IRIS1 NV

OTIS - SIGMA Date : 2011. 04. 10


FIELD ENGINEERING Page : 0 - 1 / 3

FIM 6 High Speed Adjustment

6.1. Start compensation adjustment


1. Following mechanic work should be finished thoroughly.
No. Relevant content Detailed technology
1 Guide rail flatness Whether guide rail state is correct?
2 Guide rail washing Whether guide rail surface is clean?
3 Guide rail joint Whether guide rail joint deforms or joint is with steepness?
adjustment
4 Guide shoe state Whether the condition of that the guide shoe is clamped
occurs?
5 Roping state Whether rope tension force is conformable?
6 Over-balance Whether over-balance of car and counterweight device is
within standard range?
7 Car components Whether assembly state of car components and panel is
assembly state excellent?

2. Determine whether PTM runs normally in the system.


-. In Para. setup mode, change F187 into “14”.
No. Relevant content Detailed technology
187 Leveling induction 0: running times 1: ENC conflict (above 1000is
Calibration running not good)
2,3: CAN communication (96 4: rotary speed of the motor
exceed is not good)
5: bus voltage 6: output current
7: output rotating moment 8: magnetic pole position
9,10: ENC position 11: spare moment
12,13: radiator temperature 14: load marking
15: PTM #1 mark 16: PTM #2 mark

-.Load which is same with the right side shown on primary menu.
-.0 means 0%, 1024 means 100% load. Normal Simplex
Eg.: if load is 50%, 512 should be shown. === 00000088 ===
-.If F187 is changed into 15, PTM #1 will appear. 1 Floor 0.00m/s
If it is changed into 16, PTM #2 will appear. Door Locked

3. Conduct constant-speed running within hoistway full area, and after determining start and stop state,
conduct adjustment.
-. Conduct adjustment after passing Para.setup mode.
F No. Relevant content Detailed technology
245 0% start compensation Start compensation adjustment on DN direction
248 adjustment Start compensation adjustment on UP direction
241 50% start If value of F247 is larger than 512, adjust DN direction.
242 compensation If value of F247 is larger than 512, adjust UP direction.
245 adjustment If value of F247 is less than 512, adjust DN direction.
248 If value of F247 is less than 512, adjust UP direction.
Unpublished Work Copyright © OTIS Elevator Company
IRIS1 NV
OTIS - SIGMA Date : 2011. 04. 10
FIELD ENGINEERING Page : 0 - 2 / 3

FIM 6 High Speed Adjustment

241 100% start Adjust DN direction


242 compensation Adjust UP direction
adjustment

6.2. Implantation adjustment


-. After finishing start compensation adjustment, implement implantation adjustment.
code Content Adjust Description
range
F56 Leveling adj. 0~100 Up-direction height adjustment parameter
up -.default value is 50mm, adjustment range is 0~100
- the value when it stops (exceeds) after decreasing
adjustment height, the value when it stops (comes
short) before increasing adjustment height.
F57 Leveling adj. 0~100 Down-direction height adjustment parameter
down -. default value is 50mm, adjustment range is 0~100
the value when it stops (exceeds) after decreasing
adjustment height, the value when it stops (comes
short) before increasing adjustment height.

Unpublished Work Copyright © OTIS Elevator Company


IRIS1 NV
OTIS - SIGMA Date : 2011. 04. 10
FIELD ENGINEERING Page : 0 - 3 / 3

FIM 6 High Speed Adjustment

6.3. Indicator setup

1) Shown as following figure, conduct line connecting work on indicator on hoistway side.

(PCB name: SM-04V12/A)

MIC Function Remark


name
JP1 Power supply and CAN
communication
JP2 1: Output
JP3 2: 24V 4P
JP4 3: GND
JP5 4: Input
JP6 For SPI communication
S1 For floor setup 3P
SW1 CAN communication 2P
terminal impedance

(PCB Name: SM-04V12/B)


MIC Function Remark
name
JP1 Power supply and CAN
communication 4P
JP2 For SPI communication
SW1 CAN communication 2P
terminal impedance

2) Floor No. setup is as follows.


-.Utilize umper pin jumperSI(3P)’s 1 and 2.
-.IND phase will appear F00
-.Utilize Hall button’s UP (floor increasing), Down (floor decreasing), set absolute floor of the building.
Eg.) F01=front 1 floor, R01=back1 floor, M01=wheelchair 1 floor.
-After finishing floor setup, remove Jumper pin.

Note) Setup methods for car indicator


Please utilize S01 to conduct setup.

Unpublished Work Copyright © OTIS Elevator Company