PERHITUNGAN FLOOR DECK

1. Data Perencanaan
1) Berat sendiri beton = 2400 kg/m3
2) Berat sendiri floor deck tebal 0,9 mm = 12,48 kg/m2
3) Berat spesi tebal per 1 cm = 21 kg/m2
4) Berat keramik = 24 kg/m2
5) Berat ducting + mekanikal = 19 kg/m2
6) Berat plafond + penggantung = 18 kg/m2
7) F’c = 30 Mpa (N/mm2)
8) Fy = 400 Mpa (N/mm2)

2. Analisis Pembebanan
A. Beban Mati (DL)
1) Berat sendiri beton tebal = 2400 x 0,12 = 288 kg/m2
2) Berat sendiri floor deck (tebal 0,9 mm) = 12,48 kg/m2
3) Berat spesi per cm tebal = 21 x 2 = 42 kg/m2
4) Berat keramik = 24 kg/m2
5) Berat ducting + mekanikal = 19 kg/m2
6) Berat plafond + penggantung = 18 kg/m2
+
2
DL = 403,48 kg/m

B. Beban Hidup (LL)


1) Beban hidup asrama = 250 kg/m2
+
LL = 250 kg/m2
C. Beban Maksismum Yang Digunakan
Beban maksimum yang digunakan = 403,48 kg/m2 → dipakai beban
berguna 500 kg/m2

Tabel 4.2 Brosur spesifikasi floor deck

3. Perhitungan Tebal Plat dan Tulangan Negatif


1) Data Perhitungan
a) Beban berguna (tabel brosur) = 500 kg/m2
b) Jarak antar balok rencana
Tipe B1 (arah y) = 350 cm
Tipe B1 (arah x) = 330 cm
c) Jarak antar kuda-kuda = 300 cm
d) Data floor deck dari brosur
T (tebal floor deck) = 0,90 mm
L = 350 cm
Q maks = 500 kg/m2
T (tebal pelat beton) = 15 cm
Berat per luas = 12,48 kg/m2
Berat per panjang = 7,36 kg/m
Bentang menerus tulangan negative (A) = 5,95 cm2/m = 595 mm2/m
e) Tulangan rencana ф = 10 mm → As = 78,54 mm2
A
f) Banyaknya tulangan tiap 1 meter =
As
595 𝑚𝑚2
= 78.54 𝑚𝑚2 = 7,6  10 buah
1000 𝑚𝑚
g) Jarak tulangan tarik = = 100 mm
100

Maka dipakai tulangan tarik = ф 10 - 100 mm


4. Perhitungan Shear Connector (Stud Connector)
a. Data Shear Connector (stud) yg dipakai
d = 20 mm
H = tebal plat beton + tinggi balok WF
= 120 mm + 500 mm = 620 mm
Asc = ¼ x  x d2
= ¼ x 3,14 x (20 mm)2 = 314,16 mm2
Fu = 410 MPa (N/mm2)
Fy = 250 MPa (N/mm2)
L = 6.000 mm
S = 3.000 mm
Hr = 53 mm
wr = 32 mm
Hs = hr + selimut beton
= 53 mm + 40 mm = 93 mm
tb = 120 mm – 53 mm = 67 mm

b. Data beton
9) F’c = 25 MPa (N/mm2)
10) Ec = 4.700 x √fc′
= 4.700 x √25 MPa
= 23.500 N/mm2
c. Kekuatan shear connector stud (1 buah stud)
Qn = 0,5 x Asc x (fc’ x Ec)0,5
= 0,5 x 314,16 mm2 x (25 N/mm2 𝑥 23.500 N/mm2)0,5
= 120.399,26 N
Asc x Fu = 314,16 mm2 x 410 N/mm2 = 128.805,3 N
Maka, Qn  Asc x Fu
120.399,26 N < 163.362,8 N (OK)
d. Kontrol Koefisien Reduksi
wr hs
rs = 0,6 x (
hr
) x (hr − 1)  1
32 mm 93 mm
= 0,6 x (
53 mm
) x (53 mm − 1)  1
= 0,6 x 0,6 x (1,75 − 1)  1
rs = 0,27 < 1
Maka,
Qn = Qn x rs
= 120.399,26 N x 0,27 = 32.917,99 N
e. Gaya Geser Horizontal (Vn = c)
As (connector) =
C1 = As x fy
= 314,16 mm2 x 250 N/mm2
= 78.539,816 N
C2 = 0.85 x fc’ x Ac
= 0.85 x 25 N/mm2 x (beff x tb)

𝐿 6.000 𝑚𝑚
Dimana, beff = = = 1.500 mm
4 4
beff = 1.500 mm  S = 3.000 mm (OK)
Maka, C2 = 0,85 x fc’x (beff x tb)
= 0,85 x 25 N/mm2 x (1.500 mm x 67 mm)
= 2.135.62 5 N
C2  C1
Sehingga, Vn = C2 (gaya geser 1 conector)
= 2.135.625 N

f. Menentukan Banyaknya Stud (N)


Vn 2.135.625 N
N= = = 64,88
Qn 32.917,99 N

Jadi, jumlah connector = 64,88 buah  65 buah.


𝐿
dengan jarak bentang menerus = (𝑛/2)
600 𝑐𝑚
= = 18,46 cm = 18 cm
(65/2)

Sehingga dipakai connector 2 baris dengan jarak 18 cm.


tb
hr

Balok WF 500.200.9.14

6.000 mm
Gambar 4.4 Perletakan Stud Connector

mutu E70xx

18 cm

Gambar 4.5 Detail pemasangan Stud Connector

g. Control las
11) Baja BJ 37  Fy = 240 MPa (N/mm2) = 2.400 kg/cm2
Fu = 370 MPa (N/mm2) = 3.700 kg/cm2
12) Fu las E70xx = 70 Ksi = 70 x 70,3 kg/cm3
13) Akibat Pu, maka
𝑄𝑛 32.917,99 𝑘𝑔
Pu = = = 3.358,98 kg
𝑔 9,8

Pu
fvp =
 x d2 x 0,25
3.358,98 kg
=
3,14 x (2𝑐𝑚)2 x 0,25
3.358,98 kg
=
3,14 cm2

= 1.069,20 kg/cm2

Fu =  x 0,6 x F70xx
= 0,75 x 0,6 x 70 x 70,3 kg/cm3
= 2.214,45 kg/cm3

fvp
Te =
fu
1.069,20 𝑘𝑔/𝑐𝑚2
=
2.214,45 𝑘𝑔/𝑐𝑚3
= 0,48 cm

te
a =
0,707
0,48 𝑐𝑚
=
0,707
= 0,68 cm