Sie sind auf Seite 1von 1

DOCUMENT NO.

BA4-MTB-E-CS-ECLPB-005
PT. BUKIT ASAM (PERSERO) Tbk. ELECTRICAL LOAD LIST
SWITCHGEAR/MCC : SUBSTATION 1
REV. DATE DESCRIPTION BY CHK. APR. PROJECT NO.
0 11/02/2015 Issued for Review OKT FRD FRD
1
2 -

At Load Factor Consumed Load

Utility Factor
Circuit Type
Load Type
Motor or
Absorbed
Equipment Tag Voltage Rating Data Validity Load Factor Full Load

Bus
Rev. No P&ID Number Description Load Eff. Power Factor Continuous Intermittent Standby Remarks
No. (Volt) Equipment Current (FLC)

kW kW Rev. Type Dec Dec A Cos α kW kVAR kVA A kW kVAR kVA A kW kVAR kVA A
SWITCHGEAR / MCC : SUBSTATION-1

MCC PANEL
1 FEEDER BREAKER 1 M VSD C 380 - 150.00 150.00 ME 1.00 0.90 297.91 0.85 166.67 103.29 196.08 297.91
2 HEAT EXCHANGE MOTOR 1 M DOL C 380 - 2.20 2.20 ME 1.00 0.90 4.37 0.85 2.44 1.51 2.88 4.37 Motor Drive changed from double to single by Mechanical Engin
3 CONVEYOR CV-21 M DOL C 380 - 110.00 110.00 ME 1.00 0.90 218.47 0.85 122.22 75.75 143.79 218.47
4 TRAMP IRON MAGNET & TROLLEY CV-21 M DOL C 380 - 9.00 9.00 ES 1.00 0.90 17.87 0.85 10.00 6.20 11.76 17.87
5 FEEDER BREAKER 2 M VSD C 380 - 150.00 150.00 ES 1.00 0.90 297.91 0.85 166.67 103.29 196.08 297.91
6 HEAT EXCHANGE MOTOR 2 M DOL C 380 - 2.20 2.20 ES 1.00 0.90 4.37 0.85 2.44 1.51 2.88 4.37
7 CONVEYOR CV-22 M DOL C 380 - 110.00 110.00 ME 1.00 0.90 397.21 0.85 222.22 137.72 261.44 397.21 Motor Drive changed from 200 to 110kW
8 TRAMP IRON MAGNET & TROLLEY CV-22 M DOL C 380 - 9.00 9.00 ES 1.00 0.90 17.87 0.85 10.00 6.20 11.76 17.87
9 CONVEYOR CV-23 A M DOL C 400 - 315.00 315.00 ME 1.00 0.96 559.52 0.85 329.50 204.20 387.64 559.52
10 DUST SUPPRESSION PUMP A M DOL C 380 - 75.00 75.00 ES 1.00 0.90 148.96 0.85 83.33 51.65 98.04 148.96
11 DUST SUPPRESSION PUMP B M DOL S 380 - 75.00 75.00 ES 1.00 0.90 148.96 0.85 83.33 51.65 98.04 148.96
12 SPARE 01 F - S 380 - 315.00 315.00 ES 1.00 1.00 563.05 0.85 315.00 195.22 370.59 563.05
13 SPARE 02 F - S 380 - 9.00 9.00 ES 1.00 1.00 16.09 0.85 9.00 5.58 10.59 16.09

TOTAL 1115.50 691.32 1312.35 1964.46 0.00 0.00 0.00 0.00 407.33 252.44 479.22 728.09

NOTE Description Continuous Intermittent Standby


Load Type = M (Motor), F (Feeder), and O (Other / Package) Total (kW/kVAR/kVA/A) 1115.50 691.32 1312.35 1964.46 0.00 0.00 0.00 0.00 407.33 252.44 479.22 728.09
Circuit Type = DOL (Direct Online), FR (Forward Reverse), YD (Wye-Delta), SS (Soft Starter), and VSD (Variable Speed Drive) Power Factor 0.85 0.00 0.85
Utility Factor = C (Continuous), I (Intermittent), and S (Standby) Total Rated kW 1022.40 0.00 399.00

Normal Load / Average Load = (1.00 x Total Continuous Load) + (0.50 x Total Intermittent Load) LOAD SUMMARY
Peak Load = Normal Load + (0.10 x Total Standby Load) Normal/Average Load = 1115.50 kW 691.32 kVAR 1312.35 kVA 1964.46 A
Demand Load = Peak Load + (Peak Load * 0.20) Peak Load = 1156.23 kW 716.57 kVAR 1360.27 kVA 2037.27 A
Demand Load = 1387.48 kW 859.88 kVAR 1632.33 kVA 2444.73 A