Beruflich Dokumente
Kultur Dokumente
1.3. A stract………………………………………………………………………..4
-
Chapter five: Shear walls
Conclusion……………………………………………………………………………..…..128
-
1 INTRODUCTION
THIS CHAPTER
WILL INCLUDE THE GENERAL INTRODUCTION, THE SCOPE &
OBJECTIVES OF THE PROJECT & THE APSTRACT. THE BUILDING
CONSISTING OF FOUR FLOORS AND A PLAN AREA OF 20,000 M2,
WHILE THE DESIGN WILL BE DIVIDED TO ITS STRUCTURAL
COMPONENT, I.E. TO SLABS, BEAMS, COLUMNS, WALLS AND
FOOTINGS, AND MATERIAL USED IN THIS PROJECT.
1.1. General introduction:
In any activity includes structural analysis, Structures are
Analyzed to determine their behavior under the different types of
the acting loads. This analysis is to determine all the needed data,
Such as: axial forces, moment, or shear, from the external or own
loads. To design the final safe member size and area of steel for the
total structure.
Non-Structural Elements:
Partitions: are made of masonry or brick and used to fill the
openings between columns.
Doors and windows: are made of different materials such as
wood, steel, glass, and so on.
Floor fi ish: Tiles of grou d as cera ic, ar le, porcelai … etc.
Wall fi ish: Pai t, plaster, wall paper… etc.
2
1.2.5. Programs Used:
Design and Analysis Programs
CSI ETABS 2016.
CSI SAFE 2016.
PROKON 3.
Detailing Programs:
Microsoft Office Word 2016.
Microsoft Office Excel 2016.
Autodesk AutoCAD 2018.
1.3. Abstract:
After that the design sections and areas of steel are from ETABS
and safe, checked by Prokon and manual.
4
2 LOADS
THIS CHAPTER
WILL INCLUDE THE FORCES ACTING ON THE STRUCTURE
OR IN OTHER WORDS THE FORCES WHICH THE
STRUCTURE DESIGNED TO CARRY AND MAINTAIN SAFE
WITHOUT COLLAPSING.
2.1. Introduction:
Perhaps the most important and most difficult task faced by the
structural designer is the accurate estimation of the loads that may be
applied to a structure during its life. No loads that may reasonably be
expected to occur may be overlooked. After loads are estimated, the next
problem is to decide the worst possible combinations of these loads that
might occur at one time. For instance, would a highway bridge completely
covered with ice and snow be simultaneously subjected to fast-moving
lines of heavily loaded trailer trucks in every lane and to a 90-mile lateral
wind, or is some lesser combination of these loads more reasonable?
The next few sections of this chapter provide a brief introduction to the
types of loads with which the structural designer must be familiar. The
purpose of these sections is not to discuss loads in great detail but rather
to give the reader a feel for the subject. As will be seen, loads are classed
as being dead, live, or environmental.
5
Dead loads:
Dead loads are loads of constant magnitude that remain in one
position. They include the weight of the structure under consideration
as well as any fixtures that are permanently attached to it. For a
reinforced concrete building, some dead loads are the frames, walls,
floors, ceilings, stairways, roofs, and plumbing.
To design a structure, it is necessary for the weights or dead loads of
the various parts to be estimated for use in the analysis. The exact
sizes and weights of the parts are not known until the structural
analysis is made and the members of the structure are selected. The
weights, as determined from the actual design, must be compared
with the estimated weights. If large discrepancies are present, it will
be necessary to repeat the analysis and design using better estimated
weights. Reasonable estimates of structure weights may be obtained
by referring to similar structures or to various formulas and tables
available in most civil engineering handbooks. An experienced
designer can estimate very closely the weights of most structures and
will spend little time repeating designs because of poor estimates.
The approximate weights of some common materials used for floors,
walls, roofs, and the like are given in Table 2.1.
Live loads are loads that can change in magnitude and position. They
include occupancy loads, warehouse materials, construction loads,
overhead service cranes, equipment operating loads, and many
others. In general, they are induced by gravity.
Environmental Loads
Environmental loads are loads caused by the environment in which
the structure is located. For buildings, they are caused by rain, snow,
wind, temperature change, and earthquake. Strictly speaking, these
are also live loads, but they are the result of the environment in which
the structure is located. Although they do vary with time, they are not
all caused by gravity or operating conditions, as is typical with other
live loads.
So, we will describe how to estimate loads for each kind of slabs with
some details for estimating the loads for each structural element.
Dead load for one way ribbed slab:
8
Dead load calculations for one way ribbed slab: (31 cm)
9
Dead load for two way ribbed slab:
����� ����ℎ�
Total weight for (1.04m x 1.04m) unit = = KN/m2
. ∗ .
Dead load calculations for two way ribbed slab: (25 cm)
.
Total weight for (1m x 1m) unit = = 4.8 KN/m2
. ∗ .
Get the live load from the Jordanian Loads and forces Code for loads
2
2.3. Loads of structural members:
Ribs load:
For each rib we can obtain the load acting on it by multiplying the
loads on slab by effective width.
Ribbed slabs:
Dead load of one way ribbed slab = 0.55*10.8 = 6 KN/m.rib
Dead load of two way ribbed slab = 0.52*11.2 = 5.8 KN/m.rib
Live load for one way ribbed slab = 0.55*3 = 1.65 KN/m.rib
Live load for two way ribbed slab = % load by coefficient method
*0.52*3 = KN/m.rib
Beams load:
For each beam we use tributary area for one way slab and
reactions of rib for two way slab.
Columns load:
For each column we use tributary area and then multiplying it by
the slab load.
Footings load:
It’s equal to the total load from the all stories for each vertical
member.
4
3 SLABS
THIS CHAPTER
WILL INCLUDE THE SLABS ANALYSIS AND DESIGN FOR
FLEXURE AND CHECK THE REQUIREMENT LIMITATION
ACCORDING TO ACI CODE.
3.1. Introduction:
TYPES OF SLABS:
Structural concrete slabs are constructed to provide flat surfaces, usually
horizontal, in building floors, roofs, bridges, and other types of structures.
The slab may be supported by walls, by reinforced concrete beams
usually cast monolithically with the slab, by structural steel beams, by
columns, or by the ground. The depth of a slab is usually very small
compared to its span.
5
Structural concrete slabs in buildings may be classified as follows:
1. One-way slabs: If a slab is supported on two opposite sides only, it will
bend or deflect in a direction perpendicular to the supported edges. The
structural action is one way, and the loads are carried by the slab in the
deflected short direction. This type of slab is called a one-way slab.
The slabs called two-way: If supported from all direction and the
Length/Width < 2.
3.2. Depth estimation:
Find the cases from the project plans then use most critical case:
In our project there is two cases we must check:
.
1- Case of one end continuous (ℎ �� = . )
.
.
2- Case of two end continuous (ℎ �� = . )
The critical case is one end continuous so, we will take the thickness
of slab = 31 cm.
Thickness of two way ribbed slab:
�
ℎ. �
� � ℎ∗ℎ
� =� � =
From the previous equation we can find required depth of slab and
then compare it by the assumed depth.
8
Calculations of thickness for two way ribbed slab:
. + .
ℎ. � = .
∗ ∗ + ∗ ∗
ȳ= = .
∗ + ∗
∗ ∗
�=[ + ∗ . ]+[ + ∗ . − ]
�= . ∗
9
4- By assuming (I slab = I rib):
∗ℎ
� = . ∗ =
ℎ
directions.
Then use the same procedure of beam reinforcement to find A steel, required.
2
3.3. Beams & Ribs design procedure:
Select the depth of the beam due to the type of the beam, where
There are two types of beams:
Hidden Beam
Drop Beam
Find the ultimate load due to design combination that depend on
your loads:
1.4(DL)
1.2(DL) + 1.6(LL)
As you know there are three stages before beams failure:
Stage II: On increasing the applied load, the tensile stresses at the
.
2
Stage III: at nominal (so,-called ultimate) strength, the neutral axis
has moved farther up-ward as flexural cracks penetrate more and
more toward the compression face. The steel reinforcement has
yielded and the concrete stress distribution in the compression
zone becomes more nonlinear. Below the neutral axis, the
concrete is cracked except for a very small zone. At the ultimate
stage, two types of failure can be noticed. If the beam is reinforced
with a small amount of steel, ductile failure will occur. In this type
of failure, the steel yields and the concrete crushes after
experiencing large deflections and lots of cracks. On the other
hand, if the beam is reinforced with a large amount of steel, brittle
failure will occur. The failure in this case is sudden and occurs due
to the crushing of concrete in the compression zone without
yielding of the steel and under relatively small deflections and
cracks. This is not a preferred mode of failure because it does not
give enough warning before final collapse.
22
The flexural strength Mn , using the equivalent rectangular, is
obtained as follows:
β = . − . ′
− > .
Find ∅ from:
��
=
C= .
∅
′
T=� �
2
Because the reinforcing steel is limited to an amount such that it will yield
well before the concrete reaches its ultimate strength, the value if the
nominal moment can be written as:
= − =� � −
� �
∅ = = ∅� � − )
. ′
Replacing As with �
��
and letting Rn = 2
′
. ∗
�= −√ − ′
.
�min=
.
�
�
′
= . ∗�∗
� =�∗
�
∗
∅Vc=0.75*0.17*1*√ ′ ∗ ∗
Vs=
�−∅
∅
Note that: Shear strength, Vc, provided by concrete for the ribs may be
taken greater than that for beams. This is mainly due to the interaction
between the slab and the closely spaced ribs (ACI Code, Section 8.13.8).
(Vc=(1.1)*0.17*1*√ ′ ∗ ∗
24
3.4. One way ribbed slab design:
Auto cad plan for ground and first floor showing rib direction and steel reinforcement.
25
For the given loads measured as in CH 2 and using Prokon program for
analysis and design we obtain the following:
Inputs:
f c'(MPa) 28
f y (MPa) 420
f y v (MPa) 280
% Redistribution 20
Downward/Optimized redistr. D
Cov er to centre top steel(mm) 25
Cov er to centre bot.steel(mm) 25
Dead Load Factor 1.2
Liv e Load Factor 1.6
Density of concrete (kN/m3) 0
% Liv e load permanent 25
Ø (Creep coef f icient) 2
Ecs (Free shrinkage strain) 300E-6
D 1 5.9
L 1 1.65
2
Output example for analysis and reinforcement using PROKON:
Rib1: (DL=10.8*0.55=5.9 KN/m.rib, LL=3*0.55= 1.65 KN/m.rib)
2
Manual sample for (rib 1) design for maximum positive moment
and for the maximum negative moment(+25.25 KN.m,-26.4 KN.m) :
′
ℎ
= . ∗ ∗ ∗ℎ ∗( − )
= ℎ− − � − = − − − =
−6
= . ∗ ∗ ∗ ∗( − )∗ = .
.
= . ≫ = = .
Ø .
6
∗
= = = .
∗
. ∗ ′
�= −√ −
. ′
. ∗ ∗ .
�= −√ − = .
. ∗
28
Asteel required = � ∗ ∗ = . ∗ ∗ = .
. .
[ �
∗ ∗ ]= ∗ ∗ = - checked
. ∗√ ′ . ∗√
[ ∗ ∗ ]= ∗ ∗ =
�
Try Ø 14mm:
� , � .
= = = .
� ,
� ∗ � ∗
= = = .
. ∗ ′ ∗ . ∗ ∗
.
= = = .
� .
.
= = . < . − . .
Note that: for spans with positive moment equal to or less than
Mu=25.25KN.m, use 2Ø14 mm.
29
• Design for maximum negative moment = -26.4 KN.m:
6
. ∗
= = = .
∗
. ∗ ′
�= −√ −
. ′
. ∗ ∗ .
�= −√ − = .
. ∗
Asteel required = � ∗ ∗ = . ∗ ∗ =
. .
[ �
∗ ∗ ]= ∗ ∗ = - checked
. ∗√ ′ . ∗√
[ �
∗ ∗ ]= ∗ ∗ =
Try Ø 14mm:
� , �
= = = .
� ,
� ∗ � ∗
= = =
. ∗ ′ ∗ . ∗ ∗
= = = .
� .
.
= = . < . − . .
Note that: for spans with negative moment equal to or less than Mu=26.4KN.m, use 2Ø14 mm.
� @ = .
� = . ∗ . ∗√ ′ ∗ ∗
−
= . ∗ . ∗√ ∗ ∗ ∗ = .
Note that: Vc provided by concrete for ribs may be taken 10% greater than that
for beams. This is mainly due to the interaction between the slab and the
closely spaced ribs.
(ACI-CODE 2011 S (8.13.8), Page (117))
∅� = . ∗ = . ≤ . − �
� . −
� = −� = − . = . ≤ . ∗√ ∗ ∗ ∗
∅ .
=
� ∗ �
=
. 6 ∗√ ′ ∗
� ∗ �
=
. ∗
� ∗ � ∗
�
=
KN.m KN.m
2
• For one way ribbed slab (Beams design):
. + .
WD = . ∗ = KN/m
. + .
WL = ∗ = . KN/m
4
• Inputs:
f c'(MPa) 28
f y (MPa) 420
f y v (MPa) 280
% Redistribution 20
Downward/Optimized redistr. D
Cov er to centre top steel(mm) 30
Cov er to centre bot.steel(mm) 30
Dead Load Factor 1.2
Liv e Load Factor 1.6
Density of concrete (kN/m3) 25
% Liv e load permanent 25
Ø (Creep coef f icient) 2
Ecs (Free shrinkage strain) 300E-6
D 1 60
L 1 16.7
5
• Note that: a fall ceiling will be used below the level of the slab and
the distance between the level of the slab and the falling ceiling
will be 10 cm.
• Output example for analysis and reinforcement using PROKON:
B1: (DL=60 KN/m, LL= 16.7 KN/m)
Manual sample for (B 1) design for maximum positive moment
and for the maximum negative moment(392 KN.m,297 KN.m) :
= ℎ− − � − = − − − =
6
∗
= = = .
Ø . ∗ ∗
. ∗ ′
�= −√ −
. ′
. ∗ ∗ .
�= −√ − = .
. ∗
Asteel required = � ∗ ∗ = . ∗ ∗ =
. .
[ ∗ ∗ ]= ∗ ∗ = - checked
�
. ∗√ ′ . ∗√
[ ∗ ∗ ]= ∗ ∗ = .
�
Try Ø 25 mm:
� , �
= = = .
� ,
� ∗ � ∗
= = = .
. ∗ ′ ∗ . ∗ ∗
.
= = =
� .
= = . < . − . .
6
∗
= = = .
Ø . ∗ ∗
. ∗ ′
�= −√ −
. ′
. ∗ ∗ .
�= −√ − = .
. ∗
Asteel required = � ∗ ∗ = . ∗ ∗ =
. .
[ ∗ ∗ ]= ∗ ∗ = - checked
�
. ∗√ ′ . ∗√
[ ∗ ∗ ]= ∗ ∗ =
�
8
Try Ø 25mm:
� , �
= = = .
� ,
� ∗ � 6∗
= = =
. ∗ ′ ∗ . ∗ ∗
= = = .
� .
.
= = . < . − . .
9
• Design of B1 for shear:
� @ = .
� = . ∗√ ′ ∗ ∗
−
= . ∗√ ∗ ∗ ∗ =
∅� = . ∗ = ≤ . − �
� .
� = −� = − = .
∅ .
−
≤ . ∗√ ∗ ∗ ∗ =
� ∗ �
=
. 6 ∗√ ′ ∗
� ∗ �
=
. ∗
� ∗ � ∗
= −
�
4
• This table shows the maximum reinforcement for each beam in
one way ribbed slab:
B1 800X350 7 Ø 25 9 Ø 25 3 Ø12@150mm
Beam 1:
7
31
35
4
Beam 2:
7
31
35
60
Beam 3:
7
31
40
30
Beam 4:
7
31
40
42
Beam 5:
7
31
40
Beam 6:
7
31
50
Beam 7:
7
31
30
4
3.5. Two way ribbed slab design:
For two way ribbed slab design we have used coefficient method
to find the distributed moments along short direction and long
direction and that’s ai ly due to the case of pa els accordi g to
coefficient method.
In our project we have the following cases for panels:
44
• We have choose panel 3 to design it by coefficient method
manually:
45
From table 1: Ca= 0.06, Cb= 0.04
4
Ma, positive, dead= 0.033*13.4*5.552 = 13.6 KN.m/m
Ma, positive, live= 0.039*4.8*5.552 = 5.766 KN.m/m
Mb, positive, dead= 0.022*13.4*6.12 = 11 KN.m/m
Mb, positive, live= 0.026*4.8*6.12 = 11.84 KN.m/m
∑ , �� = , , + , , = . + . = . KN. m/m
∑ , �� = , , + , , = + . = . KN. m/m
4
4- Find positive and negative moments for rib width (short direction):
Ma +ve for rib (La) = 19.4*0.52= 9.984 KN.m
Ma –ve for rib (La) = 33.6*0.52= 17.5 KN.m
Design for positive moment (short direction):
First check if rectangular or flanged action:
′
ℎ
= . ∗ ∗ ∗ℎ ∗( − )
= ℎ− − � − = − − − =
−6
= . ∗ ∗ ∗ ∗( − )∗ = . .
.
= . . ≫ = = . .
Ø .
6
. ∗
= = = .
Ø Ø∗ ∗
. ∗ ′
�= −√ −
. ′
48
. ∗ ∗ .
�= −√ − = .
. ∗
Asteel required = � ∗ ∗ = . ∗ ∗ =
. .
[ �
∗ ∗ ]= ∗ ∗ = - checked
. ∗√ ′ . ∗√
[ ∗ ∗ ]= ∗ ∗ =
�
Try Ø 12mm:
� , �
= = = .
� ,
� ∗ � 6∗
= = = .
. ∗ ′ ∗ . ∗ ∗
.
= = = .
� .
.
= = . < . − . .
49
Design for negative moment (short direction):
6
. ∗
= = = .
Ø . ∗ ∗
. ∗ ′
�= −√ −
. ′
. ∗ ∗ .
�= −√ − = .
. ∗
Asteel required = � ∗ ∗ = . ∗ ∗ =
. .
[ ∗ ∗ ]= ∗ ∗ = - checked
�
. ∗√ ′ . ∗√
[ ∗ ∗ ]= ∗ ∗ =
�
Try Ø 12mm:
� , �
= = = .
� ,
� ∗ � 6∗
= = = .
. ∗ ′ ∗ . ∗ ∗
.
= = =
� .
= = . < . − . .
5
5- Find positive and negative moments for rib width (long direction):
Ma +ve for rib (Lb) = 22.8*0.52= 11.856 KN.m
Ma –ve for rib (Lb) = 27*0.52= 14 KN.m
Design for positive moment (long direction):
First check if rectangular or flanged action:
′
ℎ
= . ∗ ∗ ∗ℎ ∗( − )
= ℎ− − � − = − − − =
−6
= . ∗ ∗ ∗ ∗( − )∗ = . .
.
= . . ≫ = = . .
Ø .
6
. ∗
= = = .
Ø Ø∗ ∗
. ∗ ′
�= −√ −
. ′
5
. ∗ ∗ .
�= −√ − = .
. ∗
Asteel required = � ∗ ∗ = . ∗ ∗ =
. .
[ �
∗ ∗ ]= ∗ ∗ = - checked
. ∗√ ′ . ∗√
[ ∗ ∗ ]= ∗ ∗ =
�
Try Ø 12mm:
� , �
= = = .
� ,
� ∗ � 6∗
= = = .
. ∗ ′ ∗ . ∗ ∗
.
= = = .
� .
.
= = . < . − . .
52
**Design for negative moment (long direction):
6
∗
= = = .
Ø . ∗ ∗
. ∗ ′
�= −√ −
. ′
. ∗ ∗ .
�= −√ − = .
. ∗
Asteel required = � ∗ ∗ = . ∗ ∗ =
. .
[ ∗ ∗ ]= ∗ ∗ = - checked
�
. ∗√ ′ . ∗√
[ ∗ ∗ ]= ∗ ∗ =
�
Try Ø 12mm:
� , �
= = = .
� ,
� ∗ � 6∗
= = = .
. ∗ ′ ∗ . ∗ ∗
.
= = =
� .
= = . < . − . .
5
6- Design for shear by using percent of load by coefficient method (Table 4):
From table for
.
= = = .
.
54
We have used the same procedure for each of panels (1, 2, 4, 5, 6, 7, 8, 9, 10)
Then by insert the loads per meter rib for each rib span on both directions the
final result of shear for (rib 1 short direction) and (rib 7 long direction) by
analysis of Prokon was as following:
55
For short direction (Rib 1):
� @ = .
� = . ∗ . ∗√ ′ ∗ ∗
−
= . ∗ . ∗√ ∗ ∗ ∗ =
∅� = . ∗ = . .
∅�
− � � �
� � � @ = min
. 6 ∗ �∗�∗√ ′
=
�
. ∗ �∗�
�
= .
5
For long direction (Rib 8):
� @ = .
� = . ∗ . ∗√ ′ ∗ ∗
−
= . ∗ . ∗√ ∗ ∗ ∗ =
∅� = . ∗ = . .
∅�
− � � �
� � � @ = min
. 6 ∗ �∗�∗√ ′
=
�
. ∗ �∗�
�
= .
5
Auto cad plan for ground and first floor showing rib direction and steel
reinforcement.
58
• This table shows the reinforcement for each rib in two way ribbed
slab:
KN.m KN.m
59
• For one way ribbed slab (Beams design):
For the design of beams for two way ribbed slab we have used the
reaction of ribs that will causes a line load on beams when the
shear force devided by the effective width (520 mm):
Example (B4):
Ultimate loads:
Service loads:
. ∗� . .
%� = = = .
. � + . . . + .
% = − . = .
Dead loads:
Prokon outputs:
Manual procedure same as beams in way way ribbed slab.
This table shows the maximum reinforcement for each beam in
one way ribbed slab:
B1 300X400 4 Ø 14 4 Ø 14 1 Ø10@200mm
B2 1000x320 12 Ø 20 12 Ø 20 3 Ø10@150mm
B5 1000x300 8 Ø 20 8 Ø 20 3 Ø10@150mm
B9 1000x250 10 Ø 20 10 Ø 20 3 Ø10@150mm
2
Beams sections for the previous given data :
Beam 1:
7
25
40
30
Beam 2:
Beam 3:
Beam 4:
Beam 5:
Beam 6:
7
25
40
30
4
Beam 7:
7
25
40
30
Beam 8:
7
25
40
Beam 9:
7
25
100
Beam 10:
7
25
40
30
5
Design of shrinkage and tempreture steel: (Topping)
� ��� � = � ��� � ∗ . � ∗
� �� = . ∗ ∗ =
Try Ø 8 mm:
6
number of bars = = .
∗
Spacing = =
6
THIS CHAPTER
WILL INCLUDE THE DESIGN OF COLUMNS, WHICH IS
REFERRED TO AS COMPRESSION MEMBERS, BECAUSE
THE COMPRESSION FORCES DOMINATE THEIR
BEHAVIOR.
4.1. Introduction:
Columns are vertical compression members of a structural frame
intended to support the load-carrying beams. They transmit loads
from the upper floors to the lower levels and, then to the soil
through the foundations. Since columns are compression
elements, failure of one column in a critical location can cause the
progressive collapse of the adjoining floors and the ultimate total
collapse of the entire structure. Structural column failure is of
major significance in terms of economic as well as human loss. This
extreme care needs to be taken in column design, with a higher
reserve strength than in the case of beams and other horizontal
structural elements, particularly since compression failure provides
little visual warning. In reinforced concrete buildings, concrete
beams, floors, and columns are cast monolithically, causing some
moments in the columns due to end restraint. Moreover, perfect
vertical alignment of columns in a multistory building is not
possible, causing loads to be eccentric relative to the center of
columns. The eccentric loads will cause moments in columns.
Therefore, a column subjected to pure axial loads does not exist in
concrete buildings. However, it can be assumed that axially loaded
columns are those with relatively small eccentricity, e, of about
0.1h or less, where h is the total depth of the column and is the
eccentric distance from the center of the column. Because
concrete has a high compressive strength and is an inexpensive
material, it can be used in the design of compression members
economically. Columns may be classified based on the following
different categories:
Based on loading, columns may be classified as follows:
1- Axially loaded columns, where loads are assumed acting at the
center of the column section.
8
A column that has large secondary moments is said to
be a slender column, and it is necessary to size its cross
section for the sum of both the primary and secondary
moments. The ACI's intent is to permit columns to be
designed as short columns if the secondary or �� effect
does not reduce their strength by more than5%.
Therefore, the transition from the short column (material
failure) to the long column (failure due to buckling) is
defined by using the ratio of the effective length to
the radius of gyration r. The height, Lu, is the unsupported
length of the column, and k is a factor that depends on
end conditions of the column and whether it is braced or
unbraced. For example, in the case of unbraced columns,
u
if is less than or equal to 22, such a column is classified
as a short column, in accordance with the ACI load criteria. Otherwise,
it is defined as a long or a slender column. The ratio /r is called the
slenderness ratio.
9
Based on frame bracing, columns may be part of a frame that is
braced against sides-way or unbraced against sides-way. Bracing
may be achieved by using shear walls or bracings in the building
frame. In braced frames, columns resist mainly gravity loads, and
shear walls resist lateral loads and wind loads. In unbraced frames,
columns resist both gravity and lateral loads, which reduce the
load capacity of the columns.
Tributary Area:
And in our project, we have calculated the total loads using this method.
BEAMS REACTIONS:
it's by finding the total sum of the beams reaction which the column
will carry.
4.2. Design procedure:
All columns in this Project are axial columns because the beams are
ce tered to the ce ter of the colu s’ ce ter, a d all fra es are
non-sway (Braced frames) as the ACI code said in section 10.10.5.1:
And we have so many shear walls from the first to end story in
the structure.
2
Ic – Moments of inertia for column
Lc – Length of Column
Ib – Moment of Inertia for beam
Lb – Beam Length
o =
ℎ− +∅ +∅
Calculate Kn and Rn
ℎ
��
o =
′��
��∗�
o = ′ ∗��∗ℎ
From the graph, for the values found in (3), read the required
reinforcement ratio �
Calculate the total steel area � = � ∗ �
Note that:
Where:
And the previous groups classified according to close range values of axial
loads for each column.
4
From CSI ETABS:
5
Sample of calculation for G1:
F’c = 28 Mpa
Fy = 420 Mpa
Lu = 3.35 m
WD = 44 KN/m2 from all floors
WL = 12 KN/m2 from all floors
Tributary area of load = 25 m2
�= . + . ∗ � �
� =( . + . )∗ =
�� ∗ 3
Area required = = =
. ∗ ′ . ∗
≤ − ( )≤
( )= − �ℎ ��
. ∗ .
= = . > − � − �
. ∗ .
. ∗ .
= = < − ℎ � − �
. ∗ .
3- Calculate emin & Mmin:
�� = + . ℎ = + . =
�� =� ∗ �� = ∗ . = . .
4- Compute EI:
= √ ′ = ∗√ =
∗
� = = . ∗
. � .
� = = = .
. �+ . . + .
. ∗ ∗� . ∗ ∗ .
�= = = .
+� + .
∗ � ∗
� = = = .
. ∗ .
= . + . ( )= . + . =
= = = . > −
�
− −
. ∗� . ∗ .
7- Find magnified eccentricity & moments:
= �� ∗ = ∗ . =
= ∗ � = . ∗ . = . .
Note that: We will use the tied-column interaction diagrams with bars in
four faces.
�
� = = =
∅ .
� ∗
= ′
= = .
∗� ∗ ∗
6
� ∗ ∗ . ∗
= ′ = = .
∗ ∗ℎ ∗ ∗
�ℎ − − −
�= = = .
ℎ
8
� , � = . ∗ ∗ =
Ø :
= = . − , Ø
500-2(30)-2(10)-16=404mm/3=134 mm
300-2(30)-2(10)-16=204 mm
= = . − , Ø
9
From Prokon program the outputs was as following:
For group 1:
8
For group 2: (300x350)
8
For group 3: (300x300)
82
5 SHEAR WALLS
THIS CHAPTER
WILL INCLUDE THE SEISMIC DESIGN OF
SHEAR WALLS.
5.1. Introduction:
Definitions—Walls and Wall Loadings:
ACI Code Section 2.2 defines a wall as follows:
Wall—Member, usually vertical, used to enclose or separate spaces.
This definition fails to consider the structural actions of walls. ACI Section 2.1 also
defines the term structural walls :
Structural wall — Wall proportioned to resist combinations of shears, moments,
and axial forces. A shear wall is a structural wall.
Major factors that affect the design of structural walls include the following:
a) The structural function of the wall relative to the rest of the structure.
The way the wall is supported and braced by the rest of the structure.
The way the wall supports and braces the rest of the structure.
a) The types of loads the wall resists.
b) The location and amount of reinforcement.
Two frequent characteristics of walls are their slenderness, height to thickness
ratio, which is generally higher than for columns, and the reinforcement ratios,
generally about a fifth to a tenth of those in columns.
Types of Walls:
Structural walls can be classified as:
a) Bearing walls — walls that are laterally supported and braced by the rest of the
structure that resist primarily in-plane vertical loads acting downward on the top of
the wall (see Figure a below). The vertical load may act eccentrically with respect to
the wall thickness, causing weak-axis bending.
b) Shear walls — walls that primarily resist lateral loads due to wind or earthquakes
acting on the building are called shear walls or structural walls. These walls often
provide lateral bracing for the rest of the structure. (See Figure b below). They
resist gravity loads transferred to the wall by the parts of the structure tributary to
the wall, plus lateral-loads (lateral shears) and moments about the strong axis of
the wall.
c) Nonbearing walls — walls that do not support gravity in-plane loads other than
their own weight. These walls may resist shears and moments due to pressures or loads
acting on one or both sides of the wall. Examples are basement walls and retaining
walls used to resist lateral soil pressures. (See Figures c and d).
83
84
Find the weight of the slab + the weight of all shear walls:
5.2. Shear Walls Design Procedure:
W= Wslab + Ws.w
Select the seismic zone from the seismic map
85
Determine Cv from table (A-7)
86
Find V, where Vmin < V < Vmax
× ×W
V=
��
Vmin= . ×�×
. �× ×W
Vmax=
� = 1 for Normal Buildings
�
∗ + ∗ +⋯
=
+ +⋯
∗ + ∗ +⋯
= + +⋯
Find eccentricity
� = . ∗
� = . ∗
= ± �
= ± �
Find JR
=∑ ∗ � + ∑ ∗ �
= �2
Find Qi
ℎ 3 ( + .6 +� )∗ 2
ℎ
� �∗|��|∗|�� �����|∗ �
�= ∗ �±
∑ � �
� �∗| �|∗|� �����|∗ ��
�=∑ ��
∗ �± �
87
The maximum moment = Me.q
Find P from tributary area
Pu = 1.2PD + 1.6PL
Use this load combination for ultimate loads:
Vu = Ve.q
Mu = 1.2MD + 0.5ML + Me.q
Find fc
�
�� ��∗
= �� + 2
> . ′
Design Boundary Element:
If yes Design Boundary Element if no use minimum
� ℎ � = .
∗�∗�
=
�
� = ∅∗
�
ℎ if . ≤ � ≤ . from UBC
�
.. say � = . then . = ∗� find b
Ties: use ∅ if bar diameter ≤ at t/4
Find T
And use ∅ if bar diameter > at t/4
�
= ∗ ∗ ∗
�
� =
Check if need shear design
∅∗ �
��
If > Ve.q
. ℎ�
� ′ .
or � . > � ∗ then design, of not use minimum
� . = . � ∗ � ∗ ′ .
+ �ℎ ∗
� = . �
ℎ�
�
>
ℎ�
� = . � ≤ .
�
Between them interpolation
88
5.3. Results of Analysis by CSI ETABS:
Direction = Multiple
Cv I
Base Shear Coefficient [UBC 1630.2.1, Eq. 30-4] =
RT
. Ca I
maximum [UBC 1630.2.1, Eq. 30-5] = = .
R
minimum [UBC 1630.2.1, Eq. 30-6] = . Ca I = .
89
Calculated Base Shear
Period Used W V Ft
Direction Vcoeff
(sec) (kN) (kN) (kN)
`X 0.34 0 17356 1800 0
Y 0.34 0 17356 1800 0
X + Ecc. Y 0.34 0 17356 1800 0
Y + Ecc. X 0.34 0 17356 1800 0
X - Ecc. Y 0.34 0 17356 1800 0
Y - Ecc. X 0.34 0 17356 1800 0
90
Calculated Center of mass and Center of rigidity
91
5.4. Manual design sample for SW (T2):
92
1- Find total weight of building:
�= +
� :
[ . ∗ . + ∗ . ∗ . ∗ . ∗ + ∗ ∗ . ∗ . ∗
+ ∗ . ∗ . ∗ . ]∗
� =
� :
[ . ∗ . + ∗ . ∗ . ∗ . ∗ + ∗ ∗ . ∗ . ∗
+ ∗ . ∗ . ∗ . ]∗
� =
∑ �= + =
� �= . & ℎ = .
/
� � , = . ℎ = . ∗ . = .
= . < . ,� =
×�×W . × . ×
�= = =
× . × .
� � = . ×�× = . ∗ . ∗ . ∗ =
. ×�×W . ∗ . × . ×
� = = = .
.
93
3- Find floor forces (fi):
Floor Wi hi Wi*hi = ∗ �−
∑
∑ ∗
̅ = = = .
∑
∑ ∗
̅ = = = .
∑
94
5- Find Center of rigidity:
∑= - 2850 428
∗
Where: = �
& =
( + . +� )∗
wall xi Ki Ki*xi
T1 0.15 3517 526
T2 3.45 3517 12134
T3 17.9 2322 41564
T4 21 2322 48762
∑= - 11678 102986
∑ ∗ ∑ ∗
̅= ∑
= = . & ̅= ∑
= = .
95
6- Find total eccentricities:
= . − . − . =− .
= . − . − . . =− .
∑= - 2850 7.2
∑= - 11678 901707
=∑ ∗ + ∑ ∗ = . + = .
96
8-Find (Q) for T2, in each floor:
� � ∗ | �| ∗ | |∗ �
�= ∗ �±
∑ �
∗| . |∗| . |
�= ∗ �− ∗ �= . �
= . ∗ =174 KN
= . ∗ = 131 KN
= . ∗ = 87 KN
= . ∗ = 43 KN
97
8-Draw shear and moment diagrams and find design loads:
� =
= .
Area of load from slab (tributary area) = (1.9*7.7) =14.63 m2
� = . ∗ . ∗ + . ∗ . ∗ =
� = . ∗ . ∗ . ∗ ∗ =
� = + =
� = ∗ . ∗ =
�� �� �� �
= . − . = .
= ∗ . = .
= ∗ . = .
98
9- Check if Boundary elements needed or not:
�� �∗
′
= + > . − �
�
∗ .
= + = < . ∗ =
. ∗ . .
� � = . ∗ ∗ =
� Ø => � = = Ø
� = Ø @ = /
99
Check one or two curtains:
∗√ ′ ∗� = ∗√ ∗ . ∗ . ∗ = > ��
=
And,
∗√ ′ ∗� = ∗√ ∗ . ∗ . ∗ = > �� =
,� �
� = . ∗ . ∗
� = . ∗ ∗ = /
∗
Ø => = =
Ø @
100
5.5. Detailing:
101
6 FOUNDATIONS
DESIGN
THIS CHAPTER
WILL INCLUDE DESIGN FOR FOOTING WITH DEFERENT
KIND“ THE I“OLATED FOOTING “QUARE FOOTING
WILL BE CHOSEN FOR MOST FOOTING SYSTEM,
COMBINED FOOTING AND SHEAR WALL FOOTINGS.
6.1. Introduction:
The most common types of footings used in buildings are the single footings
and wall footings. When a column load is transmitted to the soil by the footing,
the soil becomes compressed. The amount of settlement depends on many
factors, such as the type of soil, the load intensity, the depth below ground
level, and the type of footing. If different footings of the same structure have
different settlements, new stresses develop in the structure. Excessive
differential settlement may lead to the damage of nonstructural members in
the buildings or even failure of the affected parts.
Vertical loads are usually applied at the centroid of the footing. If the resultant
of the applied loads does not coincide with the centroid of the bearing area, a
bending moment develops. In this case, the pressure on one side of the footing
will be greater than the pressure on the other side.
The depth of the footing below the ground level is an important factor in the
design of footings. This depth should be determined from soil tests, which
should provide reliable information on safe bearing capacity at different layers
below ground level. Soil test reports specify the allowable bearing capacity to
be used in the design
2
6.2. Types of footings:
Footings must be designed to carry the column loads and transmit them to the
soil safely. The design procedure must take the following strength requirements
into consideration:
1. The area of the footing based on the allowable bearing soil capacity.
2. One-way shear.
3. Two-way shear, or punching shear.
4. Bending moment and steel reinforcement required.
5. Bearing capacity of columns at their base and dowel requirements
6. Development length of bars
7. Differential settlement
In our project we have used Single footings, combined footings & Wall footings
With the following data:
4
6.5. Design procedure:
Where: L = (1.2-1.5)*B
� = . � + .
qu =
�
From one way shear:
−
= −
� = ∗ ∗ = Ø� = . ∗Ø∗√ ′ ∗ ∗
Note that : this procedure will be repeated for the other direction.
From the previous calculation obtain the value of (d1) for b-direction &
(d2) for -direction.
5
From two way shear (Punching shear):
� = − +
= +
Ø� = . ∗Ø∗√ ′ ∗ ∗
� = − + = Ø� = . ∗Ø∗√ ′ ∗ ∗
As = ,Ø = .
Ø∗ ∗ . ∗
Check Asmin:
� . � = �. � ∗ ∗
Where :
b = 1 meter strip & �. min = . .
� = . �
For combined footing:
Where: Rs= ∑ service load which its closer to the largest Ps.
∑ . = ∗
�
= + , =
3. Determine the thickness of footing based on shear diagram:
8
Check punching shear under the largest Pu:
� = − +
= +
Ø� = . ∗Ø∗√ ′ ∗ ∗
� = − + = Ø� = . ∗Ø∗√ ′ ∗ ∗
4. Reinforcement design:
� . � = �. � ∗ ∗
Where :
b = 1 meter strip & �. min = . / .
9
For transverse steel:
Mu = qu ∗
Where:
−
=
As = ,Ø = .
Ø∗ ∗ . ∗
Check Asmin:
� . � = �. � ∗ ∗
Where :
b = 1 meter strip & �. min = . .
� , � = . ∗ . � ∗
For wall footing:
− ℎ�
= −
� = ∗ . � ∗ = Ø� = . ∗Ø∗√ ′ ∗ . � ∗
3. Reinforcement design:
�2 �−���� �ℎ� ��
Mu = qu ∗ Where: =
As = ,Ø = .
Ø∗ ∗ . ∗
Check Asmin:
� . � = �. � ∗ ∗
Where :
b = 1 meter strip & �. min = . .
Ps= 1400 KN
Qall=250 Kpa
= . => . = . => = , =
2
2. Determine the thickness of footing based on shear:
�
qu = = =
� ∗
� = ∗ ∗ = Ø� = . ∗Ø∗√ ′ ∗ ∗
� = ∗ ∗ . − = Ø� = . ∗ . ∗√ ∗ ∗ ∗
= .
� = ∗ ∗ = Ø� = . ∗Ø∗√ ′ ∗ ∗
� = ∗ ∗ . − = Ø� = . ∗ . ∗√ ∗ ∗ ∗
= .
From two way shear (Punching shear):
= + + + = . + + . + = . +
� = − + + = Ø� = . ∗Ø∗√ ′ ∗ ∗
� = − . + . + = Ø� = . ∗ . ∗√ ∗ ∗ . + ∗
= .
Take d= 0.4 m
Thickness of footing = max of (d1,d2,d3) + concrete cover + dbar
where: (concrete cover + dbar) ≅ .
= . + . = .
4
3. Reinforcement:
�2 �−
Mu = qu ∗ , ℎ = :
− − .
= = = .
.
Mu = qu ∗ = ∗ = .
∗ 6
As = = =
Ø∗ ∗ . ∗ . ∗ ∗ . ∗
Check Asmin:
� . � = �. � ∗ ∗ = . ∗ ∗ = >
a� � �� � =
∗� ∗
= = = /
�
5
For Long direction:
�2 �−
Mu = qu ∗ , ℎ = :
− − .
= = = .
.
Mu = qu ∗ = ∗ = .
∗ 6
As = = =
Ø∗ ∗ . ∗ . ∗ ∗ . ∗
Check Asmin:
� . � = �. � ∗ ∗ = . ∗ ∗ = <
a� � �� � =
∗� ∗
= = = /
�
For wall footing,L2:
Wu=506 KN/m
Ws=403 KN/m
Qall=250 Kpa
= � � ℎ
∗ � = = => = .
= = =
∗ .
− ℎ� . − .
= − = − = . −
� = ∗ . � ∗ = Ø� = . ∗Ø∗√ ′ ∗ . � ∗
. − ∗ = . ∗ . ∗√ ∗ ∗
= .
= . + . = .
3. Reinforcement for main steel:
− ℎ� . − .
= = = .
.
Mu = qu ∗ = ∗ = .
∗ 6
As = = =
Ø∗ ∗ . ∗ . ∗ ∗ . ∗
Check Asmin:
� . � = �. � ∗ ∗
Where :
� � � = . ∗ ∗ . = < −
∗� ∗
= = = /
�
� � � =
assume Ø14:
∗� ∗
= = = /
�
8
6.7. Outputs form CSI SAFE:
From CSI SAFE the following plan shows the different type of
footings in our project:
From CSI SAFE the following plan shows the Punching check for
single footings here if alue < then, it’s safe for punching:
9
From CSI SAFE the following plan shows the stresses check for
footings here if alue <Qall= 5 Kpa then, it’s safe for stress:
q= 247 Kpa < q allowable=250 Kpa, then the design for soil reaction stresses
is safe.
2
The final results of dimensions and reinforcement was as following:
Single footings:
Wall footings:
2
6.8. Detailing:
F1 (2x3x0.5):
22
F1 (2x2x0.3):
2
F1 (1x1x0.3):
24
Wall footing 1 (1x7.5x0.25):
25
Wall footing 2 (1.5x6.5x0.3):
2
Wall footing 3 (1.6x5.45x0.35):
2
Recommendations and conclusions:
General safety measures: Care must be taken before, during
and after work of the project.
Planning the project well and well by:
Manage time and control by avoiding all problems that
negatively affect time.
Manage the project by preparing the designs and drawings
within the specifications
A contract that meets the conditions guaranteeing the
rights and obligations of each of the parties to the project;
determines the full cost of the project and the time of
delivery of the project.
Hold periodic meetings to ensure that no problems occur
The use of large specialized companies working on reading the
charts and identify errors and problems to occur and choose
the best solution for them.
Supervision during implementation and preventive and curative
maintenance.
The use of machines and machines within the specifications
and codes and effective and high quality and the most
appropriate prices.
Field study, processing and site configuration
Setting the starting cost of the project and obtaining the lowest
prices for the materials.
Make monthly aggregated reports
Develop results after the end of the project to learn and gain
experience in subsequent projects.
28