DSEE100 SPECIFICATIONS
DC SUPPLY
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
INPUTS
DIGITAL INPUTS A to D
Negative switching
ANALOGUE INPUT A to C
Configurable as:
Negative switching digital input
Resistive
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
KEY FEATURES KEY BENEFITS at supply voltage
• Largest back-lit icon display in its • Ultimate size to feature ratio
AUXILIARY OUTPUTS C, D, E & F
class • Hours counter provides accurate 2 A DC at supply voltage
• Real time clock provides accurate information for monitoring and
event logging maintenance periods PULSE PICK UP
VOLTAGE RANGE
• Fully configurable via the fascia or • User-friendly set-up and button +/- 0.5 V to 70 V
PC using USB communication layout for ease of use
• Extremely efficient power save • Multiple parameters are monitored FREQUENCY RANGE
mode simultaneously which are clearly 5 Hz to 10,000 Hz
• Fuel and start outputs displayed on the largest back-lit DIMENSIONS
• 4 configurable DC outputs icon display in its class OVERALL
• 3 configurable analogue/digital • The module can be configured to 140 mm x 113 mm x 43 mm
5.5’’ x 4.4” x 1.7”
inputs suit a wide range of applications
• 4 configurable digital inputs • Uses DSE Configuration Suite PC PANEL CUT-OUT
• 3 engine maintainance alarms Software for simplified configuration 118 mm x 92 mm
• Engine speed protection • Licence-free PC software 4.6’’ x 3.6”
• Engine hours counter • IP65 rating (with optional gasket) MAXIMUM PANEL THICKNESS
• Engine pre-heat offers increased resistance to water 8 mm
• Engine run-time scheduler ingress 0.3”
• Battery voltage monitoring STORAGE TEMPERATURE RANGE
• Start on low battery voltage -40 °C to +85 °C
• Configurable remote start input -40 °F to +185 °F
• Comprehensive warning, controlled
OPERATING TEMPERATURE RANGE
shutdown or shutdown protection -30 °C to +70 °C
upon fault condition -22 °F to +158 °F
• LCD alarm indication
• Event log (50) OPTIONAL PARTS
RELATED MATERIALS
TITLE PART NO.
DSEE100 Installation Instructions 053-225
DSEE100 Operator Manual 057-268
DSEE100 PC Configuration Suite Manual 057-267
ELECTRICAL SAFETY
The DSEE100 is an easy to use The built in run time scheduler allows BS EN 60950
engine controller designed to for standalone running. Together with Safety of Information Technology Equipment,
provide flexible control with built in the on board event log, fault finding is including Electrical Business Equipment
monitoring and protection. made easy.
TEMPERATURE
BS EN 60068
The DSEE100 is fully configurable The DSE Configuration Suite PC Ab/Ae Cold Test -30 ºC
for a wide range of applications Software is used to easily make BS EN 60068-2-2
Bb/Be Dry Heat +70 ºC
such as engine driven pumps and adjustments to the operating
compressors. parameters of the controller, VIBRATION
reducing valuable development and BS EN 60068-2-6
The engine control functions, commissioning time. This software is Ten sweeps in each of three major axes
5 Hz to 8 Hz at +/-7.5 mm
including the engine start and available free of charge from the DSE 8 Hz to 500 Hz at 2 gn
load control can be achieved both Website.
automatically & manually. HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 ºC at 95% RH
The monitoring and configuration 48 Hours
of the system variables allows the BS EN 60068-2-78
Cab Damp Heat Static 40 ºC at 93% RH
DSEE100 to start and stop the engine.
48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 ms
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
4 4 3
DSEE100
7
OTHER
D+
+ W/L