JOG MOTOR CONTROL

Definition
Jogging is defined as the brief closure of a motor circuit to energize a motor
for a short period of time and perform a small movement of driven machine.

Figure below illustrates the schematic diagram of the control and power of a
Jog Motor Control.

A motor is jogged for the following reasons: to align and space machine
parts; to position a tool accurately; to thread cloth, paper, or sheet steel; and to
provide small controlled movement.
Home / Circuits / Contactors / Control / Industrial Controls / Magnetic Contactos / Motor Controls / Motor
Starters /Starters / JOG MOTOR CONTROL

JOG MOTOR CONTROL


10:35:00 PM CIRCUITS , CONTACTORS , CONTROL , INDUSTRIAL CONTROLS , MAGNETIC
CONTACTOS , MOTOR CONTROLS ,MOTOR STARTERS , STARTERS

Definition
Jogging is defined as the brief closure of a motor circuit to energize a motor
for a short period of time and perform a small movement of driven machine.

Figure below illustrates the schematic diagram of the control and power of a
Jog Motor Control.
A motor is jogged for the following reasons: to align and space machine
parts; to position a tool accurately; to thread cloth, paper, or sheet steel; and to
provide small controlled movement.

Schematic diagram of the control and power circuits of the “Jog Motor Control“
Control Operation
The start and stop operation of the jog motor control is the same as the start
and stop operation of the across line magnetic starter. In a jog motor control, a dual
push button with one normally motor control open and one normally close contacts
is inserted in between the normal STOP and START push button of the across the line
magnetic starter.

Referring to figure above, when the jog push button is pressed, current will
flow from line L1, normally closed O.L. contacts (95-96), STOP push button, Jog push
button contact (3-4) ,START push button contact (3-4), contactor C (A-B) to line L2.
The contactor C (A-B) will be energize to cause the motor M to run. Motor M will
continue running as long as the jog push button is being pressed.
At this condition the RUN pilot lamp is energize while the IDLE pilot is de-energize
because of the opening of contact C (11-12).Once the Jog push button is depressed
(released) contactor C is de-energized. The motor M will stop contact C (11-12) will
close and the IDLE lamp is energized .Contact C (13-14) will open to de-energized
the RUN pilot lamp. Even if the jog push button closes its contacts (1-2), the
contactor C can no longer energized since contact C (13-14) is already open.