Sie sind auf Seite 1von 6

Projukti Global Limited

38/1, Indira Road (3rd & 4th floor), Dhaka- 1215


Phone:+88(02)9121000, 8128777,9133999
hassan/info@projuktiglobal.com

To
The Managing Director
UTTARA GROUP
Project: Uttara Motors Assembling Plant,
256, Tejgaon I/A, Dhaka
Date: 03.02.2015
Kind. Attn.: A.T.K.M. Ismail (Former secretary, GoB) Validity: 03.03.2015
Projector Director, Quotation# PGL-1584
Uttara Properties Ltd.

Subject: Offer of Supply inatallation Testing and Commissioning of Fire Hydrant System

Sl. Description of Items Amount in


No. QTY Unit Rate in TK.
Tk.
1 FIRE
Motor PUMPS
driven:
1.1
Supply & Installation of Electrically driven Pump for fire fighting
system use shall be complete with mounting, coupled motor etc.
complete. The pump shall be minimum 60% efficient. Impeller
speed shall not be more than 2,900 rpm. Power supply shall be 400
V/3 phase/50Hz. The pump shall have a capacity to handle 500 US
GPM of water against a head of 80 meter of water. Pump shall be
operated on pressure signal from pressure switch. Checking,
carrying and Installation of motor driven fire pump shall be as per
drawing and direction and recommendation of manufacturer. 1 Nos 595,000.00 595,000.00
Foundation works shall be done by for other contractor as per
direction. Suction and delivery connection to the pumps shall be
with proper size of adapter. Water, electrical and control wiring shall
be done as per recommendation and drawing. Pump assembly shall
be properly aligned. Base shall be provided with drain.Capacity of
Pump Minimum 85 BHP / 63 KW. Ebs-ray Streamline centrifugal
end suction pump. TECO Motor. Model: 65-26

Country of origin: Australia


1.2 Diesel Engine Driven :
Supply of diesel engine driven fire pump to handle a capacity of 500
GPM of water against a total head of 80 m, but the brake horse
power capacity of the engine is of 10% higher than maximum
required. the pump shall be minimum 60% efficient.Built-in
adjustable governor rated at pump speed & load, over speed shut
down device, with all gages, free battery and battery charger, wiith 1 Nos 1,345,000.00 1,345,000.00
residential type silencer for reducing noise and exhaust along
controller and all protections and parameters in all respect.
Motor : Speed 2900 rpm, 50 Hz, 3 Phases, Capacity of pump
Minimum 85 BHP / 63 KW. Engine: MAC, Model: MD4102

Country of origin: Malaysia,


1.3 Jocky Pump

1 Nos 155,000.00 155,000.00

Fire Hydrant System


Sl. Description of Items Amount in
No.
1.3
QTY Unit Rate in TK.
Tk.
Supply, Installation, Testing & Commissioning of Multistage jockey
pump for fire fighting hydrant system to keep a certain pressure in
water distribution system. Capacity of the pump shall be 20 GPM
against a head of 80 meter of water. Pump shall be complete with
pressure switch, pump motor, starter, base plate etc. complete.
Power supply shall be 400V/50Hz, 3 phase. Checking, carrying and
Installation of Jockey pump shall be as per drawing and direction.
Foundation work for the pump shall be done by other contractor as
1 Nos 155,000.00 155,000.00
per direction. Suction and delivery connection to the pumps shall be
with proper size of adapter. Water-piping, electrical-power and
control wiring shall be done as per recommendation and drawing.
Pump assembly shall be properly aligned. Base shall be provided
with drain. Jockey pump shall maintain a constant pressure in the
piping system.Pump capacity of Pump Minimum 18 BHP, Model:
EMVI 414

Country of origin: Australia

Fire Hydrant System


Sl. Description of Items Amount in
No. QTY Unit Rate in TK.
Tk.
1.4 Fire Pump Control Panel
Supply, installation, testing and commissioning of control panels for
operation of fire fighting pumps (item 1.1) and jockey pump (item
1.2). The control panel shall have the facility to operate the pumps
automatically and manually. Automatic starting and stopping of Fire
Pumps and Jockey Pump shall be by sensing water pressure in the
pump header. The panel shall be constructed of 16 SWG mild steel
sheets and appropriately painted with two coats of approved quality
and colour of paint over a coat of primer. It shall house circuit
breakers (MCCB/MCB), AUTO-OFF-MANUAL switches, duty pump
selection switches, fuses, star-delta starters for Fire Pumps and
DOL starter for Jockey Pump, relays, pressure switches with
sensors, incoming contacts for float switches with sensors, volt-
meters, ammeters, alarm horn, panel heater and all other standard
accessories.The unit shall be UL listed/FM approved.

a) Electric Fire Pump Control Panel


b) Diesel Engine Fire Pump Control Panel 1 Set 250,000.00 250,000.00
c) Jockey Fire Pump Control Panel
2 PIPE ACCESSORIES (Foreign, Local Procurement):
Pipe accessories such as gate valves, globe valves, check
valves,PRV strainer, expansion joint etc. shall be suitable to with
stand a pressure of 250 psig. Valves of 100mm dia and above shall
be of iron body, flanged end type complete with companion flanges,
gaskets, nuts bolts etc. and valves, less than 80mm dia shall be
bronze body, threaded end type.Installations of pipe accessories
such as gate valves, globe valves, check valves,PRV strainer,
expansion joint etc. shall be as per drawing and direction. Proper
size of flanges with gasket nut-bolt shall be used. Valve installation
shall be leak proof type. Each pipe accessories shall be provided
with support, bracket or hanger so that there is no load on pipe
work. Handle of the valves shall be positioned in such a way that
operation shall be easy. If required Valve pit for service valve for
under ground pipe installation shall be done as per direction. Valve
pit shall be provided with cover and drainage system.Testing &
Commissioning of Pipe accessories such as gate valves, globe
valves, check valves, strainer, expansion joint etc. shall be as per
drawing and direction.

2.1 OS & Y Gate Valve


Gate valve shall be anti corrosive cast iron body type for 65 mm dia
and above with internal movable parts in bronze. Valve upto 50 mm
dia shall be welded socket gate type complete with companion
flanges, nut-bolt, gasket etc.(SRI / Malayasia)

a) 150mm dia 4 Nos 35,200 140,800


b) 65mm dia 0 Nos 10,000 0
c) 50 mm dia 2 Nos 9,000 18,000
d) 40 mm dia 0 Nos 0
2.2 Globe Valve 0
Globe valve 50 mm dia and smaller shall be bronze body, screwed
bonnet, rising stem, swivel disc and valve 65 mm dia and larger
shall be iron body, bolted bonnet, outside screw and yoke, rising 0
stem, bevelled wedge disc and flanged end type complete with
companion flanges with nut-bolt, gasket etc.
a) 150 mm dia 0 Nos 0
b) 65 mm dia 0 Nos 0

Fire Hydrant System


Sl. Description of Items Amount in
No. QTY Unit Rate in TK.
Tk.
2.3 NON RETURN VALVE: 0
Non-Return valves shall be re-grind able seat, screwed cap, lift type
disc, integral seal and flanges.(SRI / Malayasia) 0

a) 150mm dia 2 Nos 21,500 43,000


b) 65mm dia 1 Nos 9,500 9,500
2.4 FLEXIBLE PIPE JOINT: 0
Flexible joint shall be durable (Heavy duty) suitable to absorb shock
and system hammering and to reduce vibration transmission. Nos 0
Flexible joint shall be moulded neoprene.(SRI-Malasia)
a) 150mm dia 4 Nos 17,800 71,200
b) 40 mm dia 2 Nos 4,000 8,000
2.5 AIR VENT VALVE: 0
Automatic vent valve shall be free floating type having test cock,
20mm threaded outlets to accept drain line and threaded inlet 0
connection. Vent valve shall be 20mm size.(SRI-Malasia)
a) 20mm/25mm dia 1 Nos 2,800 2,800
2.6 Ball Valve 0
Ball valves shall be socket ball type complete with socket, nut-bolt 0
etc.(Korea)
a) 65mm dia 0 Nos 8,500 0
b) 50 mm dia 0 Nos 0
c) 40 mm dia 0 Nos 0
2.7 FOOT VALVE: 0
Foot valve shall be lift check type and shall be with strainer.(Korea)
0
a) 150mm dia, China 1 Nos 16,000 16,000
2.8 Y-STRAINER: 0
Supply, fitting, fixing and testing of Y-Strainer of cast iron/high grade
steel with stainless steel strainer. The screen shall have required
size and number of meshes. The Y-Strainer shall be flanged end
type complete with companion flanges, gaskets, nuts and bolts etc
and shall be suitable to withstand a working pressure of 200 psig 0
and shall be installed as per drawing, specifications and direction of
the Engineer-in Charge(Sri-Malasia)

a) 150mm dia 1 No 21,000 21,000


b) 65 mm dia No 7,200 0
2.9 PRESSURE SWITCH:
Pressure switch shall be complete with water pressure sensor,
pressure transmitter, mountings, tubing, electro-pneumatic switch 0
etc. complete. It shall sense pressure of water in pipe and operate
pump motor.
a) 150mm dia 1 Nos 2,500 2,500
2.10 PRESSURE RELEASING VALVE
Supply, installation and testing of Pressure Reducing Valves for
adjusting and maintaining outlet pressure to between 100 psig to 75
psig when inlet pressure varies from 250 psig to 100 psig. The Unit
shall have pressure relief connection in order to bypass pressurized
0
water in case of excessive pressure rise in the line. The valves shall
be complete with all control accessories. The unit shall be installed
as per drawings, specification and direction of the Engineer-in-
Charge. Valves shall be UL listed/FM approved.(SRI-Malasia)

a) 65 mm dia 1 Nos 13,000 13,000

Fire Hydrant System


Sl. Description of Items Amount in
No. QTY Unit Rate in TK.
Tk.
3 METERING DEVICE & CONTROLS:
Supply, Installation, Testing & Commissioning of Metering devices
shall be as per drawing and as per direction and shall be completed
with all mounting accessories. Installation of pressure gauge shall 0
be as per drawing and direction. Adapter, nipple, union, pressure
snowber, petcock etc. shall be supplied and installed as per
direction and drawing. Installation shall be easy to read the meters.

3.1 PRESSURE GAUGE:


Pressure gauge shall be of dial type of 100mm dia suitable to read
0 to 10 Kg/mm sqr. pressure. Pressure gauge shall be completed 6 Nos 2,500 15,000
with petcock, pressure snowbar, nipple etc.
5 0
5.1 40 mm Fire Hydrant:
Supply of 40 mm dia fire hydrant complete with nozzle, 30 meter
hose reel pipe of dia 40mm, swing type rack wheel, couplings, 16
BWG steel casing, 40mm dia landing valve, hand control nozzle etc.
complete. Installation, Testing & Commissioning of 40mm dia fire
hydrant complete with nozzle, 30 meter hose reel pipe of dia 40mm, 6 nos 42,500 255,000
swing type rack wheel, couplings, 16 BWG steel casing, 40mm dia
landing valve, hand control nozzle etc. complete. Installation of
40mm dia fire hydrant complete with all imported items shall be as
per drawing and direction.

6 PIPE WORK :
Supply and Installation of black steel pipe of welded type suitable to
withstand a test pressure 15 kg of water complete with bends, tees,
elbows, reducers, socket, union etc. as per drawing and
direction.Cutting of pipe welding, threading and sealing the thread
with proper type of sealing compound shall be done leak proof. Pipe
work along with fittings shall be suitable to withstand a test pressure
of 15 Kg/cm². Required flanges shall be provided in main pipe as
per direction. All Pipe including M/S. materials including outside of 0
Black steel pipe work shall be provided with two coats of cold
galvanisation after proper cleaning. All underground pipes shall be
protected with black tape wrapping. Earth cutting, filling with sand
cc pipe support at an interval of 3 meter shall be done for out door
underground pipe work. All pipe work shall be completed with
support, bracket etc. complete as per drawing and direction. 20
Schedule. ( lengths mentioned are re-measurable) (Korea)

6.1 150mm dia (6") 60 Rft 1,450 87,000


100mm dia (4") 140 Rft 880 123,200
6.4 50mm dia (2") 400 Rft 350 140,000
6.7 25mm dia (1") 20 Rft 180 3,600
8 FIRE BRIGADE CONNECTION (Imported):
Fire Brigade Connection of 150mm dia with four connections of
65mm dia each and shall be completed with non-return valve, valve
cap, chain, purging valve etc. Installation, Testing & Commissioning
of Fire Brigade Connection of 150mm dia with four connections of
65mm dia each and shall be completed with non-return valve, valve 0
cap, chain, purging valve etc. Installation of Fire Brigade
Connection shall be done on standpipe suitable to operate by Fire
service people.(SRI-Malasia)

a) Two Way Connection 1 Nos 18,000.00 18,000


9 ELECTRICAL CABLE WORKS (Local):

1 Lot 40,000 40,000

Fire Hydrant System


Sl. Description of Items Amount in
No. QTY Unit Rate in TK.
9 Tk.
Supply and Installation of single/multi core PVC insulated, PVC
sheathed electrical cable of copper conductor of following size as
per drawing & direction. The work shall be complete with water
grade PVC conduit, required ECC, conduit bends, tees, junction
1 Lot 40,000 40,000
box, pull box etc. complete as per direction and standard. Cutting of
walls floor, roof etc. mending good the damage shall be as per
direction. The Authority shall supply required power up to pump
house. Cable shall be Eastern/Paradise/ Poly Cable.

10 ERECTION, TESTING & COMMISSIONING :


After proper installation the system shall be tested and
commissioned as per direction and recommendation. Pipe work
shall be tested at a test pressure of 15 kg/cm² for 24 hours without 1 Job 200,000 200,000
any leak. After proper testing and commissioning the system shall
run for seven days upto the satisfaction of the Owner.