Sie sind auf Seite 1von 2

DC12-150(12V150Ah)

Specification
Cells Per Unit 6
Voltage Per Unit 12
Capacity 150Ah@20hr-rate to 1.75V per cell @25℃
Weight Approx. 44.5 Kg (Tolerance±1.5%)
Internal Resistance Approx. 4.2 mΩ
Terminal F12(M8)/F5(M8)
Max. Discharge Current 1500A (5 sec)
DC (Deep Cycle) series batteries provide
Design Life 12 years (floating charge)
superior high integrity and reliability.It is
Maximum Charging Current 45 A specially designed for frequent cyclic charge
and discharge.By using strong grids,thick
C3 111.6AH
plate and specially active material are designed
C5 125.5AH
Reference Capacity for repeated deep-discharge applications.
C10 143.0AH
The DC series batteries offer 30% more cyclic
C20 150.0AH
life than the standby series.It is suitable for
13.6 V~13.8 V @ 25℃
Float Charging Voltage solar and wind renewable nergy storage,mobility
Temperature Compensation: -3mV/℃/Cell
and medical equipment,V,telecom,broadband
14.6 V~14.8 V @ 25℃ and cable TV,UPS systems etc.
Cycle Use Voltage Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: 0℃~50℃
Storage: -20℃~60℃
Normal Operating Temperature Range 25℃±5℃
ISO 9001 ISO 14001 OHSAS 18001
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charged batteries before using.

Container Material A.B.S. UL94-HB, UL94-V0 Optional. MH 28539 G4M20206-0910-E-16

Dimensions
170 Φ16 Length 483±2mm (19.0 inches)
483
M8
Width 170±2mm (6.69 inches)
Height 241±2mm (9.49 inches)
5

Total Height 241±2mm (9.49 inches)


Terminal Value
241

M5 6~7 N*m
31

M6 8~10 N*m
384.5 M8 10~12 N*m
F12 Terminal Unit: mm

Constant Current Discharge Characteristics : A(25 ℃)

F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 317.8 244.9 143.5 86.2 52.7 39.7 31.4 26.5 18.1 15.3 7.79
1.65V 307.2 237.6 140.5 84.6 51.8 39.1 31.0 26.1 17.9 15.1 7.72
1.70V 293.4 228.0 136.5 82.5 50.6 38.3 30.4 25.7 17.6 14.9 7.63
1.75V 274.9 215.0 131.1 79.5 49.0 37.2 29.6 25.1 17.2 14.7 7.50
1.80V 250.2 197.6 123.7 75.5 46.7 35.6 28.5 24.2 16.7 14.3 7.32
1.85V 216.4 173.6 113.1 69.7 43.5 33.4 26.9 23.0 15.9 13.7 7.05

Constant Power Discharge Characteristics : WPC(25℃)

F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 569 451 274 170 105 79.8 63.4 53.7 37.1 31.6 16.2
1.65V 564 446 273 168 104 79.0 62.9 53.3 36.8 31.4 16.0
1.70V 545 432 266 165 102 77.6 61.9 52.5 36.3 31.0 15.9
1.75V 520 413 258 160 99.2 75.7 60.5 51.4 35.6 30.4 15.6
1.80V 481 385 246 152 95.1 72.8 58.4 49.9 34.6 29.6 15.2
1.85V 424 343 228 141 89.1 68.6 55.4 47.5 33.1 28.5 14.7
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
DC12-150(12V150Ah)
Discharge Characteristics Curve Charge Characteristic Curve for Cycle Use(IU)
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.60
Charge Volume
2.16

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 2.50

Charge Volume (%)


Charge Voltage
2.00

80 0.10 2.40
1.84
0.1C 0.05C
0.4C 0.2C 60 0.06 2.30
1.68 After 50% Discharge
0.55C
After 100% Discharge
3C 2C1C 40 0.04 2.20
1.52

1.36 20 0.02 2.10


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 2.00
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
120 2.70

100
2.60

Charge Voltage (v )
Cycle use
80
2.43~2.47VPC@25℃
Capacity(%)

2.50

60
100% 50% 30%
DOD DOD DOD 2.40

40

2.30
20 Float charging
2.27~2.30VPC@25℃
2.20
0 -20 -10 0 10 20 30 40 50
300 600 900 1200 1500 1800 2100
Number of Cycles Temperature (℃)

Temperature Effects on Capacity Storage Characteristics


120 100

100 0℃
A
0 .0 5 C 80
Capacity (% )
Capacity (% )

80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
3 .0 C A 20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
20 2.20

2.15
Battery Voltage (V)
Lift Expectancy (y ears)

16
2.10

2.05
12

2.00

8
1.95

1.90
4
1.85

0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100
Temperature(℃) State Of Capacity (%)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

SHENZHEN RITAR POWER CO.,LTD. Add: 10th Floor, Tower C, 1st Building, Software Industry Base, No.81, Xuefu Road, Nanshan District, Shenzhen,
Guangdong, China 518057
URL: www.ritarpower.com Tel: +86-755-33981668/83475380 Fax: +86-755-83475180 E-mail: sales@ritarpower.com Version 17B-0