Beruflich Dokumente
Kultur Dokumente
V100R003
Issue 05
Date 2010-05-25
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the
customer. All or part of the products, services and features described in this document may not be within the
purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information,
and recommendations in this document are provided "AS IS" without warranties, guarantees or representations
of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute the warranty of any kind, express or implied.
Website: http://www.huawei.com
Email: support@huawei.com
Purpose
This manual provides the on-site commissioning methods of the OptiX RTN 600 (with the IDU
605 installed). The commissioning items and procedure in the case of the NE commissioning
and the HOP commissioning are described respectively.
Related Versions
The following table lists the product versions related to this document.
Intended Audience
This manual is intended for the installation and commissioning engineers for the OptiX RTN
600 (with the IDU 605 installed). Before reading this manual, you must know the following:
l Basics of the digital microwave communications.
l Basics of the OptiX RTN 600 (with the IDU 605 installed). For details, refer to the OptiX
RTN 600 Radio Transmission System IDU 605 Hardware Description and OptiX RTN 600
Radio Transmission System ODU Hardware Description.
Conventions
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
General Conventions
The general conventions that may be found in this document are defined as follows.
Convention Description
GUI Conventions
The GUI conventions that may be found in this document are defined as follows.
Convention Description
Boldface Buttons, menus, parameters, tabs, windows, and dialog titles are in
boldface. For example, click OK.
> Multi-level menus are in boldface and separated by the ">" signs. For
example, choose File > Create > Folder.
Mouse Operation
The mouse operations that may be found in this document are defined as follows.
Action Description
Click Select and release the primary mouse button without moving the pointer.
Double-click Press the primary mouse button twice continuously and quickly without
moving the pointer.
Drag Press and hold the primary mouse button and move the pointer to a certain
position.
Update History
Updates between document issues are cumulative. Therefore, the latest document issue contains
all updates made in previous issues.
The descriptions of the parameters used for configuring the Hybrid/AM attribute are optimized.
Contents
2 Commissioning Preparations...................................................................................................2-1
2.1 Commissioning Items......................................................................................................................................2-2
2.1.1 NE Commissioning Items......................................................................................................................2-2
2.1.2 HOP Commissioning Items....................................................................................................................2-2
2.2 Documents and Tools Preparation..................................................................................................................2-3
2.2.1 Documents Preparation..........................................................................................................................2-4
2.2.2 Tools Preparation...................................................................................................................................2-4
2.3 Commissioning Conditions Check..................................................................................................................2-4
2.3.1 NE Commissioning Conditions Check..................................................................................................2-5
2.3.2 HOP Commissioning Conditions Check................................................................................................2-5
3 NE Commissioning Guide.......................................................................................................3-1
3.1 Powering On the Equipment...........................................................................................................................3-2
3.2 Accessing the Web LCT.................................................................................................................................3-3
3.3 Configuring Data.............................................................................................................................................3-5
3.4 Checking Alarms.............................................................................................................................................3-7
3.5 Testing the Connections of E1 Cables............................................................................................................3-8
3.5.1 Testing the Connections of E1 Cables by Using a BER Tester.............................................................3-8
3.5.2 Testing the Connections of E1 Cables Through PRBS..........................................................................3-9
A Glossary.....................................................................................................................................A-1
A.1 0-9..................................................................................................................................................................A-2
A.2 A-E................................................................................................................................................................A-2
A.3 F-J..................................................................................................................................................................A-7
A.4 K-O..............................................................................................................................................................A-10
A.5 P-T...............................................................................................................................................................A-12
A.6 U-Z..............................................................................................................................................................A-16
Figures
Tables
1 Safety Precautions
Symbols
DANGER
Indicates a hazard with a high level of risk that, if not avoided, could result in death or serious
injury.
WARNING
Indicates a hazard with a medium or low level of risk that, if not avoided, could result in minor
or moderate injury.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, could cause equipment damage,
data loss, performance degradation, or unexpected results.
NOTE
Provides additional information to emphasize or supplement important points of the main text.
l Only the qualified and skilled personnel are allowed to install, operate, and maintain the
equipment.
l Only the certified professionals are allowed to remove the safety facilities, and to
troubleshoot and maintain the equipment.
l Any replacement or change of the equipment or parts of the equipment (including the
software) must be performed by the certified or authorized personnel of Huawei.
l Any fault or error that may cause a safety problem must be reported immediately to the
person in charge.
Grounding Requirements
The grounding requirements are applicable to the equipment that needs to be grounded.
l When installing the equipment, always connect the grounding facilities first. When
removing the equipment, always disconnect the grounding facilities last.
l Do not damage the grounding conductor.
l Do not operate the equipment in the absence of a suitably installed grounding conductor.
l The equipment should be connected to the protection ground permanently. Before operating
the equipment, check the electrical connections of the equipment, and ensure that the
equipment is properly grounded.
Human Safety
l Do not operate the equipment and cables in the case of lightning.
l To avoid electric shocks, do not connect the safety extra-low voltage (SELV) circuits to
the telephone-network voltage (TNV) circuits.
l To prevent laser radiation from injuring your eyes, do not look at the optical port directly.
l Before operating the equipment, put on the electrostatic discharge (ESD) work uniforms,
wear ESD gloves or an ESD wrist strap, and take off metallic articles, such as watch,
bracelet, and ring, to prevent electric stock or injury of the human body.
l In the case of fire, keep away from the building or the area where the equipment is located
and press the fire alarm system or dial the phone number for a fire call. In this case, do not
enter the building which is on fire.
Equipment Safety
l Before operation, install the equipment firmly on the ground or other rigid objects, such as
a wall or a rack.
l When the system is operating, ensure that the ventilation hole is not blocked.
l When installing the front panel, use a tool to tighten the screws firmly.
l After installing the equipment, clean up the packing materials.
DANGER
l The high-voltage power supply provides the power for the equipment. Direct or indirect
contact of high voltage and mains supply through damp objects may result in fatal danger.
l Non-standard and improper high-voltage operations may result in certain accidents such as
fire or electric shock.
l The personnel who perform high-voltage operations must be certified for high-voltage and
AC operations.
l The AC cables must be bridged and routed according to the local rules and regulations.
l When operating AC power supply facilities, obey the local rules and regulations.
l When performing high-voltage and AC operations, use special tools rather than general
tools.
l When performing operations in a damp environment, ensure that the equipment is kept
away from water. Switch off the power supply immediately if you find any water in the
rack or if the rack is damp.
Thunderstorm
DANGER
Do not perform operations on high voltage, AC power, iron tower, or backstay in stormy weather
conditions.
Power Cable
CAUTION
Do not install or remove the power cable with the power on. Transient contact between the core
of the power cable and the conductor may generate electric arc or spark, which may cause fire
or injury to the eye.
l Before installing or removing the power cable, switch off the power supply.
l Before connecting the power cable, ensure that the power cable and label conform to the
requirements for the installation.
Fuse
CAUTION
If the fuse on the equipment blows, replace the fuse with a fuse of the same type and specifications
to ensure safe operation of the equipment.
Electrostatic Discharge
CAUTION
The static electricity generated by the human body may damage the electrostatic sensitive
components on the board, such as the large-scale integrated circuit (LSI).
l The human body generates a static electromagnetic field in the following situations: moving
of the human body, friction of the clothes, friction between shoes and the ground, and
holding ordinary plastic in hand. The static electromagnetic field will remain within the
human body for a long time.
l Before operating the equipment, parts, circuit boards, or ASICs, wear an ESD wrist strap
that is properly grounded. The ESD wrist strap can prevent the electrostatic-sensitive
components from being damaged by the static electricity in the human body.
Figure 1-1 shows the method of wearing an ESD wrist strap.
DANGER
Do not place or operate the equipment in an environment where flammable gas, explosive gas,
or smog exists.
Operations on any electronic device in an environment where explosive gas exists may cause
extreme risks.
1.4 Radiation
Electromagnetic Exposure
CAUTION
High-intensity RF signals are harmful to the human body.
If multiple transmit antennas are installed on the iron tower or backstay, you must request the
relevant personnel to shut down the transmit antenna before installing or maintaining the antenna
locally.
During the operation, the radio equipment may generate electromagnetic radiation (namely,
radiation harm). Before installing and operating the radio equipment, read the guidelines to
ensure safe operations. When installing the radio equipment, obey the local rules and regulations.
Forbidden Area
The following requirements should be met:
l The site of the antenna should be far away from the area where the electromagnetic radiation
is beyond the specified range and the public cannot reach.
l Before entering the area where the electromagnetic radiation is beyond the specified range,
the operator should learn about the area and shut down the electromagnetic radiator. The
area where the electromagnetic radiation is beyond the specified range, if any, should be
within 10 meters away from the antenna.
l A physical barrier and an eye-catching warning flag should be available in each forbidden
area.
CAUTION
When working at heights, be cautious to prevent objects from falling down.
Weight Lifting
CAUTION
Do not enter the areas under the jib arm and the goods in suspension when lifting weight.
l Ensure that the operators have completed the related training and have been certified.
l Check the weight lifting tools and ensure that they are intact.
l Lift the weight only when the weight lifting tools are firmly fixed onto the weight-bearing
object or the wall.
l Use a concise command to prevent any incorrect operation.
l Ensure that the angle between the two cables is less than or equal to 90 degrees during the
lifting, as shown in Figure 1-2.
If you intend to climb to the top, the length of the ladder should be at least one meter higher than
the eave, as shown in Figure 1-4.
Figure 1-4 Schematic diagram of the ladder one meter higher than the eave
CAUTION
Do not drill holes on the cabinet without prior permission. Improper drilling may cause damage
to the internal cables and the EMC function of the cabinet. Metallic scraps produced by the
drilling may fall into the cabinet and cause short circuits of the circuit boards.
l Before drilling a hole on the cabinet, remove the cables inside the cabinet.
l During the drilling, ensure that your eyes are protected properly. The flying metallic scraps
may cause injury to your eyes.
l Before drilling a hole on the cabinet, wear the protection gloves.
l Take measures to prevent the metallic scraps from falling into the cabinet. After the drilling,
clean up the metallic scraps.
Sharp Objects
CAUTION
When handling the equipment by hands, wear the protection gloves to avoid injury by sharp
objects.
Fans
l When replacing components, ensure that no objects such as components, screws, and tools
fall into a fan that is running, to prevent damage to the fan or equipment.
l When replacing the equipment close to a fan, do not put a finger or a board into a fan that
is running before the fan is switched off and stops running, to prevent injury to your hands
or damage to the equipment.
CAUTION
l When handling heavy objects, ensure that the weight bearing measures are taken to prevent
you from being pressed or sprained.
l When taking the chassis out from the cabinet, draw attention to the equipment that is unstable
or heavy on the cabinet, to prevent any pressing or smashing injury.
l When handling a chassis, generally, two persons rather than one person are required to
handle a heavy chassis. When handling a chassis, keep your back straight and move gently
to prevent you from being sprained.
l When moving or lifting a chassis, hold the handle or bottom of the chassis rather than the
handle of a module (such as a power supply module, a fan module, or a board) that has
been installed inside the chassis.
CAUTION
When inserting a board, wear an ESD wrist strap or ESD gloves, and handle the board gently to
avoid bending pins on the backplane.
CAUTION
Bind the signal cables separately from the high-current or high-voltage cables.
Routing Cables
In the case of extremely low temperature, heavy shock or vibration may damage the external
plastic coatings of the cables. The following requirements should be observed to ensure safe
implementation:
l All the cables can be routed only when the ambient temperature is higher than zero degrees.
l If the cables are stored in a place where the ambient temperature is lower than zero degrees,
you must transfer them to a place where the ambient temperature is room temperature at
least 24 hours before the operation.
l Handle the cables gently, especially in a low-temperature environment. Do not perform
any improper operations, for example, pushing the cables down directly from a truck.
High Temperature
WARNING
If the ambient temperature exceeds 55°C, the temperature of the front panel surface marked the
flag may exceed 70°C. When touching the front panel of the board in such an environment,
you must wear the protection gloves.
IF Cables
WARNING
Before installing or removing an IF cable, you must turn off the power switch of the IF board.
2 Commissioning Preparations
Before commissioning the equipment, you must make the related preparations.
The commissioning preparations to be made are as follows:
2.1 Commissioning Items
The commissioning items of the OptiX RTN 600 that adopts the IDU 605 are classified into two
categories: NE commissioning items and HOP commissioning items.
2.2 Documents and Tools Preparation
To commission the equipment smoothly, the related documents and tools must be available.
2.3 Commissioning Conditions Check
Before performing the NE commissioning and HOP commissioning, check whether the
equipment meets the commissioning requirements.
Procedure Remarks
Testing the Testing the Required when the E1 service is available and
connections of E1 Connections of E1 a BER tester is available on site
cables Cables by Using a
BER Tester
Procedure Remarks
Testing the E1 Testing the E1 Required when there is a BER tester on site
Service Services by Using a
BER Tester
Testing the Testing the Required when the Ethernet service of the
Ethernet Service Ethernet Service by IDU 605 1F/2F is tested by using the
Using One Laptop computer
Testing the IF 1+1 Switching Required when the IDU 605 2B/2F is
configured with 1+1 HSB/FD/SD protection
Commissioning guidelines, such as the OptiX RTN 600 Radio Transmission System IDU 605
Commissioning Guide.
Type Description
NOTE
For the hardware and software that are required for installing the Web LCT and the installation method,
refer to the OptiX iManager T2000 Web LCT User Manual.
3 NE Commissioning Guide
Prerequisite
l The hardware installation must be complete, and it should pass the installation check.
l The power supply must be available, and the fuse capacity of the power supply must meet
the requirements.
In the case of the IDU 605, it is recommended that you use a 4 A fuse for the - 48 V/- 60
V power supply system.
l The power switch on the power box (or power cabinet) must be turned off.
Precautions
CAUTION
On the front panel of the IDU 605 2B, the switches marked "ODU-S" and "ODU-M" are equipped
with locking devices. Hence, you must pull out the switch gently before you turn it. If the switch
points to "0", you can infer that the switch is off. If the switch points to "I", you can infer that it
is on.
Procedure
Step 1 Set the POWER switch on the front panel of the IDU 605 to "0".
Step 2 If the IDU 605 2B/2F is used, you should set the ODU-S and ODU-M switches on the front
panel of the IDU to "0".
Step 3 Turn on the power switch on the power box (or power cabinet).
Step 4 Connect a multimeter to the power supply (for example, the output terminal of the cabinet power
box) to test the voltage and polarity of the input power.
l When the nominal voltage of the input power is -48 V, the tested voltage should be between
-38.4 V and -57.6 V.
l When the nominal voltage of the input power is -60 V, the tested voltage should be between
-48 V and -72 V.
WARNING
When the test value of the voltage is not within the range, first rectify the fault of the power
equipment. The abnormal voltage can cause damage to the equipment, even personal injury.
Step 5 Set the POWER switch on the front panel of the IDU 605 to "I".
Step 6 Observe the indicators on the front panel of the IDU 605.
Front panel indicators should comply with the following statuses and sequences.
1. The PWR indicator on the front panel of the IDU 605 should be green.
2. The IDU indicator on the front panel of the IDU 605 should be green, flash green, and off.
The process lasts about two minutes. Then, the IDU indicator should be constantly on. If
the green indicator is constantly on, you can infer that no alarm is generated. If the yellow
indicator is constantly on, you can infer that a minor alarm or a warning arises. If the red
indicator is constantly on, you can infer that a major alarm or a critical alarm arises.
NOTE
For details about the indicators on the front panel, refer to the OptiX RTN 600 Radio Transmission System
IDU 605 Hardware Description.
Step 7 If the IDU 605 2B/2F is used, you should set the ODU-S and ODU-M switches on the front
panel of the IDU to "I".
----End
Prerequisite
The equipment must be powered on.
Procedure
Step 1 Start the laptop computer, and log in to the operating system.
Step 3 Use an Ethernet cable to connect the Ethernet port of the laptop to the port marked "ETH" on
the front panel of the IDU 605.
The ETH interface supports the MDI/MDI-X autosensing. Hence, you can use the straight-
through cable or crossover cable to connect to it.
In this case, the green indicators of the ETH interface and network interface of the laptop
computer are lit on. Also, if you set the prompt for the local area connection in the operating
system of the laptop computer, a prompt is displayed indicating that the network is connected.
If the operating system prompts an IP address conflict, set the IP address again.
Step 4 Optional: Set the Internet Explorer (IE) as the default browser.
Step 6 Optional: Disable the function that blocks the popup window.
NOTE
If there are other installed plug-ins to block the popup window, disable the function of all the plug-ins.
Step 9 Enter User Name and Password, and then click Login.
The user name of the Web LCT is admin by default, and the corresponding password is T2000
by default.
If the entered user name and the password are both correct, the NE List page is displayed in the
IE.
----End
This section lists the procedures of NE data configuration, For details on the configurations,
refer to the OptiX RTN 600 Radio Transmission System IDU 605 Configuration Guide.
Table 3-1 Flow for configuring PDH services in the guide mode
1 Creating an NE Required
2 Logging in to an NE Required
Logging in to an NE Required.
Create the VLAN Required when you need to create the IEEE
filtering table 802.1q bridge.
Prerequisite
l The equipment must be connected to the Web LCT.
l Data configuration must be complete.
Procedure
Step 1 Select an NE from the Object Tree in the NE Explorer, and then click in the toolbar.
l NESF_LOST
l TEMP_ALARM
l IF_CABLE_OPEN
l POWER_FAIL
For details on the previous alarms and about how to handle them, refer to the OptiX RTN 600
Radio Transmission System IDU 605 Maintenance Guide.
----End
Prerequisite
l The NE equipment must be configured with an E1 interface board, and the E1 port must
be connected to the opposite equipment through the DDF.
l The service data must be configured.
Precautions
NOTE
The NE equipment supports the automatic release of software loopback function, the automatic release
time is five minutes by default.
Procedure
Step 1 At the DDF, connect the BER tester to the first E1 port of the IDU.
1
2
RX TX
3
. 4
..
.
BER tester
Step 2 Set the corresponding E1 port to outloop through the Web LCT.
1. Select the PDH interface board in the Object Tree.
2. From the Function Tree, choose Configuration > PDH Interface.
3. Select By Function and select Tributary Loopback from the drop-down list.
4. Set Tributary Loopback of the E1 port to Outloop.
5. Click Apply.
6. Click OK.
Step 4 Release the outloop over the E1 port by using the Web LCT.
1. Select the PDH interface board in the Object Tree.
2. From the Function Tree, choose Configuration > PDH Interface.
3. Select By Function and select Tributary Loopback from the drop-down list.
4. Set Tributary Loopback of the E1 port to Non-Loopback.
5. Click Apply.
6. Click OK.
----End
Prerequisite
l The E1 port of the IDU 605 must travel through the DDF before being connected to another
device.
l Data configuration must be complete.
l The NE must be in normal communication with the Web LCT.
Precautions
CAUTION
l When a PRBS test is performed, the services carried on the tested path are interrupted.
l The PRBS test can be performed only in a unidirectional manner and on one path at a time.
Procedure
Step 1 At the DDF, use an E1 cable to loop back the services over the first E1 port towards the tributary
board.
Step 2 On the Web LCT, select the E1 interface board in the Object Tree.
Step 4 Select the first E1 port, and then set the PRBS-related parameters.
l Direction: Tributary
l Duration: 5
l Measured in Time: s
Step 7 When the Progress column is 100%, click Query to check the test result.
The Total PRBS column should be 0, and the curve diagram should be green.
----End
Main lobe
First side lobe
Second side lobe
Figure 4-2 shows the head-on view of a free-space model for radio propagation. The side lobes
take the main lobe as the center and are distributed in the radiate form.
90o
0o
Tracking Path
Side lobe signal readings can be mistaken for main lobe readings when signals are tracked at
different elevations (or azimuths). Figure 4-3 shows a horizontal radio propagation model of
the antenna, and signal levels at three different elevation positions ("1-7" represent the measured
signal level values of the received signal strength indicator (RSSI) port of the ODU.)
6 7
C C'
C 6 7 C' 5
4
4 5
B B'
B B'
1 2 3
A A'
2
1 3
A A'
l Line AA' represents that the main lobe of the antenna is almost aligned properly. The main
lobe is at point 2, and the first side lobes are at points 1 and 3. Slightly adjust the azimuth
of the antenna at point 2 until the peak signal appears.
l Line BB' represents that the elevation of the antenna slightly deviates from the main lobe.
The signal peaks appear at points 4 and 5. The signal peak at point 4 is higher than the
signal peak at point 5 because of the antenna characteristics. As a result, point 4 may be
mistaken for the peak point of the main lobe signal. The correct method is to set the azimuth
of the antenna to the middle position between the two signal peaks. Then, adjust the
elevation of the antenna until the three signal peaks of line AA' appear. Slightly adjust the
elevation and azimuth of the antenna at point 2 until the peak signal appears.
l Line CC' represents that the elevation of the antenna completely deviates from the main
lobe and is almost aligned with the first side lobe. The signal peak of the first side lobe at
point 6 and the signal peak of the first side lobe at point 7 appear as one signal peak. As a
result, points 6 and 7 may be mistaken for the peak point of the main lobe signal. The correct
method is to set the azimuth of the antenna to the middle of points 6 and 7. Then, adjust
the elevation of the antenna until the three signal peaks of line AA' appear. Slightly adjust
the elevation and azimuth of the antenna at point 2 until the peak signal appears.
When the side lobe peak at one side is higher than the side lobe peak at the other side, as shown
in Figure 4-4, a common error is to move the antenna left to right along line DD', or top to
bottom along line EE'. As a result, point 1 may be mistaken for the peak point of the main lobe
signal. The correct method is to adjust the elevation in the middle of points 1 and 2 or the azimuth
in the middle of points 1 and 3. Several adjustments are required so that the three signal peaks
of line AA' can appear. Slightly adjust the elevation and azimuth of the antenna at point 2 as
shown in Figure 4-3 until the peak signal appears.
Figure 4-4 Aligning the antenna with the first side lobe
E
1
2
D D'
1 2
D D'
1
3
3
E E'
E'
Prerequisite
l The NE commissioning of the radio equipment at both ends of the radio link must be
complete.
l The weather should be suitable for outdoor work. There should be no rain, snow, or fog
between stations.
l The on-site conditions must meet the requirements for the antenna to operate at heights and
the personnel required to commission the antenna must be trained to work at high altitudes.
l The ATPC Function must be disabled.
l In the case of the hybrid mode, Setting the AM function to set the AM Enable Statusbe
disabled, and the working mode of the microwave must be set to the QPSK modulation
scheme.
Precautions
l If the radio link is configured to 1+1 protection mode and one antenna is shared by the two
ODUs, power off the standby ODUs at both ends before aligning the antennas. After the
antennas are aligned, power on the standby ODUs at both ends.
l If the radio link is configured in 1+1 SD mode, align the antennas as follows:
1. Power on the main ODUs at both ends, and ensure that they are power-on during the
alignment.
2. Power off the standby ODUs at both ends, and align the main antennas at both ends.
3. Power on the standby ODU at the local end. Maintain the position of the main antenna
at the remote end, and adjust the diversity antenna at the local end.
4. Power on the standby ODU at the remote end. Maintain the position of the main
antenna at the local end, and adjust the diversity antenna at the remote end.
l If the radio link is configured in 1+1 FD mode and two antennas are used at each end, align
the antenna as follows:
1. At both ends, power on the main ODUs, power off the standby ODUs, and align the
main antennas.
2. At both ends, power off the main ODUs, power on the standby ODUs, and align the
diversity antennas.
CAUTION
l You can adjust the azimuth angle and elevation angle of the antennas by adjusting the related
nuts or screws. For details, refer to the related installation guide.
l In the IDU 605 2B/2F, the ODUs connect to the IF jumpers on the front panel of the IDU
605 through IF cables. The main ODU connects to the IF jumper over the ODU-M interface,
and the standby ODU connects to the IF jumper over the ODU-S interface. On the front panel
of the IDU, the power switch with a silkscreen of "ODU-M" controls the power supply of
the main ODU, and the power switch with a silkscreen of "ODU-S" controls the power supply
of the standby ODU.
Procedure
Step 1 Determine the azimuth of the antenna according to the installation position and height of the
antenna. Then, adjust the elevation of the antenna to the horizontal position.
Step 2 Connect a multimeter to the RSSI port on the ODU at the local end and test the voltage value
VBNC.
TIP
It is recommended that you make the test line terminated with a BNC connector at one end in advance
because it is more convenient to test the voltage value VBNC.
adjust the elevation of the antenna so that the three signal peaks in the case of line AA'
can appear. Adjust the antenna to the peak position at point 2 as shown in Figure 4-3.
3. Slightly adjust the elevation and azimuth at point 2 as shown in Figure 4-3 until the
VBNC reaches the peak within the tracked range.
4. Adjust the antenna until the VBNC voltage reaches the peak value. Fix the local antenna.
NOTE
When you tighten the antenna, ensure that the VBNC voltage remains the peak value.
Step 4 Repeat Step 2 to Step 3 to adjust the remote antenna. When the remote received signal level
(RSL) reaches the peak value, tighten the remote antenna.
Step 5 Repeat Step 2 to Step 4 for two to four times and ensure that the RSL at the local end and the
RSL at the remote end reach the peak value. Tighten the antennas at both ends.
Step 6 Use the multimeter to test the VBNC voltage at both ends. Obtain the current RSL by referring
to the relation curve between the VBNC of ODUs and the RSLs at both ends.
NOTE
The curve diagram of the VBNC and RSL is put in the carton holding the ODU.
The actual RSL must be the same as planned by the network planning department.
NOTE
l If the actual receive power of the ODU is beyond the calculated power range +/-3 dB, the ODU indicator
on the IF board flashes yellow every 300 ms. If the received power is within the calculated power range,
the ODU indicator is off.
l If the VBNC does not meet the requirements, refer to the OptiX RTN 600 Radio Transmission System
IDU 605 Maintenance Guide for fault handling.
----End
Prerequisite
The antennas must be aligned.
Precautions
Check the status of a radio link at only one end of the radio link.
Procedure
Step 1 Select the NE from the NE Explorer. Then, choose Configuration > Link Configuration from
the Function Tree.
Step 2 In IF/ODU Configuration, select the corresponding IF board. Then, right-click the IF board
and choose HOP Management from the shortcut menu.
Step 3 In the displayed HOP Management window, choose Configuration > Link Configuration
from the Function Tree. Then, click the IF/ODU Configuration tab.
Step 4 In IF/ODU Configuration, click Query.
Check the receive power and transmit power of the ODUs at both ends.
l The actual transmit power of the ODU must be the same as the designed transmit power of
the ODU.
----End
Prerequisite
l The orderwire phone must be installed correctly at the station.
l The orderwire data must be configured.
l Aligning the antenna must be complete.
Procedure
Step 1 Check the status of the orderwire phones at both sides.
The status should meet the following requirements:
l The ringing switch must be set to ON.
l The dialing mode switch must be set to T, that is, the dual-tone dialing mode must be selected.
Normally, the orderwire phone rings and at the same time the red indicator at the back of
the phone flashes.
2. Pick up the phone, and press the TALK key to talk.
In this case, the red indicator on the upper right of the front panel is on. Normally, the
talking quality is good and the voice is clear.
----End
Prerequisite
l The E1 service must be configured between stations.
l Aligning the antennas must be complete.
Precautions
NOTE
The NE equipment supports the automatic release of software loopback function, the automatic release
time is five minutes by default.
Procedure
Step 1 Connect the BER tester to the first E1 port of the equipment on the local side.
Step 2 On the equipment on the opposite side, use an E1 cable to loop back the services over the first
E1 port towards the tributary board, that is, hardware inloop over the E1 port.
If the hardware inloop fails, perform software inloop over the E1 port by using the Web LCT.
Step 3 Test the BER for 5 to 10 minutes by using the BER tester.
There should be no bit errors.
----End
Prerequisite
l The E1 service must be available between stations.
l Aligning the antenna must be complete.
l The NEs must be in normal communication with the Web LCT.
Precautions
CAUTION
l When a PRBS test is performed, the services carried on the tested path are interrupted.
l The PRBS test can be performed only in a unidirectional manner and on one path at a time.
NOTE
The NE equipment supports the automatic release of software loopback function, the automatic release
time is five minutes by default.
Procedure
Step 1 Perform software inloop over the first E1 port of the opposite NE by using the Web LCT.
Step 2 On the Web LCT, select the E1 interface board of the local NE in the Object Tree.
Step 4 Select the first E1 port, and then set the following PRBS-related parameters:
l Direction: Cross
l Duration:.5
l Measured in Time:.s
Step 7 When the Progress column is 100%, click Query to check the test result.
The Total PRBS column should be 0, and the curve diagram should be green.
Step 8 Release the loopback set in Step 1.
Step 9 Repeat Step 1 to Step 7 to test all other E1 ports.
----End
Prerequisite
The Ethernet service must be configured between stations.
NE1
IP address of laptop A
IP address 129.9.100.100
Subnet mask 255.255.0.0
Default gateway Null Laptop A
NE2
IP address of NE2:129.9.0.2
Precautions
l If the working mode of the Ethernet board is different from the working mode of the network
adapter (auto-negotiation by default), configure the working mode of the external port of
the Ethernet board. That is, set the working mode of the test port to the same mode as the
network adapter temporarily.
l If the TAG identifier of the Ethernet board is Tag Aware, you should change the identifier
to Access temporarily. The default VLAN ID can be set according to the actual situation.
l For details about how to query and set the working mode and TAG identifier, see the OptiX
RTN 600 Radio Transmission System IDU 605 Configuration Guide.
Procedure
Step 1 On the IDU side of NE1, use an Ethernet cable to connect the Ethernet port of the laptop to the
FE1 port of the equipment, as shown in Figure 4-7.
Step 2 On the IDU side of NE2, use an Ethernet cable to connect ETH port and FE1 port of the
equipment, as shown in Figure 4-8. The Ethernet service ports transmit the Ethernet services
between the two NEs.
Step 3 Set the IP address of the laptop, and ensure that the IP address and the IP address of NE 2 belong
to the same network segment.
For example:
Step 4 Display the Command Prompt window of laptop A, and run the ping 129.9.0.2 -n 200 -l 2000
command.
NOTE
----End
Prerequisite
The Ethernet service must be configured between stations.
NE1
IP address of laptop A
IP address 192.168.1.101
Subnet mask 255.255.0.0
Default gateway Null Laptop A
NE2
IP address of laptop B
IP address 192.168.1.102
Subnet mask 255.255.0.0
Default gateway Laptop B
Null
Precautions
l If the working mode of the Ethernet board is different from the working mode of the network
adapter (auto-negotiation by default), configure the working mode of the external port of
the Ethernet board. That is, set the working mode of the test port to the same mode as the
network adapter temporarily.
l If the TAG identifier of the Ethernet board is Tag Aware, you should change the identifier
to Access temporarily. The default VLAN ID can be set according to the actual situation.
l For details about how to query and set the working mode and TAG identifier, refer to the
OptiX RTN 600 Radio Transmission System IDU 605 Configuration Guide.
Procedure
Step 1 On the IDU side of NE1, use an Ethernet cable to connect the Ethernet port of laptop A to the
FE1 port of the equipment, as shown in Figure 4-10.
Step 2 On the IDU side of NE2, use an Ethernet cable to connect the Ethernet port of laptop B to the
FE1 port of the equipment, as shown in Figure 4-11.
Step 3 Set the IP addresses of both laptops, and ensure that the addresses belong to the same network
segment.
For example:
l The IP address of laptop A can be set as follows:
– IP address: 192.168.1.101
– Subnet mask: 255.255.0.0
– Default gateway: null
l The IP address of laptop B can be set as follows:
– IP address: 192.168.1.102
– Subnet mask: 255.255.0.0
– Default gateway: null
Step 4 Display the Command Prompt window, and run the ping 192.168.1.102 -n 200 -l 2000
command.
NOTE
----End
Prerequisite
The Ethernet service must be configured on the NEs, and have Created the Maintenance
Domain,Created the Maintenance Association,Created the Maintenace Point.
Procedure
Step 1 Select the NE to be tested from the NE list.
Step 2 Choose Configuration > Ethernet Maintenance > Ethernet Service OAM from the Function
Tree.
Step 3 Select an established Ethernet service maintenance point from Ethernet Service OAM. Then,
select Performance Detection from the shortcut menu.
Step 4 The Performance Detection dialog box is displayed. Set Send Mode to Burst Mode. Set the
packet length to 64 bytes, time-out to 5 seconds, and detection times to 20. Set the IDs of the
source maintenance point and sink maintenance point in Maintenance.
Step 5 Click Start Detect. After the detection is complete, the performance statistics are displayed in
Detailed Information. Analyze the statistics to determine the service performance between the
local equipment and the opposite equipment.
The loss rate in the performance statistics must be 0.
Step 6 Repeat Steps 4 and 5. Change the packet length in Send Mode. Test the service performance of
the 128-byte, 256-byte, 512-byte, 1024-byte, 1280-byte, and 1518-byte packets. The loss rate
of packets in the performance statistics must be 0.
For the Ethernet performance indexes, see the OptiX RTN 600 Radio Transmission System IDU
605 Hardware Description .
----End
Prerequisite
l The antennas must be aligned with each other.
l The modulation mode of the Hybrid radio at both stations must be set and the AM function
must be enabled.
l The E1 service must be configured.
l The weather is favorable.
Precautions
The following test procedure considers the E1 service between stations as an example.
NOTE
The NE supports the automatic release of software loopback, and the automatic release time is five minutes
by default.
Procedure
Step 1 Connect the BER tester to the first E1 port of the equipment at the local end.
Step 2 On the equipment at the opposite end, perform an inloop on the first E1 port.
If the hardware inloop is not available, perform the Software Inloop on the E1 port by using
the Web LCT.
Step 3 Configuring the Hybrid/AM Attribute. At the local end, set the AM attribute to disable and
the Manually Specified Modulation Mode to QPSK.
Step 6 Configuring the Hybrid/AM Attribute. At the local end, set the AM attribute to enable. Then,
set Modulation Mode of the Assured AM Capacity and Modulation Mode of the Full AM
Capacity according to the station planning.
NOTE
If the weather conditions are adverse, the modulation efficiency of the current mode may be lower than
the value specified in Modulation Mode of the Full AM Capacity.
----End
Prerequisite
l The antenna must be aligned with each other.
l The modulation mode of the Hybrid radio at both stations must be set and the AM function
must be enabled.
l The weather is favorable.
Procedure
Step 1 Configuring the Hybrid/AM Attribute. At the local end, set the AM attribute to disable and
the Manually Specified Modulation Mode to QPSK.
Step 2 Query the 15-minute performance of the IF board at the local end.
1. Select the corresponding IF board from the Object Tree in the NE Explorer.
2. Choose Performance > Current Performance from the Function Tree.
3. Set Monitored Object Filter Condition to All.
4. Set Monitor Period to 15-Minute.
5. In Count, select the other Errors. In Display Options, select Consecutive Severely
Errored Seconds Second.
6. Click Query.
The value of the FEC_BEF_COR_ER should be zero.
Step 3 Querying the Working State of AM.
The current modulation scheme is QPSK.
Step 4 Reset the performance register.
1. Select the corresponding IF board from the Object Tree in the NE Explorer.
2. Choose Performance > Current Performance from the Function Tree.
3. Click Reset.
The confirmation dialog box is displayed.
4. Click OK.
Step 5 Configuring the Hybrid/AM Attribute. Set the AM attribute at the local end to enable. Then,
set Modulation Mode of the Assured AM Capacity and Modulation Mode of the Full AM
Capacity according to the station planning.
Step 6 Repeat Step 2, that is, wait for a while and then query the 15-minute performance of the IF board
at the local end.
The value of the FEC_BEF_COR_ER should be zero.
Step 7 Querying the Working State of AM.
The current modulation mode should be the value specified in Modulation Mode of the Full
AM Capacity.
NOTE
If the weather conditions are adverse, the modulation efficiency of the current mode may be lower than
the value specified in Modulation Mode of the Full AM Capacity.
----End
Prerequisite
l The equipment must be configured in IF 1+1 mode.
l Aligning the antenna must be complete.
Precautions
In the IDU 605 2B/2F, the ODUs connect to the IF jumpers on the front panel of the IDU 605
through IF cables. The main ODU connects to the IF jumper over the ODU-M interface, and the
standby ODU connects to the IF jumper over the ODU-S interface. On the front panel of the
IDU, the power switch with a silkscreen of "ODU-M" controls the power supply of the main
ODU, and the power switch with a silkscreen of "ODU-S" controls the power supply of the
standby ODU.
NOTE
The NE equipment supports the automatic release of software loopback function, the automatic release
time is five minutes by default.
Procedure
Step 1 Connect one E1 port to the BER tester on the local equipment side.
Step 2 At the opposite equipment side, perform hardware inloop over the E1 port.
If the hardware inloop fails, perform software inloop over the E1 port by using the Web LCT.
Step 3 Test the BER by using the BER tester.
There should be no bit errors.
Step 4 Check the working status of the board by using the Web LCT.
1. Select an NE from the Object Tree in the NE Explorer, and then choose Configuration >
Link Configuration.
2. Select IF 1+1 Protection, and then click Query.
In Protection Group, the Active Board of Device should be the active IF board (8-IF0).
If 1+1 FD protection or 1+1 SD protection is used, the Active Board of Channel should
also be the active IF board (8-IF0).
NOTE
If a fault arises, you must rectify the fault and proceed to test the IF 1+1 protection.
Step 5 Power off the ODU-M on the front panel of the IDU.
Step 9 When Revertive Mode of the IF 1+1 protection is set to Revertive, test the BER by using the
BER tester again.
When the WTR time expires, the test result should indicate that the service recovers after a
transient interruption. WTR Time is set to 600s by default. Test the BER depending on the
actual configuration.
Step 10 Release the loopback set in Step 2.
Step 11 At the opposite station, repeat Step 1 to Step 10 to test the IF 1+1 switching of the opposite
equipment.
----End
Related Information
In the absence of a BER tester, you need not perform loopback over the E1 port or perform BER
testing. In this case, you need to check the status of Active Board of Device or Active Board
of Channel in Protection Group on the Web LCT when protection switching occurs or after
protection switching is complete.
Prerequisite
Aligning the antenna must be complete.
Precautions
If the 24-hour BER cannot be tested for each HOP of the link because of restrictions of the actual
situation, choose the E1 service of the first node and the last node to perform the test. This
operation ensures that the test path covers all the radio links.
NOTE
The NE equipment supports the automatic release of software loopback function, the automatic release
time is five minutes by default.
Procedure
Step 1 At the opposite equipment side, extract several typical E1 services, and perform hardware inloop
over the E1 ports.
If the hardware inloop fails, perform software inloop over the E1 port using the Web LCT.
Step 2 On the local equipment side, connect these E1 services serially at the DDF, and then access them
to the BER tester.
1
2
RX TX
3
. 4
..
.
BER tester
Step 3 Perform the 24-hour BER test by using the BER tester.
----End
Postrequisite
l If the first 24-hour BER test does not meet the specified requirement, find out the cause
and rectify the fault. Perform another 24-hour BER test until the test is successful.
l If the BER exceeds the nominal value in the test for a serial connection, locate the fault by
using the dichotomizing search or other methods until each channel passes the 24-hour
BER test independently.
The network management supporting tasks include all the operations performed on the NMS
during the commissioning process.
Prerequisite
l The communication between the NMS and the NE must be normal.
l You must be an NM user with "NE maintainer" authority or higher.
Context
The tributary inloop is a process where signals at an E1 port are looped back at the tributary unit
towards the IF unit.
PDH
The tributary outloop is a process where an E1 signal is looped back at the tributary unit of the
local IDU towards the remote equipment.
PDH
Precautions
CAUTION
l The services may be interrupted at the port or on the path where the loopback is performed.
l A software loopback may be cleared automatically after some time (by default, it is cleared
within five minutes). For details, see 5.2 Setting the Automatic Release Function.
Procedure
Step 1 Select the PDH interface board from the Object Tree.
Step 2 Choose Configuration > PDH Interface from the Function Tree.
Step 3 Choose By Function, and select Tributary Loopback from the drop-down list.
Step 4 Set the loopback status of the port or path according to the requirements.
----End
Prerequisite
l The communication between the NMS and the NE must be normal.
l You must be an NM user with "NE maintainer" authority or higher.
Procedure
Step 1 Select an NE from the Object Tree in the NE Explorer.
Step 2 Choose Configuration > Automatic Disabling of NE Function from the Function Tree.
Step 4 Click Apply to complete the settings for the automatic release function.
----End
Prerequisite
You must be an NM user with "NE operator" authority or higher. That is, you must be an NE
user with "Operation Level" authority or higher.
The related IF board must be added.
Precautions
l In the case of the IF boards that are configured with the 1+1 protection, set only the ATPC
attributes of the main IF board.
l The following procedure describes the configuration of ATPC parameters in the IF interface
configuration dialog box of the IF board. You can also set ATPC parameters in the following
configuration dialog box:
IF/ODU configuration
NOTE
In the IF/ODU configuration dialog box, the ATPC adjustment thresholds cannot be modified.
Procedure
Step 1 Select the IF board from the Object Tree in the NE Explorer. Choose Configuration > IF
Interface from the Function Tree.
Step 2 Click the ATPC Attributes tab.
Step 3 Set the ATPC attributes.
NOTE
The IF0 board of the IDU 605 1A/1B/2B does not support the ATPC Automatic Threshold Enable
Status.
----End
Parameters
Parameter Value Range Default Value Description
ATPC Enable Status Enabled, Disabled Disabled l This parameter specifies whether the
ATPC function is enabled. The ATPC
function enables the transmit power of a
transmitter to automatically trace the
change of the received signal level (RSL)
at the receive end within the ATPC
control range.
l In the case of areas where fast fading is
severe, it is recommended that you set
this parameter to Disabled.
ATPC Upper -20 to -75 -45 l Set the central value of the ATPC upper
Threshold (dBm) threshold and the ATPC lower threshold
so that the central value is equal to the
ATPC Lower -35 to -90 -70 required value of the receive power.
Threshold (dBm)
l Ensure that the difference between values
of the automatic ATPC upper threshold
and the automatic ATPC lower threshold
is not less than 5 dB.
ATPC Automatic Enabled, Disabled Enabled l The ATPC function enables the transmit
Threshold Enable power of a transmitter to automatically
Status trace the change of the received signal
level (RSL) at the receive end within the
ATPC control range.
l When the function is enabled, the
manually set ATPC upper and lower
thresholds are invalid. The equipment
automatically uses the preset ATPC
upper and lower thresholds based on the
working mode of the IF board.
l When the function is disabled, the
manually set ATPC upper and lower
thresholds are used.
l The IF0 board of the IDU 605 1A/1B/2B
does not support the ATPC Automatic
Threshold Enable Status.
NOTE
l Each of the ATPC parameters must be set to the same value at the two ends of a microwave link.
l During commissioning, set ATPC Enable Status to Disabled to ensure that the transmit power is not
changed. After the commissioning, re-set the ATPC attributes.
Prerequisite
You must be an NM user with "NE operator" authority or higher. That is, you must be an NE
user with "Operation Level" authority or higher.
Context
Procedure
Step 1 Select the ODU from the Object Tree in the NE Explorer. Choose Configuration > ODU
Interface from the Function Tree.
Step 6 Configure the transmit power and receive power of the ODU.
----End
Parameters
Parameter Value Range Default Value Description
Configure mute, unmute unmute l When this parameter is set to mute, the
Transmission Status transmitter of the ODU does not work but
the ODU can normally receive
microwave signals.
l When this parameter is set to unmute, the
ODU can normally receive and transmit
microwave signals.
l Generally, this parameter takes the
default value.
Prerequisite
You must be an NM user with "NE operator" authority or higher. That is, you must be an NE
user with "Operation Level" authority or higher.
Background Information
The IDU 605 1F/2F supports the Hybrid/AM function.
Procedure
Step 1 Select the target Hybrid IF board in the NE Explorer. Then, choose Configuration > Hybrid/
AM Configuration from the Function Tree.
----End
Parameters
Parameter Value Range Default Value Description
AM Enable Status l Disable - l When this parameter is set to Disable, the radio
l Enable link uses the specified modulation scheme only.
In this case, you need to select Manually
Specified Modulation Mode.
l When this parameter is set to Enable, the radio
link uses the corresponding modulation scheme
according to the channel conditions.
Hence, the Hybrid microwave can ensure the
reliable transmission of the E1 services and provide
dynamic bandwidth for the Ethernet services when
the AM function is enabled.
Modulation Mode l QPSK QPSK This parameter specifies the lowest modulation
of the Assured AM l 16QAM scheme that the AM function supports. Set this
Capacity parameter to the planned value. Generally, the value
l 32QAM of this parameter is determined by the service
l 64QAM transmission bandwidth that the Hybrid microwave
must ensure and the availability of the radio link that
l 128QAM corresponds to this modulation scheme.
l 256QAM This parameter is valid only when AM Enable
Status is set to Enable.
Modulation Mode l QPSK 128QAM This parameter specifies the highest modulation
of the Full AM l 16QAM scheme that the AM function supports. Set this
Capacity parameter to the planned value. Generally, the value
l 32QAM of this parameter is determined by the bandwidth of
l 64QAM the services that need to be transmitted over the
Hybrid microwave and the availability of the radio
l 128QAM link that corresponds to this modulation scheme.
l 256QAM This parameter is valid only when AM Enable
Status is set to Enable.
Prerequisite
You must be an NM user with "NE operator" authority or higher. That is, you must be an NE
user with "Operation Level" authority or higher.
Precautions
l The IDU 605 IF/2F supports the Ethernet board EMS4 (a logical board).
Ethernet ports FE1 - FE3 of an EMS4 board (a logical board) correspond to PORT1 -
PORT3 respectively. Port FE4/GE1 of an EMS4 board corresponds to PORT4.
Procedure
Step 1 Select the Ethernet board in the NE Explorer. Choose Configuration > Ethernet Interface
Management > Ethernet Interface from the Function Tree. Select External Port.
3. Click Apply.
3. Click Apply.
3. Click Apply.
Step 5 Optional: Set the advanced attributes of the port.
1. Click the Advanced Attributes tab.
2. Set the advanced attributes of the port.
3. Click Apply.
----End
Parameters
Parameter Value Range Default Value Description
Enabled/Disabled Enabled, Disabled Disabled l In the case of the port that accesses
services, set this parameter to Enabled.
In the case of other ports, set this
parameter to Disabled.
l If this parameter is set to Enabled for the
port that does not access services, an
ETH_LOS alarm may be generated.
Working Mode 10M Half-Duplex, Auto-Negotiation l The Ethernet ports of different types
10M Full-Duplex, support different working modes.
100M Half-Duplex, l When the equipment on the opposite side
100M Full-Duplex, works in the auto-negotiation mode, set
Auto-Negotiation (a the working mode of the equipment on
logical board EMS4, the local side to Auto-Negotiation.
PORT1 - PORT3)
l When the equipment on the opposite side
10M Half-Duplex, works in the full-duplex mode, set the
10M Full-Duplex, working mode of the equipment on the
100M Half-Duplex, local side to 10M Full-Duplex, 100M
100M Full-Duplex, Full-Duplex, or 1000M Full-Duplex
1000M Full- depending on the port rate of the
Duplex, Auto- equipment on the opposite side.
Negotiation (a
logical board EMS4, l When the equipment on the opposite side
PORT4) works in the half-duplex mode, set the
working mode of the equipment on the
local side to 10M Half-Duplex, 100M
Half-Duplex, or Auto-Negotiation
depending on the port rate of the
equipment on the opposite side.
Maximum Frame 1522/1632 (a logical 1522 The value of this parameter should be
Length board EMS4) greater than the maximum length of a frame
among all the data frames to be transported.
In the case of the IDU 605 1F/2F, set
Maximum Frame Length of all the ports
on the logical EMS4 board to the same
value.
PHY Loopback Non-Loopback, Non-Loopback l When this parameter is set to Inloop, the
Inloop Ethernet physical signals that are to be
sent to the remote end are looped back.
l In normal cases, use the default value.
TAG Access, Tag Aware, Tag Aware l When ports are configured with TAG
Hybrid flags, the ports process frames by using
the methods provided in Table 5-1.
l If all the accessed services are frames
with the VLAN tag (tagged frames), set
this parameter to Tag Aware.
l If all the accessed services are frames that
do not have the VLAN tag (untagged
frames), set this parameter to Access.
l When the accessed services contain
tagged frames and untagged frames, set
this parameter to Hybrid.
Enabling Broadcast Enabled, Disabled Disabled This parameter specifies whether to restrict
Packet Suppression the traffic of broadcast packets according to
the ratio of the broadcast packets to the total
packets. When a broadcast storm may occur
in the equipment on the opposite side, set
this parameter to Enabled.
Broadcast Packet 10% to 100% 30% The port discards the received broadcast
Suppression packets when the ratio of the received
Threshold broadcast packets to the total packets
exceeds the value of this parameter. The
value of this parameter should be greater
than the ratio of the broadcast packets to the
total packets when the broadcast storm does
not occur. Generally, set this parameter to
30% or a greater value.
Loop Detection Disabled, Enabled Disabled Sets whether to enable loop detection, which
is used to check whether a loop exists at the
port.
Loop Port Shutdown Disabled, Enabled Enabled Sets whether to enable the loop port
shutdown function. After the loop port
shutdown function is enabled, the port is
automatically shut down when a self-loop is
detected. It is recommended that this
parameter adopts the default value.
Ingress Tagged frame The port receives the The port discards the The port receives the
frame. frame. frame.
Untagged frame The port discards the The port adds the The port adds the
frame. VLAN tag to which VLAN tag to which
Default VLAN ID Default VLAN ID
and VLAN and VLAN
Priority Priority
correspond, to the correspond, to the
frame, and receives frame, and receives
the frame. the frame.
Egress Tagged frame The port transmits The port strips the l If the VLAN ID
the frame. VLAN tag from the in the frame is
frame and then Default VLAN
transmits the frame. ID, the port strips
the VLAN tag
from the frame
and then
transmits the
frame.
l If the VLAN ID
in the frame is not
Default VLAN
ID, the port
directly transmits
the frame.
NOTE
a: When the TAG attribute of a port on the EMS4 board (a logical board) that is supported by the IDU 605
1F/2F is set to Hybrid, the packet that is forwarded by this port remains the same as the packet that enters
the bridge.
Prerequisite
l The communication between the NMS and the NE must be normal.
l You must be an NM user with "NE monitor" authority or higher.
Related Information
The AM working state can be queried only when the IDU 605 1F/2F is configured with hybrid
microwave services.
Procedure
Step 1 Select an NE from the Object Tree in the NE Explorer.
Step 2 Select the corresponding IFH1 board from the NE slot layout on the right side.
Step 3 Choose Configuration > Hybrid/AM Configuration from the Function Tree.
Step 4 Select the corresponding IFH1 board in the Hybrid/AM Configuration tab page.
Step 5 Click Query.
The current modulation modes of the transmit end and the receive end of the IFH1 board are
displayed.
----End
Prerequisite
You must be an NM user with "NE operator" authority or higher. That is, you must be an NE
user with "Operation Level" authority or higher.
The board that supports the creation of the MD must be created.
Procedure
Step 1 In the NE Explorer interface, select an NE, and choose Configuration > Ethernet
Maintenance > Ethernet Service OAMfrom the Function Tree.
Step 2 In the right-hand pane, click OAM Configuration to display the OAM Configuration dialog
box.
NOTE
Step 3 Click New and select Create MD from the drop-down list.
Step 4 In the New Maintenance Domain dialog box displayed, configure the corresponding
parameters.
----End
Parameters
Field Value Default Description
Prerequisite
You must be an NM user with "NE operator" authority or higher. That is, you must be an NE
user with "Operation Level" authority or higher.
Procedure
Step 1 In the NE Explorer interface, select an NE, and choose Configuration > Ethernet
Maintenance > Ethernet Service OAMfrom the Function Tree.
Step 2 Click OAM Configuration in the right window to display the OAM Configuration dialog box.
NOTE
In this user interface, you can create or delete OAM maintenance Association (MAs).
Step 4 In the dialog box of New Maintenance Association displayed, configure the OAM parameters.
Step 5 ClickApply. The Operation Result dialog box is displayed, indicating that the operation was
successful.
Step 6 Click Close.
----End
Parameters
Field Value Default Description
Prerequisite
You must be an NM user with "NE operator" authority or higher. That is, you must be an NE
user with "Operation Level" authority or higher.
The Ethernet service must be created and activated.
Precaution
In an OAM test, all maintenance points that are involved in the operating of the same service
flow must be in the same maintenance domain. In an existing maintenance domain involved in
the same service flow, creating a maintenance point of the same level or a higher level may
damage the existing maintenance domain. As a result, the OAM test fails.
Procedure
Step 1 In the NE Explorer, select an Ethernet board and choose Configuration > Ethernet
Maintenance > Ethernet Service OAM from the Function Tree.
Step 2 Click New and the Create MP dialog box is displayed. Complete the information.
NOTE
l VLAN ID: Leave this field blank for PORT services. For PORT+VLAN services, set the VLAN ID
of the services to be monitored.
l Service Direction: Only MEPs have the directions. Set the direction from the external physical port
to the system-side VCTRUNK port as the SDH direction, and from the system-side VCTRUNK port
to the external physical port as the IP direction. MIPs can only be set as bidirectional. . If the data is
from the exterior board, the MP direction is IP. The MIPs can be only bidirectional.
Step 3 Optional: Click Advanced. In the dialog box displayed, set the corresponding parameters and
click OK.
NOTE
If an MEP is created, you can choose whether to perform the following configuration.
l Activate the CC and configure the sending period of the CC test.
l Set the timeout time for the LB or LT test.
Step 4 Click OK. A prompt appears telling you that the operation was successful. Click Close to finish
the operation.
----End
Parameters
Field Value Default Description
Level Consumer High Operator Low The priority of the MP is the priority
(7), Consumer (0) of the MD. The greater the value,
Middle(6), the higher the priority.
Consumer Low
(5), Provider
High(4),
Provider Low
(3), Operator
High(2),
Operator
Middle(1),
Operator Low
(0)
CCM Sending In the case of a In the case of a Sets the time interval for sending
Period(ms) standard MP, standard MP, the CCM packet at the maintenance
1000, 10000, 1000. point where the CC test is
6000, 600000 In the case of a performed.
In the case of a Huawei MP, l If the time interval is very short,
Huawei MP, 5000. excessive service bandwidths are
1000 to 60000. occupied.
l If the time interval is very long,
the CC test is less sensitive to the
service interruption. Thus, the
default value is recommended.
A Glossary
A.1 0-9
This section provides the terms starting with numbers.
A.2 A-E
This section provides the terms starting with letters A to E.
A.3 F-J
This section provides the terms starting with letters F to J.
A.4 K-O
This section provides the terms starting with letters K to O.
A.5 P-T
This section provides the terms starting with letters P to T.
A.6 U-Z
This section provides the terms starting with letters U to Z.
A.1 0-9
This section provides the terms starting with numbers.
1+1 protection An architecture that has one normal traffic signal, one working SNC/trail, one protection
SNC/trail and a permanent bridge. At the source end, the normal traffic signal is
permanently bridged to both the working and protection SNC/trail. At the sink end, the
normal traffic signal is selected from the better of the two SNCs/trails. Due to the
permanent bridging, the 1+1 architecture does not allow an extra unprotected traffic
signal to be provided.
1U The standard electronics industries association (EIA) rack unit (44 mm/1.75 in.)
802.1Q in 802.1Q 802.1Q in 802.1Q (QinQ) is a VLAN feature that allows the equipment to add a VLAN
tag to a tagged frame.The implementation of QinQ is to add a public VLAN tag to a
frame with a private VLAN tag, making the frame encapsulated with two layers of VLAN
tags. The frame is forwarded over the service provider's backbone network based on the
public VLAN tag. By this, a layer 2 VPN tunnel is provided to customers.The QinQ
feature enables the transmission of the private VLANs to the peer end transparently.
A.2 A-E
This section provides the terms starting with letters A to E.
Administrative Unit The information structure which provides adaptation between the higher order path layer
and the multiplex section layer. It consists of an information payload (the higher order
VC) and an AU pointer which indicates the offset of the payload frame start relative to
the multiplex section frame start.
AGC See Automatic Gain Control
AM See adaptive modulation
Analog to Digital An electronic circuit that converts continuous signals to discrete digital numbers. The
Converter reverse operation is performed by a digital-to-analog converter (DAC).
APS See Automatic Protection Switching
ARP See Address Resolution Protocol
ASK amplitude shift keying
ATPC See automatic transmit power control
AU See Administrative Unit
Automatic Gain A process or means by which gain is automatically adjusted in a specified manner as a
Control function of a specified parameter, such as received signal level.
Automatic Protection Automatic Protection Switching (APS) is the capability of a transmission system to
Switching detect a failure on a working facility and to switch to a standby facility to recover the
traffic.
automatic transmit A method of adjusting the transmit power based on fading of the transmit signal detected
power control at the receiver
B
Base Station Controller A logical entity that connects the BTS with the MSC in a GSM network. It interworks
with the BTS through the Abis interface, the MSC through the A interface. It provides
the following functions: Radio resource management, Base station management, Power
control, Handover control, and Traffic measurement. One BSC controls and manages
one or more BTSs in an actual network.
BER See Bit Error Rate
BIOS Basic Input Output System
BIP Bit-Interleaved Parity
bit error An incompatibility between a bit in a transmitted digital signal and the corresponding
bit in the received digital signal.
Bit Error Rate Bit error rate. Ratio of received bits that contain errors. BER is an important index used
to measure the communications quality of a network.
BPDU See Bridge Protocol Data Unit
Bridge Protocol Data The data messages that are exchanged across the switches within an extended LAN that
Unit uses a spanning tree protocol (STP) topology. BPDU packets contain information on
ports, addresses, priorities and costs and ensure that the data ends up where it was
intended to go. BPDU messages are exchanged across bridges to detect loops in a
network topology. The loops are then removed by shutting down selected bridges
interfaces and placing redundant switch ports in a backup, or blocked, state.
BSC See Base Station Controller
C
C-VLAN Customer VLAN
CAR See committed access rate
CBS See Committed Burst Size
CCDP See Co-Channel Dual Polarization
Central Processing The CPU is the brains of the computer. Sometimes referred to simply as the processor
Unit or central processor, the CPU is where most calculations take place.
CF See compact flash
CGMP Cisco Group Management Protocol
CIR See Committed Information Rate
CIST See Common and Internal Spanning Tree
Class of Service A class object that stores the priority mapping rules. When network congestion occurs,
the class of service (CoS) first processes services by different priority levels from high
to low. If the bandwidth is insufficient to support all services, the CoS dumps the services
of low priority.
Co-Channel Dual A channel configuration method, which uses a horizontal polarization wave and a vertical
Polarization polarization wave to transmit two signals. The Co-Channel Dual Polarization is twice
the transmission capacity of the single polarization.
committed access rate A traffic control method that uses a set of rate limits to be applied to a router interface.
CAR is a configurable method by which incoming and outgoing packets can be classified
into QoS (Quality of Service) groups, and by which the input or output transmission rate
can be defined.
Committed Burst Size committed burst size. A parameter used to define the capacity of token bucket C, that is,
the maximum burst IP packet size when the information is transferred at the committed
information rate. This parameter must be larger than 0. It is recommended that this
parameter should be not less than the maximum length of the IP packet that might be
forwarded.
Committed The rate at which a frame relay network agrees to transfer information in normal
Information Rate conditions. Namely, it is the rate, measured in bit/s, at which the token is transferred to
the leaky bucket.
Common and Internal Common and Internal Spanning Tree. The single Spanning Tree calculated by STP and
Spanning Tree RSTP together with the logical continuation of that connectivity through MST Bridges
and regions, calculatedby MSTP to ensure that all LANs in the Bridged Local Area
Network are simply and fully connected.
compact flash Compact flash (CF) was originally developed as a type of data storage device used in
portable electronic devices. For storage, CompactFlash typically uses flash memory in
a standardized enclosure.
CoS See Class of Service
CPU See Central Processing Unit
CRC See Cyclic Redundancy Check
cross polarization A technology used in the case of the Co-Channel Dual Polarization (CCDP) to eliminate
interference the cross-connect interference between two polarization waves in the CCDP.
cancellation
Cyclic Redundancy A procedure used in checking for errors in data transmission. CRC error checking uses
Check a complex calculation to generate a number based on the data transmitted. The sending
device performs the calculation before transmission and includes it in the packet that it
sends to the receiving device. The receiving device repeats the same calculation after
transmission. If both devices obtain the same result, it is assumed that the transmission
was error free. The procedure is known as a redundancy check because each transmission
includes not only data but extra (redundant) error-checking values.
Data Communication A communication network used in a TMN or between TMNs to support the Data
Network Communication Function (DCF).
Data Communications The data channel that uses the D1-D12 bytes in the overhead of an STM-N signal to
Channel transmit information on operation, management, maintenance and provision (OAM&P)
between NEs. The DCC channels that are composed of bytes D1-D3 is referred to as the
192 kbit/s DCC-R channel. The other DCC channel that are composed of bytes D4-D12
is referred to as the 576 kbit/s DCC-M channel.
DC See Direct Current
DC-C See DC-Return Common (with Ground)
DC-I See DC-Return Isolate (with Ground)
DC-Return Common A power system, in which the BGND of the DC return conductor is short-circuited with
(with Ground) the PGND on the output side of the power supply cabinet and also on the line between
the output of the power supply cabinet and the electric equipment.
DC-Return Isolate A power system, in which the BGND of the DC return conductor is short-circuited with
(with Ground) the PGND on the output side of the power supply cabinet and is isolated from the PGND
on the line between the output of the power supply cabinet and the electric equipment.
DCC See Data Communications Channel
DCN See Data Communication Network
Differentiated Services Differentiated Services CodePoint. A marker in the header of each IP packet using bits
Code Point 0-6 in the DS field. Routers provide differentiated classes of services to various service
streams/flows based on this marker. In other words, routers select corresponding PHB
according to the DSCP value.
digital modulation A digital modulation controls the changes in amplitude, phase, and frequency of the
carrier based on the changes in the baseband digital signal. In this manner, the
information can be transmitted by the carrier.
Direct Current Electrical current whose direction of flow does not reverse. The current may stop or
change amplitude, but it always flows in the same direction.
Distance Vector Distance Vector Multicast Routing Protocol. The DVMRP protocol is an Internet
Multicast Routing gateway protocol mainly based on the RIP. The protocol implements a typical dense
Protocol mode IP multicast solution. The DVMRP protocol uses IGMP to exchange routing
datagrams with its neighbors.
DSCP See Differentiated Services Code Point
dual-polarized antenna An antenna intended to radiate or receive simultaneously two independent radio waves
orthogonally polarized.
DVMRP See Distance Vector Multicast Routing Protocol
E
E-LAN Ethernet-LAN
ECC See Embedded Control Channel
Electro Magnetic Any electromagnetic disturbance that interrupts, obstructs, or otherwise degrades or
Interference limits the effective performance of electronics/electrical equipment.
electromagnetic Electromagnetic compatibility is the condition which prevails when telecommunications
compatibility equipment is performing its individually designed function in a common electromagnetic
environment without causing or suffering unacceptable degradation due to unintentional
electromagnetic interference to or from other equipment in the same environment.
[NTIA]
Embedded Control An ECC provides a logical operations channel between SDH NEs, utilizing a data
Channel communications channel (DCC) as its physical layer.
EMC See electromagnetic compatibility
EMI See Electro Magnetic Interference
EPL See Ethernet Private Line
EPLAN See ethernet private lan service
equalization A method of avoiding selective fading of frequencies. Equalization can compensate for
the changes of amplitude frequency caused by frequency selective fading.
ERPS See ethernet ring protection switching
ES-IS End System to Intermediate System
ethernet private lan An Ethernet service type, which carries Ethernet characteristic information over a
service dedocated bridge, point-to-multipoint connections, provided by SDH, PDH, ATM, or
MPLS server layer networks.
Ethernet Private Line A point-to-point interconnection between two UNIs without SDH bandwidth sharing.
Transport bandwidth is never shared between different customers.
ethernet ring protection switching mechanisms for ETH layer Ethernet ring topologies.
protection switching
ethernet virtual private An Ethernet service type, which carries Ethernet characteristic information over a shared
lan service bridge, point-to-multipoint connections, provided by SDH, PDH, ATM, or MPLS server
layer networks.
ethernet virtual private An Ethernet service type, which carries Ethernet characteristic information over shared
line service bandwidth, point-to-point connections, provided by SDH, PDH, ATM, or MPLS server
layer networks.
ETSI See European Telecommunications Standards Institute
European A standards-setting body in Europe. Also the standards body responsible for GSM.
Telecommunications
Standards Institute
A.3 F-J
This section provides the terms starting with letters F to J.
F
Fast Ethernet A type of Ethernet with a maximum transmission rate of 100 Mbit/s. It complies with
the IEEE 802.3u standard and extends the traditional media-sharing Ethernet standard.
fast link pulse The likn pulse that is used to encode information during automatic negotiation.
FCS Frame Check Sequence
FD See frequency diversity
FE See Fast Ethernet
FEC See Forward Error Correction
Field Programmable A type of semi-customized circuit used in the Application Specific Integrated Circuit
Gate Array (ASIC) field. It is developed on the basis of the programmable components, such as the
PAL, GAL, and EPLD. It not only remedies the defects of customized circuits, but also
overcomes the disadvantage of the original programmable components in terms of the
limited number of gate arraies.
FIFO See First in First out
File Transfer Protocol A member of the TCP/IP suite of protocols, used to copy files between two computers
on the Internet. Both computers must support their respective FTP roles: one must be an
FTP client and the other an FTP server.
First in First out A stack management mechanism. The first saved data is first read and invoked.
FLP See fast link pulse
Forward Error A bit error correction technology that adds the correction information to the payload at
Correction the transmit end. Based on the correction information, the bit errors generated during
transmission are corrected at the receive end.
FPGA See Field Programmable Gate Array
frequency diversity A diversity scheme that enables two or more microwave frequencies with a certain
frequency interval are used to transmit/receive the same signal and selection is then
performed between the two signals to ease the impact of fading.
FTP See File Transfer Protocol
G
gateway network A network element that is used for communication between the NE application layer and
element the NM application layer
GE See Gigabit Ethernet
Generic traffic shaping A traffic control measure that initiatively adjusts the output speed of the traffic. This is
to adapt the traffic to network resources that can be provided by the downstream router
to avoid packet discarding and congestion.
GFP Generic Framing Procedure
Gigabit Ethernet GE adopts the IEEE 802.3z. GE is compatible with 10 Mbit/s and 100 Mbit/s Ethernet.It
runs at 1000Mbit/s. Gigabit Ethernet uses a private medium, and it does not support
coaxial cables or other cables. It also supports the channels in the bandwidth mode. If
Gigabit Ethernet is, however, deployed to be the private bandwidth system with a bridge
(switch) or a router as the center, it gives full play to the performance and the bandwidth.
In the network structure, Gigabit Ethernet uses full duplex links that are private, causing
the length of the links to be sufficient for backbone applications in a building and campus.
GNE See gateway network element
Graphical User A visual computer enviroment that represents programs, files, and options with graphical
Interface images, such as icons, menus, and dialog boxes, on the screen.
GTS See Generic traffic shaping
GUI See Graphical User Interface
IGMP snooping A multicast constraint mechanism running on a layer 2 device. This protocol manages
and controls the multicast group by listening to and analyze the Internet Group
Management Protocol (IGMP) packet between hosts and layer 3 devices. In this manner,
the spread of the multicast data on layer 2 network can be prevented efficiently.
indoor unit The indoor unit of the split-structured radio equipment. It implements accessing,
multiplexing/demultiplexing, and IF processing for services.
Institute of Electrical A society of engineering and electronics professionals based in the United States but
and Electronics boasting membership from numerous other countries. The IEEE focuses on electrical,
Engineers electronics, computer engineering, and science-related matters.
intermediate frequency The transitional frequency between the frequencies of a modulated signal and an RF
signal.
intermediate frequency The transitional frequency between the frequencies of a modulated signal and an RF
signal.
Intermediate System to A protocol used by network devices (routers) .IS-IS is a kind of Interior Gateway Protocol
Intermediate System (IGP), used within the ASs. It is a link status protocol using Shortest Path First (SPF)
algorithm to calculate the route.
International The International Electrotechnical Commission (IEC) is an international and non-
Electrotechnical governmental standards organization dealing with electrical and electronical standards.
Commission
International ISO (International Organization for Standardization) is the world's largest developer and
Organization for publisher of International Standards.
Standardization
Internet Control ICMP belongs to the TCP/IP protocol suite. It is used to send error and control messages
Messages Protocol during the transmission of IP-type data packets.
Internet Group The protocol for managing the membership of Internet Protocol multicast groups among
Management Protocol the TCP/IP protocols. It is used by IP hosts and adjacent multicast routers to establish
and maintain multicast group memberships.
Internet Protocol The TCP/IP standard protocol that defines the IP packet as the unit of information sent
across an internet and provides the basis for connectionless, best-effort packet delivery
service. IP includes the ICMP control and error message protocol as an integral part. The
entire protocol suite is often referred to as TCP/IP because TCP and IP are the two
fundamental protocols. IP is standardized in RFC 791.
Internet Protocol A update version of IPv4. It is also called IP Next Generation (IPng). The specifications
Version 6 and standardizations provided by it are consistent with the Internet Engineering Task
Force (IETF).Internet Protocol Version 6 (IPv6) is also called. It is a new version of the
Internet Protocol, designed as the successor to IPv4. The specifications and
standardizations provided by it are consistent with the Internet Engineering Task Force
(IETF).The difference between IPv6 and IPv4 is that an IPv4 address has 32 bits while
an IPv6 address has 128 bits.
IP See Internet Protocol
IPv6 See Internet Protocol Version 6
IS-IS See Intermediate System to Intermediate System
ISO See International Organization for Standardization
ITU-T International Telecommunication Union - Telecommunication Standardization Sector
A.4 K-O
This section provides the terms starting with letters K to O.
L
LAG See link aggregation group
LAN See Local Area Network
LAPD Link Access Procedure on the D channel
LAPS Link Access Procedure-SDH
layer 2 switch A data forwarding method. In LAN, a network bridge or 802.3 Ethernet switch transmits
and distributes packet data based on the MAC address. Since the MAC address is the
second layer of the OSI model, this data forwarding method is called layer 2 switch.
LB See Loopback
LCAS See Link Capacity Adjustment Scheme
LDPC Low-Density Parity Check code
link aggregation group An aggregation that allows one or more links to be aggregated together to form a link
aggregation group so that a MAC clientcan treat the link aggregation group as if it were
a single link.
Link Capacity The Link Capacity Adjustment Scheme (LCAS) is designed to allow the dynamic
Adjustment Scheme provisioning of bandwidth, using VCAT, to meet customer requirements.
LMSP Linear Multiplex Section Protection
Local Area Network A network formed by the computers and workstations within the coverage of a few square
kilometers or within a single building. It features high speed and low error rate. Ethernet,
FDDI, and Token Ring are three technologies used to implement a LAN. Current LANs
are generally based on switched Ethernet or Wi-Fi technology and running at 1,000 Mbit/
s (that is, 1 Gbit/s).
Loopback A troubleshooting technique that returns a transmitted signal to its source so that the
signal or message can be analyzed for errors.
LPT Link State Path Through
M
MA See Maintenance Association
MAC See Medium Access Control
MADM Multi Add-Drop Multiplexer
Maintenance That portion of a Service Instance, preferably all of it or as much as possible, the
Association connectivity of which is maintained by CFM. It is also a full mesh of Maintenance
Entities.
Maintenance Domain The Maintenance Domain (MD) refers to the network or the part of the network for which
connectivity is managed by CFM. The devices in an MD are managed by a single ISP.
Maintenance Point Maintenance Point (MP) is one of either a MEP or a MIP.
Management A type of database used for managing the devices in a communications network. It
Information Base comprises a collection of objects in a (virtual) database used to manage entities (such as
routers and switches) in a network.
Maximum Transfer The MTU (Maximum Transmission Unit) is the size of the largest datagram that can be
Unit sent over a network.
MBS Maximum Burst Size
MD See Maintenance Domain
MDI See Medium Dependent Interface
Mean Time To Repair The average time that a device will take to recover from a failure.
Medium Access A general reference to the low-level hardware protocols used to access a particular
Control network. The term MAC address is often used as a synonym for physical addresses.
Medium Dependent The electrical and mechanical interface between the equipment and the media
Interface transmission.
MEP Maintenance End Point
MIB See Management Information Base
MP See Maintenance Point
MSP See multiplex section protection
MSTP See Multiple Spanning Tree Protocol
MTBF Mean Time Between Failure
MTTR See Mean Time To Repair
MTU See Maximum Transfer Unit
Multiple Spanning Multiple spanning tree protocol. The MSTP can be used in a loop network. Using an
Tree Protocol algorithm, the MSTP blocks redundant paths so that the loop network can be trimmed
as a tree network. In this case, the proliferation and endless cycling of packets is avoided
in the loop network.The protocol that introduces the mapping between VLANs and
multiple spanning trees. This solves the problem that data cannot be normally forwarded
in a VLAN because in STP/RSTP, only one spanning tree corresponds to all the VLANs.
multiplex section A function, which is performed to provide capability for switching a signal between and
protection including two multiplex section termination (MST) functions, from a "working" to a
"protection" channel.
N
N+1 protection A radio link protection system composed of N working channels and one protection
channel.
NE See Network Element
Network Element A network element (NE) contains both the hardware and the software running on it. One
NE is at least equipped with one system control board which manages and monitors the
entire network element. The NE software runs on the system control board.
network management The network management system in charge of the operation, administration, and
system maintenance of a network.
Network Service Access A network address defined by ISO, through which entities on the network layer can
Point access OSI network services.
NLP Normal Link Pulse
NMS See network management system
NNI Network-to-Network Interface or Network Node Interface
non-gateway network A network element whose communication with the NM application layer must be
element transferred by the gateway network element application layer.
non-GNE See non-gateway network element
NSAP See Network Service Access Point
O
OAM Operations, Administration and Maintenance
ODU See outdoor unit
Open Shortest Path A link-state, hierarchical interior gateway protocol (IGP) for network routing. Dijkstra's
First algorithm is used to calculate the shortest path tree. It uses cost as its routing metric. A
link state database is constructed of the network topology which is identical on all routers
in the area.
Open Systems A standard or "reference model" (officially defined by the International Organization of
Interconnection Standards (ISO)) for how messages should be transmitted between any two points in a
telecommunication network. The reference model defines seven layers of functions that
take place at each end of a communication.
orderwire A channel that provides voice communication between operation engineers or
maintenance engineers of different stations.
OSI See Open Systems Interconnection
OSPF See Open Shortest Path First
outdoor unit The outdoor unit of the split-structured radio equipment. It implements frequency
conversion and amplification for RF signals.
A.5 P-T
This section provides the terms starting with letters P to T.
P
PDH See Plesiochronous Digital Hierarchy
Peak Information Rate Peak Information Rate . A traffic parameter, expressed in bit/s, whose value should be
not less than the committed information rate.
PIM-DM Protocol Independent Multicast-Dense Mode
PIM-SM See Protocol Independent Multicast-Sparse Mode
Q
QoS See Quality of Service
QPSK See Quadrature Phase Shift Keying
Quadrature Phase Shift Quadrature Phase Shift Keying (QPSK) is a modulation method of data transmission
Keying through the conversion or modulation and the phase determination of the reference
signals (carrier). It is also called the fourth period or 4-phase PSK or 4-PSK. QPSK uses
four dots in the star diagram. The four dots are evenly distributed on a circle. On these
phases, each QPSK character can perform two-bit coding and display the codes in Gray
code on graph with the minimum BER.
Quality of Service Quality of Service, which determines the satisfaction of a subscriber for a service. QoS
is influenced by the following factors applicable to all services: service operability,
service accessibility, service maintainability, and service integrity.
R
Radio Freqency A type of electric current in the wireless network using AC antennas to create an
electromagnetic field. It is the abbreviation of high-frequency AC electromagnetic wave.
The AC with the frequency lower than 1 kHz is called low-frequency current. The AC
with frequency higher than 10 kHz is called high-frequency current. RF can be classified
into such high-frequency current.
Radio Network A device used in the RNS to control the usage and integrity of radio resources.
Controller
Rapid Spanning Tree An evolution of the Spanning Tree Protocol, providing for faster spanning tree
Protocol convergence after a topology change. The RSTP protocol is backward compatible with
the STP protocol.
Received signal level The signal level at a receiver input terminal.
Received Signal The received wide band power, including thermal noise and noise generated in the
Strength Indicator receiver, within the bandwidth defined by the receiver pulse shaping filter, for TDD
within a specified timeslot. The reference point for the measurement shall be the antenna
RF See Radio Freqency
RFC Request For Comment
RIP See Routing Information Protocol
RMON Remote Monitoring
RNC See Radio Network Controller
Routing Information Routing Information Protocol: A simple routing protocol that is part of the TCP/IP
Protocol protocol suite. It determines a route based on the smallest hop count between source and
destination. RIP is a distance vector protocol that routinely broadcasts routing
information to its neighboring routers and is known to waste bandwidth.
RS Reed-Solomon encoding
RSL Received Signal Level
RSSI See Received Signal Strength Indicator
RSTP See Rapid Spanning Tree Protocol
RTN Radio Transmission Node
S
SD See space diversity
SDH See Synchronous Digital Hierarchy
SFP See Small Form-Factor Pluggable
Signal Noise Ratio The SNR or S/N (Signal to Noise Ratio) of the amplitude of the desired signal to the
amplitude of noise signals at a given point in time. SNR is expressed as 10 times the
logarithm of the power ratio and is usually expressed in dB (Decibel).
Simple Network A network management protocol of TCP/IP. It enables remote users to view and modify
Management Protocol the management information of a network element. This protocol ensures the
transmission of management information between any two points. The polling
mechanism is adopted to provide basic function sets. According to SNMP, agents, which
can be hardware as well as software, can monitor the activities of various devices on the
network and report these activities to the network console workstation. Control
information about each device is maintained by a management information block.
Small Form-Factor A specification for a new generation of optical modular transceivers.
Pluggable
SNC See SubNetwork Connection
SNCP See SubNetwork Connection Protection
SNMP See Simple Network Management Protocol
synchronous transport An STM is the information structure used to support section layer connections in the
module SDH. It consists of information payload and Section Overhead (SOH) information fields
organized in a block frame structure which repeats every 125 . The information is suitably
conditioned for serial transmission on the selected media at a rate which is synchronized
to the network. A basic STM is defined at 155 520 kbit/s. This is termed STM-1. Higher
capacity STMs are formed at rates equivalent to N times this basic rate. STM capacities
for N = 4, N = 16 and N = 64 are defined; higher values are under consideration.
T
TCI Tag Control Information
TCP See TransmissionControl Protocol
TDM See Time Division Multiplexing
Telecommunication The Telecommunications Management Network is a protocol model defined by ITU-T
Management Network for managing open systems in a communications network.An architecture for
management, including planning, provisioning, installation, maintenance, operation and
administration of telecommunications equipment, networks and services.
Time Division It is a multiplexing technology. TDM divides the sampling cycle of a channel into time
Multiplexing slots (TSn, n=0, 1, 2, 3…… ), and the sampling value codes of multiple signals engross
time slots in a certain order, forming multiple multiplexing digital signals to be
transmitted over one channel.
TMN See Telecommunication Management Network
trail A type of transport entity, mainly engaged in transferring signals from the input of the
trail source to the output of the trail sink, and monitoring the integrality of the transferred
signals.
TransmissionControl The protocol within TCP/IP that governs the breakup of data messages into packets to
Protocol be sent via IP (Internet Protocol), and the reassembly and verification of the complete
messages from packets received by IP. A connection-oriented, reliable protocol (reliable
in the sense of ensuring error-free delivery), TCP corresponds to the transport layer in
the ISO/OSI reference model.
TU Tributary Unit
A.6 U-Z
This section provides the terms starting with letters U to Z.
U
UDP See User Datagram Protocol
UNI See User Network Interface
User Datagram A TCP/IP standard protocol that allows an application program on one device to send a
Protocol datagram to an application program on another. User Datagram Protocol (UDP) uses IP
to deliver datagrams. UDP provides application programs with the unreliable
connectionless packet delivery service. Thus, UDP messages can be lost, duplicated,
delayed, or delivered out of order.UDP is used to try to transmit the data packet, that is,
the destination device does not actively confirm whether the correct data packet is
received.
User Network Interface A type of ATM Forum specification that defines an interoperability standard for the
interface between ATM-based products (a router or an ATM switch) located in a private
network and the ATM switches located within the public carrier networks. Also used to
describe similar connections in Frame Relay networks.
V
VC See Virtual Container
VC-12 Virtual Container -12
VC-3 Virtual Container -3
VC-4 Virtual Container -4
VCG See virtual concatenation group
VCTRUNK A virtual concatenation group applied in data service mapping, also called the internal
port of a data service processing board
virtual concatenation A group of co-located member trail termination functions that are connected to the same
group virtual concatenation link
Virtual Container A Virtual Container is the information structure used to support path layer connections
in the SDH. It consists of information payload and path Overhead (POH) information
fields organized in a block frame structure which repeats every 125 or 500 μs.
Virtual Local Area A logical grouping of two or more nodes which are not necessarily on the same physical
Network network segment but which share the same IP network number. This is often associated
with switched Ethernet.
Virtual Private The extension of a private network that encompasses encapsulated, encrypted, and
Network authenticated links across shared or public networks. VPN connections can provide
remote access and routed connections to private networks over the Internet.
VLAN See Virtual Local Area Network
Voice over IP An IP telephony term for a set of facilities used to manage the delivery of voice
information over the Internet. VoIP involves sending voice information in a digital form
in discrete packets rather than by using the traditional circuit-committed protocols of the
public switched telephone network (PSTN).
VoIP See Voice over IP
VPN See Virtual Private Network
W
Wait to Restore Time A period of time that must elapse before a - from a fault recovered - trail/connection can
be used again to transport the normal traffic signal and/or to select the normal traffic
signal from.
X
XPD Cross-Polarization Discrimination
XPIC See cross polarization interference cancellation