Sie sind auf Seite 1von 4

CHAPTER 9

Pipe Hanging

W ITHOUT pipe hangers to support sprinkler piping, there


is no fire sprinkler system. Hangers are every bit as
important to the overall physical system as are fittings, pipe,
The job specification for a U.S. government-specified project
that I was recently involved with required the following rod
sizes for fire sprinkler pipe hangers:
and valves. A common blunder made by the beginning de-
signer is to ignore this fact completely. As a result, his plan Pipe to Be Supported Rod Size
may show routed piping depicted in an area where there is  
1 through 2 3/8
nothing of any structural strength from which to hang pipe.
2 1/2 1/2
Hence, the designer must always be cognizant of his strategy
3 1/2
for pipe hanging on a given project and how that will affect
4 5/8
his system design.
Referring to the Figure A-2 project example, we can see
that we have planned to hang the cross-main directly beneath This specification can aptly be called “overkill.” While the
a bar-joist, running the cross-main in the same direction as individuals who scripted these requirements openly admitted
the bar-joist. This has been done for the following reason: the doing so only because of a desire for conservative measures,
branch-lines (which always run perpendicular to the main the NFPA standards are what normally must be adhered to.
piping) must always run perpendicular to the bar-joists for These requirements, as outlined in Sections 6-1 and 6-2 of
reasons of economy. In our case, the branch-line piping will NFPA Pamphlet No. 13, require hangers and rod sizes of 3/8
be hung (see Figure G-1) by means of a top-beam clamp, for the above-captioned pipe sizes, and 1/2 hanger and rod
3/8 threaded rod, and a standard swivel-ring. This is the same for 6 and 8 nominal pipe sizes. In general, each section
hanger type which will be used to hang the cross-main piping, of branch-line piping shall have a hanger. For cross-mains,
and is a relatively inexpensive hanger. It is also a simple, there shall be at least one hanger between each branch-line.
labor-saving, hanger to physically install. The clamp affixes The distance from the end-sprinkler on any branch-line and
easily to the top of an ordinary bar-joist (or beam), and holds the last hanger shall not exceed 3 for 1 pipe, 4 for 1 1/4
the hanger rod securely in place to support piping in reliable pipe, and 5 for 1 1/2 and 2 pipe. The length of an armover to
fashion. Suppose that the cross-main ran in some location in a sprinkler-head shall be equipped with an additional hanger
between two bar joists. Then some type of hanging method if it is in excess of 2 for any size steel piping.
would have to be utilized. One such “spanner” type hanger in
depicted in Figure G-2. Material-wise, this is a considerably ***
more expensive hanger, mainly due to the expense of the These NFPA requirements are not only field-proven, but
unistrut, or whatever material is used to make the long span they have been mandated by code for such a long time that
between roof joists for support. Labor-wise, the installation the materials provided by hanger manufacturers and suppliers
of this hanger eats up quite a bit of field time to add to the are now appropriately standardized. For example, if you were
job expense. Although it is necessary to utilize the spanner to purchase a 4 swivel-type pipe ring, you can rest assured
or “trapeze” hanger in some installations, it is the designer’s that it will be equipped with a nut that accepts a 3/8 threaded
responsibility to try and lay out his system so that the use of rod. Similarly, the nut on a 6 swivel ring will be provided
the spanner-type hanger is eliminated or at least minimized. for 1/2 rod attachment.

‹1E\&5&3UHVV//&
NFPA #13 provides an illustrated prospectus of “ap- than 1 1/2 . Also, hanging from hollow tile is okay, but
proved” hanger types. In the 1999 edition, these are shown hanging from gypsum wallboard is not permitted.
on page 210. The reality of pipe installation, however, is that (5) Strongly consider the use of some alternative type of
the fitter is responsible to securely fasten piping to building light-weight piping in the areas where the toggle hangers
structural members, and the means by which he does so is not are to be utilized.
going to be questioned provided that the end result of secure
fastening without exceeding ordinary load requirements is A field installation time-saver is the engineered “cut” hanger
accomplished. The designer’s real job is to route his pipe so rod. These can be easily figured on any typical sprinkler job.
that something actually exists that the piping can be affixed In our project example, top-beam clamps are to be used (see
to dependably, and that affixing or hanging can be done in Figure G-1). In this case, the top of the hanger rod is installed
quick and inexpensive fashion. at an elevation about even with the underside of the roof
Figures G-3 thru G-8 show typical means by which sprin- deck. Hence, there is no take-out to be made on the hanger
kler piping is hung, and I would say that these, along with rod except for that of the swivel ring itself. The take-outs to
the top-beam clamp, cover about 99% of all sprinkler pipe be used for pipe rings by the design engineer are as follows:
hangers installed today. Any hanger manufacturer, such as
Elcen, Persing, or ITT Grinnell, publishes pamphlets and cat-
alogues illustrating their complete line of available hangers. Pipe Size Swivel Ring Take-Out

You would do yourself a favor by thumbing through one of 1 1 1/2
these to become familiar with hanger options that are avail- 1 1/4 1 1/2
able for unusual situations. One such hanger that sprinkler 1 1/2 2
contractors like to stock is the extension C-clamp, which 2 2
is a top or bottom-beam clamp that is of such width that a 2 1/2 2 1/2
hanger can be affixed at a spot a few extra inches further 3 3
from a joist or beam. If these hanging devices are on hand 3 1/2 3
in the field, they often solve a hanger problem for the fitter 4 3 1/2
in certain instances without much expense. The bulk of the 5 4
other out-of-the-ordinary hangers on the market, however, 6 5
are usually more expensive and generally reserved for use in 8 6
unique situations where typical hanging methods cannot be
used. So, in our project example, were we to shop cut hanger
rods for field use, we would simply subtract the appropriate
*** take-out figures from the known distance between the roof
It should be understood that the toggle-type hangers (see deck and the sprinkler piping to figure the desired lengths. We
Figure G-10) should only be used as a last resort. The only know that our branch-line piping is to hang, at a centerline,
time that I have heard of a problem with sprinkler piping 10 beneath the underside of the roof deck. So, 8 and 8 1/2
actually falling down due to insufficient hanger support was rod length should be shipped to the job for the branch-line
when toggles have been involved. It is generally recognized hangers. And since our 3 cross-main pipe will hang 30
that a metal lath and plaster ceiling is good support for sprin- down from the roof deck, we can be assured that a 3/8 top-
kler piping when toggles are utilized. But when toggles are beam clamp, a 3/8 × 27 threaded rod, and a 3 swivel ring
affixed to any horizontal surface sheathing that cannot sup- will be perfectly suited to provide for hanging the cross-main
port the weight of a human being, such as a drywall ceiling, at the desired elevation.
metal duct exterior, or stucco covering, then you better think Now suppose that the building in the project example had
twice about your hanging methodology. At any rate, if you a basement, and the first floor consisted of a poured concrete
are ever inclined to use toggles for hanging sprinkler pipe, slab. The hanger used for the basement piping then, would
do so only after you have contemplated the following: be some type of concrete expansion shell (see Figure G-3).
Let’s further assume that all basement piping is to hang at a
centerline elevation of 12 beneath the concrete ceiling. Well,
(1) Consult with others in your company, and perhaps even
you would have to study the manufacturer’s data sheet for the
a structural engineer. Explain what you are doing to the
particular concrete insert that is to be put into use in order to
building owner’s representative.
determine the appropriate take-out. For example, the desired
(2) Avoid using toggles on any pipe size larger than 2 . rod length to use for one-inch piping would be 11 long if a
(3) Use additional hangers, spaced closer together than nor- Phillips shell is used, 10 long for a powder-driven stud, and
mal for additional support. 11 long if a “drop-in” type shell is employed. In each case, a
(4) Bear in mind that strict adherence to the NFPA code pro- 9 1/2 long rod would suffice for 3 main piping, or 3/8 × 9
hibits the use of toggle hangers on any pipe size larger rod for 4 main piping.

‹1E\&5&3UHVV//&
The Coach Screw Rod (see Figure G-6) hanger requires One question that I have heard from engineers regarding
only a ring to attach directly to the coach screw rod itself. hanging beneath steel and bar joist construction is this: Why
If the length “X” is considered to be the dimension from the not run piping diagonal to the bar joists (at a 45◦ angle), so
bottom of the wood structural member to the centerline of that you will always be assured of a joist spot with which to
pipe, then the following table should be used to figure the cut catch a hanger regardless of the direction of main or branch-
dimension of the coach screw rod: line pipe? Although this question makes for good sense in
theory, there are three obvious reasons why this idea is a bad
Pipe Size C. S. R. Length one. First of all, it is unprofessional. Fitters derive a great
sense of accomplishment from completing a well-installed
1 , 1 1/4 X + 1/2
job, and running an entire system at a 45◦ angle to the build-
1 1/2 , 2 X
ing’s structural layout would simply look bad. Second, the
2 1/2 X − 1/2
installer likes to keep his piping straight and true by using
3 X − 1
beams and joists as benchmarks. This he could not do if the
4 X − 2
piping was designed to run at an angle to the structure. And
5 X − 1 1/2
thirdly, there are many angled metal bracing pieces1 in be-
6 X − 3
tween joists that would constantly prove to be obstructions
to the pipe run, necessitating costly offsets. The tried and
Don’t forget that pipe sizes 1 thru 4 would require 3/8 true method of pipe routing is always to run the branch-lines
coach screw rods, while 5 and 6 piping would necessitate perpendicular to the joists.
the use of 1/2 coach screw rods. One of the easiest hangers to install is the eye-rod or eye-
Since sway-bracing is used only in parts of the world sitting socket. This is depicted in Figure G-7. A drive-screw is simply
atop earthquake zones of sufficient seismic potential, sway- hammered in to a wood joist, with a washer attached, through
bracing will not be discussed here. Sway-bracing is a test the eye-socket. A rod attaches to the eye-socket easily for pipe
component on NICET examinations, and it is important to be hanging. There is only the ring take-out to be figured in for
familiar with its purpose and technique. In Section 6-4.5 of determining the rod length, but this depends on where on the
NFPA Pamphlet No. 13, sway-bracing requirements are quite wood joist the drive-screw is actually affixed. To be careful,
thoroughly defined and discussed in great detail. Be familiar figure this location to be right in the middle of the wood joist.
with this, so that you are aware of where to reference this As an example, if 2 pipe is to be hung one foot below the
information when you encounter a project located in such bottom of a 10 wood joist, I would send 3/8 × 15 eye-
a zone. Seismic zone maps are shown in the appendix of rods out to the job. To arrive at this figure, just take the 12
NFPA #13, on pages 216 and 217. As with all hanger methods, distance (pipe to bottom of joist) and add 5 for the length of
it is in your best interest to use only listed and approved pipe rod needed to extend halfway up the joist, and subtract the
hanging techniques. 2 take-out for the swivel ring.
One example of a concrete expansion shell used for in-
*** stallation beneath concrete decks is detailed in Figure G-8.
It is not hard to figure hanger rod lengths on a building These shells can easily be installed on the side of a concrete
with a sloping roof, or one that pitches down to low-point “tee” or beam and used with an eye-rod type hanger. Again,
locations where the roof drains are situated. In such cases, a there are numerous concrete shell types used today, and man-
structural plan drawing is needed–one that shows the actual ufacturer’s cut sheets need to be consulted before trying to
roof elevations at various spots. Through the use of interpo- determine the exact lengths of bolts or rods to use with these
lation, intermediate roof point elevations can be ascertained, shells. In the interests of uniformity and to reduce the cost
and thereby all hanger rod lengths can be “cut” and noted on of stock inventory, each sprinkler company usually tends to
the sprinkler plan, so that the piping can be installed so that a use the devices of one hanger supplier, and stock just one
relatively flat and even piping elevation can be maintained by expansion shell type for this reason.
the installers (utilizing the differing hanger rod lengths be-
neath the sloping ceiling). Often, these rod lengths will vary ***
from piece to piece of installed pipe. This is an engineering Know what you’re hanging to. In pipe installer jargon, there
exercise to be undertaken only if desired by the fitter. Many is something called a “wow.” A wow is a major gaffe that is
fitters insist that they would prefer to cut their own hanger visibly apparent. I once saw a 6 main installed 5 above the
rods. To conserve time, communication with field personnel floor passing right in front of a door to a shop office. That
is imperative, and you must be familiar with their preferences is a wow. Anyone who saw this great installation could only
on installation procedure. So remember, always ask the in- stand there looking at it and say, “Wow.”
staller how you can improve your engineering work to help Wows can also show up on a sprinkler plan. Let’s say you
him out as best you can, but do not waste your time with show an obstruction (such as a light fixture, beam, or some
unnecessary, and thus, unappreciated figuring. ductwork) on your plan, and then show your pipe running

‹1E\&5&3UHVV//&
right through it. This obviously would bode badly for your preparing his sprinkler layout, the designer must be aware
reputation as a designer. Another “wow” example would be to of this code requirement in order to avoid making the field
show a long length of pipe running to a sprinkler-head, where installation more difficult than it has to be.
there is nothing to hang the pipe from. Suppose you draw In conclusion, keep in mind that a responsible sprinkler
in the roof joists and then show your pipe running parallel engineer is always able to explain his engineering decisions,
to, but not near, any joists, without any explanatory note. and this includes his plan for pipe hanging methods. Hanging
The installer (who will nonetheless figure a way around this costs are included in job estimates, hangers are stocked in
misnomer) will probably call you up and ask if you figured every fabrication shop, and they are an integral part of every
on using a “skyhook” to hang this piping. Not knowing what job. Know this, and be conversant with the installing crew
you’re hanging to can only make your design work appear to understand their likes and dislikes of the various types of
less professional. pipe hanging methods.
Refer again to Figure A-2, and, in particular, to the last
sprinklers on the branch-lines. You will notice that they ex-
tend beyond the last bar joist, as opposed to being positioned ENDNOTE
directly beneath the last bar joist. There is a reason for this.
It has to do with NFPA #13 subsection 6-2.3.2 that states 1
The metal bracing elements existent in steel beam and bar joist
that the distance from the hanger rod to the centerline of an construction include pieces of angle iron that are not strong enough
upright fire sprinkler must be a minimum of three inches. In to provide support for sprinkler pipe.

‹1E\&5&3UHVV//&

Das könnte Ihnen auch gefallen