Beruflich Dokumente
Kultur Dokumente
Steam fired
Absorption chillers
Single effect
350 - 7.000 kW
SS SERIES
Steam fired single effect absorption chillers
1 B C
A Chilled water
B Refrigerant
C Closed vessel
2. The right hand side location houses the the shell vacuum and the weak solution of lithium
ABSOBER section. In this section an aqueous bromide is collected in the base. The process of
concentrated solution of lithium bromide is absorption produces heat and this is removed by
sprayed. The solution is hygroscopic, maintaining the cooling water tube bundle.
3
SS SERIES
Steam fired single effect absorption chillers
2 A B C D
F
E
3. Hygroscopic properties of the aqueous solution The collected diluted solution of lithium bromide
of lithium bromide depend on two factors: has to be re-concentrated. It is pumped to a
a) Temperature: the affinity between lithium dedicated vessel called GENERATOR. Heat is
bromide and water increases as temperature applied through a tube bundle to vaporize the
decreases. water from the diluted solution. Hot water,
b) Concentration: as this reduces its hygroscopic steam or the direct comustion of fuel is used
effect decreases. depending on type of machine.
3 A B C
F
E
4
SS SERIES
Steam fired single effect absorption chillers
4. The water vapours are pumped to another heat This condensed water is used as refrigerant to
exchanger called CONDENSER where they be sprayed in the evaporator to generate the
are condensed by a cooling water flow (the cooling effect. Therefore, the working cycle of
same water that is flowing in the absorber). the machine is completely closed.
4 A B C D E
H
G
A Condenser
B Vaporized refrigerant
C Liquid refrigerant
D Strong solution
E Generator
F Solution pump
G Chilled water
H Cooling water
I Heat source
5
SS SERIES
Steam fired single effect absorption chillers
5 IV III
A D
A
B
I II
A Cooling water
B Chilled water
C Solution pump
D Heat source
I Evaporator
II Absorber
III Generator
IV Condenser
6
SS SERIES
Steam fired single effect absorption chillers
CYCLE DESCRIPTION
12
D 3
E
1 1 9
7
A 8
S 2
11
10 5
C
Dilute Chilled Cooling Strong Open Closed
solution Refrigerant water water Steam solution valve valve
removed from the machine, the solution temperature consequently the solution concentration is very
will increase and consequently the solution affinity high) the refrigerant can directly flow into the
towards the water will decrease. So, at the end the absorber and the concentration of the solution
absorption process will become less effective. is reduced.
• Completely factory assembled and wired. For
Condenser transport facility bigger models may be shipped
The refrigerant vapors coming from the generator in two pieces. Always for transport facility
enter the condenser where they are condensed by control panel may be shipped loose.
the cooling water circulating inside the tubes. The • Leak tested in every part: upper and lower shell,
liquid refrigerant collects on the bottom of the solution heat exchanger, solution and refrigerant
condenser and it is sent to the evaporator. canned pumps, vacuum pump and purge
assembly.
Evaporator • PLC based control.
The refrigerant coming from the condenser enters • LiBr solution, refrigerant, corrosion inhibitor
the evaporator which is at a lower pressure than and octyl alcohol separately provided to be
the condenser; for this reason the refrigerant charged on site.
flash cools down to 3,7°C that is the boiling • Nitrogen is charged into the machine at a
temperature corresponding to the pressure inside pressure slightly higher than atmospheric prior
the shell and then it falls on the evaporator tubes. to shipping, in order to avoid air entering the
Once it is collected on the bottom, it is pumped machine and damaging the internals.
by the refrigerant pump to the distribution trays • Lifting lugs provided on each side of the
of the evaporator, from where it drops upon the machine.
tube bundle due to the gravity. As the refrigerant
gets in touch with the tubes, it evaporates taking MECHANICAL FEATURES
away the heat from the water circulating inside the
tubes. This water is so cooled down to the required
LOWER SHELL
temperature.
The lower shell assembly houses the evaporator and
the absorber sections. They are shell and tube type
heat exchangers, housed in a common fabricated
carbon steel shell.
MAIN FEATURES
• Stainless steel eliminator plates between the
• Double shell design: the upper shell (including evaporator and the absorber, in order to permit
the condenser and the generator) and the only to the refrigerant vapors to flow to the
lower shell (including the evaporator and the absorber, retaining the liquid in the evaporator.
absorber). • “Split” type evaporator: the evaporator is
In case of single shell design, the evaporator is divided into two different tube bundles, placed
on top of the absorber. Any non condensable on both sides of the absorber, that remains in
gas released in the absorber section will rise up the middle of the two evaporators. This solution
and there is a possibility that these gases are grants a better efficiency at part load, optimizing
trapped below the bottom of the separation the mass transfer inside the solution.
trap, and they can given time corrode the • Finned and thin wall DLP (Deoxidized Low
separation plate. Whereas in case of a double Phosphorous) copper tubes in the evaporator.
shell design, the evaporator and the absorber are In DLP copper the oxygen is removed and the
located side by side, and therefore the possibility phosphorous content is less than 0,005 ppm.
of the separation plate corrosion is eliminated. The presence of phosphorous greater than 0,005
This shell design type calls also for higher ppm in the tubes of the absorption machines
chances of internal short circuiting as when the can result in “Stress Corrosion Cracking”. At
water level in the evaporator is very high (and a microscopic level, stress corrosion cracking
8
SS SERIES
Steam fired single effect absorption chillers
takes place on the external surface of the tubes the condenser; the retained solution drops to
by the attack of a salt (e.g. LiBr) on the grain the bottom of the generator, thus reducing the
boundary. chance for the solution contaminating the pure
• Mini-finned and thin wall DLP (Deoxidized Low refrigerant.
Phosphorous) copper tubes in the absorber. In • Plain and thin wall DLP (Deoxidized Low
DLP copper the oxygen is removed and the Phosphorous) copper tubes in the condenser.
phosphorous content is less than 0,005 ppm. In DLP copper the oxygen is removed and the
The presence of phosphorous greater than 0,005 phosphorous content is less than 0,005 ppm.
ppm in the tubes of the absorption machines The presence of phosphorous greater than 0,005
can result in “Stress Corrosion Cracking”. At ppm in the tubes of the absorption machines
a microscopic level, stress corrosion cracking can result in “Stress Corrosion Cracking”. At
takes place on the external surface of the tubes a microscopic level, stress corrosion cracking
by the attack of a salt (e.g. LiBr) on the grain takes place on the external surface of the tubes
boundary. by the attack of a salt (e.g. LiBr) on the grain
• All the tubes fitted in the respective tube sheets boundary.
are duly expanded for the correct fit. All the • Stainless steel SS 430 Ti tubes in generator.
tubes are individually accessible and replaceable • Straight type tubes in generator: expansion
from either end of the chiller. coefficients of the material of tube sheet and
• Carbon steel tube sheets. tubes are very similar, avoiding the rise of
• Carbon steel absorber and evaporator headers dangerous mechanical stress due to thermal
fully removable at either side of the machine, expansion, without the use of “U” type tubes or
for easy access to the tube bundle. Headers are mobile supports.
provided with flanged nozzles. • All the tubes fitted in their respective tube sheets
• Absorber and evaporators headers with side are duly expanded for the correct fit. All the
nozzles, to grant an easy maintenance and reduce tubes are individually accessible and replaceable
the machine break down time. from either end of the chiller.
• Hinged type absorber headers, for an easy • Carbon steel tube sheets.
access to the tube bundle without need of lifting • Carbon steel condenser and generator headers
systems to support the header. fully removable at either side of the machine,
• Counter flanges provided as a standard feature for easy access to the tube bundle. Headers are
with the unit. provided with flanged nozzles.
• Plugged vents and drain connections provided • Condenser headers with side nozzles, to grant
for the water boxes. an easy maintenance and reduce the machine
• Sight glasses respectively on the evaporator and break down time.
the absorber shell. These glasses are used to • Hinged type condenser headers, for an easy
monitor the refrigerant and the solution levels access to the tube bundle without need of lifting
in the evaporator and the absorber for an easy systems to support the header.
and user friendly operation, since through them • Counter flanges provided as a standard feature
it is possible to monitor the correct working of with the unit.
the machine. • Plugged vents and drain connections provided
for the water boxes.
UPPER SHELL
• Sight glass on the generator shell. This glass
The upper shell assembly houses the condenser and is used to monitor the solution level in the
the generator sections. They are shell and tube type generator for an easy and user friendly operation,
heat exchangers, housed in a common fabricated since through them it is possible to monitor the
carbon steel shell. correct working of the machine.
• Stainless steel eliminator plates between the
HEAT EXCHANGERS
condenser and the generator, in order to
permit only the refrigerant vapors to flow to • The units are provided with two regenerative
9
SS SERIES
Steam fired single effect absorption chillers
heat exchangers to increase the efficiency of the pipe connection has a negative pressure. Since
cycle. this chamber is connected to the main shell of
- A solution heat exchanger is an integral part the machine, gases are sucked from the machine
of the machine to increase efficiency by pre- inside and sent to the purge device. Once the
heating weak solution with strong solution. This gases are inside, they are taken to the bottom of
shall be a plate type heat exchanger. The plates the chamber by the solution spray and they are
shall be of stainless steel with copper brazing. then released in the storage tank. Here they are
- A heat reclaimer shall be an integral part kept until the purge pump is not activated.
of the machine to increase efficiency by pre- • The purge pump is provided as a standard
heating weak solution with steam condensate feature on all machines. The storage tank has to
from high temperature generator. This shall be be evacuated before it gets completely full.
a shell and tube type heat exchanger with Cu:Ni • The machines can also be provided with a
90:10 tubes. palladium cell (optional feature) to automatically
evacuate the hydrogen from the machine. The
PURGE ASSEMBLY
inside walls of this cell are made with palladium.
• The units are provided with a purge system which The main device of this material is that at high
is able to continuously and automatically remove temperatures it becomes porous to hydrogen.
non condensable gases from the inside of the When the electric heater is switched on,
machine, storing them into the storage tank. palladium tubes get heated and hydrogen (most
This one is divided in two parts: a first chamber of the non condensable gases inside the machine
where gases coming from the inside of the are hydrogen) is evacuated from the cell directly
machine enter, and a second chamber that is the into the atmosphere. In this way a vacuum inside
real storage tank. A small pipe connected to the the machine is automatically maintained using a
solution pump discharge sends a small quantity completely static system.
of solution in the first chamber. The discharge
SOLUTION AND REFRIGERANT PUMPS
of this liquid is pinched to create a jet effect.
Due to this jet effect the area surrounding the • All the machines are provided with Japanese
C
I
D F G
A B
10
SS SERIES
Steam fired single effect absorption chillers
manufactured canned pumps,Teikoku made, self valves at their suction and discharge ends to ease
lubricating, factory mounted and wired. Teikoku the removal of the pumps during maintenance
is a world leader in the manufacturing of this without breaking the vacuum inside the chiller.
type of pumps and it is well known all over the • Solution pump is also provided with an AC
world for extremely high quality standards. drive as a standard feature, to have superior
• All the pumps are provided with TRG, a patented performance at part load operation.
bearing monitoring system for monitoring
CROSSOVER PIPING
the consumption of the bearings. By simply
connecting to a couple of free contacts in the • All the various sections of the machines are
terminal strip of the control panel it is possible interconnected by suitably sized seamless
to have an indication on the bearing status, carbon steel piping. All the piping is of welded
without opening the canned motor pumps. The construction complete with necessary valves
canned motor pumps are provided with over- and fittings. The absorber to the condenser
current and high temperature protection safeties crossover piping suitably welded is a standard
to prevent the motors from burnout. feature of all the machines.
• These pumps are of a bolted construction
so that if required bearing and filters can be AUTOMATIC DECRYSTALLISATION
cleaned. In case of hermetically sealed pumps SYSTEM
replacement of entire pump is the only solution. • The machines are provided with an auto-
There is great difference in leak rates caused by decrystallisation line, protecting themselves from
moving seal joint and fix seal joint. Canning crystallisation during operation. If crystallisation
avoids moving seal joint as pump has no shaft occurs, it starts inside the concentrated solution
seal. Back cover plate fitted for dismantling at the outlet of the heat exchanger, where the
the pump does not come in contact with any concentration is higher and the temperature is
moving parts. Such fixed sealing allows leak rate lower. Here the crystallisation would cause a
to be maintained within international standards partial blockage of this line that would reduce
without comprising the maintainability. the outflow of the concentrated solution from
• The pumps are also provided with isolating the generator. For the automatic decrystallisation
D G
F
E
11
SS SERIES
Steam fired single effect absorption chillers
12
SS SERIES
Steam fired single effect absorption chillers
LiBr solution is not effective in the heat transfer disk bursts open releasing the pressure inside,
process and so the capacity will be reduced. For avoiding any major damage to the machine.
this reason the refrigerant blowdown valve has
to be operated on a periodic basis. FACTORY TESTS
ABSORBER SOLENOID VALVE
SOAP TEST
• A solenoid valve is provided in absorber,
connected with the refrigerant piping. When • Nitrogen is charged into the machine at a
the solution level in absorber goes below a set pressure up to 130 to 140 kPa. After charging
value, the solenoid valve on refrigerant line gets is over, test is carried out with soap solution. A
open and refrigerant is directly sent to absorber, soap solution is spread evenly over the joints
so that the solution pump can send the proper and on the expanded tube ends. If there is any
quanity of dilute solution to the generator, in leakage the nitrogen will try to leak from the
order to keep under control the concentration. joint, and because of the soap solution, bubbles
will be formed. These leak points are marked
REFRIGERANT AND SOLUTION LEVELS
and repaired/rewelded.
CONTROL
DECAY TEST
• All the units are provided with reliable level
electrodes to control the refrigerant level in the • After repairing the leaks found out during
evaporator and the solution level in absorber. nitrogen testing, the machine is again charged
These electrodes ensure that the correct signal is with nitrogen up to 130 kPa pressure. The
given to the control panel to avoid that refrigerant machine is kept at this pressure for 24 hours. If
and solution pump will enter into a cavitation any leakage occurs nitrogen will escape to the
zone and to ensure that the correct quantity of atmosphere and the pressure will start reducing
solution is pumped inside the machine. They are thus showing the leakage. If a leakage is found
more precise and reliable than the traditional in the decay test, the joints are thoroughly
floating system. rechecked as in the previous step and they are
repaired.
RUPTURE DISK
HELIUM SPRAY TEST
• All the machines are provided with a rupture disk
as a standard feature. It is mounted on the shell • The helium molecule is the next smallest
side of the generator. When the pressure inside molecule after the hydrogen molecule in the
the generator raises above the critical value, the periodic table and it will leak through very
2
1
4
1 Level electrodes
2 Refrigerant level control system
3 Evaporator
4 Refrigerant
13
SS SERIES
Steam fired single effect absorption chillers
minute holes. The absorption machine is fully • Individual contactors and thermal overcurrent
evacuated (vacuumed). After vacuuming, the relays for all pumps motors.
machine is connected to a special helium leak • Interlocks for chilled and cooling water pumps.
detector. The helium is spread on all the joints. • Temperature sensors and display for the
As the machine is under vacuum, a leakage in following:
the joints will result in helium entering into the - Chilled water inlet and outlet.
machine which will be shown on the screen of - Cooling water inlet and outlet.
the helium leak detector. If the cumulative leak - Concentrated solution at generator outlet.
rate is more than 1 x 10-7 standard cc/sec. then - Concentrated solution sprayed in absorber.
the joints are marked and repaired. - Condensed refrigerant in “U” tube.
• Antifreeze protection safeties (PLC inbuilt
HELIUM SHROUD TEST
antifreeze alarm, antifreeze thermostat, low
• The machine is fully covered by a polythene temperature cut-out for the refrigerant pump
sheet and the helium is passed under the (L-cut), flow switch and a D.P. switch for chilled
polythene cover. The leak rate is observed in water).
the leak detector machine for 30 minutes. In • Crystallisation prevention (low cooling water
this test, the leak rate allowable is up to 1 x 10-5 inlet temperature cut-out, high temperature
standard cc/s. control for generator, control valve PLC
regulation based on generator temperature,
CONTROLS AND SAFETIES active concentration control for safe operation
with low cooling water inlet temperatures,
solution level control in absorber for solenoid
GENERAL FEATURES absorber valve opening).
The units come with a Siemens S7/200 Programmable • Alarm state annunciation through an audio
Logic Controller (PLC), provided with the most signal and appropriate messages display on the
advanced technological features to grant safe and operator interface terminal.
economic operation, in order to make these products • Last 24 hour logging facility at a sampling time
highly efficient, reliable and user friendly. of one hour intervals and last six alarms logging
The control equipment is enclosed in a rugged dust facility are provided for better understanding of
proof sheet metal casing mounted on the chiller the behavior of the unit during alarm conditions
with IP42 protection. The control panel consists of and for easy diagnosis.
the following: • Possibility to modify data logging frequency time
• Main circuit breaker for safety against electrical and make it faster after an alarm is activated.
hazards. • Machine status indication on the display.
• Terminal blocks for control and power • Possibility to connect to the client BAS/BMS/
connections. DCS systems with PPI communication protocol,
• Microprocessor based PLC Siemens S7/200 compatible with Modbus RTU slave.
for operational logic and sequence, safety and CONTROL AND SELF DIAGNOSTIC
capacity control through PID algorithm. PLC FUNCTIONS
uses a powerful CPU Siemens 226 XM.
• 4 lines with 20 characters each graphic display The control panel has the following functions:
Siemens OP77. • Remote and local access for sequential operation
• Modbus connectivity read/write as a standard of the chiller.
feature. • Steam consumption control by a tight control of
• Ultra isolation control transformer with MCB the chilled water outlet temperature accomplished
protection for control circuit. by a microprocessor PID algorithm. This
• Level electrodes for refrigerant level monitoring algorithm allows the machine to keep the chilled
in the evaporators and solution level monitoring water temperature fluctuations within the set
in absorber. values by continuously modulating the control
14
SS SERIES
Steam fired single effect absorption chillers
15
SS SERIES
Steam fired single effect absorption chillers
thermostat set point the machine trips. compare it with the calculated critical value. If
Chilled water pump interlock. The chilled actual concentration is too close to the critical
water flow is essential for the machine operation. value, concentration control system takes the
A potential free contact is to be wired from the control of the machine, modulating the control
chilled water pump motor starter or from one valve to take the concentration level back to safe
flow switch (in customer scope) to the machine values.
panel to sense the chilled water pump on/off/ Level electrodes in absorber. When the
trip status. The machine starts only if the chilled solution level in absorber goes below a set value,
water pump is on. In case the chilled water the solenoid valve on refrigerant line gets open
pump trips and in order to avoid the freezing and refrigerant is directly sent to absorber. When
of the static chilled water in the tubes inside the solution level goes below the minimum set,
the machine, it is mandatory to stop the cooling the control valve is closed until the level has
water pump. For this reason it is mandatory that raised to a safety level.
the PLC has control over the chilled and cooling
water pumps. Four potential free contacts are • Cavitation protection of refrigerant pump
provided in the panel to control the pumps If the refrigerant level in the evaporator pan falls
switching on and off. excessively, the pressure in the refrigerant pump
Chilled water differential pressure switch. If suction drops below the saturation pressure of
the chilled water flow drops below 50% of the the refrigerant and the refrigerant pump starts
rated value, machine trips. to cavitate. To ensure the minimum acceptable
Chilled water flow switch. If the chilled suction pressure the level of the refrigerant is
water flow drops below 50% of the rated value, not allowed to fall below a certain level. This is
machine trips. done by means of three level electrodes RE1,
RE2, RE3 and a level relay, 33RL.
• Crystallisation prevention The three electrodes are mounted in the
If the concentrated solution returning to the refrigerant level box assembly on the lower shell
absorber from the generator is excessively (evaporator side). RE1 electrode is the smallest
cooled, it crystallises in the heat exchanger in length and RE3 is the longest. The level is
and the operation of the machine is affected. maintained between RE1 and RE2. RE3 acts as
Crystallisation occurs either when the a reference electrode. When the level reaches
concentration of the solution (for a particular RE1, the pump starts and when goes below
temperature) goes too high or its temperature RE2, the pump stops and restarts only when the
(for a particular concentration) goes too low. The level reaches RE1 again. When the level goes
following safety functions prevent the machine below RE2, a delay of 20 seconds is provided
from crystallising: before the pump is switched off.
Control valve. When the generator temperature
is more than the critical temperature set in the • Motors protection
PLC, the control valve immediately closes. This Solution, refrigerant and purge pump overload
is to avoid a further increase in concentration. relay.
Generator high temperature safety. If the
INFORMATION DISPLAY
generator temperature exceeds the generator
high temperature set point, the machine trips. Operating information is in English language with
Cooling water low temperature safety. If the SI units. Standard information shown are:
cooling water inlet temperature drops below the • Chilled water inlet and outlet temperatures.
cooling water low temperature set point, the • Cooling water inlet and outlet temperatures.
machine trips. • Concentrated solution temperature at generator
Active concentration control. By means of outlet.
a series of different sensors, machine’s PLC is • Concentrated solution temperature sprayed in
able to calculate in every moment the maximum absorber.
solution concentration inside the machine and
16
SS SERIES
Steam fired single effect absorption chillers
ACCESSORIES
• Special tubes material for shell and tube heat
exchangers, based on the water quality circulating
17
SS SERIES
Steam fired single effect absorption chillers
TECHNICAL DATA
MODEL Unit SS 20A SS 20B SS 20C SS 20D SS 30A SS 30B
Fouling factor = 0,044 m2 K/kW in chilled water line, 0,086 m2 K/kW in cooling water line
For working conditions different from above, please contact authorized Thermax office to request a customized selec-
tion.
18
SS SERIES
Steam fired single effect absorption chillers
Fouling factor = 0,044 m2 K/kW in chilled water line, 0,086 m2 K/kW in cooling water line
For working conditions different from above, please contact authorized Thermax office to request a customized selec-
tion.
19
SS SERIES
Steam fired single effect absorption chillers
Fouling factor = 0,044 m2 K/kW in chilled water line, 0,086 m2 K/kW in cooling water line
For working conditions different from above, please contact authorized Thermax office to request a customized selec-
tion.
20
SS SERIES
Steam fired single effect absorption chillers
Fouling factor = 0,044 m2 K/kW in chilled water line, 0,086 m2 K/kW in cooling water line
For working conditions different from above, please contact authorized Thermax office to request a customized selec-
tion.
21
SS SERIES
Steam fired single effect absorption chillers
H
Model SS 20A SS 20B SS 20C SS 20D SS 30A SS 30B SS 30C SS 40A
Length (L) 2.950 2.950 3.995 3.995 4.135 4.135 4.745 4.930
Width (W) 1.880 1.880 1.880 1.880 2.210 2.210 2.210 2.345
Height (H) 2.830 2.830 2.830 2.830 2.945 2.945 2.945 3.315
B
A
D
22
SS SERIES
Steam fired single effect absorption chillers
Model B C D TOP
All models 500 500 1.200 200
(**): “A” is the clearance space for tubes maintenance and removal. It can be left on either side of the chiller,
depending on the convenience of site.
23
SS SERIES
Steam fired single effect absorption chillers
FOUNDATIONS
T T
150
2
100
1 1 Machine’s foot base
2 Foundation
2 T Machine’s weight on each
=
CTC foundation
B
=
100
100 W 100
= =
24
SS SERIES
Steam fired single effect absorption chillers
INSULATION
25
SS SERIES
Steam fired single effect absorption chillers
110
105
100
95
90
85
80
4 6 8 10 12
Chilled water outlet temperature (°C)
104
102
100
98
96
94
92
3 4 5 6 7 8 9
Chilled water temperature DT (°C)
26
SS SERIES
Steam fired single effect absorption chillers
100
90
80
70
20 22 24 26 28 30 32 34
Cooling water inlet temperature (°C)
95
Cooling capacity (%)
90
85
80
75
70
50 70 90 110 130 150
Steam pressure (kPa g)
27
SS SERIES
Steam fired single effect absorption chillers
4...20mA
MAKE UP E/P
COOLING
TOWER WATER
STEAM
T T
BLOWDOWN
T
T
(*)
T
HL
T I
FM
CHILLED WATER
LL
CONDENSATE TANK
TO BOILER
COOLING WATER
28
SS SERIES
Steam fired single effect absorption chillers
NOTES
29
Distribuidor en exclusiva para España: