Non Return Damper


Type ARK
Contents . Description

Description .................................................................. 2
Construction ................................................................ 3
Standard Sizes • Installation Details ............................ 4
Technical Data ............................................................. 5
Order Details ........ ....................................................... 6

ARK ARK 1

Non return dampers are designed for automatic shut off of Type ARK (with linked blades) is for use in systems with
individual sections of an air conditioning system. With the variable air volume.
fan running, the degree of blade opening is a function of the
air velocity. If the fan is turned off, the blades close Type ARK 1 (with adjustable stops to limit the blade opening
automatically. In a multi fan installation this prevents back angle) is for use in systems with constant air volume.
draught through the non-operating fans.
Both types of damper can be installed horizontally and
vertically.

2
Construction

Type ARK • ARK-G • ARK 1 • ARK 1 -G


ARK ARK 1
- Casing formed galvanised sheet steel As for type ARK, but:
- Aluminium blades — without coupling sections
- Aluminium coupling sections (with dampers having two or — with stops to limit blade opening angle, which are
more blades) adjustable from the outside
- Blade shafts stainless steel
- Bearings laminated material with a bearing surface of ARK 1-G
PTFE/Pb (maintenance-free) As for type ARK 1 both flanges drilled.
- Neoprene seals, temperature resistant up to 80°C
- Maximum back pressure 5000 Pa

ARK-G
As for type ARK, but both flanges drilled.

1 Casing 5 Blade shaft


2 Blade 6 Bearing
3 Seal 7 Coupling section
4 Stop angle 8 Adjustable stop (2 per blade)

max. 200

Type ARK • ARK-G

38
2
1
3

4
H

5 6
5

5 6

B 180

Type ARK 1 • ARK 1 -G


38

2
1
3

4
H

5 6

B 180

3
Standard Sizes • Installation Details
Standard Sizes Drilling Detail
20
B
B H Number of Number of Number of holes
blades Coupling

20
in mm in mm sections B dimension H dimension
Even number of holes
200 345 1 - 2 4
400 675 2 1 4 6

H
600 1005 3 1 5 9
800 1335 4 2 7 12
1000 1665 5 2 8 14
1200 1995 6 2 10 17
9.5
Any combination of dimensions B x H listed above can be supplied

Odd number of holes

Hole pitch B- and H- dimensions:


125 mm

Installation Details Installation Subframe • Matching Flange


version Code
1* 2* with one installation sub-frame 22
with one matching flange 23
with one installation sub-frame
24
and one matching flange
with two matching flanges 25
For constructions using sub-frames or matching flanges,
the casing flanges at both ends are drilled.
H + 20 / B + 20

H/B

Opening size without installation


sub-frame B / H

By using special screws in the installation sub-frame; the


damper can easily be removed and refitted even when
1* Special screw 2 * Installation sub-frame sub-frame is mortared in.
Scope of supply with installation sub-frame:
Galvanised steel angle installation sub-frame 35/35/3, screw
fixed builders work cleats, special screws, screws, nuts and
washers in galvanised steel (installation by others).
H/B

H/B

Scope of supply with matching flange:


Matching flange Galvanised steel angle matching flange 35/35/3; screws, nuts
and washers of galvanised steel (installation by others).

4
Technical Data

Nomenclature Example
B in mm: Width Data given: Non return damper type ARK
H in mm: Height B = 600 mm, H = 1005 mm
. v = 7 m/s
VL in l/s: Leakage volume flow rate (independent of
PD = 2000 Pa
width B)
. Installation in horizontal ductwork
VL in m3/h: Leakage volume flow rate (independent of Required: Total pressure drop . pt
width B) Leakage volume rate VL
v in m/s: Air velocity (related to B x H) Result: (from diagram)
pt in Pa: Total pressure drop (for duct monting) P = 100 Pa
. t
pD in Pa: Total pressure differential with damper closed VL = 1.3 l/s (4.7 m3/h)

Pressure Drop
140 Installation in horizontal
ductwork (graph 1)
120
1

100
pa
pt

80

60
pt

40 2 Installation in vertical
ductwork (graph 2)
20
pt

2 4 m/s 6 8 10
V

Leakage V olume Flow Rate


H

5000

4000

pa
pD

3000
pD

2000

1000

500
0.5 1 1.5 I/s 2 2.5 3 3.5

2 4 . 6 m3/h 8 10 12
VL

5
Order Details

This code need not be completed


Order Code for standard construction

ARK - G 600 x 1005 22

Type designation Installation sub-frame, matching flange


ARK (see page 4)
ARK-G
ARK 1 Standard sizes
ARK1 -G B x H in mm
(see page 4)

Specification Text Order Example :


Non return dampers for automatic shut off of individual Make: TROX
ventilation sections of an air conditioning system, maximum Type: ARK-G / 600 x 1005 / 22
permitted back pressure 5000 Pa (acting in closing direction). Qty: 4
Material: see data on page 3
Installation sub-frame, matching flange: see data on page 4
Make: TROX
Type: ARK • ARK - G • ARK 1 • ARK 1- G