2 and valve
set 3. After the pre-load position of the spring 6 is set to a position, if the intake pressure P1 rises,
the opening of the valve set 3 will increase, thus the outlet gas pressure P2 will increase as well.
At this time, the gas pressure at the bottom of the diaphragm set rises to push the diaphragm set to
move up. The upward movement of the diaphragm set drives the lever set to move, as the result,
the opening of the valve set decreases and the outlet gas pressure drops. When the intake gas
pressure is reduced, the valve set opening is reduced as well as the outlet gas pressure. Then, the
diaphragm set moves down under the force of the spring to increase the opening of the valve set
According to the above working principle, the pressure after the relief valve can remain
unchanged regardless of the increase or decrease of the source gas pressure to ensure a steady
Increased spring pre-load of the spring diaphragm set means increased opening of the valve set,
and heightened gas pressure after the relief valve. Decreased spring pre-load means decreased
opening of the valve set, and reduced gas pressure after the relief valve.
When installed the relief valve, orient its upper arrow to the airflow direction.
54
Operation Manual of Gas Generator Set
Relief valve
55
Operation Manual of Gas Generator Set
7.1.2 Mixer
The Venturi mixer (with national patents) developed by Camda is characterized by accurate
controlled fuel/air ratio, uniform mixing and high reliability, particularly suitable for such fuel
gases as natural gas, biogas, coalbed methane and casing head gas.
The Venturi mixer is a key part of the gas supply system and should be given special protection.
Users must ensure that the source gas pressure is 2-20 Kpa (a pressure indicator is required at the
intake). Moreover, for the sake of safety, provide an individual valve at the inlet of each gas
engine to ensure that the gas can be shut off when the engine is not working due to emergency. To
prevent impurities and hard particles away from the AVR and engine that may affect their useful
lives, a screen is required to be installed at the inlet of the proportioner. The proportioner is an
imported part comprising the mixer body and butterfly valve. If the butterfly valve shaft cannot
turn freely after the proportioner is used for a long time, perform maintenance of them.
Air flows through the Venturi tube at the center of the mixer. The gas surrounds the Venturi tube in
a round cavity and enters into the air flow through the small holes.
The air filter serves to filter dust in the air to mitigate wear of the cylinder housing and parts of the
When the filter is working, the air enters into the internal cavity through the filter intake. When the
air flows by, it drives the blades to rotate. Impurities under the centrifugal force are thrown into
the internal wall of the filter and settled at the dust exhaust mouth. The air then enters into the
central passage through the micropores on the central paper core and to the mixer.
Remove the settled dust regularly by shaking the dust exhaust month to allow the impurities to
flow out.
Every 500h of running, remove the dust in the dust collector. Every 500h, take out the filter core
and knock gently its end or blow compressed air of a pressure of no more than 490kpa(5kgf/cm2)
outward from the internal cavity of the filter core, or brush gently the surface with dirt.
Never use oil or water for cleaning. Otherwise the filter core may be easily blocked by dust to
result in insufficient air intake for the engine and lowered output power. Replace the core if it is
found damaged or too dirty to be cleaned. Pay special attention to the proper use and maintenance
of the air filter. Once the paper core is broken, its sealing surface cannot properly installed to
56
Operation Manual of Gas Generator Set
cause short circuit and thus serious damages to the cylinder, piston and piston ring, and worsen
The inlet pipe is made from cast aluminum and shared by cylinders 4 and 6. When installing the
pipe, ensure that the adjoining plane between the inlet pipe and the cylinder head is airtight. No
impurities are allowed in the inlet pipe. Otherwise, they will damaged the parts if being suctioned
Central-installed inter-cooler
1. To turbocharger inlet
2. Turbocharger
57
Operation Manual of Gas Generator Set
7.2.1Exhaust pipe
The exhaust pipe is made from heat resistance cast iron. Each cylinder shares one exhaust pipe.
Follow strictly the external connection requirements for the exhaust pipe.
Exhaust manifold
58
Operation Manual of Gas Generator Set
7.2.2 Silencer
The silencer is made by welding the silencer body, silencer, exhaust pipe and central partition
together. There are many pores on a section of the exhaust pipe inside the silencer body, which is
divided into two parts by the central partition. When it is working, the waste gas exhausted from
the cylinder enters into the exhaust pipe from the flange end, flows to the internal cavity of the
silencer body through the pores on the right side of the exhaust pipe, and then back to the exhaust
pipe through the pores on the left side of the exhaust pipe. At last, it is exhausted into the
Exhaust pipe
59
Operation Manual of Gas Generator Set
8.1 Cautions
Unless necessary, do not cut off the terminal of the current transformer (CT)!
Read the operation manual provided by the manufacturer when operating components of the
system!
Do not commission or repair the system without receiving professional training or understanding
the drawings!
8.2 Overview
Parameters of the system can be viewed through the human-machine interface (HMI) on the remote
control panel and local control panel, and can be set. Operating and protection parameters can be set
and revised under different management authorities. The system mainly comprises:
The generator set master control panel is installed in the control room. It processes all the
operation data of the generator set and conducts sequence control, logic control and PID control
according to the operation instructions and data. It comprises a PAC, a special controller and a
1. PAC. The high-performance logic controller processes and calculates various analog quantity
parameters connected by the sensor, responds to all the external hard operation instructions (hard
wiring) and soft operation instructions (HMI), and gives corresponding instructions according to
2. The generator set controller collects the alternating-current parameters (including current,
60
Operation Manual of Gas Generator Set
voltage and power) of the fuel gas generator set and the power network, and control the start,
3. The HMI enables users to check the generator set's operation parameter and status, set operation
4. D.C. power supply provides 24V DC current for the whole control system and recharges the
storage battery.
6. Ethernet switch
7. Damp heater
It is the auxiliary control panel installed beside the generators. It comprises the basic voltage and
speed adjusting module of the generator set, concentration point of all generator set data and the
middle connecting point between the remote control panel and the generator set. Data is connected
1. Remote data collection module (Advantech 5000 serial). All analog quantity parameters of the
engine and outside are input into the module and transmitted to PAC through Ethernet after being
processed. Control instructions given by PAC to the accessory devices of the generator set are also
(3) The whole system provides four operation authorities: operator, engineer, administrator and
(4) The operation system interface provides the simplified Chinese and English editions for users.
61
Operation Manual of Gas Generator Set
62
Operation Manual of Gas Generator Set
The human-machine interface, or touch display, enables users to monitor operation data of devices
and operate devices in the automatic system. It follows the WYSWYG principle and is
user-friendly
Main console
燃气发电机组
Fuel gas generator set
Initial page of the HMI, where users can choose the operation language.
63
Operation Manual of Gas Generator Set
Overview
64
Operation Manual of Gas Generator Set
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
手动 停止 自动
Manual Stop Automatic
运行选择 并网选择
Operation Grid Connection
1#散热 2#散热 3#散热 4#散热 中冷水泵
1#Cooling 2#Cooling 3#Cooling 4#Cooling Inter-cooler water pump
进风风机 预润滑泵 加油泵 后冷水泵 风闸选择
Intake air blower Pre-lubrication pump Oil-feed pump Post-cooling water pump
Airbrake selection
The "Manual" position of “Operation selection” and “Grid connection selection” indicates that the
operation switch is turn off on the control panel, the “Automatic” position needs remote signal. The
"Start, Stop" button on the local control panel (on HMI) is equal to the “Start/Stop” operation switch on
the remote control panel. However, operations on the remote control panel have the priority. If a device
is started on the remote control panel, it cannot be stopped on the local control panel; if it is started on
the local control panel, it can be started on the remote control panel.
After the generator set is started, all power network and valve operation selections will fail. Operations
will only become effective two seconds after the "Start, Stop", "Grid Connection, Disconnection"
Before the generator set is started, all pump and valve selection switches must be in the “Automatic”
65
Operation Manual of Gas Generator Set
position, otherwise, the generator set cannot be started as it will fail to pass the safety inspection. The
program can only enter the generator set start program after receiving the valve and pump starting
signals.
66
Operation Manual of Gas Generator Set
The voltage adjustment button is only effective before the generator set grid connection operation. After
the grid connection, the LED turns from yellow into red. The time that the switch is turned on and off
67
Operation Manual of Gas Generator Set
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
线电压 相电流 有功功率 发电频率
Line voltage Phase current Active power Power generating frequency
无功功率 功率因素 视在功率 合闸次数
Reactive power Power factor Apparent power Valve closing time
电度
Electric degree
额定功率 负载比例
Rated power Load percentage
前轴承 后轴承
Front bearing Rear bearing
68
Operation Manual of Gas Generator Set
Engine page
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
机油压力 缸套水压 岐管压力 中冷水压
Engine oil pressure Cylinder sleeve water pressure Manifold pressure Inter-cooler water
pressure
机油温度 缸套温度 岐管温度 中冷水压
Engine oil temperature Cylinder sleeve temperature Manifold temperature Inter-cooler water
pressure
Show the engine oil pressure and various parameters of the engine network.
69
Operation Manual of Gas Generator Set
Failure display
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
报警摘要 总数 日期 时间 点名称 报警值 报警限定 节点名
Warning summary Total number Date Time Spot Warning value Limit Node
火花塞保养 气门保养 通讯超时 急停-就地 急停-内 模块 1 丢失 模块 2 丢失
市电末合闸
Spark plug maintenance Valve maintenance Communication overtime Emergency
shutdown-local Emergency shutdown-internal Module 1 Loss Module 2 Loss Mains
supply fails to switch on
描述 分类 时间 名称 优先级 认可 群组 节点 锁定 范围 高级
Description Classification Time Name Priority Approval Group Node Lock
Scope Advance
认可点 认可屏幕 认可全部 消警 复位
Accept spot Accept screen Accept all Cancel warning Reset
If the system shows failure information, solve the failure first and then tap "Failure Reset". Tap "Cancel
When the page displays the warning information, the words turn red. After the user touches the display,
the words will turn yellow. After the failure is solved, the words will turn green.
70
Operation Manual of Gas Generator Set
Log-in page
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
Log in to the set the generator set's operation and protection parameters. Choose the username and enter
the password according to the authority. Then tap “Enter” to enter the function selecting page.
71
Operation Manual of Gas Generator Set
Basic settings
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
预润滑时 启动时间 稳定时间 怠速时间 并网时间 过载比例 停机后冷
Pre-lubrication time Start time Stable time Idle time Grid connection time Overload
percentage Post-shutdown cooling
后润滑时 启动转速 卸载空转 进风后冷 散热后冷 并网比例
Post-lubrication time Start rotation speed Unload idling Post-ventilation cooling
Post-radiation cooling Grid connection percentage
The idle time is the time between the generator set is started and enters the high speed.
The unloading idle running time is the time that the generator set continues running after the grid is
disconnected.
The time limit for grid connection is the time permitted for network connection after the network
connection switch is turned on. If the breaker is not turned on within the time, the grid connection
72
Operation Manual of Gas Generator Set
Protection setting
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
正常保养 小时 火花塞保养 小时 气门保养 小时
Normal maintenance Hour Spark plug maintenance Hour Valve maintenance Hour
已运行 小时 清零
Operating time Hour Reset
After maintenance, reset the system. Otherwise, information will remain in the system.
73
Operation Manual of Gas Generator Set
Protection setting 1
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio Failure
Log in Record
主水压高 主水压警 主水压停 主水温警 主水温停 辅水压警 辅水压停
High main water pressure Warning main water pressure Shutdown main water pressure
Warning main water temperature Shutdown main water temperature Warning accessory
停机延时
Warning high oil temperature Warning high exhaust temperature Shutdown high exhaust
74
Operation Manual of Gas Generator Set
The main water is the jacket water. The auxiliary water is the intercooler water, or low-temperature
water.
The high manifold temperature refers to high temperature of the intake manifold, or high MAP
temperature. If the auxiliary water temperature is low, while the MAP temperature is high, the
The delay time of all warnings is the same, so is that of the grid suspension.
Note that the protection setting has two pages. Tap "Next page" to enter the next page.
75
Operation Manual of Gas Generator Set
Protection setting 2
首页 整体 并网 交流 引擎 空燃比 故障 登录 记录
Home page Overall Grid connection Communication Engine Air-fuel ratio
Failure Log in Record
逆功分闸 逆功急停 电流失衡 电压失衡 高频报警 高频急停 低频报警 低频
急停
Reverse power disconnection Emergency reverse power shutdown Current unbalance
Voltage unbalance Warning high frequency Shutdown high frequency Warning low
frequency Shutdown low frequency
过流报警 过流急停 压高报警 压高急停 压低报警 压低急停 超速报警 超速急停
Warning over current Shutdown over current Warning high voltage Shutdown high
voltage Warning low voltage Shutdown low voltage Warning high speed Shutdown
high speed
The page enables users to set the A.C. current protection parameters.
76
Operation Manual of Gas Generator Set
Air-fuel ratio
The page enables users to adjust the air-fuel ratio and initiate the start grid according to the content of
methane. Users can judge whether to adjust operation of the grid according to the methane content.
Speed adjustment
This page shows parameters relating to engine rotation speed adjustment and limitation.
78
Operation Manual of Gas Generator Set
Real-time trend
点名称
Spot name
值 最高显示 工程单位
Value Highest Engineering unit
描述
Description
新的点 改变值 报警曲线图 认可点 认可群组
New spot Change Warning curve Accepted spot Accepted group
Users can choose necessary operating parameters and collect them at an interval of one minute. A text
79
Operation Manual of Gas Generator Set
4. Check the pressure and gas volume of the starting and instrument gas.
5. Check whether the selection switches are in the right position and whether the water valve
selection switch, pre-lubrication valve, bearing lubrication pump and water pump selection
6. Check whether the manual water, oil and gas valves are opened.
8. Enter the HMI “overall” page, check whether the generator set is prepared. Note that the
Turn the “Start, Stop” switch on the remote control panel to the right (read LED) for more than 2
seconds, the generator set will enter the self-check program. First, three kingston valves will be
opened and the electric ball bearing lubricant pump set will enter the "Pre-lubrication" status. Start
the pre-lubrication motor to pre-lubricate the engine (the pre-lubrication LED on the meter panel
turns red and flicks). After the pre-lubrication completes, the motor will stop. Start the pneumatic
motor to drive the engine (the motor LED on the meter panel turns red and flicks). Start the
ignition system and main fuel valve is opened. When the rotation speed reaches the starting motor
escape speed (HMI setting), the generator set is started and enters the idle status. If the rotation
speed fails to reach the idle value within the starting protection time (internal setting), the
generator set is not started and the starting motor will be stopped and a warning will be made.
Cautions:
1. In the starting process, turn the "Start, Stop" switch to the left (Green LED) at any time for
more than 2 seconds, the starting program of the generator set will be stopped immediately.
2. Pay attention to the touch screen, rotation speed, pre-lubricant pump and starting motor and to
the countdown of the status. The main fuel valve's opening status can also be monitored.
4. The operation halt before the closure of the generator breaker and the grid connection will not
80
Operation Manual of Gas Generator Set
After the generator set is started, it enters the idle status. During the period, various operating parts
of the generator set will be pre-heated and pre-lubricated. The time of the period can be set on the
HMI. In the idle speed status, the generator set is under protection.
Cautions:
1. In the idle speed operation period, turn the "Start, Stop" switch to the left (Green LED), the
2. The low oil pressure, high water temperature, high water pressure, low water pressure, high
rotation speed and high voltage protection is triggered in the idle speed rotation status.
3. Pay attention to the touch screen in the idle speed status. Parameters including the rotation
speed, oil pressure and water temperature can be monitored. The opening status of the main fuel
valve can be displayed. Pay attention to whether the rotation speed is stable and other parameters
5. Users can monitor the countdown of the idle status on the generator monitoring page.
After the idle operation ends, the generator set starts to accelerate to the rated speed and enters the
high speed status. The touch screen shows "Accelerating" in the generator set status column.
When the rotation speed of the generator set is close to the rate one (set in the HMI), the automatic
voltage stabilizer starts to work and the output voltage will be stabilized at the rated voltage.
When the generator set's voltage and frequency are stabilized at the rated status, the set enters the
status operation (stable high speed) status, users can slightly adjust the voltage and frequency on
the touch screen. In the stable operation status. all parameters should be in the normal range,
except those related to the load, and all protection measures are triggered.
Cautions:
1. In the high speed operation period, turn the "Start, Stop" switch to the left (Green LED), the
2. Pay attention to whether the voltage and frequency of the generator set are stable and whether
the differences in the voltage and frequency between the generator set and grid are normal.
3. Pay attention to whether various operation parameters of the engine are normal.
81
Operation Manual of Gas Generator Set
After a period of stable operation (stable high speed) (set in the HMI), if the “Parallel,
Disconnection” operation switch on the remote control panel is turned on the right (red LED) for
more than 2 seconds, the generator set will automatically enter the parallel operation program. The
generator set is the first generator set. If the program detects no voltage signal on the bus line, it will
directly give the switch-on instruction; if it is not the first parallel operation generator set and the
program detects voltage signal on the bus line, it will automatically start the frequency, voltage and
phase angle tracking program and give the switch-on instruction in the synchronizing range.
Cautions:
1. After entering to parallel operation program, the generator set's voltage and frequency cannot be
adjusted manually.
2. The synchroscope on the touch screen shows whether the parallel operation is tracked.
3. Power is only supplied for the under-voltage tripper only when the generator set enters the stable
high speed status. Therefore, a minor sound in the parallel operation breaker is normal when the
4. There are many settings of the generator set parallel operation in the controller. These items are set
during commissioning. Users can only revise the parameters with instructions of Camda's
technicians.
5. Do not open the door of the low-voltage panel breaker cabinet during parallel operation to ensure
safety.
6. In case of any abnormal conditions during parallel operation, turn the “Parallel operation,
Disconnection” operation switch to the left (green LED) for more than 2 seconds or press the
emergency button.
7. If the parallel operation fails within the specified time (set in the HMI), the generator set will give
(7) Loading
After the grid connection breaker closes, the power will be increased according to the target power.
When the power reaches the target one, it will fluctuate slightly.
Cautions:
1. During the loaded operation, turn the "Start, Stop" and "Grid connection, Disconnection" operation
82
Operation Manual of Gas Generator Set
switches to the left (green LED) at any time for more than 2 seconds, the generator set will
immediately enter the unloading and disconnection program. If the "Start, Stop" switch is turned, the
generator set will first unload and disconnect before cold shut-down and the back cold program will
be implemented no matter how long the generator set has operated. If the "Grid connection,
Disconnection" switch is turned, the generator set will only unload and disconnect, and continue to
(8) Unloading
If it is necessary to shut down the generator set for maintenance or other reasons, turn the "Start,
Stop" switch to the left (green LED) for more than 2 seconds, the generator set will immediately
enter the unloading and shutdown program. The system will automatically reduce the load (according
to the unloading rate). When the load is decreased to the min load, the grid connection breaker will
automatically open. After the generator set continues to operate under an idle load for a period (set in
the HMI), cut off the main fuel valve and the generator set stops and enters the "Prepared" status for
After the generator set is shut down, the pre-lubrication oil pump will be started immediately to
(10) Standby
After the shutdown, the generator set enters the "Prepared" (standby) status to wait for the next start
instruction. The protection systems for the generator set is stopped, with only the safety protection
83
Operation Manual of Gas Generator Set
While fulfilling the generator set operation and parallel operation, the control system provides
comprehensive protection and warning for the generator set and accessory devices as well as
1. Safety protection system. Each generator set has an IR flame detector and a flammable gas alarm
2. Generator set protection system. The control system provides comprehensive protection for the
entire generator set, including each operation link and platform. For critical links, the system also
3. The failure protection system has three levels. The first level is warning. The control system can
give a warning and unloading signal. The second level is normal shutdown. The system will give a
warning, unload the valve and shut down the generator set. The third level is emergency shutdown. It
will shut down the generator set and give a warning at the same time.
84
Operation Manual of Gas Generator Set
Any failure, if not processed properly, may cause personal injury and equipment damage, or even
In case of any failure to the generator set, follow the instructions on the human-machine interface
1. Check if there is any information about the failure, parameters of the generator set on HMI are
normal, the generator set is prepared, pre-lubrication is normal and the motor control valve is
2. Check whether the fuel gas pressure and composition are normal and battery's voltage drop is
4. Check whether the spark plug is moistured and ignition parameters are normal.
1. The generator set cannot enter the high speed operation status. Check whether PAC sends the
conversion signal and whether 2301D speed adjustment panel receives the signal.
2. The rotation speed is not instable. Check whether the gas pressure is normal, the air-fuel ratio can
3. The pressure and speed cannot be adjusted manually. Check whether the generator set is in the
high-speed stable status. Check whether AGC-3 outputs pressure adjustment signal and whether the
Check whether the pressure and speed can be adjusted manually, whether the synchroscope can work,
breaker is recharged, under-voltage tripper of the breaker is powered, rotation speed of the generator
set is stable, and the generator set's voltage and frequency are stable.
1. The active power is not well distributed. Check whether the rated power setting is normal, speed
85
Operation Manual of Gas Generator Set
adjustment valve is opened, the output of the speed adjustment panel is normal, AGC-3 speed
2. The reactive power is not well distributed. Check whether the AGC-3 speed adjustment signal is
normal, setting of the pressure adjustment panel is normal and the voltage of the generator set is
abnormal.
86
Operation Manual of Gas Generator Set
8.7 Appendix
Settings of parameters
Serial
Parameter Scope Unit General setting
Number
1 High main water pressure 300-500 kPA 400
2 Warning main water pressure 150-300 kPA 180
3 Shutdown main water pressure 100-200 kPA 120
4 Warning main water temperature 70-90 ℃ 85
5 Shutdown main water temperature 80-100 ℃ 88
6 Warning high exhaust temperature 600-700 ℃ 650
7 Shutdown high exhaust temperature 600-700 ℃ 680
8 Warning high manifold temperature 40-70 ℃ 65
9 Shutdown high manifold temperature 40-70 ℃ 68
10 Warning accessory water pressure 150-300 kPA 180
11 Shutdown accessory water pressure 100-200 kPA 120
12 Warning accessory water temperature 40-80 ℃ 65
13 Shutdown accessory water temperature 40-80 ℃ 70
14 Warning high oil temperature 60-90 ℃ 85
15 Shutdown high oil temperature 60-90 ℃ 88
16 Warning low oil temperature 250-500 kPA 350
17 Shutdown low oil temperature 250-500 kPA 300
18 Warning delay 0-10 s 5
19 Shutdown delay 0-10 s 5
20 Generator room temperature warning 40-60 ℃ 48
21 High cylinder temperature warning 700-720 ℃ 700
22 High cylinder temperature shutdown 700-750 ℃ 720
87
Operation Manual of Gas Generator Set
Protection setting
Serial
Parameter Scope Unit General setting
Number
Emergency reverse
1 0-20 % 15
power shutdown
2 Current unbalance 0-20 % 15
3 Voltage unbalance 0-10 % 6
High frequency
4 90-110 % 105
warning
High frequency
5 90-110 % 108
emergency shutdown
Low frequency
6 80-100 % 95
warning
Low frequency
7 80-100 % 92
emergency shutdown
Over current
8 90-120 % 105
warning
Over current
9 90-129 % 110
emergency shutdown
High voltage
10 100-110 % 105
warning
High voltage
11 100-110 % 108
emergency shutdown
Low voltage
12 90-100 % 95
warning
Low voltage
13 90-100 % 92
emergency shutdown
14 Over speed warning 100-110 % 105
Over speed
15 100-110 % 108
emergency shutdown
Reverse power
16 0-20 % 8
disconnection
88
Operation Manual of Gas Generator Set
Before using our engine, select appropriate fuel gas, engine oil and coolant based on the particular
application environment and conditions. The useful life of the engine is largely dependent upon
The Venturi mixer (with national patents) developed by Camda used in our gas generator set is
characterized by accurate controlled fuel/air ratio, uniform mixing and high reliability, particularly
suitable for such fuel gases as natural gas and methane. The gas used is free of free water, crude
Gas requirements: total sulfur content is not more than 200ppm, H2S content is not more than
100ppm. Relative humidity of gas at the inlet is less than 80%, and no water condensation is
allowed on the engine parts. The recommended gas temperature of the engine is at least 15℃
above the dew point temperature. Generally, humidity is not a problem for natural gas. The
maximum H2 allowed in the fuel gas is 12%vol, the maximum solid particle size in the gas is 5um,
Air pressure requirements: 2 -20kPa, A pressure above this range must be reduced by a pressure
relief valve, otherwise will lead to improper working of and even damage to the engine. On the
other hand, gas pressure needs to be increased for systems with a pressure lower than the inlet
pressure in order to ensure proper working of the generator set. (The above data is for reference
only and subject to changes according to the actual working environment of the engine) .
The engine oil is used to lubricate and cool the moving parts and remove the impurities from the
parts and prevent them from rusting. Its quality not only affect the performance and useful life.
For this, it should be selected based on the operating environment temperature of the engine, so
that it can maintain good liquidity at the minimum environment temperature and proper kinematic
89
Operation Manual of Gas Generator Set
A common standard for lubricating engine oil for gas engine has be available now. Other than ash,
the lubricant oil used for gas engine contains other key ingredients, including phosphor of a low
content, high anti oxidation and nitration agent (usually produced at a high temperature) and
Generally, the engine oil used has a moderate content of ash, quality paraffin, stable anti oxidation
and nitration performance, and is able to protect the machine at a high temperature and reduce
carbon sink and residues. Therefore, it can keep the machine in a good condition and running for a
long time. Additionally, the low foaming rate, high demulsification and good anti-corrosion of the
oil can effectively protect the cylinders and gears, reduce wear of the piston ring, cylinder liner
and valve seat. It has the advantage of cleaning the engine and preventing sediments. In addition, a
number of additives in the engine oil can prevent wear of the piston and the cylinder surface.
e Minimizing sediments
The recommended engine oil is Total NATERIA MJ40, with the following characteristics:
Typical
Method Unit NATERIA MJ40
characteristics
SAE class 40
Kinematic viscosity at
ISO 3104 mm2/s 148
40℃
90
Operation Manual of Gas Generator Set
100℃
SAE class 40
It is recommended to change the engine oil every 500-800 hours, dependent upon the engine
When the engine oil tested achieves the following number, it should be replaced. The
pH value Min. 4
Water % 0.1
91
Operation Manual of Gas Generator Set
Tin Sn mg/kg ≤5
oil
9.1.3 Coolant
During the assembling of the engine, pay attention that the quality of cooling water will affect
the thermal transfer. Any water treatment process is intended to protect the cooling system from
being eroded , and prevent from the entry of deposits and scale, which may weaken the continuous
It is recommended to use clean soft water as the coolant for directly cooling the engine in the
cooling system, for example, distilled water, deionized water, drinkable tap water, rainwater or
clarified river water. Well water or other ground water (hard water) can easily produce scale inside
the engine water jacket due to its high content of minerals, affecting the cooling effect and causing
faults. If only hard water is available restricted by conditions, do not use it directly until it has
(b)Add a small amount of caustic soda, mix, settle and then use the above clear water.
The best way to avoid problems arising from erosion, oxidation, deposited sediments is to add
sufficient additives in the water of the cooling system, which can protect the metal surfaces in the
system by producing a rustproof layer on the metal surfaces to prevent erosion of the cooling
system.
Various antiseptic additives can be used for protecting the gas engine from erosion and rust.
92
Operation Manual of Gas Generator Set
Phosphate Steel, iron, Unstable, worn fast, sediments (caused by hard water)
aluminum
dioxide)
Silicon (silica acid) Aluminum, iron, Membrane produced by fast wear, even green membrane,
Carboxyl-contained Aluminum,
Prevent the coolant from freezing to break related parts when using the engine at a temperature
below 0℃. To prevent water from freezing, it is better to use high-quality anti-freezer, even in hot
days, as such products will raise the melting point of water. Avoid water boiling and evaporating.
An anti-freezer product is a liquid lyotrope made from ethylene glycol. A sufficient amount can
not only mitigate the risks of freezing and evaporation, but also improve the non-corrosive
Use anti-freezing liquid with a suitable condensation point according to the ambient temperature
or add hot water before the engine starts. But drain the water after it stops.
Prevent fire when using the anti-freezing liquid as ethylene glycol and alcohol are inflammable.
Before using the anti-freezer for the engine, clean the dirt from its cooling system to prevent new
Use a cleaning solution to clean the cooling system if there is too much deposit and dirt. The
solution can be prepared with water, Na2CO3 and Na2SiO3, by adding 40g Na2CO3 and 10g
Na2SiO3 in to a liter of water. When cleaning the cooling system, inject the cleaning solution into
the cooling water jacket, start the engine until the outlet water temperature is above 6℃, stop the
engine after it runs for two hours and drain the solution. Cleanse the engine with clean fresh water
twice after the engine is cooled. Then drain the water and inject the cooling water and start the
engine again until the outlet water temperature reaches above 75℃. Stop the engine and drain the
93
Operation Manual of Gas Generator Set
The mixed coolant comprises 50% ethylene glycol anti-freezer and 50% pure water. The
Propylene glycol can replace ethylene glycol, but its concentration can only be 50%.
Ethylene glycol
n
50% -23℃(-9°F) 106℃(223°F)
Propylene glycol
on
50% -29℃(-20°F) 106℃(223°F)
Chloride 40mg/L
Sulfate 100mg/L
Note: Water not meeting the requirements will cause the production of solid sediments in the
94
Operation Manual of Gas Generator Set
9.2 Conditions for the location for installing and using the gas generator set
(2) Clean environment, no articles that will produce corrosive acidic or alkaline gas and steam
(4) If the generator set is installed in a special room, the foundation should be horizontal platform,
which is +200mm longer and +200mm wider than the generator set, 200mm above the ground.
Place the generator set directly on the platform, preferably with an elastic liner in between to
prevent vibration.
(5) If the generator set is used indoor, the hot air from the fan and the waste gas from the gas
generator should be channeled to outdoor. The exhaust pipes should not be too small in diameter,
(6) Erect cable brackets indoor which are covered by flooring. All the connecting cables between
the generator set and the low-voltage distribution cabinet should be laid in the cable brackets.
(7) The generator set should be provided with grounding wire and grounded safely.
(8) Consult the civil engineering designer, fire control, electrical and plumbing technicians when
The generator set can be installed in the basement, on the ground or rooftop. Generally, there
should be sufficient space in the engine room for ventilation and sufficient working space around
Basic space of a generator room=area of all distances + area of the generator (see below for the
95
Operation Manual of Gas Generator Set
96
Operation Manual of Gas Generator Set
The floor should be even. Generally, the concrete thickness of generator sets of 500KW or below
should be no lower than 250mm. If the generator set power exceeds 500kW, the required thickness
Users can select the quality and dimensions of the base according to the actual situation.
The base thickness and floor load capacity can be calculated in the method described below:
The load on the floor depends on the weight of the whole generator (including fuel and water),
volume and the quantity of shockproof pads. If the base is directly fixed onto the floor,
If there are shockproof pads, and the weight of the generator is evenly distributed on every pad,
Therefore, the floor load can be reduced by increasing the quantity of shockproof pads.
If the weight is not evenly distributed, the maximum floor pressure will be produced on the pad
bearing the maximum weight (assuming all the pads are of the same size).
97
Operation Manual of Gas Generator Set
9.4.1 Generally, shockproof pads have been installed on the rigid base of a generator and the
alternator and engine have been calibrated in the course of production. So just install the generator
set at the expected position and keep it horizontal. (see the figure below)
发动机 Engine
发电机 Generator
9.4.2 If no shockproof pads are provided, other shockproof devices must be in place when the
generator set is placed on the flat base. Rubber pads or steel balls together with rubber pads can be
used to eliminate shock to prevent damages to the machine and improper vibration.
9.4.3 If possible, compact the soil or refill concrete first under the concrete base, and then apply a
200mm shockproof layer of a mixture of cement, asphalt, cinder and water to effectively prevent
The natural vibration frequency of the plate should be twice of the rotating speed of the engine. If
it is close to the rotating speed of the engine, resonance may occur in some part of the building.
9.4.4 Ventilation
The running of the engine and the alternator will distribute heat in the room and increase the room
temperature. Thus it is necessary to ventilate the room to effectively control the temperature rise in
the generator room and provide cool and fresh air to the generator.
9.4.5 Circulation
A good ventilation system requires sufficient air inflow and outflow and free circulation in the
98
Operation Manual of Gas Generator Set
room. Therefore, there must be enough space in the generator room to allow free air circulation so
Cautions:
1) Hot air from the generator set should be directed outdoor with an air director, which should be
sealed with the air outlet on wall to prevent backflow of hot air to reduce the cooling effect (as
intake (and air director) according to the particular structure of the generator room.
3) The temperature in the generator room should be no higher than 43°C. Otherwise, not only the
power of the generator set will be reduced but also the electric components may be damaged. If it
is possible that the temperature may be above 43°C, preferably use two exhaust fans to accelerate
ventilation in the room. The two fans are installed in the incoming and outgoing air directors, with
one blows in cooling air into the room and the other exhaust hot air from the room.
4) Required area of air outlet: the air outlet area must be 1.3 times or above of the radiation area of
the water tank. If a protection mesh is provided on the air outlet, enlarge the size of the air outlet
according to the area of the wire mesh. If an air deflector is provided at the air outlet, enlarge the
size of the air outlet according to the effective pass-through area of the air deflector.
5) Required area of air inlet: the air inlet area must be 1.3 times or above of the air outlet area. If a
protection mesh is provided on the air inlet, enlarge the size of the air inlet according to the
99
Operation Manual of Gas Generator Set
effective pass-through area of the wire mesh; if an air deflector is provided on the air inlet, enlarge
the size of the air inlet according to the effective pass-through area of the air deflector.
发动机 Engine
散热器 Radiator
帆布罩 Canvas cover
导向筒 Guide pipe
出风口 Air outlet
地面 Ground
Note: the air inlet and outlet are of the same area. The R on the figure is no less than 150mm.
1) The engine is located to the extent that the air vent duct is as short as possible and the number
2) Normally, the air vent duct goes out of the external wall and extents to the rooftop along the
external wall. There is a sleeve outside the wall opening to absorb vibration. And an expansion
joint is provided on the duct to compensate the difference in length as the result of expansion and
contraction. Generally, the air vent duct is not allowed to share an flue with other devices as one of
3) The exhausted air can directly enter into a special flue, which can serve as an outlet of the
4) The silencer can be installed within the flue or the room. Its tail pipe extends to the outside. The
air vane guide should be installed within the flue to guide the air from the radiator upward and
100
Operation Manual of Gas Generator Set
5) For engines on rooftop penthouse, individual outdoor shelter or trailer, the exhausted fume from
the air vent duct and the exhausted air from the radiator can flow on the shelter without any flue.
Sometime to achieve this purpose, the radiator is fixed horizontally and an electric motor is used
1) The exposed part of the air vent duct should not contact with wood or other inflammable
matters. The vent pipe inside the building (including the silencer in the room) should be covered
with suitable thermal insulating materials to avoid burning people and reduce the temperature.
2) The air vent duct should be installed vertically or horizontally without tilting; there should be
no more than 3 bends; the vent pipe should be no more than 3000mm long.
Too many bends and too long vent pipe will affect the exhaust back pressure of the engine, and
1)The gas exhausted from the generator is not only harmful but also hot. Pay attention to fire
protection and poisoning prevention !Do not orient the air outlet directly to cables or other
The waste gas from the engine contains carbon monoxide, which is a colorless, odorless, toxic gas,
and causes people to die unknowingly. Symptoms of carbon monoxide poisoning include:
1.Dizziness 5.arrhythmia
3.Headache 7.vomiting
1) The level of noise is determined based on the size and sound pressure level of the generator
room. Reduce the generator noise with reference to noise standards for corresponding
environment. Too high standard will incur unnecessary overspending and is not recommended.
2) In many cases of installation, the generator noise can be reduced to the acceptable level by
101
Operation Manual of Gas Generator Set
fixing the generator with elastic fixers, controlling air exhaust and intake and installing radiator
fans.
3) If the generator noise is still high after the above measures are taken, erect soundproof panels
around the room and the generator, install acoustic panels on the walls of the generator room, or
place the generator in a especially designed soundproof shelter to reduce the noise.
Power lines should be designed and installed in compliance with the relevant national or industrial
1) AC power line
The current intensity of AC conductors installed on site between the output end of the generator
set and the first over-current protection device should be higher than 115% of the FLA.
The conductor between the output end of the generator set and the first over-current protection
device should be as short as possible (generally no more than 10m). The current carrying capacity
Neutral line current intensity is permitted to be equivalent to or larger than the maximum
unbalanced single-phase load value. In case of an apparently non-linear load, select the neutral
2) Grounding
An effective system should ensure that sudden power failure will not endanger personal life and
operators' health at any time. Requirements for good grounding: low resistance, avoiding lightning
stroke and short-circuit, a capacity of repeatedly driving high current, and a capability of fulfilling
System grounding: The neutral line of Camda generator set is not grounded during operation. If as
an individual power supply (with 4-pole switch), the neutral line should be connected to the
system ground wire by an electrician. If the neutral line of the generator is found to be connected
with the ground wire, a typical application is to connect it to the neutral point of a 3-pole switch,
in which case the neutral point of the generator should not be grounded on the side of the
generator. If the neutral line cannot be separately grounded, the grounding point of the neutral line
and the mains should be marked as required by the electric power standard.
Equipment grounding: A grounding terminal is provided on the base of the generator set. An
102
Operation Manual of Gas Generator Set
on-line breaker can provide a grounding terminal. According to the electric power standard, a
dedicated grounding wire is required. The flexible conduit absorbing vibration is not allowed to be
the ground electrode. To protect the safety of people and equipment, the national standard
Control line: the DC and AC control lines to the switch and remote display should be separated
from the power transmission line. Use stranded wire and flexible conduit for the connection to the
generator set.
103
Operation Manual of Gas Generator Set
Check and adjust the conditions of the engine and other parts of the generator set. The connection
and fixation of all components must be reliable and correct. The cooling water system and electric
start system of the engine are reliably connected, without leak or loosening. The switches can
operate smoothly. The lubricating system is in good condition as well as the gas supply system and
ignition system. Otherwise, repair and adjust them immediately before starting the machine.
All the gas engines provided by Camda have go through running-in process and can operate with
load straight away. The recommended load for operation for the first time is 80-90% of the rated
output power.
1) Remove the dust, water, oil and rust stains on the engine surface.
2) Check whether all mechanical connectors and fasteners are loosen, all moving parts can
turn freely, and there is any friction or jam; and check whether all wires are connected
firmly and correctly, contacts are reliable, and there is any loosening or coming-off.
4) Check whether the engine oil in the bottom case of gas engine oil is sufficient.
5) Check whether the cooler has been filled up with cooling water.
For selecting an engine, users should not only consider the rated power of the matched generator
or other working machines but also the load factor of the working machines. For example, are they
working intermittently or continuously? What are their loads? If the operation economy of the
working machine is considered, such consideration should be extended to the match between the
load working characteristics and the engine characteristics. Proper rated power of the engine and
match between the engine and the working machines are prerequisites for reliability, long useful
life and economical operation of the engine. Otherwise, the engine may be overloaded and
unnecessary faults caused, or its power cannot be fully utilized if under-loaded, which is not only
uneconomical but also likely to cause problems such as engine oil flees.
104
Operation Manual of Gas Generator Set
The Camda generator set can be working stably and continuously at 50%-90% of the rated
power.
1) Check whether the pressure indicator on the gas pipe is working properly. Turn on the gas
supply valve, adjust the gas pressure to 0.8-1.0Kpa. Turn on the power, keep the idle/rated switch
of the speed governor on one side, and press the start button to start the engine. Once the oil
temperature, water temperature and oil pressure have achieved the required levels respectively,
turn the idle/rated switch to the rated position to allow the engine to run at its operating speed.
2) Turn on the draining valve at the bottom of the surge tank to drain the sewer and exhaust the air
3) If the engine cannot be started after three attempts, turn off the gas switch and start the engine
again to exhaust the residual gas from the exhaust system. Before the re-start, check and
4) Maintain the rotating speed at about 1500rpm or 1800rpm after the gas generator set is started.
Pay close attention to the reading of the engine oil pressure. If there is no indication of the
5) At this moment, if the engine is working properly, turn off the air switch and then increase the
load gradually. Note that the air switch has a voltage-loss protection device. Never close the
switch before the voltage of the generator reaches the rated pressure (to close it, pull down the
6) For new engines or those not working for more than 5, turn the crankshaft for 3-5 times before
starting them.
7) For standby engines for emergency use, to enable them to start quickly in emergency, start them
1) When the engine is working properly, the voltage should be about 400V or 440V-480V, the
current should be no higher than the generator's rated current, the frequency should be about 50Hz
or 60Hz, the water temperature of the gas engine should be no higher than 95℃, the engine oil
temperature no higher than 110℃, and the engine oil pressure within the range of 0.4-0.6MPa. Pay
attention to their changes when the generator set is running. If any specified value is exceeded,
105
Operation Manual of Gas Generator Set
2) Check from time to time all pipes of the gas engine. Make repairs immediately if there is any
damage or leakage.
3) Observe the color of the exhausted air from the gas engine. The exhausted gas is colorless when
4) Allow no water, oil, metal or other impurities to enter into the engine.
5) If the engine is not working normally and required to be powered off or stopped, press the
6) During the operation of the engine, take records frequently of relevant readings, ambient
temperature, running time and stop time, reasons for stop, and results of inspections or provisional
servicing, etc.
When all are prepared, turn on the gas valve, connect to the starting power supply, press the button
to start the engine. Once the engine is started, pay attention to the engine oil pressure meter and
make sure the pressure is normal. The engine should be operating at an idle speed for a period of
time. During this time, observe the operation of every part of the engine to find whether it is
working properly and there is any abnormal sound, and deal with and solve problems if any. The
idle operation also works to raise the engine temperature, especially in winter. This is necessary
After ensuring the engine temperature has reached a certain level through observation of the water
temperature during the idle operation, operate the electronic control "throttle" to accelerate the
engine to the rated operating speed, adjust the pressure and frequency of the engine to the rated
106
Operation Manual of Gas Generator Set
values, then close the switch to output load. To ensure a load is available outside when the switch
is closed, it is recommended to set the no-load speed (frequency) to a little bit high before the
closing. As the load is changing, adapt the "oil volume" control switch, that is, the potentiometer
of the electronic speed governor to meet the required output and ensure stable voltage and
frequency.
Due to the difference in applying the engine between high altitude areas and plains, there are some
changes to the performance and application of the engine. Users in the high altitude areas may
The low air pressure, thin air, low oxygen content and low ambient temperature in high altitude
areas may disable the engine, particularly the naturally aspirated engine, to generate the specified
Considering the tendency of ignition delay under the high altitude condition, to improve the
operation economy of the engine, increase the ignition advance angle properly.
As the result of higher altitude, reduced power and increased exhaust temperature, users should
take into account the engine's working capacity in high altitude areas in selecting an engine to
With the elevation of altitude, the ambient temperature drops compared to that in plains, at about
0.6℃ per 1000m rise in altitude. Together with thin air in high altitude areas, the engine start
performance is worse than in plains. Users should take support measures suitable for
low-temperature start.
1) Before stopping the engine, reduce the load gradually, turn the speed switch to the low-speed
position for idle operation for 10 minutes, then turn off the gas valve to stop the engine and power
it off. Try not to stop the engine suddenly under full load to prevent accidents such as overheating.
2) When the ambient temperature is below 5℃, drain all the water remaining in the water cooler,
circulating water pump, engine oil cooler and engine body in the gas engine cooling system, and
prevent it from freezing. It is unnecessary to drain the water if anti-freezer liquid has been used.
3) If the engine will be stored for a long time, after the last stop, drain the used engine oil from the
engine body and inject the sealing oil instead, and seal the engine after it is running for 2 minutes.
4) Clean the entire set and prepare for the next start and operation.
107
Operation Manual of Gas Generator Set
Special Notice
During the production process, major components of the fuel gas generator set may be improved
or modified. Changes that do not affect the product performance are not explained. Therefore, the
We hope that users can notify us of any problems and give us suggestion so that we can continue
108