Beruflich Dokumente
Kultur Dokumente
MQT1913
MQT1913
Liquid Cooled Cold Plate
Features
3000 Watt heat rejection @ 8 LPM with a 24° C temperature rise from the fluid inlet to the maximum cold plate
?
temperature
Patent pending Q-CHILL internal fin technology provides for a more uniform top cold plate surface temperature
?
Low pressure drop for reduced system cost (1.16 PSI @ 8 LPM)
?
Low cost proven aluminum solution with performance comparable to copper based solutions
?
Power Compact and light (1.2 kg)
?
Compatible with industry accepted coolants
?
Metallurgical seal for robustness and a high pressure rating
?
PERFORMANCE CURVES
Flow Rate GPM
1.0 1.5 2.0 2.5 PSI / Bar
0.018 2.25 / 0.155
Cooling Fluid:
0.016 2.00 / 0.138 50% Ethylene Glycol
Thermal Resistance (ºC/Watt)
50% Water
0.014 1.75 / 0.121
Thermal Resistance values
0.012 1.50 / 0.103 use the difference between the
Pressure Drop
Maximum Cold Plate Temp.
0.010 1.25 / 0.086
and the Fluid Inlet Temp.
0.008 1.00 / 0.069
Pressure Drop Includes
0.006 0.75 / 0.052 1/4 - 18 NPT Barb Fittings
MECHANICAL OUTLINE
20 89 89
Ø 5.5, THRU M6x1.0 X 15 DP
6 PLACES 12 PLACES
¼-18 NPT
4 PLACES
MODULE SIDE
0.025/25.4
0.8um
71.5
130
119
93
29.3
+0.3 17 17
10.0 -0.3
R 4.3, 4 PLACES 48 48 48
202