Sie sind auf Seite 1von 38

Coordination #5

COORINATION ON ETAP
TUTORIAL
#5

JP Engineering
Engr. Junjie G. Pito
Coordination #5

INTRODUCTION

JP Engineering
Engr. Junjie G. Pito
Coordination #5
BREAKER CHARACTERISTIC TRIPPING TIME

UNPROTECTED
AREA

PROTECTED
AREA

JP Engineering
Engr. Junjie G. Pito
Coordination #5
BREAKER CHARACTERISTIC

MAXIMUM
CLEARING TIME

MINIMUM
CLEARING TIME

JP Engineering
Engr. Junjie G. Pito
Coordination #5
BREAKER CHARACTERISTIC

IEEE 242 PAGE 211

JP Engineering
Engr. Junjie G. Pito
Coordination #5
BREAKER CHARACTERISTIC

CABLE AMPACITY/
UNPROTECTED PANELBOARD
PROTECTED
AREA OVERLOADING AREA

PANELBOARD LOAD
TRANSFORMER
DAMAGE CURVE

MOTOR CURVE

CABLE
DAMAGE CURVE

FAULT
TRANSFORMER INRUSH
CURRENT

JP Engineering
Engr. Junjie G. Pito
Coordination #5
BREAKER CHARACTERISTIC

LONG TIME PICKUP

LONG TIME
BAND/DELAY

SHORT TIME PICKUP

SHORT TIME INSTANTANEOUS PICK UP


BAND/DELAY

JP Engineering
Engr. Junjie G. Pito
Coordination #5

IEEE 242 PAGE 212

JP Engineering
Engr. Junjie G. Pito
Coordination #5

IEEE 242 PAGE 597

JP Engineering
Engr. Junjie G. Pito
Coordination #5

ETAP

JP Engineering
Engr. Junjie G. Pito
Coordination #5

PREPARATION ITEMS NEEDED

MATCH ETAP SETTING TO PROJECT SPECIFICATION


BUS

XFORMER

CABLE

IN. MOTOR

LV BREAKER

JP Engineering
Engr. Junjie G. Pito
Coordination #5
PREPARE ONE LINE DIAGRAM
PREPARE TO TRANSFER DATA TO STAR VIEW

STAR SYSTEM

JP Engineering
Engr. Junjie G. Pito
Coordination #5

TCC VIEW

GRID AXIS

Uncheck 0.4kV
TO SHOW THE GRID Check

100/10

JP Engineering
Engr. Junjie G. Pito
Coordination #5

TRANSFERING DATA FROM SLD TO TCC

ARRANGE WITH OF STAR AND


ONE LINE DIAGRAM

JP Engineering
Engr. Junjie G. Pito
Coordination #5

TRANSFERING DATA FROM SLD TO TCC

CLOSE THIS
WINDOW
ARRANGE THIS 2 WINDOW

JP Engineering
Engr. Junjie G. Pito
Coordination #5

TRANSFERING DATA FROM SLD TO TCC

ONE LINE DIAGRAM VIEW AND


STAR VIEW ARE ON SIDE BY SIDE

JP Engineering
Engr. Junjie G. Pito
Coordination #5

TRANSFERING DATA FROM SLD TO TCC

Select All Shift + Drag

JP Engineering
Engr. Junjie G. Pito
Coordination #5

PROTECTION
COORDINATION

JP Engineering
Engr. Junjie G. Pito
INDUCTION MOTOR Coordination #5

MOTOR DATA
Rated Ampere 13.54 A
Acceleration time 3 sec
Rotor Thermal Limit Hot Start = 19 sec.
Cold Start = 42 sec.

JP Engineering
Engr. Junjie G. Pito
MOTOR SETTINGS INDUCTION MOTOR Coordination #5

NAMEPLATE IMP PROTECTION

kV

HP or kW

kVA as
per TER
SET

Adjust
Inrush

JP Engineering
Engr. Junjie G. Pito
INDUCTION MOTOR Coordination #5

MOTOR
PARAMETERS MOTOR FEEDER
PLOTTED

Feeder Size 3C x 6mm²


Feeder Ampacity 36 A

JP Engineering
Engr. Junjie G. Pito
FEEDER SETTINGS INDUCTION MOTOR Coordination #5

INFO LIBRARY AMPACITY

Preferred
Name

Change
Properties

User def. (TER)

JP Engineering
Engr. Junjie G. Pito
INDUCTION MOTOR Coordination #5

CABLE
PARAMETERS
PLOTTED

NEXT WILL BE THE MOTOR


PROTECTION DEVICE
(BREAKER)

JP Engineering
Engr. Junjie G. Pito
PROTECTION SETTING INDUCTION MOTOR Coordination #5

RATING LIBRARY TRIP DEVICE

JP Engineering
Engr. Junjie G. Pito
BUS 2 Coordination #5

NEED TO BE BUS 2
MANUALLY
PLOTTED Rated Ampere 103.98 A
Max. Fault Value 16.1 kA
Min. Fault (0.38) 6.12 kA
Feeder Size 4C x 95mm²
Feeder Ampacity 272 A

JP Engineering
Engr. Junjie G. Pito
BUS 2 Coordination #5

MANUAL PLOTTING SETTING


MANUAL INPUT ON TCC

Preferred
Name

kV = 0.4
F. Value = 16.1

DO THE SAME FOR THE


MINIMUM FAULT
JP Engineering
Engr. Junjie G. Pito
BUS 2 Coordination #5

MANUAL PLOTTING SETTING


MANUAL INPUT ON TCC

Preferred
Name

TO BE VISIBLE IN
THE TCC

JP Engineering
Engr. Junjie G. Pito
BUS 2 Coordination #5

FOR CABLE
THE SAME PROCEDURE AS PREVIOUS SLIDE JP Engineering
Engr. Junjie G. Pito
BUS 2 Coordination #5
PROTECTION SETTING
RATING LIBRARY TRIP DEVICE

JP Engineering
Engr. Junjie G. Pito
BUS 3 Coordination #5

BUS 3
Rated Ampere 354.7 A
Max. Fault Value 29.8 kA
Min. Fault (0.38) 11.3 kA
Feeder Size 2 No. [4C x 120mm²]
Feeder Ampacity 502 A

JP Engineering
Engr. Junjie G. Pito
BUS 3 Coordination #5

THE SAME PROCEDURE AS PREVIOUS SLIDE

JP Engineering
Engr. Junjie G. Pito
BUS 3 Coordination #5

TCC kA

JP Engineering
Engr. Junjie G. Pito
BUS 3 Coordination #5
PROTECTION SETTING
RATING LIBRARY TRIP DEVICE

JP Engineering
Engr. Junjie G. Pito
BUS 5 Coordination #5

BUS 5
Rated Ampere 1701.2 A
Max. Fault Value 40.9 kA
Min. Fault (0.38) 15.5 kA
Feeder Size 4 No. [4C x 630mm²]
Feeder Ampacity 4736 A

Transformer Characteristic – 1600 kVA


@ 6% Z

JP Engineering
Engr. Junjie G. Pito
BUS 5 Coordination #5
TRANSFORMER SETTING
RATING PROTECTION IMPEDANCE

JP Engineering
Engr. Junjie G. Pito
BUS 5 Coordination #5

THE SAME PROCEDURE AS PREVIOUS SLIDE

JP Engineering
Engr. Junjie G. Pito
BUS 5 Coordination #5
PROTECTION SETTING
RATING LIBRARY TRIP DEVICE

JP Engineering
Engr. Junjie G. Pito
Coordination #5

JP Engineering
Engr. Junjie G. Pito

Das könnte Ihnen auch gefallen