Site Test Report

Contract No.: N-16391


TRANSCO RETROFIT – GRL REPLACEMENT
AT 4 CIRCUITS

Contractor Siemens LLC Equipment AUTORECLOSE RELAY F25/79


Consultant Feeder/ Circuit BAY C03 TWPS2
Substation 400kV SHAHAMA (SHME) SS Page 1 of 6

Test Report of Autorecose Relay Type 7VK611

1) General data:

Ordered MLFB: 7VK6111-5AB92-4YN0 Sr.No : BF 1804500132

Built in MLFB: 7VK6111-5AB92-4YN0/EE Built-in Firmwere Version :V04.71

Built-in rated current IN: 1A 5A Built-in P Set:V04.71.02

Built-in rated aux. voltage (DC):110-250 V DC Software Used: DIGSI 4.90

CT ratio: 2000 / 1 A VT ratio: 380000/√3/ 110/√3

Feeder: BAY C03 400KV OHL - SHME to TWPS2

2) Configuration of protection functions:


a) Autoreclose (1P only) Configured Not Configured
b) Synchrocheck Configured Not Configured
c) Back up OC/EF Protection Configured Not Configured
d) Under/Over Voltage Protection Configured Not Configured
e) Under/Over Frequency Protection Configured Not Configured

SIEMENS TRANSCO
Signature Signature
Name Josip Spolador Name Mohamed El Shair
Date 09-05-2018 Date 09-05-2018
Site Test Report
Contract No.: N-16391
TRANSCO RETROFIT – GRL REPLACEMENT
AT 4 CIRCUITS

Contractor Siemens LLC Equipment AUTORECLOSE RELAY F25/79


Consultant Feeder/ Circuit BAY C03 TWPS2
Substation 400kV SHAHAMA (SHME) SS Page 2 of 6

3) General inspection & testing:

SL NO. B-General inspection & testing: Checked

a) Installation & wiring correct to relevant drawings


b) Relay case connected to local earth bar
c) Measured value check
d) Relay binary input and output checked
e) Watch dog contact checked
f) Visual inspection of unit
g) Fault recorder
h) LED / Function Keys are working & labels provided
a) Display of Date & Time in the Relay
b) CB close and trip test

1) Measured values:
VT Ratio: 380000/√3 / 110/√3 Volts

Line voltage:

Phase Injected Injected Voltage (V) Expected Reading (kV) Actual Reading (kV)
R-Y 63.51 220 219

Busbar voltage:

Phase Injected Injected Voltage (V) Expected Reading (kV) Actual Reading (kV)
R-Y 63.51 220 219

SIEMENS TRANSCO
Signature Signature
Name Josip Spolador Name Mohamed El Shair
Date 09-05-2018 Date 09-05-2018
Site Test Report
Contract No.: N-16391
TRANSCO RETROFIT – GRL REPLACEMENT
AT 4 CIRCUITS

Contractor Siemens LLC Equipment AUTORECLOSE RELAY F25/79


Consultant Feeder/ Circuit BAY C03 TWPS2
Substation 400kV SHAHAMA (SHME) SS Page 3 of 6

2) Binary input function check:

Binary Relay Drwng Ref.


Function Checked
Input Terminal Page
BI1 F5-F10 Block 3P AR (L) 32

BI2 F6-F10 Spare 32

BI3 F7-F10 Block AR 32

BI4 F8-F10 CB Ready for AR 32

BI5 F9-F10 Spare 32


BI6 K15-J12 Spare 34

BI7 K16-J12 Spare 34

BI8 K17-J12 Protection Trip L1 34

BI9 K18-J12 Protection Trip L2 34

BI10 J1-J12 Protection Trip L3 34

BI11 J2-J12 Spare 34

BI12 J3-J12 Spare 34

BI13 J4-J12 AR OFF 34

BI14 J5-J12 Test mode 34

BI15 J6-J12 BB VT MCB trip 34

BI16 J7-J12 Line VT MCB trip 34

BI17 J8-J12 Spare 34

BI18 J9-J12 Spare 34

BI19 J10-J12 Spare 34


BI20 J11-J12 Spare 34

SIEMENS TRANSCO
Signature Signature
Name Josip Spolador Name Mohamed El Shair
Date 09-05-2018 Date 09-05-2018
Site Test Report
Contract No.: N-16391
TRANSCO RETROFIT – GRL REPLACEMENT
AT 4 CIRCUITS

Contractor Siemens LLC Equipment AUTORECLOSE RELAY F25/79


Consultant Feeder/ Circuit BAY C03 TWPS2
Substation 400kV SHAHAMA (SHME) SS Page 4 of 6

3) Binary output check

Binary Relay
Function Drg.Ref Page Checked
Output Terminal

BO-1 R5-R1 Spare 35

B0-2 R5-R2 Spare 35

BO-3 R5-R3 Spare 35

BO-4 R5-R4 Spare 35

BO-5 R5-R6 AR close command 35

BO-6 R7-R8 1P trip permited 35

BO-7 R9-R10 AR close command 35

BO-8 R11-R12 Spare --

BO-9 K3-K1 Spare --

BO-10 K3-K2 AR 3P Trip 35 (40)

BO-11 K11-K7 Definite trip 24

B0-12 K11-K8 Spare --

BO-13 K6-K5 AR Blocked /Final trip 52

BO-14 K6-K4 Spare --

BO-15 K11-K9 Spare --

BO-16 K11-K10 Spare --

BO-17 K13-K12 Definite trip 33

BO-18 K13-K14 Spare --


LIVE
K3-K4 Watch dog 25
STATUS

SIEMENS TRANSCO
Signature Signature
Name Josip Spolador Name Mohamed El Shair
Date 09-05-2018 Date 09-05-2018
Site Test Report
Contract No.: N-16391
TRANSCO RETROFIT – GRL REPLACEMENT
AT 4 CIRCUITS

Contractor Siemens LLC Equipment AUTORECLOSE RELAY F25/79


Consultant Feeder/ Circuit BAY C03 TWPS2
Substation 400kV SHAHAMA (SHME) SS Page 5 of 6

4) LED function:

LED no Function LED Type Checked

1 AR ON U
2 AR OFF U
3 AR IN PROGRES L
4 EXT. TRIP L1 L
5 EXT. TRIP L2 L
6 EXT. TRIP L3 L
7 CB CLOSED U
8 CB NOT READY U
9 AR BLOCKED U
10
11 AR NOT READY U
12 SYNCHECK BLOCKED U
13 1P TRIP PERMITED U
14 AR CLOSE COMMAND L

Function Key Function Checked

F1 Event Log
F2 Primary Values
F3 Last Fault
F4 MLFB

SIEMENS TRANSCO
Signature Signature
Name Josip Spolador Name Mohamed El Shair
Date 09-05-2018 Date 09-05-2018
Site Test Report
Contract No.: N-16391
TRANSCO RETROFIT – GRL REPLACEMENT
AT 4 CIRCUITS

Contractor Siemens LLC Equipment AUTORECLOSE RELAY F25/79


Consultant Feeder/ Circuit BAY C03 TWPS2
Substation 400kV SHAHAMA (SHME) SS Page 6 of 6

5) Testing of AR function:

Test Item Checked Remark

1-pole AR successful R phase

1-pole AR successful Y phase

1-pole AR successful B phase

Evolving fault in dead time --> AR blocked final 3p trip

Fault in reclaim time --> AR blocked final 3p trip

3-pole trip --> AR blocked final 3p trip

2,3,4 zone trip --> AR blocked final 3p trip

fault not cleared during monitoring time --> AR blocked final 3p trip

CB not ready --> AR blocked

AR blocked after manual close

AR blocked by BI

6) Test Instruments Used:

Calibration due
Description Make Serial No. Type
date
Secondary Injection Kit OMICRON DF930F CMC356 14-12-2018
Multimeter Fluke 20780061 Fluke 289 01-06-2018

7) Reference:

S.No Drawing title Drawing No


1. 400 kV OHL Feeder Protection M2 Schematic N16391/XX/XX/X/XX

8) Attachments:
a. Omicron Printout.
b. Digsi Print out

SIEMENS TRANSCO
Signature Signature
Name Josip Spolador Name Mohamed El Shair
Date 09-05-2018 Date 09-05-2018
7VK611 V4_7_prn

SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

SHAHAMA / C03 / 7VK611 V4.7

MLFB: 7VK61115AB924YN0
Parameter-set version: V04.71.02
Device path: C:\Siemens\DIGSI4\D4Proj\Shahama\P7DI\GV\SD\00000006
Author:
Creation date: 06.05.18 10:19:44
Last modified: 10.05.18 07:24:04
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS
1 Device Configuration ...................................................................................................................................................................… 2
2 Configuration - short (column-oriented) .......................................................................................................................................… 3
2.1 Binary inputs ................................................................................................................................................................................… 3
2.2 Binary outputs ..............................................................................................................................................................................… 3
2.3 LEDs ............................................................................................................................................................................................… 3
3 Interfaces .....................................................................................................................................................................................… 4
3.1 Serial interface on PC: .................................................................................................................................................................… 4
3.2 VD addresses .................................................................................................................................................................................. 4
3.3 Operator Interface ........................................................................................................................................................................… 4
3.4 Service interface ..........................................................................................................................................................................… 4
3.5 IEC 103 on devi… .......................................................................................................................................................................… 4
4 Passwords ....................................................................................................................................................................................... 5
5 General Device Settings ..............................................................................................................................................................… 6
5.1 Group Device ...............................................................................................................................................................................… 6
6 Power System Data 1 ..................................................................................................................................................................… 7
6.1 Group Power System Data 1; Group Transformers .....................................................................................................................… 7
6.2 Group Power System Data 1; Group Power System ...................................................................................................................… 7
6.3 Group Power System Data 1; Group Breaker .............................................................................................................................… 7
7 Oscillographic Fault Records .......................................................................................................................................................… 8
7.1 Group Oscillographic Fault Records ............................................................................................................................................… 8
8 Settings groups ............................................................................................................................................................................… 9
8.1 Group Power System Data 2; Group Power System ...................................................................................................................… 9
8.2 Group Power System Data 2; Group Line Status ........................................................................................................................… 9
8.3 Group Automatic Reclosure; Group General ...............................................................................................................................… 9
8.4 Group Automatic Reclosure; Group 1st AR-cyle ............................................................................................................................. 9
8.5 Group Automatic Reclosure; Group 3pTRIP/DLC/RDT .............................................................................................................… 10
8.6 Group Synchronism and Voltage Check; Group General ..........................................................................................................… 10
8.7 Group Synchronism and Voltage Check; Group with AR .............................................................................................................. 10
8.8 Group Synchronism and Voltage Check; Group Man.Close+CNTRL .......................................................................................… 10
9 Time Synchronization .................................................................................................................................................................... 12

Page 1 of 12
7VK611 V4_7_prn
Device Configuration
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0106 Voltage transformer connection 1-phase
0107 Current transformer connection NO
0110 Trip mode 1-/3pole
0133 Auto-Reclose Function 1 AR-cycle
0134 Auto-Reclose control mode with Trip but without Action time
0135 Synchronism and Voltage Check Enabled
0140 Trip Circuit Supervision Disabled

Page 2 of 12
7VK611 V4_7_prn
Configuration - short (column-oriented)
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

2 Configuration - short (column-oriented)

2.1 Binary inputs


Binary inputs
Binary inputs No. Group Information Type Configuration

1 02738 Autoreclosure >AR: Block 3pole AR-cycle SP L


3 02703 Autoreclosure >AR: Block auto-reclose function SP H
4 00379 P.System Data 2 >CB aux. contact 3pole Closed SP H
4 00371 P.System Data 2 >CB1 READY (for AR,CB-Test) SP H
8 02712 Autoreclosure >AR: External trip L1 for AR start SP H
9 02713 Autoreclosure >AR: External trip L2 for AR start SP H
10 02714 Autoreclosure >AR: External trip L3 for AR start SP H
13 02701 Autoreclosure >AR: Switch on auto-reclose function SP L
13 02702 Autoreclosure >AR: Switch off auto-reclose function SP H
14 00015 Device >Test mode SP L
15 00362 P.System Data 2 >Failure: Usy4 VT (MCB tripped) SP H
16 00361 P.System Data 2 >Failure: Feeder VT (MCB tripped) SP H

2.2 Binary outputs


Binary outputs
BO No. Group Information Type Configuration

5 02851 Autoreclosure AR: Close command OUT U


6 02864 Autoreclosure AR: 1pole trip permitted by internal AR OUT U
7 02851 Autoreclosure AR: Close command OUT U
10 02871 Autoreclosure AR: TRIP command 3pole OUT U
11 00536 P.System Data 2 Relay Definitive TRIP OUT U
13 00536 P.System Data 2 Relay Definitive TRIP OUT U
13 02783 Autoreclosure AR: Auto-reclose is blocked OUT U
17 00536 P.System Data 2 Relay Definitive TRIP OUT U

2.3 LEDs
LEDs
LEDs No. Group Information Type Configuration

1 02782 Autoreclosure AR: Auto-reclose is switched on IntSP U


2 02781 Autoreclosure AR: Auto-reclose is switched off OUT U
3 02801 Autoreclosure AR: Auto-reclose in progress OUT L
4 02712 Autoreclosure >AR: External trip L1 for AR start SP L
5 02713 Autoreclosure >AR: External trip L2 for AR start SP L
6 02714 Autoreclosure >AR: External trip L3 for AR start SP L
7 00379 P.System Data 2 >CB aux. contact 3pole Closed SP U
8 02787 Autoreclosure AR: Circuit breaker not ready OUT U
9 02783 Autoreclosure AR: Auto-reclose is blocked OUT U
11 02784 Autoreclosure AR: Auto-reclose is not ready OUT U
12 02931 Sync. Check Synchro-check is switched OFF OUT U
12 02932 Sync. Check Synchro-check is BLOCKED OUT U
12 02934 Sync. Check Synchro-check function faulty OUT U
13 02864 Autoreclosure AR: 1pole trip permitted by internal AR OUT U
14 02851 Autoreclosure AR: Close command OUT L

Page 3 of 12
7VK611 V4_7_prn
Interfaces
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

3 Interfaces

3.1 Serial interface on PC:

Address (operator interface device): 1


Frame: 8 E(ven) 1
Baud rate: 115200
COM interface: 1
Frame, Baud Rate and Address settings: Apply from "Operator Interface" tab

3.2 VD addresses

DIGSI VD address: 3
SIPROTEC VD address: 10010
Proxy VD address: 4
SIPROTEC T103 VD address: 6

3.3 Operator Interface

Address: 1
Frame: 8 E(ven) 1
Baud rate: 115200
Max. telegram gap (0...50): 0
IP address: 192.168.1.1
Subnet mask: 255.255.255.0
Link layer: PPP (point-to-point, serial)
Access authorization at the port for parameterization: Enabled
Access authorization at the port for test and diagnosis: Enabled
Web Monitor operation: Full access

3.4 Service interface

Address: 1
Frame: 8 E(ven) 1
Baud rate: 38400
Max. telegram gap (0...50): 0
IP address: 192.168.2.1
Subnet mask: 255.255.255.0
Link layer: PPP (point-to-point, serial)
Access authorization at the port for parameterization: Enabled
Access authorization at the port for test and diagnosis: Enabled
Web Monitor operation: Reading

3.5 IEC 103 on device

Address: 1
Frame: 8 E(ven) 1
Baud rate: 19200
Max. telegram gap (0...50): 0
Measured value transmission: Private
DPI transmission: with interm. pos. 11 (V3)
Expanded fault record channels: -

Page 4 of 12
7VK611 V4_7_prn
Passwords
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

4 Passwords

Number Function Active

1 Password for switching/selecting/updating Enabled


2 Password for unlocked switching Enabled
4 Password for testing and diagnostics Enabled
5 Password for single parameters Enabled
6 Password for hardware test menus Enabled
7 Password for parameter set Enabled
50 Switchgear password 1 Enabled
51 Switchgear password 2 Enabled
52 Switchgear password 3 Enabled
53 Switchgear password 4 Enabled
54 Switchgear password 5 Enabled
55 Switchgear password 6 Enabled
56 Switchgear password 7 Enabled
57 Switchgear password 8 Enabled
58 Switchgear password 9 Enabled
59 Switchgear password 10 Enabled
100 Serial-Login: Password for full access rights (Web Monitor) Enabled
101 Serial-Login: Password for changing access rights (Web Monitor) Enabled
102 Serial-Login: Password for read-only access rights (Web Monitor) Enabled

Page 5 of 12
7VK611 V4_7_prn
General Device Settings
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

5 General Device Settings

5.1 Group Device


Group Device
No. Settings Value Group

0610 Fault Display on LED / LCD Display Targets on every Pickup All
0625A Minimum hold time of latched LEDs 0 min All
0640 Start image Default Display image 5 All

Page 6 of 12
7VK611 V4_7_prn
Power System Data 1
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

6 Power System Data 1

6.1 Group Power System Data 1; Group Transformers


Group Power System Data 1; Group Transformers
No. Settings Value Group

0203 Rated Primary Voltage 380.0 kV All


0204 Rated Secondary Voltage (Ph-Ph) 110 V All
0206 CT Rated Secondary Current 1A All
0210 U4 voltage transformer is Usy2 transformer All
0214A Angle adjustment Usy2-Usy1 0° All
0215 Matching ratio Usy1 / Usy2 1.00 All

6.2 Group Power System Data 1; Group Power System


Group Power System Data 1; Group Power System
No. Settings Value Group

0207 System Starpoint is Solid Earthed All


0230 Rated Frequency 50 Hz All

6.3 Group Power System Data 1; Group Breaker


Group Power System Data 1; Group Breaker
No. Settings Value Group

0239 Closing (operating) time of CB 0.06 sec All


0240A Minimum TRIP Command Duration 0.10 sec All
0241A Maximum Close Command Duration 0.20 sec All
0242 Dead Time for CB test-autoreclosure 0.10 sec All

Page 7 of 12
7VK611 V4_7_prn
Oscillographic Fault Records
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

7 Oscillographic Fault Records

7.1 Group Oscillographic Fault Records


Group Oscillographic Fault Records
No. Settings Value Group

0402A Waveform Capture Save with Pickup All


0403A Scope of Waveform Data Power System fault All
0410 Max. length of a Waveform Capture Record 2.00 sec All
0411 Captured Waveform Prior to Trigger 0.50 sec All
0412 Captured Waveform after Event 0.50 sec All
0415 Capture Time via Binary Input 1.00 sec All

Page 8 of 12
7VK611 V4_7_prn
Settings groups
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

8 Settings groups

8.1 Group Power System Data 2; Group Power System


Group Power System Data 2; Group Power System
No. Settings Value Group

1103 Measurement: Full Scale Voltage (100%) 380.0 kV A

8.2 Group Power System Data 2; Group Line Status


Group Power System Data 2; Group Line Status
No. Settings Value Group

1131A Pole Open Voltage Threshold 30 V A


1135 RESET of Trip Command with Pole Open Current Threshold only A
1136 open pole detector with measurement (U/I,trip,pickup,CBaux) A
1150A Seal-in Time after MANUAL closures 0.30 sec A
1151 Manual CLOSE COMMAND generation NO A
1152 MANUAL Closure Impulse after CONTROL <none> All

8.3 Group Automatic Reclosure; Group General


Group Automatic Reclosure; Group General
No. Settings Value Group

3401 Auto-Reclose function ON A


3402 CB ready interrogation at 1st trip YES A
3403 Reclaim time after successful AR cycle 180.00 sec A
3404 AR blocking duration after manual close 10.00 sec A
3406 Evolving fault recognition with Trip A
3407 Evolving fault (during the dead time) blocks AR A
3408 AR start-signal monitoring time 0.20 sec A
3409 Circuit Breaker (CB) Supervision Time 3.00 sec A
3410 Send delay for remote close command oo sec A
3411A Maximum dead time extension oo sec A

8.4 Group Automatic Reclosure; Group 1st AR-cyle


Group Automatic Reclosure; Group 1st AR-cyle
No. Settings Value Group

3456 Dead time after 1pole trip 0.50 sec A


3457 Dead time after 3pole trip 0.30 sec A
3458 Dead time after evolving fault 0.50 sec A
3459 CB ready interrogation before reclosing NO A
3460 Request for synchro-check after 3pole AR YES A

Page 9 of 12
7VK611 V4_7_prn

SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

8.5 Group Automatic Reclosure; Group 3pTRIP/DLC/RDT


Group Automatic Reclosure; Group 3pTRIP/DLC/RDT
No. Settings Value Group

3430 3pole TRIP by AR YES A

8.6 Group Synchronism and Voltage Check; Group General


Group Synchronism and Voltage Check; Group General
No. Settings Value Group

3501 Synchronism and Voltage Check function ON A


3502 Voltage threshold dead line / bus 22 V A
3503 Voltage threshold live line / bus 88 V A
3504 Maximum permissible voltage 121 V A
3507 Maximum duration of synchronism-check 0.50 sec A
3508 Synchronous condition stability timer 0.00 sec A
3509 Synchronizable circuit breaker <none> All

8.7 Group Synchronism and Voltage Check; Group with AR


Group Synchronism and Voltage Check; Group with AR
No. Settings Value Group

3510 Operating mode with AR without consideration of CB closing time A


3511 Maximum voltage difference 11.0 V A
3512 Maximum frequency difference 0.10 Hz A
3513 Maximum angle difference 20 ° A
3515A AR at Usy2>, Usy1>, and Synchr. YES A
3516 AR at Usy1< and Usy2> YES A
3517 AR at Usy1> and Usy2< YES A
3518 AR at Usy1< and Usy2< NO A
3519 Override of any check before AR NO A

8.8 Group Synchronism and Voltage Check; Group Man.Close+CNTRL


Group Synchronism and Voltage Check; Group Man.Close+CNTRL
No. Settings Value Group

3530 Operating mode with Man.Cl without consideration of CB closing time A


3531 Maximum voltage difference 11.0 V A
3532 Maximum frequency difference 0.10 Hz A
3533 Maximum angle difference 10 ° A
3535A Manual Close at Usy2>, Usy1>, and Synchr YES A

Page 10 of 12
7VK611 V4_7_prn

SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

Group Synchronism and Voltage Check; Group Man.Close+CNTRL(2)


No. Settings Value Group

3536 Manual Close at Usy1< and Usy2> YES A


3537 Manual Close at Usy1> and Usy2< YES A
3538 Manual Close at Usy1< and Usy2< NO A
3539 Override of any check before Man.Cl NO A

Page 11 of 12
7VK611 V4_7_prn
Time Synchronization
SIMATIC SHAHAMA / C03 / 7VK611 V4.7/7VK611 10.05.18 07:24:20

9 Time Synchronization

Source of time synchronization: Internal Clock


Fault indication after: 10 Min.
Time format for display German
Offset to time signal: 00:00
Time zone offset to GMT: +01:00

Page 12 of 12