Sie sind auf Seite 1von 65

FIRE PUMPS GENERAL PUMPS

ESPAÑA

FM
APPROVED
EX26841

www.pumpsgp.com
GENERAL PUMPS
ESPAÑA

General Pumps SL., was established more than


25 years ago in Valencia, Spain.
We are a major manufacturer in Spain of a wide
variety of water pumps for various applications.
We have two factories in Spain with the total space
of more than 2600 Sq. M.
Today we have one of the most comprehensive
ranges of pumps for Fire, HVAC, Water Treatment
and Plumbing Industry. The product line ranges
from small domestic pumps to large Industrial
application pumps. The pumps can be offered in
various Metallurgies such as Cast Iron, Stainless
Steel, Bronze, etc.
We have our product distribution channels in
North and South America, Europe, Middle East
and Far East. More than 75% of our sales revenue
is generated through exports across the world.
We have a comprehensive range of Fire Pumps
which are UL Listed and FM Approved.
The Quality Management System at our
manufacturing facility is certified to the latest
International Standard of ISO 9001.
We believe in providing our customers with a
complete solution for all their Fire Pumping needs.
Our Engineers can assist you in making the right
choice of product for your Fire Pumping
Application.

Contents
Horizontal split case fire pumps - UL listed, FM Approved 4
End Suction Fire Pumps - UL listed, FM Approved 10
Jockey Pumps 26
Horizontal Split Case Fire Pumps

FM
APPROVED
EX26841

Introduction
General Pumps offers FGHC series state-of-the-art fire There fire pumps typically consist of the following equipments:
pumps with diesel engine or electric motor driven, horizontal • Horizontal Split Case pump.
split case pump. • Electric motor or Diesel Engine
• Cooling system for Diesel Engine
These pumps are typically used in fire-fighting applications • Fuel system for Diesel Engine
for supplying water to fire hose reels, fire hydrants or • Battery for Diesel Engine electric start
• Exhaust system for Diesel Engine
sprinkler systems.
• Diesel Engine / Electric Motor Fire pump controller
• Suction and Discharge pressure gauges
Pumps have a discharge range from 450 to 1250 USgpm
• Air relief valve
and the head range from 4.4 to 14.7 bar.
• Casing Relief Valve for Motor Fire Pump
• Base frame
These fire pumps meet or exceed the requirements of
NFPA20. All above equipments except fuel supply tank and fire pump
controller are mounted on a common base frame.
Installations of these pumps would ensure the safety of
human life, buildings, and expensive equipments and General Pumps can also supply Packaged fire pumping
plants. FGHC fire pumpset shall be used only where a system with all required accessories ready for site installation.
positive suction is provided as specified in NFPA20.

GENERAL PUMPS
ESPAÑA 4
GENERAL PUMPS S.L. Quotation System 17.5.2.0

Pump Performance Datasheet


Customer : Quote number :
Customer reference : Size : FGHC 125-100-250 UL/FM
Item number : Default Stages :1
Service : Based on curve number : FLHC 125-100-250-2900
Quantity :1 Date last saved : 12 Dec 2017 8:14 PM
Operating Conditions Liquid
Flow, rated : 500.0 (750.0) USgpm Liquid type : Water
Differential head / pressure, rated (requested) : 9.00 (8.73) bar Additional liquid description :
Differential head / pressure, rated (actual) : 9.05 bar Solids diameter, max : 0.00 mm
Suction pressure, rated / max : 0.00 / 0.00 bar.g Solids concentration, by volume : 0.00 %
NPSH available, rated : Ample Temperature, max : 20.00 deg C
Frequency : 50 Hz Fluid density, rated / max : 0.999 / 0.999 kg/dm3
Performance Viscosity, rated : 1.00 cSt
Speed, rated : 2900 rpm Vapor pressure, rated : 0.00 bar.a
Impeller diameter, rated : 258 mm Material
Impeller diameter, maximum : 264 mm Material selected : Standard
Impeller diameter, minimum : 198 mm Pressure Data
Efficiency : 51.45 (65.13) % Maximum working pressure : 9.18 bar.g
NPSH required / margin required : - (-) / 0.00 m Maximum allowable working pressure : N/A
nq (imp. eye flow) / S (imp. eye flow) : 31 / - Metric units Maximum allowable suction pressure : N/A
MCSF :- Hydrostatic test pressure : N/A
Head, maximum, rated diameter : 9.18 bar Driver & Power Data (@Max density)
Head rise to shutoff : 1.98 (5.10) % Driver sizing specification : Rated power
Flow, best eff. point : 1,305.9 USgpm Margin over specification : 0.00 %
Flow ratio, rated / BEP : 38.29 (57.43) % Service factor : 1.00
Diameter ratio (rated / max) : 97.73 % Power, hydraulic : 28.39 (41.32) kW
Head ratio (rated dia / max dia) : 94.07 % Power, rated : 55.18 (63.44) kW
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Power, maximum, rated diameter : 87.92 kW
Selection status : Acceptable Minimum recommended motor rating : 55.93 kW / 75.00 hp
15.0

13.5

12.0

10.5
264 mm 50
258 mm 60 67
72
9.0 75 76
Head - bar

76
7.5 75

6.0 72
198 mm

4.5 67

60
3.0

1.5

0.0

120

90 264 mm
Power - kW

258 mm

60

30 198 mm

0
0 200 400 600 800 1,000 1,200 1,400 1,600 1,800
Flow - USgpm

GENERAL PUMPS S.L. · Pol. Ind. El Oliveral (U.E.7, Nave n°1) - Calle W · 46394 Ribarroja del Turia · Valencia Spain,
phone: +34 96 1665200 · fax: +34 96 1665052 · www.pumpsgp.com
Dimensions
k1 k2 a f
l

h2
v

h1
DNs

DNd
w

u
s m3 m3

d
h5
n1 Ø1/2” m2
n3 n3 m1
n2 e1 t

Model DNs DNd k1 k2 v n1 n2 n3 a f h1 h2 h5 s w m1 m2 m3 d l e1 u t

FGHC 125-100-250 125 100 310 250 170 250 350 100 323 402 320 199 25 22 282 320 240 95 32 81 65 10 35,3

FGHC 150-125-315 150 125 350 300 195 300 440 140 333 434 375 244 25 22 309 350 250 99 38 102 85 10 41

Flange Dimensions

ØD
ØB

ØC
ØA

ANSI 250 Flange Dimensions


Suction Discharge
Model
ØD x Nos. ØD x Nos.
ØA ØB ØC ØA ØB ØC
of holes of holes

FGHC 125-100-250 280 235 211 Ø7/8” x 8 255 200 176 Ø7/8” x 8

FGHC 150-125-315 320 270 246 Ø7/8” x 12 280 235 211 Ø7/8” x 8

GENERAL PUMPS
7 ESPAÑA
General Pump Features

1 - Impeller & Casing 2 - Shaft


• Minimal axial thrust due to double-entry impeller. • Heavy duty stainless steel shaft completely sealed and dry for
• Impeller is dynamically balanced to grade G6.3 balance zero corrosion.
quality in accordance to ISO 1940-1. • Short and rigid with negligible vibrations.
• Impeller & Casing are designed using state of art CFD tools • Replaceable shaft protecting sleeves.
to ensure optimal performance. • No threads exposed to pump medium, long operating life
and no corrosion.
• Adjustment-free assembly.

3 - Bearing 4 - Seal
• Heavy duty and grease lubricated antifriction • Asbestos - free, soft packed stuffing boxes.
bearings for long service life.
• Open gland, enough space for service activities.

5 - Casing
• In-line axially split design which permits removal of the complete Impeller Shaft Assembly without removing the pipes & motor.
• Short distance between bearings.
• Leak-tight due to compact joint flange with long Pre-stessed bolts.
• Counter-rotation possible with similar parts.
• Easy mounting self-aligning upper casing.
• Flange drilled as per ANSI B16.1 class 250.
• Smooth surface inside & CED coated for superior corrosion protection.
• Replaceable wear ring protect the casing and the impeller running clearances.
• Heavy duty casing design for high working pressure.

GENERAL PUMPS
ESPAÑA 6
Exploded View
32
GENERAL PUMPS

31
ESPAÑA

10
3

11
2
13

6 16 28
4
22 5

26
12 15
7
29 18
8 20
8

9 30

23
14
17
25
27
1 19
24
21
Part no. Part name Part no. Part name Part no. Part name Part no. Part name
1 Split casing 11 R.H. Sleeve 21 Cap screw with spring washer 31 Hose pipe
2 Impeller 12 L.H. Sleeve 22 Cap screw 32 Automatic Air Release Valve
3 Bearing housing 13 Shaft sleeve 23 Cap screw
4 Back cover 14 Shaft sleeve 24 Ball bearing
5 Shaft 15 Stud 25 'O' ring
6 Wear ring 16 Key 26 Graphite packing
7 Gland 17 Lantern ring 27 Hex nut
8 Internal bearing cover 18 Water thrower 28 Key
9 External bearing cover 19 Drain plug 29 Grease nipple
10 External bearing cover(drive) 20 'O’ ring 30 Dowel pin
Approved Fire Pump Models with Rating

RATED CAPACITY- 450 US GPM


UL Listed FM Approved Rated Suction Discharge
Sr. No. Pump Model Pressure Pressure Speed Inlet Dia. Outlet Dia. Stage(s)
(psi) (bar) (psi) (bar) (rpm) (inch) (inch)

1 FGHC 125-100-250 71-131 4.89-9 75-136 5.1-9.3 2900 5 4 1

RATED CAPACITY- 500 US GPM


UL Listed FM Approved Rated Suction Discharge
Sr. No. Pump Model Pressure Pressure Speed Inlet Dia. Outlet Dia. Stage(s)
(psi) (bar) (psi) (bar) (rpm) (inch) (inch)

1 FGHC 125-100-250 71-131 4.89-9 74-135 5.10-9.3 2900 5 4 1

2 FGHC 150-125-315 131-214 9-14.75 131-214 9-14.75 2900 6 5 1

RATED CAPACITY- 750 US GPM


UL Listed FM Approved Rated Suction Discharge
Sr. No. Pump Model Pressure Pressure Speed Inlet Dia. Outlet Dia. Stage(s)
(psi) (bar) (psi) (bar) (rpm) (inch) (inch)

1 FGHC 125-100-250 65-130 4.4-8.96 66-132 4.5-9.10 2900 5 4 1

2 FGHC 150-125-315 129-213 8.8-14.68 129-212 8.8-14.61 2900 6 5 1

RATED CAPACITY- 1000 US GPM


UL Listed FM Approved Rated Suction Discharge
Sr. No. Pump Model Pressure Pressure Speed Inlet Dia. Outlet Dia. Stage(s)
(psi) (bar) (psi) (bar) (rpm) (inch) (inch)

1 FGHC 150-125-315 127-210 8.75-14.4 126-209 8.68-14.4 2900 6 5 1

RATED CAPACITY- 1250 US GPM


UL Listed FM Approved Rated Suction Discharge
Sr. No. Pump Model Pressure Pressure Speed Inlet Dia. Outlet Dia. Stage(s)
(psi) (bar) (psi) (bar) (rpm) (inch) (inch)

1 FGHC 150-125-315 121-205 8.34-14.13 119-204 8.20-14 2900 6 5 1

GENERAL PUMPS
9 ESPAÑA
Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Documents

Model GPY
Full Service Reduced Voltage
Wye-delta Open
Electric Fire Pump Controller

Contents:
• Data Sheets
• Dimensional Data
• Wiring Schematics
• Field Connections
Note: The drawings included in this package are for controllers covered
under our standard offering. Actual AS BUILT drawings may differ
from what is shown in this package.

March 2018
Technical Data
Model GPY Electric Fire Pump Controller

3L3 1M T3
From normal
3L2 T2
incoming power through
Disconnecting Means 3L1 T1

(IS/CB)*
M
CR4
1M 2M T5
CR5 1S T4
2M
T6
CR5 2M
3L1
1S
1S

GPY 3L2

Across-the line
600 starting
Open transition
Locked rotor current
% of full load
Line current

Transition current
Starting Method: Reduced Voltage
Wye-delta open 210
Typical Voltage Applied at Start: 100% Wye delta starting

Inrush Current: 33% of normal load current Full load current

Starting Torque: 33%


20 40 60 80 100
Motor Type: Wye-delta Percent of motor speed (%)
No. of Contactors: 2 at 58%, 1 at 33% of motor FLC
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC

Built to NFPA 20 (latest edition)


• UL218 - Fire Pump Controllers
Underwriters Laboratory (UL)
• CSA C22.2 No. 14 Industrial Control Equipment
Standard,
Listings, FM Global Class 1321/1323
Approvals and New York City Accepted for use in the City of New York by the Department of Buildings
Certifications Seismic Certification See page 6 for details
Optional
CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
□ Standard: NEMA 2 (IP31)
Optional
□ NEMA 12 □ NEMA 4X-304 sst painted □ IP54
□ NEMA 3 □NEMA 4X-304 sst brushed finish □ IP55
Enclosure □ NEMA 3R □NEMA 4X-316 sst painted □ IP65
□ NEMA 4 □ NEMA 4X-316 sst brushed finish □ IP66
Accessories Paint Specifications
• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle • Glossy textured finish
*Please see Disconnecting Means details on page 3.

March 2018 2
Technical Data
Model GPY Electric Fire Pump Controller

Shortcircuit 200V to 208V 220V to 240V 380V to 416V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating HP (kw)

Standard 100kA
5-150 (3.7 - 110) 5-200 (3.7 - 147) 5-300 (3.7 - 220) 5-450 (3.7 - 335) n/a
Optional 150kA

Standard 50kA 200 (147) 250 (184) 350 - 450 (257 - 335) 500 (373)
5-500
(3.7- 373)
Optional 100kA n/a n/a n/a n/a

Ambient Standard: Optional:


Temperature □ 5°C to 40°C / 41°F to 104°F □ 5°C to 55°C / 41°F to 131°F
Rating Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.

Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
Service Entrance
Suitable as service entrance equipment
Rating

Emergency Start • Flange mounted • Integrated limit switch


Handle • Pull and latch activation • Across the line start (direct on line)

Locked Rotor • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current

Electrical • Voltage phase to phase (normal power)


Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (standard display at 0-300PSI)
• Externally mounted with protective cover

March 2018 3
Technical Data
Model GPY Electric Fire Pump Controller

Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)


• Power available • Deluge valve start • Pump on demand/Automatic start
• Motor run • Remote automatic start • Low discharge pressure
Visual Indications
• Periodic test • Remote manual start • Pump room temperature (ºF or ºC)
• Manual start • Emergency start • Lockout

Visual only
• Pump room alarm • Phase loss L1 • Overcurrent
• Pump on demand • Phase loss L2 • Undercurrent
• Motor trouble • Phase loss L3 • Undervoltage
• Power Loss • Low pump room temperature • Overvoltage
• Phase reversal • Weekly Test cut-in not reached • Invalid Cut-in
Visual & Audible
Alarms • Phase unbalance • Control voltage not healthy • Service required

Visual and Audible


• Locked rotor current
• Fail to start
• Low water level
• Low suction pressure

DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Common pump room alarm (field re-assignable)**
• Overvoltage
• Undervoltage
Remote Alarm • Phase unbalance
Contacts • Low pump room temperature
• High Pump room temperature
• Common motor trouble (field re-assignable)**
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
• Free (field programmable)**

**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.

March 2018 4
Technical Data
Model GPY Electric Fire Pump Controller

• Embedded microcomputer with software PLC logic


ViZiTouch V2 • 7.0” color touch screen (HMI technology)
Operator Interface • Upgradable software
• Multi-language
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPx
• Start on pressure drop
Automatic Start
• Remote start signal from automatic device
• Start pushbutton
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer ***
• Minimum run timer ***(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

***Can only be used if approved by the AHJ

March 2018 5
Technical Data
Model GPY Electric Fire Pump Controller

Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 15014
A Tobalski Watkins Affiliate
Company
Mounting
Rigid base and wall mounting
details
Seismic
Building Test Seismic AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria Parameters
SDS z/h IP
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016

RRS for Nonstructural Components Testing


10.0
Spectral Response Acceleration (g)

1.0

0.1
0.1 1.0 10.0
Frequency, f (Hz)

Horiz. Level 1 Vert. Level 1

Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
• OSHPD Special Seismic Certification Preapproval (OSP)

March 2018 6
Technical Data
Model GPY Electric Fire Pump Controller

A4 Flow switch provision High water reservoir level c/w visual indication
C18
Foam pump application w/o pressure and alarm contact (DPDT)
A8
transducer and run test solenoid valve. C19 Emergency start alarm contact (DPDT)
A9 Low zone pump control function C20 Manual start alarm contact (DPDT)
A10 Middle zone pump control function C21 Deluge valve start alarm contact (DPDT)
A11 High zone pump control function C22 Remote automatic start alarm contact (DPDT)
Non-pressure actuated controller w/o pressure C23 Remote manual start alarm contact (DPDT)
A13
transducer and run test solenoid valve
High pump room temperature alarm contact
Lockout/interlock circuit from equipment C24
A16 (DPDT)
installed inside the pump room
Second set of standard alarm contacts (DPDT)
Built in alarm panel (120V.AC supervisory C25
(Typical for city of Los Angeles and Denver)
power) providing indication for:
• Audible alarm & silence pushbutton for motor Additional visual and alarm contact (Specify
B11 Cx
run, phase reversal, loss of phase. function) (DPDT)
• Pilot lights for loss of phase & supervisory Low suction pressure transducer for fresh
power available D1 water rated at 0-300PSI with visual indication
Built in alarm panel same as B11 but 220- and alarm contact
B11B
240VAC supervisory power Low suction pressure transducer for sea water
High motor temperature c/w thermoster relay D1A rated at 0-300PSI with visual indication and
B19A alarm contact
and alarm contacts (DPDT)
High motor temperature c/w PT100 relay and Pressure transducer and run test solenoid
B19B D5 valve for fresh water rated for 0-500PSI (for
alarm contacts (DPDT)
factory calibration purposes only)
Ground fault alarm detection c/w visual
B21 Pressure transducer and run test solenoid
indication and alarm contact (DPDT) D5D
valve for sea water rated for 0-500PSI
C1 Extra motor run alarm contact (DPDT)
D10 Omit mounting feet (when applicable)
C4 Periodic test alarm contact (DPDT)
High withstand rating for
C6 Low discharge pressure alarm contact (DPDT) D13 (normal power section)
Low pump room temperature alarm contact • 208V to 480V = 150kA • 600V = 100kA
C7
(DPDT) D14 Anti-condensation heater & thermostat
Low water reservoir level alarm contact
C10
(DPDT) D14A Anti-condensation heater & humidistat
High electric motor temperature alarm contact
C11 Anti-condensation heater & thermostat &
(DPDT) D14B
humidistat
High electric motor vibration c/w visual
C12
indication and alarm contact (DPDT) D15 Tropicalization
Pump on demand / automatic start alarm
C14 D18 CE Mark with factory certificate
contact (DPDT)
Modbus with RTU frame format and RS485
C15 Pump fail to start alarm contact (DPDT) D26
connection
C16 Control voltage healthy alarm contact (DPDT) Motor heater connection (external single
D27
Flow meter valve loop open c/w visual phase power source and heater on/off contact)
C17
indication and alarm contact (DPDT)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

March 2018 7
Technical Data
Model GPY Electric Fire Pump Controller

Motor heater connection (internal single L01 Other language and English (bilingual)
D27A phase power source and heater on/off
contact) L02 French

D28 Customized drawing set L03 Spanish


L04 German
Field programmable I/O board -
D34A
5 Input / 5 output L05 Italian
Redundant pressure transducer for fresh L06 Polish
D36
water rated for 0-500PSI
Redundant pressure transducer for sea L07 Romanian
D36A
water rated for 0-500PSI L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese

Additional Options:

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

March 2018 8
Technical Data
Model GPY Electric Fire Pump Controller

ViZiTouch V2 Operator Interface

PMS 295 PMS 361 Noir

Home

2 3

8
5 6 7

1 - Color touch screen 3 - Screen protector


2 - Onscreen menu 4 - Power LED (3 colors)
• HOME page 5 - START button
• ALARM page 6 - STOP button
• CONFIGURATION page 7 - RUN TEST button
• HISTORY page 8 - USB port
• SERVICE page
• MANUAL page
• LANGUAGES page

March 2018 9
Electric Fire Pump Controller Model:GPA/GPP/GPY
Dimensions Built to the latest edition of the NFPA 20 standard

27 1/4" [694]
26 3/8" [671]
1/2" [12] 17 3/4" [452] 24" [610]

14" [356] 22 1/2" [572]

See Notes

48" [1220]
55 1/8" [1400]

54" [1372]
51 7/8" [1318]

27" [685]
21 1/4" [541] 21 5/8" [549]

1" [25] Adjustable Feet

Sensing Line Connection - 1/2 " F.NPT


28" [711]
26" [660]
Drain - 3/8 " M.TUBE 7" [178] 1" [25]

Voltage / Power Table


9 1/8" [233] Normal
7" [178] Power and
Motor Leads
12" [305]
Voltage Min HP Max HP Entrance

208 40 60 Notes: 1 1/4" [31] 3 1/2" [89] 4" [102]


1" [25]
220 - 240 40 60
- Standard NEMA: NEMA 2
- Standard paint : textured red RAL 3002.
380 - 400 - 415 75 125 - All dimensions are in inches [millimeters].
- Center of ViZiTouch screen: 47-5/8" [1208] from Bottom.
440 - 480 75 150 - Bottom conduit entrance through removable gland plate recommended.
- Use watertight conduit and connector only.
600 100 150 - Protect equipment against drilling chips.
- Door swing equal to door width.
- Seismic mounting to be rigid wall and base only.
Drawing for information only. Projection
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1. Valve Change 21/11/17 GPX-DI261 /E
0. First issue 16/11/16 CDL
All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller
Reduced Voltage / Wye-Delta (Open Transition)
Model: GPY
Wiring schematic Built to the latest edition of the NFPA 20 standard
IS1 CB1
1L3 3L3 CT3 1M**
1L2 3L2 CT2
1L1 3L1 CT1

White

White

White
CR4

Black

Black

Black
17
ST1 1M 3L3 64 66 68 2M**
65 67 69
SA1 CR5
18
1S
20
3L2
3L1
2M
4 2 3L1 CR5 2M
19 21
1S To J2-J3-J4 To J76
1S
2
1
3L2
NO NO +
C J40 J14 AI4
Motor Run C
TB1
NC NC -
2
1

NO NO +
C J42 J15 AI3
Power Available C
TB2
NC NC -
2
1

NO NO +
C J37 J16 AI2
Phase Reversal C
TB3
NC NC -
2
1
Red
NO NO
J39
+
White
PT1
Pump Room Alarm C C J17 AI1
TB4 Black
NC NC -

1
2

NO
LS1 **
NO LS1-1
C J41 LS1
Motor Trouble C
TB5 J54 LS1-2
NC NC
2
1
UP
NO J20
NO
C J55
(Field Programmable) C
TB6 DOWN
NC NC J8
VMB1
Black - +
J46 Red
AB1
AB
Remote Manual Start IN1

SV
SV1-1 Brown SV1
Lockout IN2 J43 SV1-2 Blue

I/O
Remote Automatic Start J1* IN3

4
Deluge Valve J45
J2* IN4 ST 2
J25
Water Reservoir Low IN5
J44 24V in XTR1
IN6 24V out 3L2
X1 H2
1 24VAC
IN7 J47 24VAC 3 X2 H1
3L1
IN8
NC
J36 CR4-1
CR4
C
CR4-2
CR4
NO

NC
J38 CR5-1
CR5
C
CR5-2
CR5
NO

GF

69
L3 68
J76 67
L2 66 To CT1-CT2-CT3 Legend

65 1M-2M Contactors
1S Contactor
L1 64
AB Alarm Bell
CB Circuit Breaker
CR Control Relay

J53 CT Current Transformer


EB Electric I/O Board
IS Isolating Switch
J Jumper
J4 L3 3L3 LS Limit Switch
PT Pressure Transducer
SA Surge Arrester

J3 L2 ST Shunt Trip
3L2 To 3L1-3L2-3L3
SV Solenoid Valve
VMB ViZiTouch Main Board

EB1 J2 L1 3L1 XTR Transformer

Drawing for information only.


* Remove jumper to use this feature Manufacturer reserves the right to modify this drawing without notice.
** Contact closes when emergency start is in "ON" position Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 Removed (fail safe) text from Power Available relay 20/02/17 GPY-WS600 /E
0 First issue 10/11/16 CDL
2017 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing for Isolating Switch Built to the latest edition of the NFPA 20 standard
Power Terminals
3 Phases Notes:
Bonding Incoming Power 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
Ground 2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
L1 L2 L3
IS1

COPPER CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (300 to 500) 1x (500) 2x (4/0 to 500) 2x (250 to 500) 2x (400 to 600) -------- -------- -------- -------- -------- --------

220 to 240 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
2x (400 to 600)
380 to 416 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (300 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (500 to 600) 2x (600) --------
2x (400 to 500)
440 to 480 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

ALUMINUM CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
5 " (127 mm) 8 " (203 mm) 10 " (254 mm)
Space

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0 to 250) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 250) 1x (4/0 to 250) 1x (250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
1x(500) 90°C or
208 1x (400 to 500) 2x (300 to 500) 2x (350 to 500) 2x (600) -------- -------- -------- -------- -------- --------
2x(4/0 to 250) **

220 to 240 1x (350 to 500) 1x (500) 2x (250 to 500) 2x (300 to 500) 2x (500) 2x (600) 90°C * -------- -------- -------- -------- --------
1x (350) ** 2x (500 to 600)
380 to 416 1x (3/0 to 250) 1x (250) 1x (400 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (400 to 500) 2x (600) 90°C * 2x (600) 90°C * --------
N/A ** 2x (500)
1x (300) ** or
440 to 480 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (500) 2x (250) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (600) 2x (600) 90°C *
1x (250) 90°C *
600 1x (1 to 1/0) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 1x (500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 General Revision (added AL coverage) 10/07/17 GPX-TD602 1/2 /E
0 First issue 16/03/17 CDL
2017 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing For GPP,GPY & GPW Built to the latest edition of the NFPA 20 standard

Notes:
Motor Terminals 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
2M 1M 2M 1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
T7 T8 T9 T1 T2 T3 T6 T4 T5 T1 T2 T3

M M
Model : GPP Models : GPW & GPY

COPPER CONDUCTORS for Motor Connection (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (2 to 3/0) 1x (1 to 2/0)

220 to 240 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 2/0)

380 to 416 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0)

440 to 480 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2)

600 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (1/0 to 300) 2x (3/0 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (1/0 to 2/0) 1x (3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (4/0 to 350) -------- -------- -------- -------- --------

380 to 416 1x (4 to 2/0) 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 350) 2x (4/0 to 350) --------

440 to 480 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300) 2x (3/0 to 350) 2x (4/0 to 350)

600 1x (6 to 2) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (250 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300)

ALUMINUM CONDUCTORS for Contactor (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (4 to 1/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0)

220 to 240 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (2 to 2/0) 1x (1 to 2/0) 1x (1/0 to 2/0)

380 to 416 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2) 1x (3 to 1/0)

440 to 480 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (4 to 2)

600 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (3/0) Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (2/0) 90°C * Consult Factory 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (300 to 350) -------- -------- -------- -------- --------

380 to 416 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (1/0 to 2/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (250 to 300) 2x (300 to 350) 2x (300 to 350) --------

440 to 480 1x (3 to 2/0) 1x (2 to 2/0) 1x (2/0) 90°C * 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 350) 2x (300 to 350)

600 1x (4 to 2) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * Consult Factory 2x (3/0 to 300) 2x (4/0 to 300)

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 General Revision (added AL coverage) 10/07/17 GPX-TD602 2/2 /E
0 First issue 16/03/17 CDL
2017 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing Built to the latest edition of the NFPA 20 standard

Control Terminals (EB1) Remote Alarm Terminals (EB1)


Terminals Wire Size: Terminals Wire Size:
24 - 12 AWG 24 - 12 AWG
0.5 Nm 0.5 Nm

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Remote Manual Start Close to start pump IN1 J25 Motor Run J40
1
Normally open TB1
NO
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Lockout Close to block start IN2 J25 Power Available J42
1
Normally open TB2
NO
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Remote Automatic Start Open to start pump J1* IN3 J25 J37
Phase Reversal Normally open
1
TB3
NO
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Deluge Valve Open to start pump J2* IN4 J25 Pump Room Alarm ** J39
1
Normally open TB4
NO
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C

Alarm Inputs (EB1) Motor Trouble **


Opens to alarm
1
NC
J41
Normally open TB5
Terminals Wire Size: NO
24 - 12 AWG Normally closed Closes to alarm C
0.5 Nm Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Water Reservoir Low Close to signal alarm IN5 J25 (Field Programmable ***) J55
1
Normally open TB6
NO
Normally closed Closes to alarm C
Opens to alarm NC

Network Connection (VMB1)


Shielded Female Connector RJ45

Modbus TCP/IP I/O

* Remove jumper to use this feature Drawing for information only.


** Re-assignable Manufacturer reserves the right to modify this drawing without notice.
*** Not available on GPS models Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved General Revision (added AL coverage)
1 10/07/17 GPX-TD603 /E
0 First issue 16/03/17 CDL
2017 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Applications Features & benefits
The FGHC fire pumps are used in fire-fighting applications FGHC fire pumps offers all features & benefits as mentioned in our
for supplying water to fire hose reels, fire hydrants or GHC standard pump series data booklet. Following are the
sprinkler systems in areas which are prone to the additional features & benefits offered by these pumps :

hazards of fire. • State-of-the-art design fire pumping system.


• UL listed/FM approved/NFPA-20 design

The typical applications are as follow: • Diesel engine as well as electric motor driven pump

• Commercial complexes and high rise buildings • Rugged construction

• Petrochemical industries and Gas plants • Liberal water passages

• Oil and Gas on-shore &off-shore platforms • Automatic air relief valve

• Oil terminals • Efficient operation

• Airports and ports • Lower initial cost

• Jetties • Reduced installation time and cost

• Marine applications • Simplified piping design

• Power stations and transformer stations • Suitable for space saving installation systems and retrofit
applications
• Chemical industries
• Easy access to all working parts
• Manufacturing plants
• Ease of maintenance
• Fire-work industries
• Single source unit responsibility.
• Warehouses/godowns.

GENERAL PUMPS
5 ESPAÑA
GENERAL PUMPS S.L. Quotation System 17.5.2.0

Pump Performance Datasheet


Customer : Quote number :
Customer reference : Size : FGHC 125-100-250 UL/FM
Item number : Default Stages :1
Service : Based on curve number : FLHC 125-100-250-2900
Quantity :1 Date last saved : 12 Dec 2017 8:20 PM
Operating Conditions Liquid
Flow, rated : 500.0 (750.0) USgpm Liquid type : Water
Differential head / pressure, rated (requested) : 9.00 (8.73) bar Additional liquid description :
Differential head / pressure, rated (actual) : 9.08 bar Solids diameter, max : 0.00 mm
Suction pressure, rated / max : 0.00 / 0.00 bar.g Solids concentration, by volume : 0.00 %
NPSH available, rated : Ample Temperature, max : 20.00 deg C
Frequency : 50 Hz Fluid density, rated / max : 0.999 / 0.999 kg/dm3
Performance Viscosity, rated : 1.00 cSt
Speed, rated : 3000 rpm Vapor pressure, rated : 0.00 bar.a
Impeller diameter, rated : 251 mm Material
Impeller diameter, maximum : 264 mm Material selected : Standard
Impeller diameter, minimum : 198 mm Pressure Data
Efficiency : 50.69 (64.45) % Maximum working pressure : 9.19 bar.g
NPSH required / margin required : - (-) / 0.00 m Maximum allowable working pressure : N/A
nq (imp. eye flow) / S (imp. eye flow) : 31 / - Metric units Maximum allowable suction pressure : N/A
MCSF :- Hydrostatic test pressure : N/A
Head, maximum, rated diameter : 9.19 bar Driver & Power Data (@Max density)
Head rise to shutoff : 2.10 (5.30) % Driver sizing specification : Rated power
Flow, best eff. point : 1,302.6 USgpm Margin over specification : 0.00 %
Flow ratio, rated / BEP : 38.39 (57.58) % Service factor : 1.00
Diameter ratio (rated / max) : 95.08 % Power, hydraulic : 28.39 (41.29) kW
Head ratio (rated dia / max dia) : 87.79 % Power, rated : 56.00 (64.07) kW
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Power, maximum, rated diameter : 88.61 kW
Selection status : Acceptable Minimum recommended motor rating : 61.89 kW / 83.00 hp
15.0

13.5

12.0

264 mm
10.5 50 60 67
72
251 mm 75
76
9.0
Head - bar

76
75
7.5
72
6.0 198 mm
67
4.5
60
3.0

1.5

0.0

120
264 mm
90
Power - kW

251 mm

60

30 198 mm

0
0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000
Flow - USgpm

GENERAL PUMPS S.L. · Pol. Ind. El Oliveral (U.E.7, Nave n°1) - Calle W · 46394 Ribarroja del Turia · Valencia Spain,
phone: +34 96 1665200 · fax: +34 96 1665052 · www.pumpsgp.com
® MODELS
JU4H-UF04 JU4H-UF14 JU4H-UF24 JU4H-UFH2 JU4H-UF50
JU4H-UF10 JU4H-UF20 JU4H-UF34 JU4H-UF40 JU4H-UF52
FIRE PUMP ENGINES JU4H-UF12 JU4H-UF22 JU4H-UFH0 JU4H-UF42 JU4H-UF54

UK Purchased
FM-UL-cUL APPROVED RATINGS KW/BHP
JU4H RATED SPEED
MODEL 1470 1760 2100 2350 2600 2800 3000
UF04 37 50 41 55 45 60 45 60
UF10 31 41 38 51 41 55
UF12 41 55 44 59
UF14 41 55 44 59 52 70 53 71
UF20 45 60 50 67 54 72
UF22 54 72 56 75
UF24 54 72 56 75 60 80 62 83
UF34 63 85 63 85 78 104 86 115
UFH0 54 73 66 88 73 98
UFH2 73 98 74 99
UF40 70 94 78 105 79 106
UF42 79 106 79 106
UF50 59 79 82 110 97 130 95 127
UF52 95 127 95 127
Picture shown represents a JU4H-NA engine model
UF54 91 122 104 139 108 145 108 145

SPECIFICATIONS
JU4H MODELS
ITEM
UF04/10/12/14 UF20/22/24 UF34 UFH0/H2 UF40/42 UF50/52/54
Number of Cylinders 4
Aspiration NA T
Rotation* CW
Overall Dimensions – mm (in.) 989 (39) H x 1226 (48) L x 916 (36.1) W 1166 (45.9) H x 1357 (53.4) L x 934 (36.8) W
Crankshaft Centerline Height – mm (in.) 356 (14)
Weight – kg (lb) 413 (910) 424 (935)
Compression Ratio 17.6:1 17.0:1
Displacement – l (cu. in.) 4.5 (275)
Engine Type 4 Stroke Cycle – Inline Construction
Bore & Stroke – mm ( in.) 106 x 127 (4.19 x 5.00)
Installation Drawing D545
Wiring Diagram AC C07651
Wiring Diagram DC C072145
Engine Series John Deere 4045 Series

Abbreviations: CW – Clockwise NA – Naturally Aspirated T – Turbocharged L - Length W – Width H - Height


*Rotation viewed from Heat Exchanger / Front of engine

CERTIFIED POWER RATING ENGINE RATINGS BASELINES


• Each engine is factory tested to verify power and performance. • Engines are to be used for stationary emergency standby fire pump service only. Engines
are to be tested in accordance with NFPA 25.
• Although FM-UL ratings are shown at specific speeds, Clarke engines can be
applied at any intermediate speed. To determine the intermediate speed power; • Engines are rated at standard SAE conditions of 29.61 in. (752.1 mm) Hg barometer and
make a linear interpolation from the Clarke FM-UL power curve. Contact Clarke or 77°F (25°C) inlet air temperature [approximates 300 ft. (91.4 m) above sea level] by the
your Pump OEM Representative to obtain details. testing laboratory (see SAE Standard J 1349).
• A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall
be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)
• A deduction of 1 percent from engine horsepower rating as corrected to standard SAE
FM conditions shall be made for diesel engines for every 10°F (5.6°C) above 77°F (25°C)
ambient temperature.

Page 1 of 12
® MODELS
JU4H-UF10 JU4H-UF20 JU4H-UF34 JU4H-UF40
JU4H-UF12 JU4H-UF22 JU4H-UFH0 JU4H-UF42 JU4H-UF52
FIRE PUMP ENGINES JU4H-UF14 JU4H-UF24 JU4H-UFH2 JU4H-UF50 JU4H-UF54

ENGINE EQUIPMENT
EQUIPMENT STANDARD OPTIONAL
Air Cleaner Direct Mounted, Washable, Indoor Service with Drip Shield Disposable, Drip Proof, Indoor Service Outdoor Type, Single or
Two Stage (Cyclonic)
Alarms Overspeed Alarm & Shutdown, Low Oil Pressure, Low & High Low Coolant Level, Low Oil Level, Oil Filter Differential Pressure,
Coolant Temperature, Low Raw Water Flow, High Raw Water Fuel Filter Differential Pressure, Air Filter Restriction
Temperature
Alternator 12V-DC, 42 Amps; with Poly-Vee Belt and Guard 24V-DC, 40 Amps; with Belt Guard
Coupling Bare Flywheel Listed Driveshaft and Guard, UF10/12/14, UF20/22/24 – CDS10-
SC; UFH0/H2, UF40/42 – CDS20-SC; UF50/52/54 – CDS30-S1
Engine Heater 230V-AC, 1000 Watt 115V-AC, 1000 Watt
Exhaust Flex Connection For NA Engines - SS, Clamped, 3” SS Flex, Clamped, 4” & 5”
For T Engines – SS, Clamped, 4”
Exhaust Protection Blankets on Naturally Aspirated Models, Metal Guards on Manifolds
and Turbocharger on Turbocharged Models
Flywheel Housing SAE #3
Flywheel Power Take Off 11.5” SAE Industrial Flywheel Connection
Fuel Connections Fire Resistant, Flexible, USA Coast Guard Approved, Supply and
Return Lines
Fuel Filter Primary Filter with Priming Pump
Fuel Injection System Stanadyne, Direct Injection
Fuel Solenoid 12V-DC Energized to Stop (ETS) 12V-DC Energized to Run (ETR); 24V-DC Energized to Run (ETR);
24V-DC Energized to Stop (ETS)
Governor, Speed Constant Speed, Mechanical
Heat Exchanger Tube and Shell Type, 4 BAR (60 PSI), BSP(F) Connections Sea Water Compatible
Instrument Panel English and Metric, Tachometer, Hourmeter, Water Temperature,
Oil Pressure and Two (2) Voltmeters
Junction Box Integral with Instrument Panel; For DC Wiring Interconnection to
Engine Controller
Lube Oil Cooler Engine Water Cooled, Plate Type
Lube Oil Filter Full Flow with By-Pass Valve
Lube Oil Pump Gear Driven, Gear Type
Manual Start Control On Instrument Panel with Control Position Warning Light
Overspeed Control Electronic with Reset and Test on Instrument Panel
Raw Water Cooling Loop – Galvanized Seawater, All 316SS, High Pressure
w\Alarms
Raw Water Cooling Loop – Automatic from Fire Pump Controller and from Engine Instrument Not Supplied (for Vertical Turbine Fire Pump Applications)
Solenoid Operation Panel (for Horizontal Fire Pump Applications)
Run – Stop Control On Instrument Panel with Control Position Warning Light
Starters Two (2) 12V-DC Two (2) 24V-DC
Throttle Control Adjustable Speed Control, Tamper Proof
Water Pump Centrifugal Type, Poly-Vee Belt Driven

Abbreviations: DC –Direct Current, AC – Alternating Current, SAE – Society of Automotive Engineers, NA – Naturally Aspirated, T- Turbocharged, BSP(F) – British
Standard Pipe Thread (Female), SS – Stainless Steel

UK, Ltd. Fire Protection Products, Inc.


Grange Works, Lomond Rd., Coatbridge, ML5-2NN 100 Progress Place, Cincinnati, Ohio 45246
United Kingdom United States of America
Tel +44-1236-429946 Fax +44-1236-427274 Tel +1-513-475-FIRE (3473) Fax +1-513-771-8930
www.clarkefire.com www.clarkefire.com

C133432 revM Specifications and information contained in this brochure subject to change without notice.
11APR17 Page 2 of 12
FIRE PUMP MODEL: JU4H-UF24
Heat Exchanger Cooled
Naturally Aspirated
4.5L 4 Cylinder

62
62

60
60

58

56
56

54
54

52
1750 2000 2250 2500 2750 3000 3250
ENGINE SPEED - RPM
RESTRICTED:
USE ONLY FOR STAND-BY FIRE PUMP APPLICATIONS

ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77°F (25°C) AIR INLET TEMPERATURE NAMEPLATE kW (MAXIMUM PUMP LOAD)
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
THIS DRAWING AND THE IN- CREATED DATE CREATED
FORMATION HEREIN ARE OUR 05/19/04
PROPERTY AND MAY BE USED BY
OTHER ONLY AS AUTHORIZED BY
US. UNPUBLISHED -- ALL RIGHTS
ENGINE MODEL JU4H-UF24
RESERVED UNDER THE DRAWING NO. REV
KEN WAULIGMAN 27OCT06 COPYRIGHT LAWS. C131944 B

Page 3 of 12
JU4H-UF24
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Basic Engine Description
Engine Manufacturer John Deere Co.
Ignition Type Compression (Diesel)
Number of Cylinders 4
Bore and Stroke - mm (in) 106 (4.19) X 127 (5)
Displacement - L (in³) 4.5 (275)
Compression Ratio 17.6:1
Valves per cylinder
Intake 1
Exhaust 1
Combustion System Direct Injection
Engine Type In-Line, 4 Stroke Cycle
Fuel Management Control Mechanical, Rotary Pump
Firing Order (CW Rotation) 1-3-4-2
Aspiration Natural
Charge Air Cooling Type None
Rotation, viewed from front of engine, Clockwise (CW) Standard
Engine Crankcase Vent System Open
Installation Drawing D545
Weight - kg (lb) 413 (910)

Power Rating 2350 2600 2800 3000


Nameplate Power - kW (HP)[1] 54 (72) 56 (75) 60 (80) 62 (83)

Cooling System - [C051001] 2350 2600 2800 3000


Engine Coolant Heat - kW (Btu/sec) 42.2 (40) 44.3 (42) 46.4 (44) 47.5 (45)
Engine Radiated Heat - kW (Btu/sec) 9 (8.5) 9.2 (8.7) 9.6 (9.1) 9.8 (9.3)
Heat Exchanger Minimum Flow
15°C (60°F) Raw H20 - L/min (gal/min) 30.3 (8) 34.1 (9) 37.9 (10) 41.6 (11)
37°C (100°F) Raw H20 - L/min (gal/min) 37.9 (10) 41.6 (11) 45.4 (12) 49.2 (13)
Heat Exchanger Maximum Cooling Raw Water
Inlet Pressure - bar (psi) 14 (203)
Flow - L/min (gal/min) 98.4 (26)
Typical Engine H20 Operating Temp - °C (°F) 76.7 (170) - 87.8 (190)
Thermostat
Start to Open - °C (°F) 76.7 (170)
Fully Opened - °C (°F) 87.8 (190)
Engine Coolant Capacity - L (qt) 14 (14.79)
Coolant Pressure Cap - kPa (lb/in²) 68.9 (10)
Maximum Engine Coolant Temperature - °C (°F) 93.3 (200)
Minimum Engine Coolant Temperature - °C (°F) 71.1 (160)
High Coolant Temp Alarm Switch - °C (°F) 96.1 (205)

Electric System - DC Standard Optional


System Voltage (Nominal) 12 24
Battery Capacity for Ambients Above 0°C (32°F)
Voltage (Nominal) 12 {C07633} 24 {C07633}
Qty. Per Battery Bank 1 2
SAE size per J537 8D 8D
CCA @ -18°C (0°F) 1400 1400
Reserve Capacity - Minutes 430 430
Battery Cable Circuit, Max Resistance - ohm 0.0012 0.0012
Battery Cable Minimum Size
0-3.1m Circuit Length[2] 00 00
3.1m-4.1m Circuit Length[2] 000 000
4.1m-5.1m Circuit Length[2] 0000 0000
Charging Alternator Maximum Output - Amp, 40 {C071363} 55 {C071366}
Starter Cranking Amps, Rolling - @15°C (60°F) 225 {C07888/C07889} 250 {C07819/C07820}

NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. 1Derate 3% per every 1000 ft. [304.8 m] Page 1 of 2
above 300 ft. [91.4 m] and derate 1% for every 10 °F [5.55 °C] above 77° [25°C]. 2Positive and Negative Cables Combined Length.

Page 4 of 12
JU4H-UF24
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Exhaust System (Single Exhaust Outlet) 2350 2600 2800 3000
Exhaust Flow - m³/min (ft.³/min) 13.3 (469) 15 (531) 16.5 (581) 17.8 (630)
Exhaust Temperature - °C (°F) 580 (1076) 591 (1095) 599 (1110) 607 (1125)
Maximum Allowable Back Pressure - kPa (in H20) 7.5 (30) 7.5 (30) 7.5 (30) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in) [3] 76.2 (3) 76.2 (3) 76.2 (3) 76.2 (3)

Fuel System 2350 2600 2800 3000


Fuel Consumption - L/hr (gal/hr) 21.2 (5.6) 22 (5.8) 22.7 (6) 23.5 (6.2)
Fuel Return - L/hr (gal/hr) 34.1 (9) 36 (9.5) 37.5 (9.9) 39 (10.3)
Fuel Supply - L/hr (gal/hr) 55.3 (14.6) 57.9 (15.3) 60.2 (15.9) 62.5 (16.5)
Fuel Pressure - kPa (lb/in²) 20.7 (3) - 41.4 (6)
Minimum Line Size - Supply - in. .50 Schedule 40 Steel Pipe
Pipe Outer Diameter - mm (in) 21.5 (0.848)
Minimum Line Size - Return - in. .375 Schedule 40 Steel Pipe
Pipe Outer Diameter - mm (in) 17.1 (0.675)
Maximum Allowable Fuel Pump Suction Lift
with clean Filter - mH20 (in H20) 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft) 1.4 (4.5)
Fuel Filter Micron Size 2

Heater System Standard Optional


Engine Coolant Heater
Wattage (Nominal) 1000 1000
Voltage - AC, 1 Phase 230 (+5%, -10%) 115 (+5%, -10%)
Part Number {C122192} {C122188}

Air System 2350 2600 2800 3000


Combustion Air Flow - m³/min (ft.³/min) 4.7 (166) 5.3 (186) 5.7 (202) 6.2 (218)
Air Cleaner Standard Optional
Part Number {C03249} {C03327}
Type Indoor Service Only, Canister,
with Shield Single-Stage
Cleaning method Washable Disposable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in H20) 2.5 (10) 2.5 (10)
Clean Air Cleaner - kPa (in H20) 1.2 (5) 1.2 (5)
Maximum Allowable Temperature (Air To Engine Inlet) - °C (°F)<*> 54.4 (130)

Lubrication System
Oil Pressure - normal - kPa (lb/in²) 345 (50) - 655 (95)
Low Oil Pressure Alarm Switch - kPa (lb/in²) 138 (20)
In Pan Oil Temperature - °C (°F) 104 (220) - 118 (245)
Total Oil Capacity with Filter - L (qt) 14.7 (15.5)

Lube Oil Heater Optional Optional


Wattage (Nominal) 150 150
Voltage 240V (+5%, -10%) 120V (+5%, -10%)
Part Number C04431 C04430

Performance 2350 2600 2800 3000


BMEP - kPa (lb/in²) 607 (88) 572 (83) 565 (82) 552 (80)
Piston Speed - m/min (ft/min) 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m C131537
Power Curve C131944

3Minimum Exhaust Pipe Diameter is based on: 15 feet of pipe, one 90° elbow, and one Industrial silencer. A Back-pressure flow analysis
must be performed on the actual field installed exhaust system to assure engine maximum allowable back pressure is not exceeded. See Exhaust
Sizing Calculator on www.clarkefire.com.
{ } indicates component reference part number.

Page 2 of 2
C131265 Rev K
DSP 14OCT16

Page 5 of 12
CLARKE
Fire Protection Products
JU4H, JU4R & JU6H, JU6R ENGINE MODELS
ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner Cylinder Head
Type…………..………….. .. Indoor Usage Only Type…….. …………………Slab 2 Valve
Oiled Fabric Pleats Material……………………. Annealed Gray Iron
Material……..…..…….………Surgical Cotton
Aluminum Mesh Cylinder Liners
Type…….. …………………Centrifugal Cast, Wet Liner
Air Cleaner - Optional Material………………..….…Alloy Iron Plateau, Honed
Type…………………………. Canister
Material………………………Pleated Paper Fuel Pump
Housing………………..……… Enclosed Type…………………………Diaphragm
Drive…………………………Cam Lobe
Camshaft
Material………….………….. Cast Iron Heat Exchanger (USA) - JU4H & JU6H Only
Chill Hardened Type…………………………Tube & Shell
Location…………...….…….. In Block Materials
Drive……………….………..…Gear, Spur Tube & Headers……………Copper
Type of Cam…………..….... Ground Shell…………………………Copper
Electrode……………………Zinc
Charge Air Cooler (JU6H-60,62,68,74,84, ADK0,
AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8, AARG,
ADP8, ADP0, ADT0, AD88, ADR8, AD98, ADS0, ADW8,
ADX8, AD98 only)
Type……….. ..…………….Raw Water Cooled Heat Exchanger (UK) - JU4H & JU6H Only
Materials (in contact with raw water) Type…………………………Tube & Bundle
Tubes……… ……………………90/10 CU/NI
Headers ……………………36500 Muntz Materials
Covers ……………………83600 Red Brass Tube & Headers……………Copper
Plumbing ……………………316 Stainless Steel/ Brass Shell………..……………. Aluminum
90/10 Silicone
Injection Pump
Charge Air Cooler (JU6R-AA67, 59, 61, PF, Q7, RF, Type……………………….. Rotary
S9, 83 only) Drive…………………………Gear
Type…...……………………Air to Air Cooled
Materials Lubrication Cooler
Core…………………………Aluminum Type…………………………Plate

Coolant Pump Lubrication Pump


Type……….………………… Centrifugal Type…………………………Gear
Drive……………………………Poly Vee Belt Drive…………………………Gear

Coolant Thermostat Main Bearings


Type…………………………… Non Blocking Type…………………………Precision Half Shells
Qty…………………………… 1 Material………………………
Steel Backed-Aluminum
Lined
Cooling Loop (Galvanized)
Tees, Elbows, Pipe…………Galvanized Steel Piston
Ball Valves……………………Brass ASTM B 124, Type and Material…………Aluminum Alloy with
Solenoid Valve………………Brass Reinforced Top Ring Groove
Pressure Regulator…………Bronze Cooling………………………Oil Jet Spray
Strainer……………………… Cast Iron (1/2" - 1" loops) or
Bronze (1.25" - 2" loops) Piston Pin
Type…………………………Full Floating - Offset

Cooling Loop (Sea Water) Piston Rings


Tees, Elbows, Pipe…………316 Stainless Steel Number/Piston…………… 3
Ball Valves……………………316 Stainless Steel Top………………………… Keystone Barrel Faced -
Solenoid Valve………………316 Stainless Steel Plasma Coated
Pressure Regulator/Strainer Cast Brass ASTM B176 Second………………………Tapered Cast Iron
C87800 Third…………………………Double Rail Type
w/Expander Spring
Cooling Loop (316SS)
Tees, Elbows, Pipe…………316 Stainless Steel Radiator - JU4R & JU6R Only
Ball Valves……………………316 Stainless Steel Type……………………… Plate Fin
Solenoid Valve………………316 Stainless Steel Materials
Pressure Regulator/Strainer 316 Stainless Steel Core……………………… Copper & Brass
Tank & Structure……….. Steel
Connecting Rod
Type…………………………… I-Beam Taper Valves
Material………………………Forged Steel Alloy Type…….. …………………Poppet
Arrangement………… ……Overhead Valve
Crank Pin Bearings Number/Cylinder…………… 1 intake
Type…………………………… Precision Half Shell 1 exhaust
Number………………………1 Pair Per Cylinder Operating Mechanism……Mechanical Rocker Arm
Material………………………Wear-Guard Type of Lifter…………….. Large Head
Valve Seat Insert……………Replaceable
Crankshaft
Material………………………Forged Steel
Type of Balance………………
Dynamic

Cylinder Block
Type…………………………… One Piece with
Non-Siamese Cylinders
Material………………………Annealed Gray Iron

C13615 04NOV14
Page 6 of 12
Page 7 of 12
Page 8 of 12
Page 9 of 12
JU4H-UF24
Stationary Fire Pump Engine Driver
EMISSION DATA
EPA 40 CFR Part 60

4 Cylinders
Four Cycle
Lean Burn
Naturally Aspirated

500 PPM SULFUR #2 DIESEL FUEL


FUEL GRAMS / HP- HR EXHAUST
RPM BHP (3) GAL/HR (4) CFM
NMHC NOx CO PM °F (°C)
(L/HR) (m3/min)
2800 80 6.0 (22.6) 0.30 4.15 1.71 0.15 1110 (599) 581 (16)
3000 83 6.2 (23.3) 0.33 3.94 2.36 0.18 1125 (607) 630 (18)

Notes:
1) 4045DF159 Base Engine Model manufactured by John Deere Corporation.
For John Deere Emissions Conformance to EPA 40 CFR Part 60 see Page 2 of 2.
2) The Emission Warranty for this engine is provided directly to the owner
by John Deere Corporation. A copy of the John Deere Emission Warranty can
be found in the Clarke Operation and Maintenance Manual.
3) Engines are rated at standard conditions of 29.61in. (7521 mm) Hg barometer
and 77°F (25° C) inlet air temperature. (SAE J1349)
4) PM is a measure of total particulate matter, including PM 10 .

CLARKE
FIRE PROTECTION PRODUCTS
3133 EAST KEMPER ROAD
C131868 REV.D CINCINNATI, OH 45241
23APR14 AC PAGE 1 OF 2

Page 10 of 12
CLARKE
www.clarkefire.com Fire Protection Products

JU4H-UF24
FIRE PUMP DRIVER

NOISE DATA

Mechanical Engine Noise *


Octave Band
RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)

2800 80 103.5 65.9 71.6 88.3 87.7 94.2 99.1 97.4 94.2 86.2 75.0

3000 83 104.4 65.7 72.3 87.0 88.4 96.6 100.0 98.8 97.8 89.3 75.6

Raw Exhaust Engine Noise **


Octave Band
RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)

2800-3000 80-83 104 93.8 98.2 92.9 95.1 94.7 97.4 93.6 84.3 77.9

* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.

** Values above are provided at 23ft (7m), 90° horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the
engine.

The above data reflects values for a typical engine of this model, speed and power in a free-field environment.

Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the
overall noise levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.

C131537 revC 3JUL13 DSP

Page 12 of 12
Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Documents

Model GPD
Diesel Engine Driven Fire Pump Controller

Contents:
• Data Sheets
• Dimensional Data
• Wiring Schematics
• Field Connections
Note: The drawings included in this package are for controllers covered
under our standard offering. Actual AS BUILT drawings may differ
from what is shown in this package.

March 2017
Technical Data
Model GPD Diesel Fire Pump Controller

Built to NFPA 20 (latest edition)


• UL218 - Fire Pump Controllers
Underwriters Laboratory (UL)
• CSA C22.2 No. 14 Industrial Control Equipment
Standard,
Listings, FM Global Class 1321/1323
Approvals and New York City Accepted for use in the City of New York by the Department of Buildings
Certifications Seismic Certification See page 5 for details
Optional
CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
□ Standard: NEMA 2 (IP31)
Optional
□ NEMA 12 □ NEMA 4X-304 sst painted □ IP54
□ NEMA 3 □ NEMA 4X-304 sst brushed finish □ IP55
Enclosure □ NEMA 3R □ NEMA 4X-316 sst painted □ IP65
□ NEMA 4 □ NEMA 4X-316 sst brushed finish □ IP66
Accessories Paint Specifications
• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle • Glossy textured finish

Standard
Ambient
Temperature
□ 5°C to 40°C / 41°F to 104°F
Optional
Rating
□ 5°C to 55°C / 41°F to 131°F

AC □ 120V / 1ph / 60hz


□ 208V to 240V / 1ph / 50-60hz
DC □ 12VDC
General □ 24VDC
Grounding system • Negative
• Two independent fully automatic
Battery chargers • 10A continuous charge
• 500mA trickle charge
• Battery 1 & Battery 2 voltage
Electrical Reading • Battery 1 & Battery 2 charging amperage
• Charging mode
• Continuous system pressure display
Pressure Reading
• Cut-in and cut-out pressure setting
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event Recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device

March 2017 2
Technical Data
Model GPD Diesel Fire Pump Controller

• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing connection 1/2” Female NPT
Pressure sensing • Drain connection 3/8”
• Rated and calibrated for 0-500psi working pressure
• Externally mounted with protective cover
Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)
• Engine run
• Main switch AUTO
• Main switch in OFF
• Main switch in HAND
Visual Indications
• Periodic test
• Cranking Cycle
• AC Power available
• Pump room temperature (ºF or ºC)

Visual only
• Pump on demand • Loss of continuity with contactor 1 • Battery 1 overvoltage
• Overpressure • Loss of continuity with contactor 2 • Battery 2 overvoltage
• Underpressure • Weekly test cut-in not reached • High raw water temperature
• Service required • Engine ECM warning • Low raw water flow

Visual and Audible


Visual & Audible • AC Failure • Weak battery 1 • Low fuel level
Alarms • DC Failure • Weak battery 2 • High fuel level
• Battery fail 1 • Engine fail when running • Engine ECM in alternate position
• Battery fail 2 • Engine fail to start • Engine fuel injection malfunction
• Charger fail 1 • Engine overspeed • Engine high temperature
• Charger fail 2 • Low ambient temperature • Engine low temperature
• Engine trouble • Water reservoir low • Engine ECM fault
• Pump room trouble • Water reservoir high • Engine low oil pressure
• Controller trouble • Fuel tank leak • Low suction pressure

DPDT-8A-250V.AC
• Engine run
• Common controller trouble
• Charger #1 & Charger #2 failure • Pressure line failure
• Common engine trouble
• High engine temperature • Battery #1 & battery #2 failure • Overspeed
• Fail to start • DC failure • Fail when running
Remote Alarm
• Fuel injection malfunction** • Loss of continuity (starter) #1 and/or #2 • Low oil pressure
Contacts
• ECM selector switch in alternate position***
• Common pump room alarm (field re-assignable)*
• Low fuel level • Low suction pressure • Water reservoir low
• High fuel level • Low pump room temperature • Water reservoir empty
• Fuel tank leak • High pump room temperature • AC Failure
• H-O-A selector switch in OFF or HAND
• Free (field programmable)*

*Except if option C13 is ordered. Tornatech reserves the right to use any of these four alarm points for special specific application requirements
**Applicable to electronic engines only.
*** Applicable to electronic engines only. Alarms when ECM selector switch on the engine is in alternate mode.

March 2017 3
Technical Data
Model GPD Diesel Fire Pump Controller

• Low fuel level


Terminals for
• Remote AUTOMATIC start
Field Connections
• Deluge valve start (re-assignable)
for External
• Fuel tank leak (re-assignable)
Devices
• High fuel level (re-assignable)
• Embedded microcomputer with software PLC logic
ViZiTouch V2 • 7.0” color touch screen (HMI technology)
Operator Interface • Upgradable software
• Multi-language
• Hand-Off-Auto
Selector Switch
• Behind lockable and breakable cover
• Start on pressure drop
Automatic Start
• Remote start signal from automatic device
• Crank 1 and Crank 2 start pushbuttons
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• 6 consecutive cycle attempts
Crank Cycle • 3 X 15s crank from battery 1 or 2 alternatively
Operation • 15s rest in between each crank attempt
• Manual with Stop pushbutton
Stopping
• Automatic after expiration of minimum run timer ****
• Minimum run timer ****(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPD

Automatic Start Manual or Remote Start Run Test or Periodic Test


Alarm and High Coolant Alarm only Alarm only Shutdown
shutdown
schedule Low Oil Pressure Alarm only Alarm only Shutdown
Overspeed Shutdown Shutdown Shutdown

Wall Mount Floor Mount


Approx. shipping Approx. shipping
Approx. Shipping Approx. Shipping
Starting Voltage dimensions in inches dimensions in inches
Weight in Lbs (kg) Weight in Lbs (kg)
(mm) (mm)

12V.DC
32" l x 29" w x 16" h 32” l x 29” w x 26” h
85 (39) 115 (52)
(813 x 737 x 407 ) (813 x 737 x 661)
24V.DC

**** Automatic shutdown shall be approved by the AHJ.

March 2017 4
Technical Data
Model GPD Diesel Fire Pump Controller

Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 15014
A Tobalski Watkins Affiliate
Company
Mounting
Rigid wall mounting
details
Seismic
Building Test Seismic AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria Parameters
SDS z/h IP
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016

RRS for Nonstructural Components Testing


10.0
Spectral Response Acceleration (g)

1.0

0.1
0.1 1.0 10.0
Frequency, f (Hz)

Horiz. Level 1 Vert. Level 1

Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
• OSHPD Special Seismic Certification Preapproval (OSP)

March 2017 5
Technical Data
Model GPD Diesel Fire Pump Controller

A1 Periodic test alarm contact (DPDT) Engine block heater circuit - 6KW max
C7A (same voltage as battery charger primary)
A2 Overspeed alarm contact (DPDT) Foam pump application w/o pressure transducer and
C8 run test solenoid valve
A3 Low oil pressure alarm contact (DPDT)
Non pressure actuated controller w/o pressure trans-
A4 High coolant temperature alarm contact (DPDT) C9 ducer and run test solenoid valve

A5 Failure to start alarm contacts alarm contact (DPDT) C13 Louver activation circuit (battery power specific)
Delayed automatic start on AC power failure
A6 Battery 1 & 2 failure alarm contact (2 x DPDT) C14 (factory set at 15 minutes)
A7 Charger 1 & 2 failure alarm contact (2 x DPDT)
C15 Low zone pump control function
A8 AC failure alarm contact (DPDT) C16 Middle zone pump control function
System overpressure alarm contact (For engines with
A9 PLD) (DPDT)
C17 High zone pump control function
Lockout/interlock circuit from equipment installed inside
A11 Extra controller trouble alarm contact (DPDT) C19 the pump room
A12 Extra engine trouble alarm contact (DPDT) Pressure transducer and run test solenoid valve for
D4 fresh water rated for 0-500psi (for factory calibration
Additional engine alarm contact (DPDT) purposes only)
Ax (specify function)
Pressure transducer and run test solenoid valve for sea
B1 Low fuel level alarm contact (DPDT) D6 water rated for 0-500PSI

B2 Water reservoir level low alarm contact (DPDT) Low fuel level float switch supplied as separate item
D7A (1-1/4”)
B3 Water reservoir empty alarm contact (DPDT) Low fuel level float switch supplied as separate item
D7B (1-1/2”)
B4 Low pump room temperature alarm contact (DPDT)
High fuel level float switch supplied as separate item
D8A
B5 High fuel level alarm contact (DPDT) (1-1/4”)
Low system (discharge) pressure alarm contact High fuel level float switch supplied as separate item
B6 D8B (1-1/2”)
(DPDT)

B7 Low suction pressure alarm contact (DPDT) D9A Anti-condensation heater & thermostat

B8 Pump on demand alarm contact (DPDT) D9B Anti-condensation heater & humidistat

B9 Fuel tank leak alarm contact (DPDT) D9C Anti-condensation heater & thermostat & humidistat
Low suction pressure transducer for fresh water rated
B10 Main relief valve open alarm contact (DPDT) D11 at 0-300PSI with visual indication and alarm contact
B11 Flow meter loop valve open alarm contact (DPDT) Low suction pressure transducer for sea water rated at
D11A 0-300PSI with visual indication and alarm contact
B12 Water reservoir level high alarm contact (DPDT)
D12 Tropicalization
B13 High pump room temperature alarm contact (DPDT)
D25 Mounting stand
Additional pump room alarm contact (DPDT) (specify
Bx function) D25A Mounting stand SST- 304 painted
C5 CE Mark with factory certificate D25B Mounting stand SST- 304 brushed finish
Nickel – cadmium battery chargers (Battery data sheet
C6 required) D25C Mounting stand SST- 316 painted
Engine block heater circuit - 3KW max D25D Mounting stand SST- 316 brushed finish
C7 (same voltage as battery charger primary)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

March 2017 6
Technical Data
Model GPD Diesel Fire Pump Controller

D26 Combined low and high fuel level float switch (1-1/4”) L01 Other language and English (bilingual)
D26A Combined low and high fuel level float switch (1-1/2”) L02 French
D27 Fuel level probe (2”) Level indication L03 Spanish
D28A Field programmable I/O board - 5 Input / 5 output L04 German
Redundant pressure transducer for fresh water rated L05 Italian
D30 for 0-500PSI
Redundant pressure transducer for sea water rated for L06 Polish
D31 0-500PSI
L07 Romanian
D32 Modbus with RTU frame format and RS485 connection
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese

Additional Options:

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

March 2017 7
Technical Data
Model GPD Diesel Fire Pump Controller

ViZiTouch V2 Operator Interface


®

PMS 295 PMS 361 Noir

Home

2 3

9
5 6 7 8

1 - Color touch screen 3 - Screen protector


2 - Onscreen menu 4 - Power LED (3 colors)
• HOME page 5 - CRANK 1 button
• ALARM page 6 - CRANK 2 button
• CONFIGURATION page 7 - STOP button
• HISTORY page 8 - RUN TEST button
• SERVICE page 9 - USB port
• MANUAL page
• LANGUAGES page

March 2017 8
Diesel Engine Fire Pump Controller Model:GPD
12Vdc or 24Vdc Negative Ground
Dimensions Built to the latest edition of the NFPA 20 standard

27" [684] 9 5/8" [245]


26" [661] 8 5/8" [220]
23 5/8" [600] 1/2" [12]
7 7/8" [200] 22 1/8" [562]

See Notes
28 7/8" [732] 27 1/2" [700]
29 7/8" [757]
20 1/4" [514]

2 7/8" [73]

6 7/8" [174]

- Controller standard without mounting stand.


- Order option D25 if mounting stand required.

20 1/2" [520] 13 1/8" [333]

23 5/8" [600]
Sensing Line Connection - 1/2 " F.NPT
Drain - 3/8 " M.TUBE
23 3/8" [594]
5" [127]

6 1/2" [166] 4 1/2" [115] 7 1/8" [182]

1 1/4" [31] 10 7/8" [275]


Notes:
13 1/8" [333]
- Standard: NEMA 2
- Standard paint : textured red RAL 3002.
- All dimensions are in inches [millimeters].
- Center of ViZiTouch screen: 20-1/4" [514] from bottom (no feet).
- Bottom conduit entrance through removable gland plate recommended.
- Use watertight conduit and connector only.
- Protect equipment against drilling chips.
- Door swing equal to door width.
- Seismic mounting to be rigid wall only.

Drawing for information only. Projection


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
GPD-DI700 /E
0. First issue 18/11/16 CDL
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Wiring schematic Built to the latest edition of the NFPA 20 standard
2
1
NO Black - +
Controller Trouble
NO
C C J36 J50 Red
AB1
(Fail Safe) TB1 AB
NC NC
2
1

NO NO
J37 Brown SV1
Engine Run / Louver Activation Circuit C C
TB2 J24
SV
Blue
VMB1
NC NC
2
1

NO NO
C J38
Main Switch in HAND or OFF C
TB3 +
NC Analog Input
NC J16 AI5
2 Flow / Spare Temperature
1 -
NO NO I/O
Engine Trouble C J39
C +
TB4 Analog Input
NC NC
J14 AI4
2 Fuel Level
1 -

COM
NO NO

DI5

DI4
Pump Room Alarm C J40
C +
TB5 Analog Input
NC
NC J15 AI3
2 Water Level / Suction Pressure 30 32 31
1 -
NO NO
C J42
(Field Programmable) C
TB6 +
NC
NC J17 AI2
-
SS1 H
OFF
A
Red
+
White
PT1
Low Fuel Level IN1 J18 AI1
- Black AUTO
Remote Auto Start J1* IN2
HAND
Deluge Valve Start J2* IN3 J25 53
J44 VIN
54
Fuel Tank Leak IN4

High Fuel Level IN5 J20 UP

DOWN
J8
MP+
J35
MP-

ECM Selector Switch in Alternate Position 301 301


J4 24V in
Fuel Injection Malfunction 302 302 24V out

Electronic Control Module Warning 303 15


303
BC1

BOOST
B1+ B1
16
Electronic Control Module Fault 304 304 B1- B2
J103 J106 17
CF1 Com
PLD Low Suction Pressure

ALARM
305 305 18 NO
High Raw Water Temperature 310 310 NC

Low Raw Water Flow 311 311 BATT. SUPPLY

+ - L N
19
Low Engine Temperature 312 312
BC2
BOOST

B2+ B1
B2-
20 B2
J107 63 11 13 54
Energize to Start Solenoid 1 1 CF2
21 Com
ALARM

22 NO
Engine Run 2 2
NC
Overspeed 3 3
BATT. SUPPLY
Low Oil Pressure 4 4 + - L N

High Engine Temperature 5 5 62


62
Battery 1 6 6 J104 6
6 CB3 83 11 14 54

Battery 2 8 8 63
63
Start Contactor 1 9 9 11
J105 11
Start Contactor 2 10 10

11 11 83
Ground 83
Ground 11 8
11 8
82 CB4
Energize to Stop Solenoid 12 12 DB1 82

Legend
53 54 AB Alarm Bell
BC Battery Charger
CB Circuit Breaker

IS1 CB2 DB Diesel I/O Board

53 F Filter
14
1L L' IS Isolating Switch
L
CB1 J Jumper
120-240 VAC
50-60Hz F1 13
PT
SS
Pressure Transducer
Selector Switch
1N
N 54 SV Solenoid Valve
E N' VMB ViZiTouch Main Board

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
* Remove jumper to use this feature Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved 1 Corrected SS1 inputs 16/01/17 GPD-WS700 /E
0 First issue 10/11/16 CDL
2017 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Layout Built to the latest edition of the NFPA 20 standard

Designation Description
BC1-BC2 Battery Charger #1 and #2
CB1-2 Magnetic Breaker 1 Pole 10 A
CB3-4 Magnetic Breaker 1 Pole 16 A
DB1 I/O Diesel Board
F1 Filter
IS1 Isolating Switch

SS1 Lockable 3 Position Selector Switch


VMB1 ViZiTouch Main Board

BC1

VMB1

BC2
CB3
CB4
CB1
CB2
54

0 - OFF 0 - OFF 0 - OFF 0 - OFF F1

SS1

IS1
DOWN
UP

24V out
+

VIN

24V in

B1-

B2-
AB

SV

B1+

B2+
AI5

AI4

AI3

AI2

AI1

CF1

CF2

62

63

83

82
6

DB1
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC
C

C
2

MP+
IN1

IN2

IN3

IN4

IN5

10

11

11

12
MP-

301

302

303

304

305

310

311

312

2
3

4
5

6
8

9
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC
C

C
1

Front Door Layout Internal Layout

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
GPD-LY700 /E
0 First issue 21/11/16 CDL
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Terminal Diagram Built to the latest edition of the NFPA 20 standard
Power Supply Remote Alarm Terminals (DB1)
Terminals Wire Size: Terminals Wire Size:
14 - 6 AWG 24 - 12 AWG
3.9 Nm 0.5 Nm

120-240 VAC L
50-60Hz IS1 Normally closed
2

N Opens to alarm
NO

Normally open C

Controller Trouble Closes to alarm NC


G (Fail Safe)
Normally open
1
J36
TB1
NO
Normally closed Closes to alarm C
Opens to alarm
Engine Connections (DB1) NC

2
Normally open NO
Energize to Start Solenoid Closes to alarm
1 1 Engine Run Normally closed C

Engine Run
Opens to alarm NC
J37
2 2 1
TB2
Normally open NO
Overspeed Louver Activation Circuit Normally closed Closes to alarm
3 3 C
Opens to alarm NC
Low Oil Pressure
4 4
2
High Engine Temperature Normally open
5 5 NO
Normally closed Closes to alarm C
Battery 1 Opens to alarm
6 6 J104 NC
J38
Main Switch in HAND or OFF 1
Battery 2 Normally open TB3
NO
8 8 Closes to alarm
Normally closed C
Start Contactor 1 Opens to alarm NC
9 9
Engine Terminal Strip

Start Contactor 2 2
10 10 Normally open NO
Ground Normally closed Closes to alarm C
11 11
Opens to alarm NC
Engine Trouble ** J39
Ground 1
TB4
11 11 Normally open NO
Normally closed Closes to alarm C
Energize to Stop Solenoid
12 12 Opens to alarm NC

2
ECM Selector Switch in Alternate Position Normally open NO
301 301
Normally closed Closes to alarm C
Fuel Injection Malfunction Opens to alarm
302 302 NC
J40
Pump Room Alarm ** 1
Normally open TB5
Electronic Control Module Warning NO
303 303 Closes to alarm
Normally closed C
Electronic Control Module Fault Opens to alarm NC
304 304

PLD Low Suction Pressure J103 2


305 305 Normally open NO
Normally closed Closes to alarm
High Raw Water Temperature C
310 310 Opens to alarm NC
(Field Programmable) J42
1
Low Raw Water Flow Normally open TB6
311 311 NO
Normally closed Closes to alarm C
Low Engine Temperature
312 312 Opens to alarm NC

Field Connections (DB1)


Terminals Wire Size:
24 - 12 AWG
0.5 Nm

Low Fuel Level IN1 All wiring between the controller and diesel engine shall be stranded
(NFPA20)
Remote Auto Start J1* IN2

Deluge Valve Start ** J2* IN3


J25 Wiring between controller and engine (terminals 301, 302, 303, 304, 305,
Fuel Tank Leak ** IN4
310, 311, 312, 2 ,3 ,4 ,5) must be #14AWG as minimum.

High Fuel Level ** IN5

Wiring between controller and engine (terminals 12 [rated at 10A or 22A for
20 seconds] 1, 9, 10 [rated at 10A]) must be stranded #10AWG as minimum.
Network Connection (VMB1)
Shielded Female Connector RJ45

Wiring between controller and engine (terminals 6, 8, 11 [rated at 30A]) must


be stranded and sized according to distance.
Modbus TCP/IP I/O
Drawing for information only.
* Remove jumper to use this feature Manufacturer reserves the right to modify this drawing without notice.
** Re-assignable Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
GPD-TD700 /E
0 First issue 10/11/16 CDL
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Louver Connection Built to the latest edition of the NFPA 20 standard

Located in Controller
Engine Run Alarm Contacts

C-NO C-NC

Normally open Normally closed


Closes to alarm Opens to alarm

NO
NO
J37
C
TB2
C
NC
NC

M
Louvers Motor

Power Supply from a Reliable


External Power Source
(See NFPA20-2016 11.3.2 & A 11.3.2)

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
GPD-TD701 /E
0 First issue 10/11/16
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Jockey Pump

Introduction
Jockey Pump are small, motor driven pumps used in When the water pressure drops below the pre-set level, the
conjunction with main fire pumps to compensate for minor pressure switch energizes a starter which activates the
leaks in the fire protection system and automatically Jockey Pump. Correct water pressure is therefore maintained
maintain stand-by pressure. This reduces wear on the at all times. An optional minimum run timer will prevent the
main pump and controller caused by unnecessary, Jockey Pump from being started too frequently. This timer will
frequent operation. Jockey Pump controllers are available ensure operation for a minimum of 2 minutes. If a fire should
start, the pressure will continue to drop and the main Fire
for across-the-line starting.
Pump wil start. Automatic controllers also include a
"Hand-off Automatic" selector switch for manual operation.
Occasionally in a Fire Pump system, water leakage will
occur at flanged or threaded pipe connections, valve
stems, stuffing boxes, etc. This normal loss of water will
lower the system pressure gradually until the main Fire
pump is required to start. To minimize wear on the Fire
Pump resulting from unnecessary operation, a Jockey
Pump is recommended for the system. In a Jockey Pump
system a small pump, motor and Controller / pressure
switch unit is installed in the piping system.

GENERAL PUMPS
ESPAÑA 26
GENERAL PUMPS S.L. Quotation System 18.5.5

Pump Performance Datasheet


Customer : Quote number : 716378
Customer reference : Size : GCR10-14
Item number : 001 Stages : 14
Service : Based on curve number : LCR10-14-2-50
Quantity :1 Date last saved : 02 Feb 2019 7:59 PM
Operating Conditions Liquid
Flow, rated : 11.40 m3/h Liquid type : Water
Head, rated (requested) : 100.0 m Additional liquid description :
Head, rated (actual) : 100.0 m Solids diameter, max : 0.0 mm
Suction pressure, rated / max : 0.00 / 0.00 bar.g Solids concentration, by volume : 0.00 %
NPSH available : Ample Temperature : 20.00 deg C
Frequency : 50 Hz Fluid density : 0.999 / 0.999 kg/dm3
Performance Viscosity : 1.00 cSt
Speed : 2900 rpm Vapor pressure, rated : 0.00 bar.a
Impeller dia. : 92.0 mm Material
Impeller diameter, maximum : 92.0 mm Material selected : Standard
Impeller diameter, minimum : 92.0 mm Pressure Data
Efficiency : 69.99 % Maximum working pressure : 14.14 bar.g
NPSH required / margin required : 2.68 / 0.00 m Maximum allowable working pressure : 16.00 bar.g
nq (imp. eye flow) / S (imp. eye flow) : 34 / 85 Metric units Maximum allowable suction pressure : 10.00 bar.g
MCSF :- Hydrostatic test pressure : 24.00 bar.g
Head max. : 144.4 m Driver & Power Data (@Max density)
Head rise to shutoff : 43.06 % Driver sizing specification : Maximum power
Flow, best eff. point : 10.53 m3/h Margin over specification : 0.00 %
Flow ratio, rated / BEP : 108.23 % Service factor : 1.00
Diameter ratio (rated / max) : 100.00 % Power, hydraulic : 3.10 kW
Head ratio (rated dia / max dia) : 100.00 % Power, rated : 4.43 kW
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Power, maximum : 4.47 kW
Selection status : Acceptable Motor rating : 5.59 kW / 7.50 hp
200
Performance based on test acceptance - ISO 9906:2012 3B
180

160
92.0 mm 53 59 63
140 67
69
70
Head - m

120
70
69
100 67
80

60

40

20

6.0
Power - kW

4.5
92.0 mm
3.0

1.5

0.0
NPSHr - m

5.0

2.5

0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Flow - m3/h

GENERAL PUMPS S.L. · Pol. Ind. El Oliveral (U.E.7, Nave n°1) - Calle W · 46394 Ribarroja del Turia · Valencia Spain,
phone: +34 96 1665200 · fax: +34 96 1665052 · www.pumpsgp.com
GENERAL PUMPS S.L. Quotation System 18.5.5

Pump Performance Curve


200
Performance based on test acceptance - ISO 9906:2012 3B
180

160
92.0 mm 53 59 63
140 67
69
70
120
Head - m

70
100 69
67
80

60

40

20

6.0
Power - kW

4.5
92.0 mm
3.0

1.5

0.0
NPSHr - m

5.0

2.5

0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Flow - m3/h
Customer : Size : GCR10-14 Flow, rated : 11.40 m3/h
Customer reference : Stages : 14 Head, rated : 100.0 m
Item number : 001 Speed : 2900 rpm Fluid density : 0.999 / 0.999 kg/dm3
Service : Based on curve number : LCR10-14-2-50 Viscosity : 1.00 cSt
Quantity :1 Efficiency : 69.99 % Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00
Quote number : 716378 Power, rated : 4.43 kW
Date last saved : 02 Feb 2019 7:59 PM NPSH required : 2.68 m

GENERAL PUMPS S.L. · Pol. Ind. El Oliveral (U.E.7, Nave n°1) - Calle W · 46394 Ribarroja del Turia · Valencia Spain,
phone: +34 96 1665200 · fax: +34 96 1665052 · www.pumpsgp.com
GENERAL PUMPS S.L. Quotation System 18.5.5

Multi-Speed Performance Curve


200
Performance based on test acceptance - ISO 9906:2012 3B
180

160

140

120
Head - m

100

80 2900 rpm

60
2610 rpm
2320 rpm
40 2030 rpm
1740 rpm
20
1450 rpm

6.0

4.5
Power - kW

2900 rpm

3.0 2610 rpm


2320 rpm
1.5 2030 rpm
1740 rpm
1450 rpm
0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Flow - m3/h
Customer : Size : GCR10-14 Flow, rated : 11.40 m3/h
Customer reference : Stages : 14 Head, rated : 100.0 m
Item number : 001 Based on curve number : LCR10-14-2-50 Speed : 2900 rpm
Service : Efficiency : 69.99 % Impeller dia. : 92.0 mm
Quantity :1 Power, rated : 4.43 kW Fluid density : 0.999 / 0.999 kg/dm3
Quote number : 716378 NPSH required : 2.68 m Viscosity : 1.00 cSt
Date last saved : 02 Feb 2019 7:59 PM Frequency : 50 Hz Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00
Nominal speed : 2900 rpm

GENERAL PUMPS S.L. · Pol. Ind. El Oliveral (U.E.7, Nave n°1) - Calle W · 46394 Ribarroja del Turia · Valencia Spain,
phone: +34 96 1665200 · fax: +34 96 1665052 · www.pumpsgp.com
GENERAL PUMPS S.L. Quotation System 18.5.5

Pump Performance - Additional Data


Customer : Quote number : 716378
Customer reference : Size : GCR10-14
Item number : 001 Stages : 14
Service : Speed : 2900 rpm
Quantity :1 Intellicode :
Date last saved : 02 Feb 2019 7:59 PM
Performance Data Stage, Speed and Solids Limits
Head, maximum diameter, rated flow : 100.0 m Stages, maximum : 14
Head, minimum diameter, rated flow : 100.0 m Stages, minimum : 14
Head max. : 144.4 m Pump speed limit, maximum : 2900 rpm
Efficiency adjustment factor, total : 1.00 Pump speed limit, minimum : 1200 rpm
Power adjustment, total : 0.00 kW Curve speed limit, maximum : 2900 rpm
Head adjustment factor, total : 1.00 Curve speed limit, minimum : 1200 rpm
Flow adjustment factor, total : 1.00 Variable speed limit, minimum :-
NPSHR adjustment factor, total : 1.00 Solids size limit : 0.0 mm
NPSH margin dictated by pump supplier : 0.00 m Typical Driver Data
NPSH margin dictated by user : 0.00 m Driver speed, full load : 2900 rpm
NPSH margin used (added to 'required' values) : 0.00 m Driver speed, rated load : 2900 rpm
Mechanical Limits Driver efficiency, 100% load : N/A
Torque, rated power, rated speed : 1.53 kW/1000 rpm Driver efficiency, 75% load : N/A
Torque, maximum power, rated speed : 1.54 kW/1000 rpm Driver efficiency, 50% load : N/A
Torque, driver power, full load speed : 1.93 kW/1000 rpm
Torque, driver power, rated speed : 1.93 kW/1000 rpm
Torque, pump shaft limit :-
Radial load, worst case :-
Radial load limit :-
Impeller peripheral speed, rated :-
Impeller peripheral speed limit :-
Various Performance Data Flow (m3/h) Head (m) Efficiency (%) NPSHr (m) Power (kW)
Shutoff, rated diameter 0.00 143.1 - - 1.67
Shutoff, maximum diameter 0.00 143.1 - - 1.67
MCSF - - - - -
Rated flow, minimum diameter 11.40 100.0 69.99 - 4.43
Rated flow, maximum diameter 11.40 100.0 69.99 - 4.43
BEP flow, rated diameter 10.53 109.2 70.54 2.28 4.43
120% rated flow, rated diameter 13.68 74.33 60.48 4.28 4.57
End of curve, rated diameter 13.00 82.02 64.93 3.70 4.47
End of curve, minimum diameter 13.00 82.02 64.93 3.70 4.47
End of curve, maximum diameter 13.00 82.02 64.93 3.70 4.47
Maximum value, rated diameter - 144.4 70.54 - 4.47
Maximum value, maximum diameter - - 70.54 - 4.47
System differential pressure @ Density, rated @ Density, max
Differential pressure, rated flow, rated diameter (bar) 9.80 9.80
Differential pressure, shutoff, rated diameter (bar) 14.02 14.02
Differential pressure, shutoff, maximum diameter (bar) 14.02 14.02
Discharge pressure @ Suction @ Suction @ Suction @ Suction
pressure, rated pressure, max pressure, rated pressure, max
Discharge pressure, rated flow, rated diameter (bar.g) 9.80 9.80 9.80 9.80
Discharge pressure, shutoff, rated diameter (bar.g) 14.02 14.02 14.02 14.02
Discharge pressure, shutoff, maximum diameter (bar.g) 14.02 14.02 14.02 14.02
Ratios
Maximum flow / rated flow, rated diameter : 114.04 % Head rated diameter / head minimum diameter, rated flow : 100.00 %
Construction
Orientation : Standard Curve Tolerance : ISO 9906:2012 3B
Construction Specifications : Standard

GENERAL PUMPS S.L. · Pol. Ind. El Oliveral (U.E.7, Nave n°1) - Calle W · 46394 Ribarroja del Turia · Valencia Spain,
phone: +34 96 1665200 · fax: +34 96 1665052 · www.pumpsgp.com
Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data Submittal Document


Model JP3
Across the Line Start
Jockey Pump Controller

Contents:
• Data Sheets
• Dimensional Data
• Wiring Schematics
• Field Connections

Note: The drawings included in this package are for controllers covered under our standard offering.
Actual AS BUILT drawings may differ from what is shown in this package.
SEISMIC COMPLIANT

August 2015
ICC-ES AC156
IBC 2015
CBC 2013
M

Technical Data
Model JP3 Jockey Pump Controller

JP3

SEISMIC COMPLIANT

ICC-ES AC156
IBC 2015
CBC 2013

Starting Method: Full Voltage


Across the line (Direct on line)
Typical Voltage Applied at Start: 100%
Inrush Current: 6 x normal load current
Starting Torque: 100%
Motor Type: Across the line (Direct on line)
No. of Contactors: 1 at 100% of horsepower
Min. ampacity of motor conductors: 3 at 125% x 100% of Full load Current (FLC)

Underwriters Laboratory (UL) UL508A - Industrial Pump Controllers


CSA CSA C22.2 No. 14 Industrial Control Equipment
New York City Accepted for use in the City of New York by the Department of Buildings
Listing
Seismic Certification See page 4 for details
Optional
□ CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
□ Standard: NEMA 2 (IP31)
Optional
□ NEMA 12 □ NEMA 4X-304 sst painted
□ NEMA 3 □ NEMA 4X-304 sst brushed finish
Enclosure □ NEMA 3R □ NEMA 4X-316 sst painted
□ NEMA 4 □ NEMA 4X-316 sst brushed finish
Accessories Paint Specifications
• Wall mounting lugs ( x4) • Red RAL3002
• Powder coating
• Glossy textured finish

August 2015 2
Technical Data
Model JP3 Jockey Pump Controller

• Main disconnect – rotary type - door interlocked


Fuseless Motor
• Thermo-magnetic motor protector
Starter
• Contactor
Control Circuit • 24V.AC
• Solid state controls
iPD+ Operator
• All adjustments on door front
Interface
• Navigation pushbuttons
• Pressure transducer for fresh water application 316 stainless steel construction
Pressure Sensing • Rated for 0-600psi working pressure
• Pressure sensing line connection ¼” Male NPT
• Manual motor start/run LED
• Automatic motor start/run LED
• Motor overload
• Pressure reading
• Start pressure
• Stop pressure
Visual Indications • System pressure
• System pressure diagnostic LED’s
• Green: system pressure at or above stop pressure
• Yellow: system pressure between start and stop pressure
• Red: system pressure at or below start pressure
• AUTO mode
• OFF mode
• Minimum run timer (off delay)
Timers • Delay start timer (on delay)
• Visual countdown
• Pump start counter
Counters
• Elapsed timer meter (hours / non-resettable)
• OFF-AUTO pushbutton
Operators
• Start and Stop pushbutton
Automatic Start Start on pressure drop

Manual Start Start pushbutton


Operation
Stopping Stop pushbutton
Field adjustable & • Minimum run timer (off delay)
Timers
visual countdown • Delay start timer (on delay)

August 2015 3
Technical Data
Model JP3 Jockey Pump Controller

Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 2014-0906-CO-001
A Tobalski Watkins Affiliate
Company
Mounting
Rigid wall mounting
details
Seismic
Building Test AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria
SDS z/h IP
Seismic
Information 2.0 1.0 1.5 3.20 2.40 1.33 0.53
IBC 2015, ICC-ES
CBC 2013 AC156
3.2 0.0 1.5 3.20 1.28 2.13 0.85

RRS for Nonstructural Components Testing


10.0
Spectral Response Acceleration (g)

1.0

0.1
0.1 1.0 10.0
Frequency, f (Hz)

Horiz. Level 1 Vert. Level 1

Note: Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2013. CBC compliance is not applicable to
OSHPD 1 & 4 buildings.

August 2015 4
Technical Data
Model JP3 Jockey Pump Controller

A5 Motor run alarm contact L01 Other language and English (bilingual)
A6 Loss of power alarm contact L02 French
A7 Overload or short circuit alarm contact L03 Spanish
D12 CE Mark c/w externally mounted wetted parts L04 German
D13A Externally mounted wetted parts L05 Italian
D14 Export packing for 1 controller L06 Polish
D18 Audible alarm L07 Romanian
D19 Anti-condensation heater and thermostat L08 Hungarian
D20 Anti-condensation heater and humidistat L09 Slovak
D21 Tropicalization L10 Croatian
D22 Phase reversal / failure pilot light and alarm contact L11 Czech
D23 Controller power healthy pilot light and alarm contact L12 Portuguese
Pump failure via current sensing relay with pilot light and dry L13 Dutch
D24
alarm contact
L14 Russian
D25 Low zone pump control function
L15 Turkish
D26 Mid zone pump control function
L16 Swedish
D27 High zone pump control function
L17 Bulgarian
D28 Selector switch in auto alarm contacts
L18 Thai
D29 Selector switch in off alarm contacts
L19 Indonesian
D30 Motor heater circuit
L20 Slovenian
Service entrance rated - 100kA short circuit withstand rating:
L21 Danish
• 120V/1ph (0.5hp max.)
• 240V/1ph (1hp max.) L22 Greek
D32 • 200V-208V - 60hz (2hp max.) L23 Arabic
• 220V-240V - 60hz (3hp max.)
• 380V-416V - 50hz - 60hz (5hp max.) L24 Hebrew
• 440V-480V - 60hz (5hp max.) L25 Chinese
Service entrance rated - 65kA short circuit withstand rating:
• 120V/1ph (0.5hp max.)
• 240V/1ph (1hp max.)
D33 • 200V-208V - 60hz (3hp-15hp max.)
• 220V-240V - 60hz (515hp max.)
• 380V-416V - 50hz - 60hz (7.5hp - 40hp max.)
• 440V-480V - 60hz (7.5hp-40hp max.)
Service entrance rated - 42kA short circuit withstand rating:
D34
• 600V - 60hz (7.5hp max.)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

August 2015 5
Technical Data
Model JP3 Jockey Pump Controller

iPD+ Operator Interface

3 2

4 7

HAND AUTO

5
8

1 - Power on LED 6 - STOP pushbutton


2 - System status LED 7 - Auto start LED
3 - Digital display 8 - Navigation keypad
4 - Hand start LED 9 - ON - OFF pushbutton
5 - START pushbutton

August 2015 6
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
NYC
Dpt of Building
Approved

Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY


A Model:JP3 2 IPD + R221B 23/01/14 Drawing No. A
Dimensions Built to the latest edition of the UL 508A & CSA C22.2 No.14 standard
3
4
Added Seismic Logo
Terminals and dimensions tables updated. Layout modified.
24/08/15
09/10/15
JP3-DI500/E

FU1 DS
B B
D

XTR1
F C

C C
Main Disconnect
G

Y
ON
R

OL1

OFF
HAND G G AUTO
C1

G DS

B E
D D

PT1
Underwriters
Laboratories Inc.
LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX
DANGER
Rating
E Label E
Standard Internal Layout
3
8 "[9] x4

Sensing Line Connection 1/4 " M.NPT


F F

Dimensions*
Maximum Motor Horsepower Enclosure Dimensions Door Dimensions Anchor Dimensions
200-208V 220-240V 380-416V 440-480V 575-600V AXBXC DXE FXG
G G
10HP 10HP 15HP 20HP 25HP 10- "X12- "
20HP 30HP 40HP 60HP 60HP

A
H H

Notes: Drawing for information only.


- Standard NEMA: NEMA 2
Manufacturer reserves the right to modify this drawing without notice.
- Standard Paint: Textured Red RAL 3002.
I - All Dimensions are in Inches [Millimeters] Contact manufacturer for "As Built" drawing. I
- Use Watertight Conduit and Connector Only. *Dimensions may change depending on option required. Consult Factory for exact Projection

- Protect Equipment Against Drilling Chips. dimensions.


- Door Swing Equal to Door Width
0 1 2 3 4 5 6 7 8
2015 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
NYC
Dpt of Building
Approved

Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY


A Model:JP3 2 IPD + R221B 23/01/14 Drawing No. A
Wiring schematic Built to the latest edition of the UL 508A & CSA C22.2 No.14 standard
3
4
Added Seismic Logo
Terminals and dimensions tables updated. Layout modified.
24/08/15
09/10/15
JP3-WS500/E

L1 L2 L3 PT1
Pressure Sensor
B Type 0-50mV B
G
DS G

Green
White
Black
Y

Red
R

B W G R 5 S

RESET
J5
HAND G G AUTO

PsIn-
PsOut-
PsOut+
PsIn+
OL1
C 34 33 7 C
9 IN1 J9
J21
G
IN2
OUTPUT ON J8

J19
A1
A2
OUT1 "IPD+"
D A1 D
OUT2 F5
A2
24Vdc

FU1 J2 J3 J1
XTR1
24Vac 24Vac
H2 X1 3 A2 A1
3 1 22 8
H1 X2
1
E E

A1 A2
C1

F F

G G

H H
OL1

C1

I
- Drawing for information only. I
G Manufacturer reserves the right to modify this drawing without notice.
T1 T2 T3
Contact manufacturer for "As Built" drawing.
P1
0 1 2 3 4 5 6 7 8
2015 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller
NYC
Dpt of Building
Approved

Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY


A Model:JP3 2 IPD + R221B 23/01/14 Drawing No. A
Line and Motor Terminal Size Built to the latest edition of the UL 508A & CSA C22.2 No.14 standard
3
4
Added Seismic Logo
Terminals and dimensions tables updated. Layout modified.
24/08/15
09/10/15
JP3-TD500/E

B B

Power Connections and Motor Connections

3 Phase
Incoming Power
Bonding Ground

C C

L1 L2 L3
DS

C1

D T1 T2 T3 D

E E

Line Terminals (L1,L2,L3,GND)


Maximum Motor Horsepower
Wire Size Copper Only Torque Wire Size Ground Copper Only
200-208V 220-240V 380-416V 440-480V 575-600V
10HP 10HP 20HP 20HP 25HP #14 AWG - #6 AWG 2 Nm #14 AWG - #2 AWG
F 20HP 30HP 40HP 60HP 60HP #12 AWG - #1 AWG 6 Nm #6 AWG - #2 AWG F

G G

Motor Terminals (T1,T2,T3,GND)


Maximum Motor Horsepower
Wire Size Copper Only Torque Wire Size Ground Copper Only
200-208V 220-240V 380-416V 440-480V 575-600V
5HP 7.5HP 10HP 15HP 20HP #14 AWG - #10 AWG 1.8 Nm #14 AWG - #2 AWG
H 10HP 10HP 15HP 20HP 25HP #14 AWG - #6 AWG 2.5 Nm #12 AWG - #2 AWG H
15HP 20HP 30HP 50HP 50HP #10 AWG - #3 AWG 5 Nm #12 AWG - #2 AWG
20HP 30HP 40HP 60HP 60HP #10 AWG - #2 AWG 11.3 Nm #12 AWG - #2 AWG

I I

0 1 2 3 4 5 6 7 8
2015 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
PRESSURE GAUGE HD FIRE PROTECT
PVT. LTD.

TECHNICAL DATA MODEL:HDP


MODEL HDP, HDP-1, HDP-2
DIAL SIZE HDP & HDP-1 - 90mm (3.5”)
HDP-2 - 100 MM (4”)
CONNECTION 1/4” BSPT (Standard Supply)
1/4” NPT (Optional)
RANGE HDP - 0 to16 Kg./Sq.Cm
& 0-250 PSI
HDP-1 - 0 to 21 Kg./Sq.Cm
& 0-300 PSI
HDP-2 - 0 to 21 Kg./Sq.Cm UL
& 0-300 PSI ®

LISTED
BURDON TUBE & HDP & HDP-1 - Phosphorus 40BN
WETTED PARTS Bronze Burdon Tube &
Brass moving parts
MODEL:HDP-1
HDP-2 - Monel
DIAL TYPE White background
black graduation scale
with dual reading in
Kg./ Sq.Cm and PSI
CASE AND BAZEL Polished Stainless Steel Case
with positive seal against
weather, moisture & dust.
HDP-2 is Glycerine filled.
MOUNTING Direct
WINDOW Hardened Glass UL
®

ACCURACY +/- 2% of FSD for LISTED


40BN
middle half of scale
WEIGHT (Approx) 0.3 Kg for HDP & HDP-1 MODEL:HDP-2
0.8 Kg for HDP-2
APPROVALS HDP - UL Listed
HDP-1, HDP-2 - UL Listed &
(FM Approved)
REFERENCE UL 393, NFPA-13
STANDARD FM CLASS NUMBER 2311
ORDERING Specify connection & Model
INFORMATION

DESCRIPTION UL
®
Pressure Gauges are specifically designed for Fire
Sprinkler Services. Model HDP & HDP-1 has corrosion LISTED
40BN
resistant polished stainless steel case and Bazel and
Brass wetted parts. Model HDP-2 is having Monel
internal and Glycerine filled for sea water application. gauge. Use PTFE tape around male threads of the
The dial has pressure reading in KG/SQCM and PSI. gauge for sealing. Pressure gauge must be mounted
The gauge window is hardened glass. in vertical position and isolated with valve or cock.
The pressure gauge must be handled with due care.
The pressure gauge must be mounted by square For best results , the storage as well as any further
provided for spanner grip on the socket and not by shipment be made in original packing only.
turning the case. Turning of case will damage the

NOVEMBER, 2015 PAGE 1 OF 2 HD 115


HD FIRE PROTECT
PVT. LTD.

The pressure gauge, which is visibly damaged, should CAUTION


not be installed. It is recommended that the
1) Do not over tighten the Gauge
pressure gauges must be inspected regularly for
possible corrosion or damage. 2) Do not tighten the gauge by holding dial.
Always use spanner to tighten.
The gauge must be periodically calibrated as per
requirement of NFPA/TAC or as per local authority Note: Pressure guages are mass calibrated, hence
having jurisdiction. individual calibration certificate in not provided.

31

6 8 10

12
100 150
4

Ø100
HD FIRE PROTECT PVT. LTD.

14
50 200
2

129
16
250 2
psi Kg/cm
AIR/WATER
0

PRESSURE GAUGE FOR


FIRE PROTECTION
LISTED
SERVICE
40 BN
MODEL - HDP

1/4" BSPT

HDP
31 47

150
150
20
0
10

10
0

20
0

8 12
10

10
0

14 8 12
6 14
6
Ø100

Ø108
HD FIRE PROTECT PVT. LTD.
16 HD FIRE PROTECT PVT. LTD.
4 16
4

132
250
50

129

18
250
50

2 18
2
20 Monel Bourdon
0 21 20
AIR/WATER 0 AIR/WATER 21
Kg/cm² PRESSURE GAUGE FOR

0 PRESSURE GAUGE FOR


FIRE PROTECTION
SERVICE Kg/cm²
LISTED
40 BN
FIRE PROTECTION
SERVICE
MODEL HDP - 1
FM
Psi 300 0
LISTED Psi 300
APPROVED 40 BN MODEL HDP - 2 FM
APPROVED

1/4" BSPT 1/4" BSPT


HDP 1 HDP 2
LIMITED WARRANTY
HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person
to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of
shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer’s warranty.
No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained.
HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer’s representatives.
HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is
found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly
or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured
by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any
damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire’s product liability exceed an amount equal to the sale price.
The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited
to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.

NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the
provision of government codes or ordinances wherever applicable.
The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope.
Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or
damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved with
the company.

D-6/2, ROAD NO. 34, WAGLE INDUSTRIAL ESTATE, THANE 400 604, INDIA.
HD FIRE PROTECT PVT. LTD. • TEL: + (91) 22 2158 2600 • FAX: +(91) 22 2158 2602
Protecting What Matters Most to You • EMAIL: info@hdfire.com • WEB: www.hdfire.com

NOVEMBER, 2015 PAGE 2 OF 2 HD 115


VENTURI FIRE PUMP FLOW SYSTEM

Line Pump Meter Range Meter Range Model Model Model Number Model Number
Size GPM Min. & Max. Min. & Max. Number Number 150# Flanged <Threaded>
GPM LPM Grooved Butt Weld *300# FLANGED*
**1-1/4” 25 12.5 – 50 47 - 189 * 1.25”-25-G 1.25”-25-B * 1.25”-25-F 1.25”-25-T

**2” 50 25 – 100 95 - 379 * 2”-50-G 2”-50-B * 2”-50-F 2”-50-T

**2-1/2” 100 50 - 200 189 - 757 2.5”-100-G 2.5”-100-B 2.5”-100-F *2.5”-100-F3

3” 150 75 – 300 284 - 1136 3”-150-G 3”-150-B 3”-150-F *3”-150-F3


3” 200 100 – 400 379 - 1514 3”-200-G 3”-200-B 3”-200-F *3”-150-F3

4” 250 125 – 500 473 - 1893 4”-250-G 4”-250-B 4”-250-F *4”-250-F3


4” 300 150 – 600 568 - 2271 4”-300-G 4”-300-B 4”-300-F *4”-300-F3
4” 400 200 – 800 757 - 3028 4”-400-G 4”-400-B 4”-400-F *4”-400-F3
4” 450 225 – 900 852 - 3407 4”-450-G 4”-450-B 4”-450-F *4”-450-F3

5” 450 225 – 900 852 - 3407 5”-450-G 5”-450-B 5”-450-F *5”-450-F3


5” 500 250 – 1000 946 - 3785 5”-500-G 5”-500-B 5”-500-F *5”-500-F3
5” 750 375 – 1500 1420 - 5678 5”-750-G 5”-750-B 5”-750-F *5”-750-F3

6” 500 250 – 1000 946 - 3785 6”-500-G 6”-500-B 6”-500-F 6”-500-F3


6” 750 375 – 1500 1420 - 5678 6”-750-G 6”-750-B 6”-750-F 6”-750-F3
6” 1000 500 – 2000 1893 - 7570 6”-1000-G 6”-1000-B 6”-1000-F 6”-1000-F3
6” 1250 625- 2500 2366 - 9462 6”-1250-G 6”-1250-B 6”-1250-F 6”-1250-F3

* DENOTES NON-
NON-STOCK ITEM, PLEASE CHECK WITH FACTORY FOR AVAILA
AVAILABILITY
**SIZES 1-1/4”, 2”, 2-1/2", & 14” ARE NOT FM APPROVED PER FACTORY MUTUAL**

8800 JEFFERSON HIGHWAY – OSSEO, MN 55369


PHONE (763) 391-0990 FAX (763) 391-7668 E-MAIL:chucksutton@msn.com