Beruflich Dokumente
Kultur Dokumente
7 m
Three phase transmission line in balanced condition can be represented by a single phase
circuit as illustrated by example in Figure 3.22.
R1 XL1 R2 XL2
Figure 3.22. Example of single phase circuit to represent three phase line
The resistance, inductance, and capacitance in the circuit are obtained by techniques
discussed in previous sections.Normally, inductive reactance and capacitive susceptance
are used in the equivalent circuit. Resistance and inductance are series parameters while
capacitance is shunt parameter in the circuit.
Physically, all line parameters are distributed uniformly along the line. However, to
simplify the line analysis, typically the parameters are assumed as lumped elements at a
given point in the equivalent circuit. In this section we will describe modelling techniques
available to lump the line parameters based on length of the line.
63
3.6.1 Short Line Representation
Transmission line with length of less than 80 km can be categorised as short line. For this
type of line, capacitive effect is insignificant and normally not included in the equivalent
circuit. The per phase circuit for the short line representation consists of the series
parameters as shown in Figure 3.23.
IS IR
R XL
VRL
VS VR
Referring to Figure 3.23, VS and IS are phase voltage and phase current, respectively, at
the sending end of the line. While VR and IR are phase voltage and current, respectively,
at receiving or load end. Total line resistance per phase (in ohm) and total inductive
reactance per phase (in ohm) are represented by the symbols R and XL, respectively.
Z = R + jX L = Z ∠θ Z (3.62)
It should be noted that currents IS and IR are the same, while voltages VS and VR are
different due to the voltage drop VRL in the line impedance. The relationships are
described by the following equations:
VS =VR + IRZ (3.63)
IS = IR = I (3.64)
Typically, the phase voltage for VR is taken as reference phasor in the analysis, i.e.
VR=VR ∠0°, where VR is the magnitudefor VR.
where A, B, C, and D are known as ABCD parameters for transmission line. It can be
shown that for short line, A = 1, B = Z, C = 0, and D = 1. Furthermore, AD - BC = 1
64
Example:
A 30 km, three phase 50 Hz transmission line is transferring power to a 500 kW load with
power factor of 0.9 lagging. The load voltage is 10 kV. Given resistance and inductance
of the line per phase of 0.1 Ω per km and 0.424 mH per km, respectively, calculate (i)
current and (ii) voltage at the sending end of the line.
Solution:
(i) Phase current at the sending end is equal to that at the receiving end, that is
IS = 32.1∠-25.8° A.
Self-assessment Question:
3.6. Solve the previous example question, with the power factor for 500 kW load is
now changed to a leading power factor of 0.8.
[36.1∠36.9° A, 10005∠31.8° V]
For transmission line over 80 km of length, the capacitive effect is quite significant and
cannot be neglected in the line representation. The medium-length line representation is
used for line with length of between 80 km to 240 km. All line parameters are still
represented as lumped elements. There exists two representations for the medium lines,
namely T or π−circuit representation.
65
A. T-circuit Representation
Figure 3.24 shows per phase circuit for T-circuit representation. Note that the series
Z R X
impedance is divided into two parts equally, each with = + j (in ohm) and the line
2 2 2
admittance, which is the capacitive susceptance (Y = jBC) is lumped to a shunt branch for
which BC = 2πfC (in mho).
Z Z
2 2
R XL R XL
IS 2
IR
2 2 2
VS Y=jBC VR
For the circuit in Figure 3.24, with voltage VR taken as the reference, the equation for
sending end voltage is
Z Z
VS = I S + IR + VR
2 2
Z Z Z
= [I R + (VR + I R )Y] + IR + VR
2 2 2
ZY 1
= (1 + ) VR + (Z + YZ 2 ) I R (3.66)
14 4244 23 1442 4 443
A B
The formula for sending end current is
Z
I S = I R + (VR + I R ) Y
2
1
= Y{ VR + (1 + YZ) I R (3.67)
C 1442244 3
D
Briefly, the ABCD matrix for T-circuit representation is
1 1 2
VS 1 + 2 YZ Z + 4 YZ VR
I = 1 (3.68)
S Y 1 + YZ I R
2
or
66
-1
1 1
R
V 1 + YZ Z + YZ 2 VS
2 4
I = 1 I (3.69)
R Y 1 + YZ S
2
B. π–circuit Representation
The per-phase representation for nominal π-circuit is given in Figure 3.25. In the circuit,
the series impedance is lumped together as Z = R + jXL while the line susceptance is
Y B 2π fC
divided into two shunt elements, each with admittance of =j C =j .
2 2 2
Z
IS R XL IR
VS Y Y VR
2 2
From Figure 3.25, by taking VR as the reference, one can obtain the following:
1
VS = (1 + YZ)VR + ZI
{ R (3.70)
14 42244
3 B
A
and
Y Y
IS = VS + VR + I R
2 2
1 1 1
= [(1 + YZ)VR + ZI R ] Y + YVR + I R
2 2 2
1 1
= (Y + Y 2 Z)VR + (1 + YZ)I R (3.71)
1442 4 44 3 142 2 43
C D
The parameters for the π− circuit can be expressed in matrix form as follows:
67
1
VS 1 + 2 YZ Z VR
I = 1 1 I (3.72)
S Y + Y 2 Z 1 + YZ R
4 2
Example:
Solution:
(i) Using T-circuit representation, the phase voltage at the sending end is
(84.4∠63.0 o )(0.6 x 10 -3 ∠90 o )
VS = 1 + 17320.5 +
2
(0.6 x 10 -3 ∠90 o )(84.4∠63.0 o ) 2
84.4∠63.0 o + 9.6
4
= 17304.7∠3.0° V,
68
The sending end current is
(0.6 x 10 -3 ∠90 o )(84.4∠63.0 o )
I S = (0.6 x 10 -3 ∠90 o )17320.5 + 1 + 9.6
2
= 14.1∠48.2° A.
The equivalent circuit for short and medium line representations are not suitable for a
very long transmission lines, that is lines over 240 km. It is due to the distributed nature
of the line parameters.
Figure 3.26 shows one part of a line with a length of dx at a distance x from the receiving
end of the line. The part has series impedance of zdx and admittance of ydx (which is the
capacitive susceptance bCdx), where z and y are impedance and admittance, respectively,
per unit length of the line.
69
dI x
= yVx (3.74)
dx
zdx
IS Ix+dIx rdx xLdx IR
dIx
dVx
VS ydx Vx VR
Vx+dVx
Section length, x
dx
Line length, l
Figure 3.26
Integrating Equations (3.73) and (3.74) with respect to x, results into the following:
d 2 Vx dI
2
= z x (3.75)
dx dx
and
d2Ix dV
2
=y x (3.76)
dx dx
The terms dVx/dx and dIx/dx in Equations (3.76) dan (3.75) respectively are substituted
into Equations (3.73) and (3.74) to yield
d 2 Vx
= yzVx (3.77)
dx 2
and
d 2I x
= yzIx (3.78)
dx2
At the sending end (where x = 0), Vx = VR and Ix = IR .Thus, the solution of equations
(3.77) and (3.78) result into
z
V(x) = (cosh yz x)VR + ( sinh yz x)I R
14243 y
A 1442443
B
= (cosh γ x)VR + (Z C sinh γ x)I R (3.79)
and
y
I(x) = ( sinh yz x)VR + (cosh yz x)I R
z
1442443 14243
D
C
70
= (YC sinh γ x)VR + (cosh γ x)I R (3.80)
and
IS = (YC sinh γ l )VR + (cosh γ l )I R (3.83)
To simplify calculation, the following relationships are normally used for the sinh γl and
cosh γl terms.
sinh γl = sinh(αl +jβl ) = sinh αl cos βl + jcosh αl sin βl (3.85)
71
cosh γl = cosh(αl +jβl ) = cosh αl cos βl + jsinh αl sin βl (3.86)
and
Y = total shunt admittance per phase
=yl =(jb)l . (3.88)
Example:
A 370 km three phase transmission line is utilised to deliver power to a 125 MW load
with unity power factor at voltage of 215 kV. The line has series parameter of
-6
0.52∠79.1° Ω/km and shunt parameter of 3.2 x 10 mho/km. Compute current and
voltage at the sending end of the line.
Solution:
Series impedance of the line is
z = 0.52 ∠79.1°Ω/km,
90 o + 79.1o
γl = yzl = 3.2 x 10 -6 x 0.52 ∠ x370 = 0.4773 ∠84.6°.
2
= 0.0449 + j0.4752 Np.
z 0.52 79.1o - 90 o
ZC = = ∠ = 403.1 ∠-5.5° Ω.
y 3.2 x 10 -6 2
215000
VR = = 124130 ∠0° V to neutral.
3
125000000
IR = = 335.7 ∠0° A.
3 x 215000 x 1
72
VS = (0.8904 ∠1.3°)(124130) + (403.1 ∠-5.5°)(0.4597 ∠85.0°)(335.7)
= 137468.4 ∠27.6° V,
In general, phase voltage and current at sending end of transmission line can be
represented in phasor form as
Vs = |Vs|∠θVS and Is = |Is|∠θIS (3.89)
Similarly, phasor representations for phase voltage and current at the receiving end of the
line are
VR = |VR|∠0° and IR = |IR|∠θIR (3.90)
If all four phasors in Equations (3.89) and (3.90) are known, then power flow in the line,
as well as line efficiency, can be obtained. In most cases, phase voltage at the receiving
end is taken as a reference phasor, i.e. the angle for VR in Equation (3.9) is set to zero.
From Equations (3.91) and (3.92), the real power magnitudes delivered by the source and
that received by the load respectively, are
PS = Re[SS] = 3|Vs||Is|cos(θVS- θIS) (3.93)
PR = Re[SR]= 3|VR||IR|cosθIR (3.94)
The efficiency of the transmission line is a ratio of the power received by the load to the
power generated by the source, i.e.
Output Power (receiving end) VR I R cosθ IR
η = = (3.96)
Input Power (sending end) VS I S cos(θ VS − θ IS )
73
The efficiency can be expressed in percentage by multiplying 100 to Equation (3.96).
Voltage regulation for transmission line is the degree of voltage rise at the receiving end
of the line when a rated load (or known as full load) is completely removed from the load
terminal, with sending end voltage is fixed. The voltage relationship to determine line
regulation can be expressed as
V - VR -FL
Voltage regulation = R - NL (3.97)
VR -FL
where VR-NL dan VR-FL are receiving end voltages without load and with full-load,
respectively.
Example:
The following results have been obtained from previous example on short line model:
Phase voltage and current at load terminal:
VR = 5773.5 ∠0° V.
IR = 32.1∠-25.8° A.
Phase voltage and current at sending end terminal:
VS = 5916.6∠0.7° V.
IS = 32.1∠-25.8° A.
Based on these data, the efficiency and voltage regulation for the line can be calculated as
follows:
VR I R cosφ R V cosφ R 5773.5 cos 25.8 O
Efficiency, η = = R =
3VS I S cosφ S VS cosφ S 5916.6 cos(0.7 + 25.8) O
= 0.98. (or 98%)
5916.6 - 5773.5
Voltage regulation = = 0.025 (or 2.5%).
5773.5
Note that the value of VR-NL is the same as the sending end voltage since current IR is zero
at no-load condition. While VR-FL is the value of receiving end voltage when the line is
loaded.
Example:
The data for T-circuit line modelling (refer to Section 3.6.2) have been obtained as
follows:
VR= 17320.5 ∠0° V dan IR = 9.6 ∠0° A.
VS = 17304.7∠3.0° V dan IS = 14.1∠48.2° A.
74