Use a variable-speed pump and minimize valve pressure drops.
Oct 30, 2018

This column is moderated by Béla Lipták, automation and safety consultant and editor of the Instrument and
Automation Engineers' Handbook (IAEH). If you have an automation-related question for this column, write
to liptakbela@aol.com.

Q: Delivery of transmix fuel to two separation towers is being upgraded. Coriolis meters were installed and are
currently functioning. Two PID flow control loops currently maintain flow. The transmix liquid passes through
a series of heat exchangers on its way to the towers. It is estimated that between the friction losses in the
heat exchangers and the elevation change, the head loss is on the order of 30 psi.

The Coriolis meters require minimum pressure to function. Now, the pump can’t meet the minimum pressure for
both towers in service, so only one tower is in service. A new pump and VFD will be installed. Two pressure
transmitters will also be installed—one right after the pump, the other up by the towers just before the split to the
two flowmeters. There is an estimated 30-45-second lag between a change in pump speed and an observed
change in pressure at the flowmeters.

The plan is to use a new PID pressure loop to maintain the pressure just downstream of the new pump by
adjusting the VFD. The second transmitter up by the flowmeters will be used with logic that helps avoid low
pressure at the flowmeters: If pressure up there falls below a threshold, logic will put the flow loops in manual
and start closing the valves to build pressure back up.

The question is whether this design concept is sound and valid. Or will there surely be interaction? Or maybe it
will work but we have to try it and fine tune it?

William Love
williamlove@live.com

https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 1/8
11/10/2018 How to optimize pumping cost

As-planned system
Figure 1: Delete pressure controls because
pressure and flow can't be independently
controlled. Once flow is controlled, the
pressure is determined by the system.

A: This is a valuable question because it applies to all pumping system applications. The important point to
remember is that one cannot independently control both the pressure and the flow of liquids flowing in a pipeline,
because pressure is dependent on flow. Therefore, the proposed control system (Figure 1) is unworkable.

The relationship between flow and pressure is determined by the pump and system curves (Figure 2) and the
operating pressure (sum of static head and friction loss) is at the point where the two curves cross.

Liquids are incompressible, so there is no dead time between flow and pressure. Therefore, the cited dead time
of 30-45 seconds is in error. Cascade control can’t be used because the flow and pressure time constants are
nearly identical, while for good cascade control, the slave must be an order of magnitude faster than the master.

If you want to save pumping energy, you can control the speed of the variable-speed pump using a valve
position controller (VPC). The VPC minimizes the valve pressure drops by opening the valve that is most open
to 90%, all the time. As shown in Figure 3, if the system was designed so that normal operation would require an
average speed of about 50%, you will require only 13% of the horsepower of using a constant speed pump
(100% speed in Figure 3) .

Operating point
Figure 2: The system curve determines the
relationship between flow and pressure. The
operating pressure will be at the point where
the pump (dotted) and the system (solid)
curves cross.

https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 2/8
11/10/2018 How to optimize pumping cost

For a variety of other pump optimization schemes, read the pump chapter in the 4th edition of Volume 2 of my
handbook.

My recommendation for your system is shown in Figure 4. Note that I also added a pressure safety valve (PSV)
to protect your system against overpressure.

Millions of dollars could be saved in various industrial applications if all pumping energy costs were minimized
the same way as shown in Figure 4..

Béla Lipták
liptakbela@aol.com

A: I suggest that you review the design of the centrifugal pump. With a given impeller, the pump will pump a
volume of liquid at a given head at a given speed. If the pump can’t provide the required head at a given speed,
then increasing the rotational speed at the VFD will increase the head. The governing law of physics is the
Pump Affinity Law:

1. The flow (GPM) varies proportionally with the change in speed. This means that twice the speed is twice the
flow. One-third speed is one-third the flow.
2. The pump head (pressure) varies with the square of the change in the speed. Doubling the speed generates
four times the head. At 80% speed, the head generated is 64%.
3. The power requirement (horsepower or kilowatts) varies by the cube of the change in speed. Twice the
speed would consume eight times the power; half the speed would require one-eighth the power to drive the
pump.

Figure head
Figure 3: If a valve position controller (VPC) is added, this independent control loop can keep
the most open valve always 90% open by modulating the pump speed. If the pump is over-
sized, the operating cost savings can be substantial.

A speed change at the pump must immediately appear as a pressure increase at the flowmeter in this liquid-
filled system. The 30-45-second delay is just not physically possible; the pumped liquid has to go somewhere. If
the VFD responds to the speed change properly, the pressure increase should be instantaneous. Many VFDs
have filters installed on speed change to prevent too rapid a speed change that might result in pipe hammer.
However, 30-45 seconds seems out of reason.

In a filled piping system, VFD speed change will result in an immediate change in flow rate and pressure head
unless a ramping function is configured or the pipe is not filled with liquid. What you describe is not possible with
a filled pipe.

Dick Caro
DickCaro@CMC.us

https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 3/8
11/10/2018 How to optimize pumping cost

Recommended configuration
Figure 4: When optimized, the valve position controller (VPC) always minimizes the system
pressure drop by keeping the most open valve at 90% open.

A: From the information available, you are up against two very critical conditions: Dead time is very detrimental
to the best performance a feedback controller can accomplish, as integrated error is directly proportional to the
dead time. You can always use a PI-Deadtime compensated, however, it comes at a price of reduced
robustness margins. The stability of the loop will depend on the precision of the estimation of the dead time, and
stability will be compromised when the dead time estimation is either too short or too long.

Now, it is very strange that you have such a long dead time in the flow of an incompressible fluid, so you may
want to verify the correct operation of your field devices. The interaction of liquids is typically severe and even
detuning one of the controllers may not give the stability and the performance your process may require.
Decoupling also has a price to pay—the higher the relative gain, the narrower the stability margin of the system
with respect to the mismatch between the actual process and its model.

If the pump discharge pressure can exceed the pipe pressure rating, that is unacceptable. From the control
viewpoint, you should install high pressure control override to either slow down the pump or open up the flow
valve (s). Not pretty, but functional. And I would strongly recommend the installation of a pressure relieve valve.

S. Nino
Snino@SummaControlSolutions.com

Want to get content like this in your inbox?


Subscribe to our Enewsletters here!

Related Content

Factoring life cycle variables helps make intelligent motor-drive purchases


The largest potential for electric motor energy savings lies in system- and process-level…

Motors, drives deliver force behind the scenes


https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 4/8
11/10/2018 How to optimize pumping cost

Hardworking rotating devices are getting help from variable-speed devices, efficiency rules,…

Monitor your Pump for Process Efficiency


Repairing or replacing damaged pumps can be very expensive, but installing a point flow/level…

Drive turns pump into smart, connected asset


Process optimization, energy management and asset management benefit from services-based…

Most Popular
Past 7 Days Past 30 Days Past 6 Months All Time

01 Honeywell cybersecurity research reveals USB devices as significant threats to industrial


facilities

02 Sensor security issues are a global issue – yet they are not being addressed and people are
dying
The lack of cyber security of sensors are a real, but unaddressed problem.

03 Software eases field device integration


Information models and OPC UA power programmable paths to protocol…

04 Robot makes moo-ving safer


Cargill’s beef plant in Schuyler, Neb., implemented a robot into its…

05 Wireless technology ready for industrial prime time

https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 5/8
11/10/2018 How to optimize pumping cost

https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 6/8
11/10/2018 How to optimize pumping cost

About
Contact Us
Advertise
Media Kit
Rates & Spec
Privacy Policy
Legal / T&C

Content
Voices
Blogs
Out of Control Cartoons
News
Webinar series
White Papers
Multimedia
Special Reports
Events
Products
Technology Roundups
E-lits

Magazine
Subscribe
Digital Edition
Issue Archive
Reprints

Site Tools
Knowledge Center
Microsites
Company Profiles
Site Map

Stay Connected
My Account
Newsletters
Social Media
RSS

Contact Us | Advertise | Privacy Policy | Legal Disclaimers, Terms & Conditions

https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 7/8
11/10/2018 How to optimize pumping cost
Copyright © 2004 - 2018 Control Global. All rights reserved.
P: 630-467-1300 | 1501 E. Woodfield Road, Suite 400N, Schaumburg, IL 60173

Chemical Processing | Control | Control Design | Food Processing | Pharmaceutical Manufacturing | Plant Services | Smart
Industry

https://www.controlglobal.com/articles/2018/how-to-optimize-pumping-cost?utm_source=hs_email&utm_medium=email&utm_content=67353892… 8/8

Das könnte Ihnen auch gefallen