Miniature Circuit Breakers (MCB)

Multi 9
Definition
Main functions

 Melindungi kabel thd  Symbol


beban lebih dan hubung
pendek
 Arus mengalir tanpa
kepanasan pada kabel
 Buka dan tutup rangkaian
di bawah arus rate
 melndungi thd gangguan
isolasi (see earth leakage
protection module)

Miniature circuit = switch + trip unit breaker (MCB) 4

Customer Training - Freddy Suhartono - April 2000 - English 2


Definition
A Multi 9 circuit breaker has:

 Sistem mekanis utk buka dan tutup


circuits
 Sebuah bimetal utk tindakan thd
overloads
 Magnetik utk tindakan thd short circuits

Miniature circuit = switch + trip unit breaker (MCB) 4

Customer Training - Freddy Suhartono - April 2000 - English 3


Definition
Main performances
 It has standardized modular dimensions
  125
  50 kA
  440 V CA

It fits in your pocket... 4

Customer Training - Freddy Suhartono - April 2000 - English 4


Definition
 The modular design meets 2  Multi 9 standard
criteria:  Multi 9 switchgear comes in 9 mm pitch 4
 mounting on a 35 mm
symmetrical rail
 dimensions
- modules in widths of 44 maxi
17.5 mm + 0.5 - 0 21.3

- external part = 45 mm
- depth between 55 and 70 mm
81
45 35
width maxi

symmetrical 10 maxi 60
external
rail depth part

Customer Training - Freddy Suhartono - April 2000 - English 5


The technology
Active parts

C60N NC100 / NC125

terminal terminal

bimetral strip fixed contact

strip braid moving


contact
moving strip braid
contact
magnetic
trip
magnetic trip
strip braid
bimetal strip
load side load side
terminal terminal
4

Customer Training - Freddy Suhartono - April 2000 - English 6


Overload protection
 A bimetal strip is used:
 to protect the cable against overloads
 symbol:
 principle of the bimetal: in a Multi 9 circuit
breaker 4

NC45 NC100 / NC125

bimetal
tripping bar
tripping bar
bimetal

screw
calibration

strip
braid

Customer Training - Freddy Suhartono - April 2000 - English 7


Overload protection

 Thermal tripping curve


 the "thermal" part of the t (s)
tripping curve must be in
sesuai dg the standard tripping

no
tripping

destruction
of bimetal
accuracy

Legend:
In = rated current In Ind Id I/In
Ind = no tripping current
Id = tripping current 4

Customer Training - Freddy Suhartono - April 2000 - English 8


Overload protection

 Temperature derating
 our circuit breakers do not have temperature
compensation
 if the calibration temperature is different from
the ambient temperature: derating is required

Simultaneous multi-pole tripping 4

Customer Training - Freddy Suhartono - April 2000 - English 9


Short-circuit protection

Short-circuit current is given as RMS or peak


(Isc or Îsc)
RMS = Root Mean Square in symmetrical DC
(with PF = I)

Short-circuit protection must limit thermal stress in the


cable in order to prevent cable damage (which may
reach vaporization of the copper in some cases)

Comments slide 29

Customer Training - Freddy Suhartono - April 2000 - English 10


Short-circuit protection
The arc in Multi 9 circuit breakers

NC45 NC100 / NC125

arcing
horn arcing
horn

"By-pass" technique for the "By-pass" technique for the protection of


protection of sensitive parts sensitive parts of the circuit breaker (magnetic
of the circuit breaker DC trip)
breaking is difficult 2 breaking techniques used by Multi 9 4

Customer Training - Freddy Suhartono - April 2000 - English 11


Short-circuit protection
Magnetic tripping curve

t (s) destruction
of the solenoid

tripping
no
tripping

Legend:
Ind = no tripping current Ind Id I/In
Id = tripping current
Our curves are instantaneous tripping curves 4

Customer Training - Freddy Suhartono - April 2000 - English 12


The magnetic tripping levels with high inrush
current:
like LV/LV transformers
 C Curve
 5 and 10 In control and protection of
circuits with high short-circuit current
in industrial and domestic distributions
 D and K curves tripping betwen
 tripping: 10 to 14 In; more particulary
adopted for installations with high
inrush currents like LV/LV transformers
 B curve  Z curve
 3 and 5 In protection  2.4 to 3.6 In protection against
low short-circuit current electronic circuits
generators  MA curve
M
 12 In; protection only against
G short-circuit and high inrush currents
such as motors, coil 4

Customer Training - Freddy Suhartono - April 2000 - English 13


Marking
 Front panel marking:  Side panel marking:

Circuit breaker marking is governed by strict


rules in accordance with the standards and
decisions made by the manufacturer 4

Customer Training - Freddy Suhartono - April 2000 - English 14


Choosing a circuit breaker
In conclusion

 A Multi 9 circuit breaker is determined by:


 rating
 breaking capacity
 number of poles
 voltage
 tripping curve
 standard
 frequency
 type of load 4

Customer Training - Freddy Suhartono - April 2000 - English 15


Auxiliaries: C60

 4 types of auxiliaries for our  SD: alarm switch


Multi 9 circuit breakers  MX + OF: shunt trip
 OF: indication switch  MN: undervoltage release

OF SD MX+OF MN C60

44/3
54/3

51/3
52/3
53/3

54 mm maxi
The information is transmitted via a
mechanical link C60/NC100 and NC125
auxiliaries are not compatible 4

Customer Training - Freddy Suhartono - April 2000 - English 16


Auxiliaries: NC100 - NC125
 4 types of auxiliaries for our  SD: alarm switch
Multi 9 circuit breakers  MX + OF: shunt trip
 OF: indication switch  MN: undervoltage release

OF SD NC100H MN or MX+OF
or Vigi
33/3

34/3

27/3

35/3

36/3
The information is transmitted via a
mechanical link C60/NC100 and NC125
auxiliaries are not compatible 4

Customer Training - Freddy Suhartono - April 2000 - English 17


End presentation

Customer Training - Freddy Suhartono - April 2000 - English 18