1 2 3 4 5 6 7 8 9 10 11 12

CLASS B GATIC COVER DISCHARGE PIPE GRADED TO


NOTES: AND SURROUND. AUTHORISED DISCHARGE POINT
A 1. BURIED FLANGES, BOLTS, NUTS ETC. ARE TO BE CLEANED AND PRIMED WITH A
(MIN. OPENING 600x600) (MIN SIZE = 1.5 x INLET DIA.)
PETROLATUM PASTE AND WRAPPED WITH A DOUBLE LAYER OF PETROLATUM
MARKER POST IMPREGNATED SYNTHETIC CARRIER TAPE PRIOR TO BACKFILLING.
(REFER: WSS-016)
2. ALL BOLTS, NUTS AND WASHERS TO BE HOT DIP GALVANISED IN
ACCORDANCE WITH AS 1214 AND AS/NZS 4680.

3. DEPTH OF OUTLET PIPE IS SITE/ LOCATION DEPENDENT.

PRE-CAST CONCRETE OR 4. THIS DRAWING IS TO BE READ IN-CONJUCNTION WITH WSS-016 AND

=
RECYCLED PLASTIC SURROUND WSS-024.
AND CAST IRON VALVE BOX 150
(REFER: WSS-024) 5. REFER TO THE TABLE ON THIS DRAWING FOR SIZING AND ENSURE SCOUR
B B
CONNECTION IS WITHIN 50 METERS OF PUMP SCOUR CHAMBER.
F.S.L.
6. FOR CHAMBER DEPTHS GREATER THAN 3.0m REFER TO THE ICON WATER

1800 SQ.
PRINCIPAL ENGINEER FOR GUIDANCE.

VALVE KEY SHAFT 7. ALL PIPE PENETRATIONS THROUGH THE CHAMBER WALL ARE TO BE SEALED
RISER AND BLOCK SUPPORT WITH AN APPROVED WATERSTOP (e.g. HYDROTITE). A A
(REFER: WSS-016)
SCOUR TEE 8. THRUST BLOCKS NOT REQUIRED FOR FULLY RESTRAINED (e.g. FLANGED)
PIPE.

=
C C

SCOUR OUTLET PIPEWORK SIZING SCHEDULE


SCOUR FLOW TO MAINS DIA. (DN) SCOUR VALVE (DN) TEE (DNxDN) OUTFALL PIPE (DN)
THRUST BLOCK
AUTHORISED
(REFER WSS-014) OUTFALL 150-200 80 80x80 80
DISCHARGE POINT
PIPE ON FALLING GRADE
OR SCOUR CHAMBER 225-300 100 100x100 100
SCOUR VALVE (NOTE 3)
(REFER TABLE ON 375-600 150 150x100 100
THIS DRAWING FOR SIZING)
CAST IRON SURFACE
PUMP SCOUR CHAMBER
750 225 225x150 150 25 IN URBAN AREAS SCALE: 1 : 10 CONCRETE SLAB
BOX FOR SV
SCOUR CONNECTION TYPE A 100 IN RURAL AREAS PRE-CAST OR CAST IN-SITU
SCALE: 1 : 10
D D

600 MIN. COVER


50
EXTENSION
SPINDLE TO

500
WSA PS-262
NON TRAFICABLE AREAS: TRAFFICABLE AREAS: MARKER POST
WEBFORGE GALV. STEEL "C SERIES" PRE-CAST CONCRETE OR CAST IRON (REFER: WSS-016)
GRATING, PADLOCKABLE C/W KEEPER (CONCRETE INFILL) COVER WITH VERTICAL RUNG LADDER
PLATES (REFER DETAILS ON WSS-079) LOAD (CLASS) RATING TO SUIT C/W EXTENDABLE STANCHIONS
E LOCATION (REFER WSS-002 AND WSS-023) E
25 IN URBAN AREAS EXTENSION SPINDLE
100 IN RURAL AREAS SUPPORT BRACKET
F.S.L.
PRE-CAST OR
CAST IN-SITU MAINTENANCE SHAFT
PRE-CAST REINFORCED AND BASE. MIN. INTERNAL DIA. 1200
CONC. RISER 50 MIN. AND MIN. WALL THICKNESS 150

3000 MAX (NOTE 6)


900 MAX.

150 MAX.
MIN. SIZE: 750 OR 750 SQ. VALVE KEY SHAFT RISER (REF. WSS-016)
MAX. SIZE: 900 SQ.
PUDDLE FLANGE

500
(FACTORY FITTED)
50

F SELECTED COMPACTED FILL F


TO UNDERSIDE OF CHAMBER
"ROCKER" PIPE
20 STONE OR GRAVEL L=400 MIN. TO 600 MAX.

TEE GATE VALVE


(REFER TABLE ON THIS SCOUR FLOW TO
RESILIENT
DRAWING FOR SIZING) AUTHORISED
SCOUR VALVE SEALED
DISCHARGE POINT
SCOUR TEE (REFER TABLE ON OR SCOUR CHAMBER FLOW FROM TYPE A
THIS DRAWING
OUTFALL SCOUR CONNECTION

300 MIN.
FOR SIZING) 150
PIPE ON FALLING GRADE (NOTE 5)
GIBAULT MIN.
(NOTE 3) COUPLING
G RISER TO SUIT G

THRUST BLOCK
(REFER WSS-014)
SCOUR CONNECTION TYPE B SECTIONAL ELEVATION A-A
SCALE: 1 : 10
SCALE: 1 : 10

Drawn: Date: Drawing Type:


M. Matusiak 27/07/2016 STANDARD DRAWING
Designed:
K. Danenbergsons
Standard Drawing
WATER MAINS DN100-DN750
Engineering Drawing Status:
I. McRae
H A ISSUED FOR USE AND TRANSITION TO WSAA CODES 28/10/2016 I. McRae P. Language
Checked:

Verified:
4/11/2016
Current H
No. DESCRIPTION DATE ENG CHECKED VERIFIED DESIGN AUTH
SCOUR INSTALLATIONS
Rev
The information contained within this drawing & associated electronic file shall remain the property of Icon Water and shall not be copied or used for any other
purpose without express written permission from Icon Water. © Icon Water. 2016
Design
Authority: P. Language 9/11/2016
GENERAL ARRANGEMENTS AND DETAILS A1 WSS-071 A
1 2 3 4 5 6 7 8 9 10 11 12