FC901 FC2005
Building Technologies
Fire Safety & Security Products
FC2005/FC901 installation instruction
Accessories and separate parts
Accessory
items Content Installation instruction Qty
2.1
2 Cable between batteries and main board, refer to figure 1,figure 2 1
2.3
2.2
3.2
3.1 3.3
3 Cable between City tie board and main board, refer to figure 2 1
Earth cable between enclosure and main board, refer to figure 1 and
4 4.2 figure 2 1
4.1
8 Cable ties 10
Note: Item 3,6,7,11,S1and S2 are not delivered with the FC901 and FC2005.And should be ordered separately.
Assembling notes
1. Mount the batteries with battery brackets.
2. Mount the power supply MOV, then mount the power supply to the enclosure.
3. Mount the City tie module onto the main board according to the Figure 2 (City tie module is optional).
(The power supply input cable and output cable are not included in the FC901 and FC2005 package).
4. Tie the cables to the enclosure with cable tie, refer to the Figure 1(Cable tie features).
5. Mount the Main board assembly onto the Enclosure according to Figure 3.
6. Mount the Lock pin to the Front door axis(Both are included in the Enclosure package)
Building Technologies Document ID: A5Q00039713A FC2005/FC901 installation instruction
Fire Safety & Security Products Page 1/12 02.2012
FC2005/FC901 installation instruction
Battery, Power supply and City tie PCB assembly installation instruction
Pay attention to the battery polarity at 2.1 and 2.2
Detail A
5.1(2)
Cable tie feature
S2
Brownout 5.2(2)
Power supply
9
7
6 S1
S3
11
3.1 Detail B
4.2
3.2
10
2.3
From 1 to 4
From left to right: TP1295,TP1294,TP1293,TP1292
TP1295,TP1294,TP1293,TP1292
1
2
3
4
3.1
X2 Output 2 X3 Output 1
Connect to 3.2 Connect to 3.3
Detail C
S5
- N_BN
+N_BP
- N_AN
+ N_AP
5 7/64”
18 1/8”
CerberusTM
16 ½”
8 1/4”
4 1/4” MAX
21 1/4”
CerberusTM
19 5/8”
8 1/4”
A_NO
A_CO
A_NC
Relays
U_NO
U_CO
U_NC
S_NO
S_CO
S_NC
Battery connector
DACT
DACT
PORT2
DACT
Notification Application
N_AP
Circuits(NAC)
N_AN
N_BP
N_BN
LL_SP
City tie or
lease line
LL_SN
CT_P
CT_N
EARTH
Series interface circuit
PR_B
PR_A
GND1
EARTH
SE_B
SE_A
GND1
Auxiliary power
X1_P
X1_N
X2_P
X2_N
S_AP
S_AN
EARTH
SLC loop
S_BP
DC power input
6.5A@26VDC
S_BN
EARTH
Note: All the wiring must be in according with local codes and National Electric Code.
Class A Class B
50 max devices
...
...
to the shield (if used)
0.07A@6-32 VDC
50 max devices
...
shield (if used)
0.07A@6-32 VDC
0.07A@6-32 VDC
EARTH
EARTH
EARTH
EARTH
S_BN
S_AN
S_BN
S_AN
S_BP
S_AP
S_BP
S_AP
Auxiliary power
Non supervised and power limited
Conventional detectors
+ +
- - 24V
applicance
Normal 0.05A @19-28VDC
Alarm 0.75A @19-28VDC
Normal 0.05A @19-28VDC
Alarm 0.75A @19-28VDC
Power -
Power +
Max. current= 0.75A
X1_N
X2_P
X1_P
FSD
8 FSD max
FSD
FSD
GND1 (Reserved)
GND1 (Reserved)
EARTH
EARTH
PR_A
PR_B
SE_A
SE_B
LL_SP
CT_N
CT_P
0V Trouble (OUTPUT 1)
-26VDC Supervisory (OUTPUT 2)
External Circuit Resistance 2K-5K ohms
M unicipal Tie Voltage 350mA@26VDC Active(19-28VDC on Battery)
+26VDC Normal & 1mA Supervisory Current
350mA Alarm@+26VDC
M unicipal Tie Trip Coil 14.5 ohms
M unicipal Tie Supervisory Current 1mA
N_AN
N_BP
N_AP
(Primary Lines Incoming Telco Phone Lines) (Secondary Lines Incoming Telco Phone Lines)
Ring Ring
Tip Ring Tip Ring
To premises phones To premises phones
Tip Tip
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
RJ31-X RJ31-X
Jack Jack
Secondary Phone line
PORT1
DACT
DACT
Relays
Non power limited, 2.0A@30VDC(Resistive), 0.5A@30VAC(Resistive)
U_NO
A_CO
A_NO
S_CO
S_NO
U_NC
A_NC
S_NC
T_CO
T_NO
T_NC