Beruflich Dokumente
Kultur Dokumente
Description .................................................................. 2
Construction ................................................................ 3
Standard Sizes • Installation Details ............................ 4
Technical Data ............................................................. 5
Order Details ........ ....................................................... 6
ARK ARK 1
Non return dampers are designed for automatic shut off of Type ARK (with linked blades) is for use in systems with
individual sections of an air conditioning system. With the variable air volume.
fan running, the degree of blade opening is a function of the
air velocity. If the fan is turned off, the blades close Type ARK 1 (with adjustable stops to limit the blade opening
automatically. In a multi fan installation this prevents back angle) is for use in systems with constant air volume.
draught through the non-operating fans.
Both types of damper can be installed horizontally and
vertically.
2
Construction
ARK-G
As for type ARK, but both flanges drilled.
max. 200
38
2
1
3
4
H
5 6
5
5 6
B 180
2
1
3
4
H
5 6
B 180
3
Standard Sizes • Installation Details
Standard Sizes Drilling Detail
20
B
B H Number of Number of Number of holes
blades Coupling
20
in mm in mm sections B dimension H dimension
Even number of holes
200 345 1 - 2 4
400 675 2 1 4 6
H
600 1005 3 1 5 9
800 1335 4 2 7 12
1000 1665 5 2 8 14
1200 1995 6 2 10 17
9.5
Any combination of dimensions B x H listed above can be supplied
H/B
H/B
4
Technical Data
Nomenclature Example
B in mm: Width Data given: Non return damper type ARK
H in mm: Height B = 600 mm, H = 1005 mm
. v = 7 m/s
VL in l/s: Leakage volume flow rate (independent of
PD = 2000 Pa
width B)
. Installation in horizontal ductwork
VL in m3/h: Leakage volume flow rate (independent of Required: Total pressure drop . pt
width B) Leakage volume rate VL
v in m/s: Air velocity (related to B x H) Result: (from diagram)
pt in Pa: Total pressure drop (for duct monting) P = 100 Pa
. t
pD in Pa: Total pressure differential with damper closed VL = 1.3 l/s (4.7 m3/h)
Pressure Drop
140 Installation in horizontal
ductwork (graph 1)
120
1
100
pa
pt
80
60
pt
40 2 Installation in vertical
ductwork (graph 2)
20
pt
2 4 m/s 6 8 10
V
5000
4000
pa
pD
3000
pD
2000
1000
500
0.5 1 1.5 I/s 2 2.5 3 3.5
2 4 . 6 m3/h 8 10 12
VL
5
Order Details