Sie sind auf Seite 1von 52

Installation, Operation,

and Maintenance

Split System Air Conditioners


Odyssey™ ™
Cooling Condenser — 6 to 25 Tons
(60 Hz) (50 Hz)
TTA073D***A TTA061D***A
TTA090D***A TTA076D***A
TTA120D/E/F***A TTA086D***A
TTA150E***A TTA101D/E/F***A
TTA180E/F***A TTA126E***A
TTA240E***A TTA156E/F***A
TTA240F***A TTA201E/F***A
TTA300F***A TTA251F***A

S A F E T Y WA R N I N G
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.

January 2014 SS-SVX10D-EN


Introduction
Read this manual thoroughly before operating or WA R N I N G
servicing this unit.
Prope r Fi el d Wi ring a nd Groundi ng
Warnings, Cautions, and Notices Required!
Fa il u re to f ol lo w c ode c o ul d r es u lt i n de at h or
Safety advisories appear throughout this manual as s e r i o u s i n j u r y.
required. Your personal safety and the proper All field w ir in g MUST be p er for med b y qualif ied
operation of this machine depend upon the strict per sonnel. Improperly installed and grounded
observance of these precautions. field wiring poses FIRE and ELECTROCUTION
h a z a r d s . To a v o i d t h e s e h a z a r d s , y o u M U S T f o l l o w
The three types of advisories are defined as follows:
requirements for field wiring installation and
Indicates a potentially hazardous situation grounding as described in NEC and your local/
WARNING which, if not avoided, could result in death or state electrical codes.
serious injury.

CAUTION
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
WA R N I N G
moderate injury. It could also be used to alert Pe r s o n a l P r o t e c t i v e E q u i p m e n t ( P P E )
against unsafe practices.
Required!
Indicates a situation that could result in
NOTICE Fa il u re to w ea r pro pe r PPE f or t he j ob b ei ng
equipment or property-damage only
accidents. u n d e rt a k e n c o u l d r e s u l t i n d e a t h o r s e r i o u s i n j u r y.
Te ch n i c i a n s , i n o r d e r t o p r o t e c t t h e m s e l v e s f r o m
p o t e n t i a l e l e c t r i c a l , m e ch a n i c a l , a n d ch e m i c a l
Important Environmental Concerns h azards, MUST follow pr ecaut io ns in th is man ual
Scientific research has shown that certain man-made a n d o n t h e t a g s , s t i ck e r s , a n d l a b e l s , a s w e l l a s t h e
chemicals can affect the earth’s naturally occurring instructions below:
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified • Before installing/servicing this unit,
chemicals that may affect the ozone layer are t e ch n i c i a n s M U ST p u t o n a l l Pe r s o n a l
refrigerants that contain Chlorine, Fluorine and Carbon Pr o t e c t i v e E q u i p m e n t ( P P E ) r e c o m m e n d e d
(CFCs) and those containing Hydrogen, Chlorine, f o r t h e w o r k b e i n g u n d e rt a k e n . A LWAY S r e f e r
Fluorine and Carbon (HCFCs). Not all refrigerants to appropriate MSDS sheets and OSHA
containing these compounds have the same potential guidelines for proper PPE.
impact to the environment. Trane advocates the • When working with or around hazardous
responsible handling of all refrigerants-including ch e m i c a l s , A LWAY S r e f e r t o t h e a p p r o p r i a t e
industry replacements for CFCs such as HCFCs and MSDS sheets and OSHA guidelines for
HFCs. in for mat io n on a ll owa bl e pe r s ona l e x pos ur e
levels, proper respiratory protection and
Important Responsible Refrigerant handling recommendations.
Practices • I f t h e r e i s a r i s k o f a r c o r f l a s h , t e ch n i c i a n s
Trane believes that responsible refrigerant practices are M U S T p u t o n a l l Pe r s o n a l P r o t e c t i v e
important to the environment, our customers, and the E q u i p m e n t ( P P E ) i n a c c o r d a n c e w i t h N F PA
air conditioning industry. All technicians who handle 7 0 E o r o t h e r c o u n t r y- s p e c i f i c r e q u i r e m e n t s
refrigerants must be certified. The Federal Clean Air Act for arc flash protection, PRIOR to servicing
(Section 608) sets forth the requirements for handling, the unit.
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow
them.

©2014 Trane All rights reserved SS-SVX10D-EN


Introduction

WA R N I N G Copyright
Re f r i g e r a n t u n de r H i g h Pr e s s u r e ! This document and the information in it are the
Fai l ure t o fol l ow i ns tr uc ti on s be l ow c ou ld re s ul t in property of Trane and may not be used or reproduced
a n e x p l o s i o n w h i ch c o u l d r e s u l t i n d e a t h o r s e r i o u s in whole or in part, without the written permission of
injury or equipment damage. Trane. Trane reserves the right to revise this publication
at any time and to make changes to its content without
Sy s t e m c o n t a i n s o i l a n d r e f r i g e r a n t u n d e r h i g h
obligation to notify any person of such revision or
pre ssu re . Recove r r ef ri ge ra nt to re li e ve pre ssu re
befor e op en in g t he system. See u nit namep late for change.
re fri ge ra nt ty pe . Do no t u se non -a pp rove d
refrigerants, refrigerant substitutes, or refrigerant Trademarks
additi ves.
All trademarks referenced in this document are the
trademarks of their respective owners.
WA R N I N G
R - 4 10 A R e f r i g e r a n t u n d e r H i g h e r Revision History
Pr e s s u r e t h a n R - 2 2 ! Removed warranty chapter, updated with running
Fai l ure t o us e pr ope r eq ui pm e nt o r c om p on en ts a s edits.
de sc ri b ed be l ow, c ou ld re s ul t i n e qu i pme nt fa i li ng
a n d p o s s i b l y e x p l o d i n g , w h i ch c o u l d r e s u l t i n
d e a t h , s e r i o u s i n j u r y, o r e q u i p m e n t d a m a g e .
T h e u n i t s d e s c r i b e d i n t h i s m a n u a l u s e R - 4 10 A
r e f r i g e r a n t w h i ch o p e r a t e s a t h i g h e r p r e s s u r e s
t h a n R - 2 2 . U s e O N LY R - 4 10 A r a t e d s e r v i c e
eq ui pm e nt or c om p one nt s w it h the s e un it s. For
s p e c i f i c h a n d l i n g c o n c e r n s w i t h R - 4 10 A , p l e a s e
c o n t a c t y o u r l o c a l Tr a n e r e p r e s e n t a t i v e .

SS-SVX10D-EN 3
Table of Contents
Model Number Description . . . . . . . . . . . . . . . . . 6 Control Circuit Features . . . . . . . . . . . . . . . . . . 41
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . 6 Discharge Temperature Limit
(DTL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
General Information . . . . . . . . . . . . . . . . . . . . . . . . 7 Low Outdoor Ambient Cooling . . . . . . . . 41
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Evaporator Defrost Control
(EDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Low Pressure Cut-Out (LPCO) . . . . . . . . . 41
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 High Pressure Cut-Out (HPCO) . . . . . . . . 41
Inspection Checklist . . . . . . . . . . . . . . . . . . . 8 Internal Overload Protector
(IOL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Testing for Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . 8
Lifting Recommendations . . . . . . . . . . . . . . . . . 8 Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Electromechanical Controls. . . . . . . . . . . . . . . 42
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Unit Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Evaporator Fan (Indoor Supply
Structural Preparation . . . . . . . . . . . . . . . . . 9 Air) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Rooftop Mounting . . . . . . . . . . . . . . . . . . . . 9 Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . 42
Ground Level Mounting . . . . . . . . . . . . . . . 9
ReliaTel™ Controls . . . . . . . . . . . . . . . . . . . . . . 42
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . 10 Control Cooling Mode . . . . . . . . . . . . . . . . 42
Control Evaporator Fan
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . 19 Control Heating Operation . . . . . . . . . . . . 43
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Service Test Modes for ReliaTel™
Refrigerant Piping Guidelines. . . . . . . . . . . . . 21 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Refrigerant Piping Procedures (Outdoor Test Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Units). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Step Test Mode . . . . . . . . . . . . . . . . . . . . . . 44
Resistance Test Mode . . . . . . . . . . . . . . . . 44
Refrigerant Piping Procedures (Indoor Auto Test Mode . . . . . . . . . . . . . . . . . . . . . . 44
Unit). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Leak Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
System Evacuation. . . . . . . . . . . . . . . . . . . 23 Troubleshooting ReliaTel™ Controls. . . . . . . 45
Insulating and Isolating Refrigerant System Status Checkout Procedure . . . . . . . 45
Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Method 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Refrigerant Charging Procedure . . . . . . . . . . 24 Method 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Liquid Charging . . . . . . . . . . . . . . . . . . . . . . . . . 26 Resetting Cooling and Heating


Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 27 Method 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Unit Power Supply . . . . . . . . . . . . . . . . . . . 27 Method 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Low Voltage Wiring . . . . . . . . . . . . . . . . . . 28
Electromechanical Controls . . . . . . . . . . . 28 Zone Temperature Sensor (ZTS) Service
ReliaTel™ Controls . . . . . . . . . . . . . . . . . . . 28 Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 29 Temperature Tests . . . . . . . . . . . . . . . . . . . . . . . 47
Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . 31 Test 1 - Zone Temperature
Thermistor (ZTEMP). . . . . . . . . . . . . . . . . . 47
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Test 2 - Cooling Set Point (CSP) and
Charging Charts and Superheat . . . . . . . . . . . 35 Heating Set Point (HSP). . . . . . . . . . . . . . . 47
Test 3 - System Mode and Fan
Installation Checklist. . . . . . . . . . . . . . . . . . . . . . . 40 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . 40 Test 4 - LED Indicator Test (SYS ON,
HEAT, & COOL). . . . . . . . . . . . . . . . . . . . . . . 48
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 40
Programmable & Digital Zone Sensor
Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

4 SS-SVX10D-EN
Ta b l e o f C o n t e n t s

Testing Serial Communication Maintenance Log . . . . . . . . . . . . . . . . . . . . . . . . 50


Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
RLCI Loss of Communications. . . . . . . . . 48 Wiring Diagram Matrix . . . . . . . . . . . . . . . . . . . . 51

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Annually (Cooling Season) . . . . . . . . . . . . . . . 49
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

SS-SVX10D-EN 5
Model Number Description
Cooling Condenser
TTA 2 40 F 3 00 * *

123 456 7 8 9 10 11 12

TTA 201 F D 00 * *

123 456 7 8 9 10 11 12

All products are identified by a multiple-character E = Dual Compressor, Dual Circuit


model number that precisely identifies a particular type F = Dual Compressor, Single Circuit (Manifold Scroll
of unit. An explanation of the alphanumeric Compressors)
identification code is provided. Its use will enable the
DIGIT 8: Electrical Characteristics
owner/operator, installing contractors, and service
engineers to define the operation, specific 3 = 208–230/60/3
components, and other options for any specific unit. 4 = 460/60/3
When ordering replacement parts or requesting W = 575/60/3
service, be sure to refer to the specific model number, D = 380-415/50/3
serial number, and DL number (if applicable) stamped K = 380/60/3
on the unit nameplate.
D I G I T S 9 - 10 : F a c t o r y I n s t a l l e d O p t i o n s
D I G I T S 1 - 3 : Pr o d u c t Ty p e
00 = Packed Stock
TTA = Split System Cooling 0S = Black Epoxy Coated Coil
DIGITS 4 - 6: Nominal Gross Cooling Capacity 0R = ReliaTel, no LCI Board
(MBh) 0T = ReliaTel, no LCI Board with Black Epoxy Coated
061 = 5 Tons (50Hz) Coil
076 = 6.25 Tons (50Hz) 0U = ReliaTel, with LCI Board
086 = 7 Tons (50Hz) 0W = ReliaTel, with LCI Board and Black Epoxy Coated
101 = 8.33 Tons (50Hz) Coil
126 = 10.4 Tons (50Hz) H0 = Hail Guard with Packed Stock
156 = 13.0 Tons (50Hz) HS = Hail Guard with Black Epoxy Coated Coil
201 = 16.7 Tons (50Hz) HR = Hail Guard with ReliaTel, no LCI Board
251 = 20.9 Tons (50Hz) HT = Hail Guard with ReliaTel, no LCI Board with Black
Epoxy Coated Coil
073 = 6 Tons (60Hz)
HU = Hail Guard with ReliaTel, with LCI Board
090 = 7.5 Tons (60Hz)
HW = Hail Guard with ReliaTel, with LCI Board and
120 = 10 Tons (60Hz)
Black Epoxy Coated Coil
150 = 12.5 Tons (60Hz)
180 = 15 Tons (60Hz) D I G I T S 11 : M i n o r D e s i g n S e q u e n c e
240 = 20 Tons (60Hz) * = Current Design Sequence1
300 = 25 Tons (60Hz) D I GI TS 12 : Serv i c e D ig it
DIGIT 7: Major Develo pment Seq uence * = Current Design Sequence1
D = Single Compressor, Single Circuit

1. * = sequential alpha character

6 SS-SVX10D-EN
General Information
This manual describes proper installation, operation, N o t e : It is not the intention of this manual to cover all
and maintenance procedures for air-cooled systems. By possible variations in systems that may occur or
carefully reviewing the information within this manual to provide comprehensive information
and following the instructions, the risk of improper concerning every possible contingency that may
operation and/or component damage will be be encountered during an installation. If
minimized. It is important that periodic maintenance be additional information is required or if specific
performed to help assure trouble free operation. problems arise that are not fully discussed in this
Should equipment failure occur, contact a qualified manual, contact your local sales office.
service organization with qualified, experienced HVAC Use the ”Installation Checklist,” p. 40 provided In this
technicians to properly diagnose and repair this manual to verify that all necessary installation
equipment. procedures have been completed. Do not use the
I m p o rt a n t : All phases of this installation must comply checklist as a substitute for reading the information
with the NATIONAL, STATE & LOCAL contained in the manual. Read the entire manual
CODES. In addition to local codes, the before beginning installation procedures.
installation must conform with National
Electric Code -ANSI/NFPA NO. 70 LATEST
REVISION.
Unit Description
Any individual installing, maintaining, or servicing this These condensers come with single, dual and
equipment must be properly trained, licensed and manifolded compressor options. Single compressor
qualified. outdoor units feature a single refrigeration circuitry,
requiring only one set of refrigerant lines. Dual
I m p o rt a n t : Do not remove the VFD without first compressor/dual circuit models give true stand-by
contacting technical support! For protection; if one compressor fails, the second will
performance-related questions and automatically start-up. Also, the first compressor can
diagnostic support in North America call 1- be serviced without shutting down the unit since the
877-872-6363. Any return requires a claim refrigerant circuits are independent. During light load
number FIRST. Removal of the VFD prior to conditions, only one compressor will operate to save
this step will void the unit’s warranties. energy.The dual manifolded scroll compressors come
Installation procedures should be performed in the with two stages of capacity modulation and a single
sequence that they appear in this manual. Do not refrigeration circuit.
destroy or remove the manual from the unit. The
manual should remain weather-protected with the unit
until all installation procedures are complete.

SS-SVX10D-EN 7
Pre-Installation
Unit Inspection Lifting Recommendations
Inspect material carefully for any shipping damage. If
damaged, it must be reported to, and claims made
WA R N I N G
against the transportation company. Compare the I m p r o p e r U n i t L i ft !
information that appears on the unit nameplate with F a i l u r e t o p r o p e r l y l i ft u n i t c o u l d r e s u l t i n u n i t
ordering and submittal data to ensure the proper unit dropping and possibly crushing operator/
was shipped. Available power supply must be t e ch n i c i a n w h i ch c o u l d r e s u l t i n d e a t h o r s e r i o u s
compatible with electrical characteristics specified on i n j u r y, a n d e q u i p m e n t o r p r o p e rt y- o n l y d a m a g e .
component nameplates. Replace damaged parts with Te s t l i ft u n i t a p p r o x i m a t e l y 2 4 i n ch e s t o v e r i f y
authorized parts only. p r o p e r c e n t e r o f g r a v i t y l i ft p o i n t . To a v o i d
d r o p p i n g o f u n i t , r e p o s i t i o n l i ft i n g p o i n t i f u n i t i s
Inspection Checklist not level.
To protect against loss due to damage incurred in
transit, complete the following checklist upon receipt of N OT I C E
the unit.
Equipment Damage!
Inspect individual pieces of the shipment before
Use spreader bar s to prevent straps from
accepting the unit. Check for obvious damage to the
d a m a g i n g t h e u n i t . I n s t a l l t h e b a r s b e t w e e n l i ft i n g
unit or packing material.
s t r a p s , b o t h u n d e r n e a t h t h e u n i t a n d a b ov e t h e
Inspect the unit for concealed damage before it is unit to prevent the straps from crushing the unit
stored and as soon as possible after delivery. cabinet or damaging the finish.
Concealed damage must be reported within 15
days. If concealed damage is discovered, stop Before preparing the unit for lifting, estimate the
unpacking the shipment. Do not remove damaged approximate center of gravity for lifting safety. Because
material from the receiving location. Take photos of of placement of internal components, the unit weight
the damage if possible. The owner must provide may be unevenly distributed. See ”Weights”, p. 19 for
reasonable evidence that the damage did not occur approximate unit weights.
after delivery. The crated unit can be moved using a forklift of suitable
Notify the carrier’s terminal of damage immediately capacity. For lifting the unit, attach lifting straps or
by phone and by mail. Request an immediate joint slings securely to the lifting holes at each corner (see
inspection of the damage by the carrier and the unit drawings in ”Weights”, p. 19). Use spreader bars to
consignee. protect the unit casing from damage. Test lift the unit to
determine proper balance and stability.
Notify the sales representative and arrange for
repair. Do not repair the unit until the damage is
inspected by the carrier’s representative. Clearances
Provide enough space around the unit to allow
Testing for Leaks unrestricted access to all service points. Refer to the
”Dimensional Data,” p. 10 for unit dimensions and
All units are shipped with a holding charge of nitrogen
minimum required service and free air clearances.
in each circuit and should be leak tested before
Observe the following points to ensure proper unit
installation.
operation.
1. Remove the access panel.
1. Do not install the unit under a low overhang.
2. Locate the liquid line or suction line access valve for Condenser discharge must not be restricted—refer
each circuit. to notes in ”Dimensional Data drawings,” p. 10.
3. Install gauges to determine if the circuits are still I m p o rt a n t : Do not obstruct condenser discharge
pressurized. If not, the charge has escaped and air. This can result in warm air
should be repaired as required to obtain a leak-free recirculation through the coil.
circuit.
2. Do not locate the unit in a position where runoff
water can fall into the fan discharge openings.
3. Condenser intake air is supplied from three or four
sides of the unit. Adhere to the minimum required
clearances given in unit dimensional drawings (see
”Dimensional Data,” p. 10).

8 SS-SVX10D-EN
Pre-Installation

Unit Mounting Figure 1. Roof mounted unit

WA R N I N G Ou td o o r Un it
Ga s (S u ctio n )
Mounting Integrity! Lin e - In s u la te d
Fai l ure t o fol l ow i ns tr uc ti on be l ow c ou ld r es ul t i n Liq u id Lin e
death or serious injury or possible equipment or In s u la te d
p r o p e rt y- o n l y d a m a g e . 6”
E n s u r e t h e r o o f s t r u c t u r e s u p p o rt s a r e s t r o n g Un it Mo u n tin g Ra d iu s
Ch a n n e ls
e n o u g h t o s u p p o rt t h e w e i g h t o f t h e u n i t a n d a n y
accessories. Ele va tio n
(Mo u n tin g Fra m e )

Structural Preparation
N OT I C E
Ro o f D a m a g e ! Ro o f
Co n s tru ctio n
Sy s t e m c o n t a i n s o i l a n d r e f r i g e r a n t u n d e r h i g h
pressu re. Roof s shou ld b e pr otected fro m Ro o f Tru s s in g
exposure to oils and refrigerant in the system. If
r o o ft o p i s n o t p r o t e c t e d , d a m a g e t o t h e r o o f m a y
o c c u r. Ce ilin g

I m p o rt a n t : Refer to local building codes for proper


installation. All installation must comply Ground Level Mounting
with local building codes. For ground level installation, the unit base should be
adequately supported and hold the unit near level. The
Rooftop Mounting installation must meet the guidelines set forth in local
If the unit will be roof mounted, determine for certain codes. The support should extend two inches beyond
that the structure is strong enough to support the unit the unit base channels at all points. The unit and
and any required accessories, see ”Weights”, p. 19. The support must be isolated from any adjacent structure to
unit should be elevated on a level, field fabricated four- prevent possible noise or vibration problems. Any
inch steel or wood 4" x 4" mounting frame. Complete ground level location must comply with required
the frame and secure it into position before lifting the clearances given in the unit dimensional drawings (see
unit to the roof. The mounting frame must support a ”Dimensional Data,” p. 10).
minimum of three of the unit’s four sides and should
span roof supports to distribute the load on the roof.

SS-SVX10D-EN 9
Dimensional Data
Figure 2. Height, width and depth measurements

H
W
D
D W

H - in. (mm) W - in. (mm) D - in. (mm)

TTA 061, 073, 076, 090 39.125 (993.8) 42.125 (1070) 36 (914.4)

TTA 086, 101, 120 39.125 (993.8) 52.125 (1324) 40 (1016)

TTA 126, 150 45.125 (1146.1) 52.125 (1324) 40 (1016)

TTA 156, 180, 201, 240TTA180B, 240B 45.125 (1146.1) 95.5 (2425.7) 45.875 (1165.2)

TTA 251, 300 51.125 (1298.6) 95.5 (2425.7) 45.875 (1165.2)

N o t e : Full dimensional data available on next pages.

10 SS-SVX10D-EN
Dimensional Data

Figure 3. 5, 6, 6.25, 7.5 ton condensing unit, single compressor


SEE NOTE 3

NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
W ALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219. 2)
SERVICE PANEL 3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)

SEE NOTE 4
HAIL GUARD
(OP TIONAL)

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE) S EE NOTE 1

35 15/1 6"
HAIL GUARD (912 .8) REFRIGERANT ACCES S
(OP TIONAL) LINE VOLTAGE WITH HAIL GUARD
33 7/8"
(86 0.4)
CONT ROL WIRING

SER VICE P ANEL 39 3/16"


(995.3)
34 1/8" (866.8) 26 15/16"
29 13/16" (684.2)
(757.2) 14 3/8"
16 7/16"
(417.5) (365.1)

1/16"
7 15/16" (1.59) 6" (152.4) 2 7/8"
(201.6) 6" (152.4) (73)
SUCTION LINE
21 11 /16" 1 7/8"
(55 0.9) (47.6) 40 15/16"
LIQUID LINE (1039.8)
33 13/1 6" 41 15/16"
(858 .8) (1065. 2)
WITH HAIL GUARD
SERVIC E P ANEL S IDE

3" (76. 2) 7/16" (11.11) DIA. IS OLATOR MOUNTING


HOLES (OUTS IDE HOLES - 4 P LACES )

40 3/4" BOTTOM
(1035) 34 3/4"
(882.6) OF UNIT

4 3/16"
(106.36)
1 13/16" 27 11/ 16" 2 5/16"
(46) (703.3 ) (58.7)

SS-SVX10D-EN 11
Dimensional Data

Figure 4. 7, 8.33, 10 ton condensing unit, single compressor


SEE NOTE 3

NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
SERVICE PANEL WALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)
HAIL GUARD
SEE NOTE 4 (OP TIONAL)

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE
S EE NOTE 1
39 15 /16"
(1014 .4) REFRIGERANT ACCES S
HAIL GUARD 4 1/4" WITH HAIL GUARD
(OP TIONAL) (108)
1 1/4" 37 15/1 6"
(31.7) LINE VOLTAGE
(963 .6)
CONTROL WIRING

39 1/8"
SER VICE P ANEL (993.8)
34 1/16" (865.2)
29 3/4" 26 7/8"
(755.6) (682.6)
14 5/16"
7 1/2" 8 1/4" (363.5)
(190.5) (209.5)
1/16"
SUCTION LINE (1.6) 1 7/8"
1 15/16" (49.2) 6" 25 11/1 6" 6" (47.6)
LIQUID LINE (152. 4) (652 .5) (152. 4) 2 7/8" (73)
4 15/16" 50 15/16"
(125.4) 37 11/1 6" (1294)
(957 .3)
51 15/16"
(1319.2)
WITH HAIL GUARD

SERVICE P ANEL S IDE

7/16" (11.1) DIA. IS OLATOR MOUNTING


3" (76. 2)
HOLES (OUTS IDE HOLES - 4 P LACES )

50 3/4"
(1289) BOTTOM
44 3/4" OF UNIT
(1136.6)

3 13/16"
(96.8)

2 3/16" 31 11/1 6" 1 11/16"


(55.6) (804.9) (42.9)

12 SS-SVX10D-EN
Dimensional Data

Figure 5. 8.33, 10 ton condensing unit, dual compressor


SEE NOTE 3

NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
W ALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
SERVICE PANEL 3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING).

HAIL GUARD
SEE NOTE 4
(OP TIONAL)

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE)

S EE NOTE 1
39 15 /16"
(1014 .4) REFRIGERANT ACCES S
HAIL GUARD WITH HAIL GUARD
(OP TIONAL) 1 1/4" (31.7)
4 1/4" LINE VOLTAGE
37 15/1 6"
(108) (963 .6)
CONTROL WIRING

34 1/16" 39 1/8"
(865.2) SER VICE P ANEL (993.8)
29 3/4"
(755.6) 26 7/8"
(682.6)
14 5/16"
6 3/8" 7 7/8" (363.5)
(162) (200)
9 1/4" 10 3/8"
LIQUID LINE (235) (263.5) 1/16"
(1.6) 1 7/8"
6" 25 11/1 6" 6" (47.6)
SUCTION LINE (152. 4) (652 .5) (152. 4) 2 7/8" (73)
5 1/16" (128.6)
50 15/16"
3 15/16" (100) 37 11/1 6" (1294)
(957 .3)
51 15/16"
2 1/2" (63.5) (1319.2)
WITH HAIL GUARD
SERVICE P ANEL S IDE

7/16" (11.1) DIA. IS OLATOR MOUNTING


3" (76. 2)
HOLES (OUTS IDE HOLES - 4 P LACES )

50 3/4"
(1289) BOTTOM
44 3/4" OF UNIT
(1136.6)

3 13/16"
(96.8)

2 3/16" 31 11/1 6" 1 11/16"


(55.6) (804.9) (42.9)

SS-SVX10D-EN 13
Dimensional Data

Figure 6. 8.33, 10 ton condensing unit, manifolded compressor


SEE NOTE 3

NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
SERVICE PANEL 2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
W ALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)
HAIL GUARD
SEE NOTE 4 (OP TIONAL)

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE)

S EE NOTE 1
39 15 /16"
(1014 .4) REFRIGERANT ACCES S
HAIL GUARD 1 1/4" (31.7)
WITH HAIL GUARD
(OP TIONAL)
4 1/4" LINE VOLTAGE
(108) 37 15/1 6"
CONTROL WIRING (963 .6)

34 1/16" 39 1/8"
SER VICE P ANEL (993.8)
29 3/4" (865.2)
(755.6) 26 7/8"
(682.6)
8 5/16" 14 5/16"
(211) (363.5)

SUCTION LINE 1/16"


(1.6) 1 7/8"
4 15/16" (125.4) 6" 25 11/1 6" 6" (47.6)
LIQUID LINE
(152. 4) (652 .5) (152. 4) 2 7/8" (73)
1 15/16" (49.2)
50 15/16"
37 11/1 6" (1294)
(957 .3)
51 15/16"
(1319.2)
WITH HAIL GUARD
SERVICE P ANEL S IDE

7/16" (11.1) DIA. IS OLATOR MOUNTING


3" (76. 2) HOLES (OUTS IDE HOLES - 4 P LACES )

50 3/4" BOTTOM
(1289) 44 3/4" OF UNIT
(1136.6)

3 13/16"
(96.8)

2 3/16" 31 11/1 6" 1 11/16"


(55.6) (804.9) (42.9)

14 SS-SVX10D-EN
Dimensional Data

Figure 7. 10.4, 12.5 ton condensing unit, dual compressor


SEE NOTE 3 NOTES :
1. ACCES S OP ENING IS FOR FIELD INS TALLED BAYLOAM ACCES S ORY.
2. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
WALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
3. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
SERVICE PANEL
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING).

SEE NOTE 4
HAIL GUARD
(OP TIONAL)

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 2
FOR CLEARANCE

1 1/4" (31.7)
39 15 /16"
(1014 .4)
HAIL GUARD 4 1/4" WITH HAIL GUARD S EE NOTE 1
(OP TIONAL) (108) LINE VOLTAGE 37 15/1 6"
(963 .6) REFRIGERANT ACCES S
CONTROL WIRING

35 3/4" 44 3/4"
SER VICE P ANEL
(908) (1136.6)
42 5/16" 32 7/8"
(1074.7) (835)
14 5/16"
9 5/16" (363.5)
(236.5)
1/16"
11 3/8" (1.6)
LIQUID LINE 7 7/8" (289) 25 11/1 6"
6 3/8" 6" 6" 1 13/16"
(652 .5)
(161.9) (200) (152. 4) (152. 4) (46)
37 11/1 6"
SUCTION LINE (957 .3) 2 7/8"
5 1/16" (128.6) (73)
50 15/16"
(1294)
3 3/16" (81)
SERVI CE P ANEL S IDE 51 15/16"
(1319.2)
WITH HAIL GUARD
3" (76. 2)

7/16" (11.1) DIA. IS OLATOR MOUNTING


HOLES (OUTS IDE HOLES - 4 P LACES )

50 3/4"
44 3/4" BOTTOM
(1289)
(1136.6) OF UNIT

3 13/16 "
(96.8)
2 3/16" 31 11 /16" 1 11/16"
(55.6) (804.9 ) (42.9)

SS-SVX10D-EN 15
Dimensional Data

Figure 8. 13, 16.7, 15, 20 ton condensing unit, dual compressor

SEE NOTE 2 NOTES :


1. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
WALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
2. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
3. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)

HAIL GUARD
(OP TIONAL)
SEE NOTE 3

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 1
FOR CLEARANCE)

SERVICE PANEL
DETAIL A 46"
95 7/16" (1168.4)
(2424) WITH HAIL GUARD
WITH HAIL GUARD
41 7/16" 44"
(1052.5) (1117. 6)

HAIL GUARD
(OP TIONAL) HAIL GUARD
(OP TIONAL)

45 1/8"
(1146.2)

3 3/8" 1/16"
(85.7) 3/16"
SER VICE (1.6)
6 5/8" (4.8)
P ANEL
(168.3) 41 3/8"
(1051) 9" 25 11/16" 9"
(228.6) (652.5) (228. 6)
93 5/16"
(2370.1)
9 1/4" (235)

6 13/16" (173)
7/16" (11.1) DIA. ISOLATOR MOUNTING 1 3/16" (30.2)
CONTROL
HOLES (OUTS IDE HOLES - 4 P LACES ) LINE VOLTAGE WIRING

SERVICE PANEL SIDE


S UCTION LINE

REFRIGERANT ACCES S
41 5/8"
39 7/8" (1057.3)
(1012.8)
18 3/4"
BOTTOM OF UNIT
41 1/ 2" (476.2) 14 5/8"
36 7/8" (105 4) (371.5)
(936.6)
12 9/16"
(319.1) LIQUID LINES
5 9/16"
4 3/8"
(141.3)
(111.1)
3" (76. 2) 2 3/16" 6 13/16" S UCTION LINE 6 5/16" (160.3)
87" (55.6) (173)
(2210) 3 11/16" (93.7)
93" 15/16" (23.8)
(2362.2)
FRO NT DETAIL A
DIMENS IONAL DETAIL

16 SS-SVX10D-EN
Dimensional Data

Figure 9. 13, 16.7, 15, 20 ton condensing unit, manifolded compressor

SEE NOTE 2 NOTES :


1. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
WALLS , S HRUBBERY, P RIVACY FENCES ETC. MINIMUM CLEARANCE
B ETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
C LEARANCE 48" (1219.2)
2. TOP DIS CHARGE AREA S HOULD BE UNRES TRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
3. OUTDOOR AIR TEMP ERATURE S ENS OR OP ENING (DO NOT BLOCK OP ENING)

HAIL GUARD
(OP TIONAL)
SEE NOTE 3

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 1
FOR CLEARANCE)

SERVICE PANEL
DETAIL A
46"
95 7/16" (1168.4)
(2424) WITH HAIL GUARD
WITH HAIL GUARD 44"
(1117. 6)

HAIL GUARD
(OP TIONAL) HAIL GUARD
(OP TIONAL)

45 1/8"
(1146.2)

1/16"
3/16"
SER VICE (1.6)
41 1/4" (4.8)
P ANEL
(1047.8)
9" 25 11/16" 9"
93 5/16"
(228.6) (652.5) (228. 6)
(2370.1)

6 13/16" (173)
7/16" (11.1) DIA. ISOLATOR MOUNTING
HOLES (OUTS IDE HOLES - 4 P LACES )
1 3/16" (30.2)
CONTROL WIRING
SERVICE PANEL SIDE
LINE VOLTAGE

S UCTION LINE

REFRIGERANT ACCES S
39 7/8" 41 5/8"
(1012.8) (1057.3)
BOTTOM OF UNIT 41 1/ 2" 20 1/16"
36 7/8" (105 4) (509.6) 14 5/8"
(936.6) (371.5)

4 1/8"
(104.8) 15/16" (23.8)
LIQUID LINE
3" (76. 2) 2 3/16" 6 13/16" 3 3/8" (85.7)
87" (55.6) (173)
(2210) 6 5/16" (160.3)
93" 9 1/4" (235)
(2362.2)
FRO NT DETAIL A
DIMENS IONAL DETAIL

SS-SVX10D-EN 17
Dimensional Data

Figure 10. 20.9, 25 ton condensing unit, manifolded compressor

S EE NOTE 2 NOTES :
1. MINIMUM CLEARANCE FOR P ROP ER OP ERATION IS 36" (914.4) FROM
WALLS, S HRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJ ACENT UNITS IS 72" (1828.8). RECOMMENDED S ERVICE
CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA S HOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT S HOULD BE P LACED S O ROOF RUN-OFF WATER DOES
NOT P OUR DIRECTLY ON UNIT
3. OUTDOOR AIR TEMP ERATURE S ENS OR OPENING (DO NOT BLOCK OP ENING)

SEE NOTE 3

DETAIL A

S ERVICE CLEARANCE
48" (1219.2) (S EE NOTE 1
FOR CLEARANCE) S ERVICE P ANEL

CONTROL WIRING

LINE VOLTAGE 7 13/16" (198.4) 46"


(1168.4)
6 7/16" (163.5) WITH OUT HAIL GUARD
HAIL GUARD 44 3/16"
.38" (9.7)
(OP TIONAL) (UNIT COIL) (1122.4)

HAIL GUARD
(OP TIONAL)
47 1/4"
(1200.1)
50 3/4" (1289.05)
41 7/16"
(1052.5)

13 11/16" 15 7/16"
(347.7) (381)

S UCTION LIQUID LINES .9"


LINES 6 13/16" (22.9)
(173) 9" 25 11/16" 9"
(228.6) (652.5) (228.6)
8 5/16" 38 7/8"
(211.1) (987.425)
93 5/16"
(2370.1)
5 13/16" (147.6)
OP TIONAL REAR ACCESS 7/16" DIA. IS OLATOR
DIMENS IONAL DETAIL MOUNTING HOLES LINE VOLTAGE CONTROL WIRING
(OUTS IDE HOLES - 4 P LACES )

S ERVICE P ANEL S IDE


S UCTION LINES

REFRIGERANT ACCES S
47 3/4"
LIQUID LINES 40 5/8" (1212.8)
(1031.9)
36 7/8"
BOTTOM OF UNIT (936. 6) 41 1/2"
14 5/8"
(1054.1)
(371.5)
S CALE 1. 000

1 11/16" (42.9)
6 13/16" 4 1/4"
(173) 41 3/8"
(108) 1 5/16"
S CALE 1. 00 0

(1051)
(33.3)
8 1/4"
3" 2 3/16" (209.5)
(76.2) (55.6)
87"
(2209.8) FRONT DETAIL A
93" DIMENS IONAL DETAIL
(2362.2)

18 SS-SVX10D-EN
Weights
Cooling Condenser
Table 1. TTA unit and corner weights — lbs (60 Hz)

Shipping Net Max Corner Weights


Tons Model No.
Max (lbs) (lbs)
1 2 3 4

6 TTA073D 365 300 85 90 44 81

7.5 TTA090D 363 298 84 89 44 81

TTA120D 467 395 133 103 70 89

10 TTA120E 510 438 137 127 88 86

TTA120F 509 438 129 140 83 86

12.5 TTA150E 543 468 130 151 79 108

TTA180E 850 723 207 204 151 161


15
TTA180F 852 725 196 208 153 168

TTA240E 970 837 262 240 164 171


20
TTA240F 966 835 257 249 153 176

25 TTA300F 1168 1037 338 266 241 194

Table 2. TTA unit and corner weights — lbs (50 Hz)


Shipping Net Max Corner Weights
Tons Model No.
Max (lbs) (lbs) 1 2 3 4
5 TTA061D 164 135 38 41 20 36
6.25 TTA076D 163 134 38 40 20 36
7 TTA086D 213 181 61 47 32 41
TTA101D 210 178 60 47 31 40
8.33 TTA101E 230 197 62 57 40 39
TTA101F 229 197 58 63 37 39
10.4 TTA126E 244 211 59 68 36 49
TTA156E 383 325 93 92 68 72
13
TTA156F 383 326 88 94 69 76
TTA201E 437 377 118 108 74 77
16.7
TTA201F 435 376 116 112 69 79
20.9 TTA251F 530 470 153 121 109 88

SS-SVX10D-EN 19
We i g h t s

Figure 11. TTA073, 090, 120, 150, TTA061, 076, 101 Figure 12. TTA180, 240, 300, TTA156, 201, 251
#3 #4

#4 #1

#1
#3

#2
S ER
AC C VIC E
ES S #2

S ER
S ER AC C VIC E
ES S
AC C VIC E
ES S

LIFTING HOLES
(BOTH S IDES )

LIFTING HOLES (BOTH S IDES )

20 SS-SVX10D-EN
Installation
Refrigerant Piping Guidelines
Figure 13. Allowable elevation difference: Cooling only TTA above indoor unit

Contact m an ufacturer for review

Figure 14. Allowable elevation difference: TTA below indoor unit

Contact m anufacturer for review

Accep tab le liq uid -riser heig ht


b ased on total liq uid -lin e len g th
(TTA b elow ind oor un it)

N o t e : Route refrigerant piping for minimum linear length, minimum number of bends and fittings (no reducers) and
minimum amount of line exposed to outdoor ambients.

SS-SVX10D-EN 21
Installation

Refrigerant Piping Procedures N OT I C E


(Outdoor Units) Syste m Component Dam age!
Do no t remov e th e sea l ca ps f rom re fr ig era nt
WA R N I N G connections, or open the service valves until
R - 4 10 A R e f r i g e r a n t u n d e r H i g h e r p r ep ar ed t o b r a ze r e f r ig er an t li n e s t o t h e
connections. Excessi ve exposure to atmosphere (>
Pr e s s u r e t h a n R - 2 2 ! 5 m i n . ) m a y a l l o w m o i s t u r e o r d i rt t o c o n t a m i n a t e
Fai l ure t o us e pr ope r eq ui pm e nt o r c om p on en ts a s the system, damaging valve seals and causing ice
de sc ri b ed be l ow, c ou ld re s ul t i n e qu i pme nt fa i li ng formation in system components.
a n d p o s s i b l y e x p l o d i n g , w h i ch c o u l d r e s u l t i n
d e a t h , s e r i o u s i n j u r y, o r e q u i p m e n t d a m a g e .
T h e u n i t s d e s c r i b e d i n t h i s m a n u a l u s e R - 4 10 A WA R N I N G
r e f r i g e r a n t w h i ch o p e r a t e s a t h i g h e r p r e s s u r e s Hazard of Explosion and Deadly
t h a n R - 2 2 . U s e O N LY R - 4 10 A r a t e d s e r v i c e Gases!
eq ui pm e nt or c om p one nt s w it h the s e un it s. For
Fa il u re to f ol lo w a ll pro pe r s af e re fr ig era nt
s p e c i f i c h a n d l i n g c o n c e r n s w i t h R - 4 10 A , p l e a s e
c o n t a c t y o u r l o c a l Tr a n e r e p r e s e n t a t i v e . handling practices could result in death or serious
i n j u r y.
Each TTA unit ships with a holding charge of dry N e v e r s o l d e r, b r a z e o r w e l d o n r e f r i g e r a n t l i n e s o r
nitrogen. The nitrogen should be removed and the a ny uni t comp one nt s th at a re a bov e a tmosp he ric
entire system evacuated (at the proper time) to avoid pressure or where refrigerant may be present.
possible contamination. Al way s re move re fri ge ra nt by fol l ow in g t he
g u i d e l i n e s e s t a b l i s h e d b y t h e E PA F e d e r a l C l e a n
1. Remove the compressor service access panel. Air Act or other state or local codes as appropriate.
2. Locate the liquid and suction line service valves. A ft e r r e f r i g e r a n t r e m o v a l , u s e d r y n i t r o g e n t o
Check that the piping connection stubs on the b r i n g s y s t e m b a ck t o a t m o s p h e r i c p r e s s u r e b e f o r e
valves (Figure 15, p. 22) line up properly with the opening system for repair s. Mixtures of
holes in the unit cabinet. refrigerants and air under pressure may become
combustible in the presence of an ignition source
Figure 15. Outdoor units - refrigerant piping (with dry leading to an explosion. Excessi ve heat from
nitrogen) soldering, brazing or welding with refrigerant
v a p o r s p r e s e n t c a n f o r m h i g h l y t ox i c ga s e s a n d
e x t r e m e l y c o rr o s i v e a c i d s .

4. Cut, fit and braze tubing, starting at the outdoor unit


and work toward the indoor unit. See
recommended tube sizes, Table 4, p. 25.
N o t e : Use long radius ells for all 90° bends.
All brazing should be done using a 2 to 3 psig dry
nitrogen purge flowing through the pipe being
brazed, see Figure 15, p. 22.

N OT I C E
Syste m Component Dam age!
Install a regulating valve between the nitrogen
s o u r c e a n d t h e ga u g e m a n i f o l d . U n r e g u l a t e d
pressure can damage system components.

3. Remove the refrigerant connection seal caps and N OT I C E


open the service valve slowly to release the Syste m Component Dam age!
nitrogen from the unit. We t - w r a p a l l v a l v e s a n d p r o t e c t p a i n t e d s u r f a c e s
from excessi ve heat. Heat can damage system
components and the unit finish.

5. Shut off nitrogen supply. Shut off the manifold


valve for the line that is connected to the suction
line service valve. Disconnect the line from the
gauge port on the valve.

22 SS-SVX10D-EN
Installation

Refrigerant Piping Procedures WA R N I N G


(Indoor Unit) Hazard of Explosion!
Once liquid and suction lines are complete to the Fa il u re to f ol lo w re co m m en de d s af e le a k te s t
refrigerant connections on the indoor unit, remove the procedures could result in death or serious injury
gauge port core(s) on the indoor unit connection stubs o r e q u i p m e n t o r p r o p e rt y- o n l y - d a m a g e .
to release the dry nitrogen charge. N e v e r u s e a n o p e n f l a m e t o d e t e c t ga s l e a k s . U s e a
leak test solution for leak testing.
N OT I C E After the brazing operation of refrigerant lines to both
Unit Damage! the outdoor and indoor unit is completed, the field
Do n ot a ppl y h ea t to re move se al ca ps un ti l th e brazed connections must be checked for leaks.
ga u g e p o rt c o r e s h a v e b e e n r e m o v e d . I f s e a l c a p s Pressurize the system through the service valve with
are intact, application of heat may generate dry nitrogen to 200 psi. Use soap bubbles or other leak-
excessi ve pressure in the unit and result in checking methods to ensure that all field joints are leak
damage to the coil or expansion valve. free. If not, release pressure, repair and repeat leak test.

1. Remove both seal caps from the indoor unit System Evacuation
connection stubs.
1. After completion of leak check, evacuate the
N OT I C E system.
Unit Damage! 2. Attach appropriate hoses from manifold gauge to
gas and liquid line pressure taps.
Do n ot re move the se a l cap s fr om r ef ri ge ra nt
connections, or open the service valves until N o t e : Unnecessary switching of hoses can be
prepared to braze refrigerant lines to the avoided and complete evacuation of all lines
c o n n e c t i o n s . D u e t o t h e h i g h hy g r o s c o p i c leading to sealed system can be
p r o p e rt i e s o f t h e R - 4 10 A o i l , e x c e s s i v e e x p o s u r e t o accomplished with manifold center hose and
atmosphere will allow moisture to contaminate connecting branch hose to a cylinder of R-
t h e s y s t e m , d a m a g i n g t h e c o m p r e s s o r. 410A and vacuum pump.
3. Attach center hose of manifold gauges to vacuum
2. Turn on nitrogen supply. Nitrogen enters through
pump.
the liquid line gauge port.
3. Braze the liquid line connections. N OT I C E
4. Open the gauge port on the suction line and then O p e r a t i n g U n d e r Va c u u m !
braze the suction line to the connection stub.
Do not operate or apply power to the compressor
Nitrogen will bleed out the open gauge port on the
w hi le und er a v a cu um . Fa i lu re to f ol lo w th es e
suction line.
instructions will result in compressor failure.
5. Shut off nitrogen supply.
4. Evacuate the system to hold a 500 micron vacuum.
Leak Check 5. Close off valve to vacuum pump and observe the
micron gauge. If gauge pressure rises above 500
WA R N I N G microns in one minute, then evacuation is
incomplete or the system has a leak.
Hazard of Explosion!
Fai l ure t o fol l ow t he se rec o m m en da ti ons c oul d 6. If vacuum gauge does not rise above 500 microns in
result in death or serious injury or equipment or 10 minutes, the evacuation should be complete.
p r o p e rt y- o n l y d a m a g e .
Use only dry nitrogen with a pressure regulator for N OT I C E
pre ssu ri zin g uni t. Do n ot use a ce ty le ne , ox yg en or Equipment Damage!
compressed air or mixtures containing them for C h a r g e w i t h a c c e s s p o rt o n t h e l i q u i d l i n e s e r v i c e
pressure testing. Do not use mixtures of a v a l v e o n l y.
hy d r o g e n c o n t a i n i n g r e f r i g e r a n t a n d a i r a b ov e
atmospheric pressure for pressure testing as they 7. With vacuum pump and micron gauge blanked off,
may become flammable and could result in an open valve on R-410A cylinder and allow refrigerant
e x p l o s i o n . Re f r i g e r a n t , w h e n u s e d a s a t r a c e ga s pressure to build up to about 80 psig.
should only be mixed with dry nitrogen for
8. Close valve on the R-410A supply cylinder. Close
pressurizing units.
valves on manifold gauge set and remove
refrigerant charging hoses from liquid and gas

SS-SVX10D-EN 23
Installation

gauge ports. Refrigerant Charging Procedure


9. Leak test the entire system. Using proper If charging by weight, refer to Table 4, p. 25 for starting
procedures and caution, as described in the change. If refrigerant adjustments are needed because
previous section, repair any leaks found and repeat of length of line, refer to ”Charging Charts and
the leak test. Superheat,” p. 35.
Charge by weight through the gauge port on the liquid
Insulating and Isolating line. Once the charge enters the system, backseat
(open) the liquid line service valve and disconnect the
Refrigerant Lines charging line and replace the cap on the gauge port.
Insulate the entire suction line with refrigerant piping Notes:
insulation. Also insulate any portion of the liquid line
exposed to temperature extremes. Insulate and isolate • R-410A should only be charged in the liquid
liquid and suction lines from each other. Isolate state.
refrigerant lines from the structure and any duct work. • When possible, always charge the
I m p o rt a n t : refrigerant into the liquid line of the unit.
1. To prevent possible noise or vibration • If the entire charge can’t be charged into the
problems, be certain to isolate liquid line, the balance of the unit charge can
refrigerant lines from the building. be metered through a charging manifold set
as liquid — preferably through a schrader
2. All suction and hot gas bypass piping (if valve into the suction line to the compressor
installed) should be insulated from the — only while the compressor is running.
termination in the air handler to the
condensing unit cabinet entry. Failure to • Check and adjust superheat using Table 9, p.
do so can cause condensate drip off and 38, then re-check charging charts to
performance degradation. determine if charge corrections are
necessary.
3. Prior to starting a unit, it is advisable to
have the approved oils available in the
event oil needs to be added to the
N OT I C E
system. Equipment Damage!
N e v e r ch a r g e l i q u i d r e f r i g e r a n t i n t o t h e s u c t i o n
N OT I C E l i n e o f t h e u n i t w i t h t h e c o m p r e s s o r o ff.
Equipment Damage!
Figure 16. Outdoor units - refrigerant piping
T h i s i s P O E o i l , w h i ch r e a d i l y a b s o r b s m o i s t u r e .
Alwa ys us e ne w oi l a nd n ev e r l e av e c on ta in er s
open to atmosphere while not in use.

Table 3. TTA approved oils

Unit Model Number Approved Oils

TTA061, TTA073, TTA076,


TTA090, TTA101, TTA120, Trane Oil Part Number
TTA126, TTA150, TTA156, OIL00094 (1 quart container)
TTA180, TTA251, TTA300

Trane Oil Part Number


OIL00079 (1 quart container)
TTA086, TTA201, TTA240
or OIL00080 (1 gallon
container).

For units equipped with compressors containing site


glasses, the oil level must be visible through the sight
glass when the compressor is running under stabilized
conditions and a few minutes after the compressor has
stopped.

24 SS-SVX10D-EN
Installation

Table 4. Estimated charge levels at ARI rated line lengths (25 feet) - 50 & 60 Hz

Refrigerant Charge Per Circuit

Liquid Line Vapor Line


Matched Set Circuit 1 Circuit 2 Diameter Diameter

TTA061D w/TWE076D(a) 15.7 N/A 0.5 (1/2”) 1.125 (1 1/8”)

TTA073D w/TWE090D(a) 15.7 N/A 0.5 (1/2”) 1.125 (1 1/8”)

TTA076D w/TWE076D 17.6 N/A 0.625 (5/8”) 1.375 (1 3/8”)

TTA086D w/TWE101D 22.5 N/A 0.5 (1/2”) 1.375 (1 3/8”)

TTA090D w/TWE090D 17.6 N/A 0.625 (5/8”) 1.375 (1 3/8”)

TTA101D w/TWE101D 22.5 N/A 0.5 (1/2”) 1.375 (1 3/8”)

TTA120D w/TWE120D 22.5 N/A 0.5 (1/2”) 1.375 (1 3/8”)

TTA101E w/TWE101E 12.2 12.6 0.5 (1/2”) 1.125 (1 1/8”)

TTA120E w/TWE101D 12.2 12.6 0.5 (1/2”) 1.125 (1 1/8”)

TTA101F w/TWE101D 21.2 N/A 0.5 (1/2”) 1.375 (1 3/8”)

TTA120F w/TWE120D 21.2 N/A 0.5 (1/2”) 1.375 (1 3/8”)

TTA126E w/TWE126E 15.2 15.5 0.5 (1/2”) 1.125 (1 1/8”)

TTA150E w/TWE150E 15.2 15.5 0.5 (1/2”) 1.125 (1 1/8”)

TTA156E w/TWE156E 19.5 19.5 0.5 (1/2”) 1.375 (1 3/8”)

TTA180E w/TWE180E 19.5 19.5 0.5 (1/2”) 1.375 (1 3/8”)

TTA156F w/TWE156E 37.6 N/A 0.625 (5/8”) 1.625 (1 5/8”)

TTA180F w/TWE180E 37.6 N/A 0.625 (5/8”) 1.625 (1 5/8”)

TTA201E w/TWE201E 21.9 21.9 0.5 (1/2”) 1.375 (1 3/8”)

TTA240E w/TWE240E 21.9 21.9 0.5 (1/2”) 1.375 (1 3/8”)

TTA201F w/TWE201E 41.3 N/A 0.625 (5/8”) 1.625 (1 5/8”)

TTA240F w/TWE240E 41.3 N/A 0.625 (5/8”) 1.625 (1 5/8”)

TTA251F w/TWE251E(b) 62.5 N/A 0.625 (5/8”) 2.125 (2 1/8”)

TTA300F w/TWE300E(b) 62.5 N/A 0.625 (5/8”) 2.125 (2 1/8”)

Notes:
1. For line lengths other than 25', please refer to the Application Guide (SS-APG008-EN) for charge levels and line sizes.
2. See Figure 17, p. 26 and Figure 18, p. 26 for transition tube location and electrical connections.

(a) TTA061D and TTA073D need a reducer for vapor line. (1.375 to 1.125 inch) (1 3/8” to 1 1/8”)
(b) TTA251F and TTA300F are provided with a transition tube to be installed outside of the unit for front or rear access, (1.625 to 2.125 inch) (1 5/8" to 2 1/
8").

SS-SVX10D-EN 25
Installation

Figure 17. TTA 251, 300 transition tube location

Suction Line Transition Tube

Figure 18. TTA251, 300 rear refrigerant and electrical connections


Lo w Vo lt a g e ( Re a r Acce s s )

Po p - in Wire Tie
( Pro vid e d )

Line Vo lt a g e ( Re a r Acce s s ) Ro u t e wire s a wa y


fro m h o t t u b e s a n d
s h a rp e d g e s

Trans it io n Tu b e
( Pro vid e d )
Ce n t e r Divid e r Pa n e l

Suc t io n Co n n e ct io n
( Fie ld In s t a lle d )

Suc t io n Co n n e ct io n
( Fie ld In s t a lle d )
COMPRES S OR S IDE A
( S ECTIONED)

Liquid Charging N o t e : The compressor access panel must be installed


when the unit is running and being charged.
This procedure is accomplished with the unit Manifold hoses must be routed through
operating. Electrical connections must be complete. Do refrigerant gauge access hole(s). See
not proceed until the system is ready to operate. ”Dimensional Data,” p. 10 for specific locations.

26 SS-SVX10D-EN
Installation

WA R N I N G Electrical Wiring
Li ve Electrical Components! WA R N I N G
Fai l ure t o fol l ow al l e le c tr ic a l s af et y pr ec a uti on s
when exposed to li ve electrical components could Prope r Fi el d Wi ring a nd Groundi ng
r e s u l t i n d e a t h o r s e r i o u s i n j u r y. Required!
When it is necessary to work with li ve electrical Fa il u re to f ol lo w c ode c o ul d r es u lt i n de at h or
components, have a qualified licensed electrician s e r i o u s i n j u r y.
or other indi vidual who has been properly trained All field w ir in g MUST be p er for med b y qualif ied
in handling li ve electrical components perform per sonnel. Improperly installed and grounded
these tasks. field wiring poses FIRE and ELECTROCUTION
h a z a r d s . To a v o i d t h e s e h a z a r d s , y o u M U S T f o l l o w
1. Turn on power to the unit. Allow the system to run requirements for field wiring installation and
for 15 minutes to stabilize operating conditions. grounding as described in NEC and your local/
2. Measure airflow across the indoor coil. Compare state electrical codes.
the measurements with the fan performance data in
the Data/Submittal or Service Facts. Once proper Field wiring consists of providing power supply to the
airflow is established, compare discharge pressure unit, installing the system indoor thermostat and
and liquid temperature to the ”Charging Charts,” p. providing low voltage system interconnecting wiring.
35. Add or remove refrigerant (liquid only) as Access to electrical connection locations is shown in
required to obtain correct discharge pressure and ”Dimensional Data,” p. 10. Determine proper wire sizes
liquid temperature. and unit protective fusing requirements by referring to
the unit nameplate and/or the unit Service Facts. Field
3. Check suction line superheat and condenser sub- wiring diagrams for accessories are shipped with the
cooling to ensure the unit is operating properly. accessory.
4. Disconnect all power to the unit.
I m p o rt a n t : If the unit is charged and left without Unit Power Supply
power until a later date, the crankcase The installer must provide line voltage circuit(s) to the
heater should be energized for a unit main power terminals as shown by the unit wiring
minimum of 8 hours prior to powering diagrams (available through e-Library or by contacting
the compressor(s). a local sales office) or field wiring. Power supply must
include a disconnect switch in a location convenient to
WA R N I N G the unit. Ground the unit according to local codes and
provide flexible conduit if codes require and/or if
H a z a r d o u s Vo l t a g e w / C a p a c i t o r s ! vibration transmission may cause noise problems.
F a i l u r e t o d i s c o n n e c t p o w e r a n d d i s ch a r g e
capacitor s before servicing could result in death or I m p o rt a n t : All wiring must comply with applicable
s e r i o u s i n j u r y. local and national (NEC) codes. Type and
D i s c o n n e c t a l l e l e c t r i c p o w e r, i n c l u d i n g r e m o t e location of disconnect switches must
d i s c o n n e c t s a n d d i s ch a r g e a l l m o t o r s t a rt / r u n comply with all applicable codes.
c a p a c i t o r s b e f o r e s e r v i c i n g . F o l l o w p r o p e r l o ck o u t /
tagout procedures to ensure the power cannot be WA R N I N G
i n a d v e rt e n t l y e n e r g i z e d . F o r v a r i a b l e f r e q u e n c y Prope r Fi el d Wi ring a nd Groundi ng
dri ves or other energy storing components
p r o v i d e d b y Tr a n e o r o t h e r s , r e f e r t o t h e
Required!
a p p r o p r i a t e m a n u f a c t u r e r ’s l i t e r a t u r e f o r Fa il u re to f ol lo w c ode c o ul d r es u lt i n de at h or
a l l o w a b l e w a i t i n g p e r i o d s f o r d i s ch a r g e o f s e r i o u s i n j u r y.
c a p a c i t o r s . Ve r i f y w i t h a n a p p r o p r i a t e v o l t m e t e r All field w ir in g MUST be p er for med b y qualif ied
t h a t a l l c a p a c i t o r s h a v e d i s ch a r g e d . per sonnel. Improperly installed and grounded
For ad di ti on al i n for m at io n rega rdi ng t he s a fe field wiring poses FIRE and ELECTROCUTION
d i s ch a r g e o f c a p a c i t o r s , s e e P R O D - S V B 0 6 A - E N . h a z a r d s . To a v o i d t h e s e h a z a r d s , y o u M U S T f o l l o w
requirements for field wiring installation and
5. Remove the charging system from the unit. grounding as described in NEC and your local/
state electrical codes.
6. Replace all panels.

SS-SVX10D-EN 27
Installation

N OT I C E ™ Controls
ReliaTel™
Use Copper Conductor s Only! Wiring shown with dashed lines is to be furnished and
Fai l ure t o us e c op pe r c o ndu ct or s c o ul d r es ul t i n installed by the customer. All customer supplied wiring
equipment damage as unit terminals are not must be copper only and must conform to NEC and
designed to accept other types of conductors. local electrical codes. Codes may require line of sight
between disconnect switch and unit.

Low Voltage Wiring Notes:


1. When electric heater accessory is used,
Mount the indoor thermostat, zone sensor, or Night
single point power entry or dual point power
Setback Panel (NSB) in accordance with the
entry is field optional. Single point power
corresponding thermostat installation instructions.
entry option is through electric heater only.
Install color-coded, weather-proof, multi-wire cable
according to the field wiring schematics (see ”Field 2. ***Choose only one of the following;
Wiring”, p. 29). Thermostat, Zone Sensor, or NSB Panel.
Figure 20. ReliaTel jobsite connections
Electromechanical Controls
Disconnect S witch
Wiring shown with dashed lines is to be furnished and (By Others)
Note 2
installed by the customer. All customer supplied wiring
must be copper only and must conform to NEC and
local electrical codes. Codes may require line of sight B Air Handler

between disconnect switch and unit.


Electric
N o t e : When electric heater accessory is used, single Heat Accessory

point power entry or dual point power entry is


field optional. Single point power entry option is
through electric heater only. B
D Disconnect S witch
(By Others) Note 2
Figure 19. Electromechanical jobsite connections
Disconnect S witch A Disconnect S witch
(By Others) (By Others)
C E F

B Air Handler
T’s t a t Zo n e NSB P anel
Sensor

Electric A. 3 power wires, line voltage for 3 phase, (2 power wires for
T’s t a t
Heat Accessory single phase)
B. 3 power wires, line voltage for 3 phase, (2 power wires for
C single phase)
C. Cooling only thermostat: 3 to 7 wires depending on stages of
B electric heat
D Disconnect S witch D. 3 to 7 wires depending on type of outdoor unit(s)
(By Others) Note 2
E. Zone Sensor: 4 to 10 wires depending on zone sensor model(a)
A Disconnect S witch
F. Night Setback Panel: 7 wires
(By Others)

A. 3 power wires, line voltage for 3 phase, (2 power wires for (a) For SZVAV air handlers: 4 additional wires are required (2 of which
single phase) require twisted pair or shielded wire) in order to make connections
B. 3 power wires, line voltage for 3 phase, (2 power wires for between ReliaTel boards in the condenser and air handler.
single phase)
C. Cooling only thermostat: 3 to 7 wires depending on stages of
electric heat
D. 3 to 7 wires depending on type of outdoor unit(s)

28 SS-SVX10D-EN
Installation

Field Wiring
Figure 21. Night setback panel field wiring

Figure 22. Zone sensor field wiring

SS-SVX10D-EN 29
Installation

Figure 23. Thermostat field wiring

Figure 24. Thermostat wiring for electromechanical units

30 SS-SVX10D-EN
Installation

Refrigerant Circuit
Figure 25. Typical split system cooling refrigerant circuit
COOLING ONLY CIRCUIT DIAGRAM
DISCHARGE
TEMPERATURE
LIMIT (DTL)
GAUGE HIGH PRESSURE
CONNECTION SWITCH (HPCO)

NOTE A

D
NOTE A
FIELD SUPPLIED
S INTER-CONNECTING
TUBING
COMPRESSOR
EQUALIZER
EXPANSION TUBE
VALVE BULB
OUTDOOR COIL

AIR

GAUGE
CONNECTION SERVICE
VALVE
NOTE A

AIR

V
TXV
LOW PRESSURE

INDOOR COIL
SWITCH (LPCO)
SERVICE
VALVE

FILTER DRIER NOTE A


SUB-COOLING CIRCUIT

NOTE A: ONLY ONE OUTDOOR AND INDOOR


COIL REFRIGERANT ENTRY AND
EXIT CIRCUIT IS SHOWN. ALL
INDICATES DIRECTION OF MODELS HAVE MULTIPLE ENTRY
REFRIGERANT FLOW AND EXIT CIRCUITS.
NOTE B: DUAL CIRCUIT MODELS HAVE 2
REFRIGERATION CIRCUITS.

SS-SVX10D-EN 31
Electrical Data
Table 5. Electrical characteristics — compressor and condenser fan motors — 60 Hz
Compressor Motor Condenser Fan Motor
Unit Amps Amps
Tons Model
Number No. Volts Phase RLA LRA No. Volts Phase FLA LRA
(Ea.) (Ea.) (Ea.) (Ea.)
TTA073D3 1 208-230 3 22.4 149 1 208-230 1 3.1 8.1
TTA073D4 1 460 3 10.6 75 1 460 1 1.6 3.8
6
TTA073DK 1 380 3 11.3 88 1 380 1 2.7 7
TTA073DW 1 575 3 7.9 54 1 575 1 1.2 3
TTA090D3 1 208-230 3 25 164 1 208-230 1 3.1 8.1
TTA090D4 1 460 3 12.9 100 1 460 1 1.6 3.8
7.5
TTA090DK 1 380 3 14.3 94.3 1 380 1 2.7 7
TTA090DW 1 575 3 10.6 78 1 575 1 1.2 3
TTA120D3 1 208-230 3 30.1 225 1 208-230 1 5 14.4
TTA120D4 1 460 3 16.7 114 1 460 1 2.5 5.8
10
TTA120DK 1 380 3 19.8 140 1 380 1 3.4 7.8
TTA120DW 1 575 3 12.4 80 1 575 1 2 5.1
TTA120E3 2 208-230 3 16 110 1 208-230 1 5 14.4
TTA120E4 2 460 3 7.8 52 1 460 1 2.5 5.8
10
TTA120EK 2 380 3 10.4 65.6 1 380 1 3.4 7.8
TTA120EW 2 575 3 6 38.9 1 575 1 2 5.1
TTA120F3 2 208-230 3 17.6 123 1 208-230 1 5 14.4
10 TTA120F4 2 460 3 9.6 62 1 460 1 2.5 5.8
TTA120FW 2 575 3 6.1 40 1 575 1 2 5.1
TTA150E3 2 208-230 3 22.4 149 1 208-230 1 5 14.4
TTA150E4 2 460 3 10.6 75 1 460 1 2.5 5.8
12.5
TTA150EK 2 380 3 11.3 88 1 380 1 3.4 7.8
TTA150EW 2 575 3 8.6 54 1 575 1 2 5.1
TTA180E3 2 208-230 3 25 164 2 208-230 1 5 14.4
TTA180E4 2 460 3 12.2 100 2 460 1 2.5 5.8
15
TTA180EK 2 380 3 14.3 94.3 2 380 1 3.4 7.8
TTA180EW 2 575 3 9.6 78 2 575 1 2 5.1
TTA180F3 2 208-230 3 25 164 2 208-230 1 5 14.4
TTA180F4 2 460 3 12.2 100 2 460 1 2.5 5.8
15
TTA180FK 2 380 3 14.3 94.3 2 380 1 3.4 7.8
TTA180FW 2 575 3 9.9 78 2 575 1 2 5.1
TTA240E3 2 208-230 3 39.1 267 2 208-230 1 5 14.4
TTA240E4 2 460 3 18.6 142 2 460 1 2.5 5.8
20
TTA240EK 2 380 3 23.1 160 2 380 1 3.4 7.8
TTA240EW 2 575 3 15.4 103 2 575 1 2 5.1
TTA240F3 2 208-230 3 39.1 267 2 208-230 1 5 14.4
TTA240F4 2 460 3 19.8 142 2 460 1 2.5 5.8
20
TTA240FK 2 380 3 23.1 160 2 380 1 3.4 7.8
TTA240FW 2 575 3 15.8 103 2 575 1 2 5.1
TTA300F3 2 208-230 3 53.6 245 2 208-230 1 5 14.4
TTA300F4 2 460 3 20.7 125 2 460 1 2.5 5.8
25
TTA300FK 2 380 3 26.4 145 2 380 1 3.4 7.8
TTA300FW 2 575 3 16.4 100 2 575 1 2 5.1
Note: Electrical characteristics reflect nameplate values and are calculated in accordance with cULus and ARI specifications.

32 SS-SVX10D-EN
Electrical Data

Table 6. Unit wiring — condensing units — 60 Hz


Unit Operating Maximum Fuse or HACR
Tons Unit Model Number Minimum Circuit Ampacity
Voltage Range Circuit Breaker Size
TTA073D3 187-253 31.1 40
TTA073D4 414-506 14.9 20
6
TTA073DK 342-418 16.8 20
TTA073DW 518-632 11.1 15
TTA090D3 187-253 34.4 45
TTA090D4 414-506 17.7 25
7.5
TTA090DK 342-418 20.6 25
TTA090DW 518-632 14.5 20
TTA120D3 187-253 42.6 60
TTA120D4 414-506 23.4 30
10
TTA120DK 342-418 28.2 35
TTA120DW 518-632 17.5 25
TTA120E3 187-253 41 45
TTA120E4 414-506 20.1 25
10
TTA120EK 342-418 26.9 30
TTA120EW 518-632 15.5 20
TTA120F3 187-253 44.6 50
10 TTA120F4 414-506 24.1 30
TTA120FW 518-632 15.7 20
TTA150E3 187-253 55.4 70
TTA150E4 414-506 26.4 30
12.5
TTA150EK 342-418 28.8 35
TTA150EW 518-632 21.4 25
TTA180E3 187-253 66.3 80
TTA180E4 414-506 32.5 40
15
TTA180EK 342-418 39 45
TTA180EW 518-632 25.6 30
TTA180F3 187-253 66.3 80
TTA180F4 414-506 32.5 40
15
TTA180FK 342-418 39 45
TTA180FW 518-632 26.3 30
TTA240E3 187-253 98 110
TTA240E4 414-506 46.9 60
20
TTA240EK 342-418 58.8 70
TTA240EW 518-632 38.7 45
TTA240F3 187-253 98 110
TTA240F4 414-506 49.6 60
20
TTA240FK 342-418 58.8 70
TTA240FW 518-632 39.6 45
TTA300F3 187-253 130.6 150
TTA300F4 414-506 51.6 60
25
TTA300FK 342-418 66.2 70
TTA300FW 518-632 40.9 45
Notes:
1. Electrical characteristics reflect nameplate values and are calculated in accordance with cULus and ARI specifications. 7.5 and 10 ton values
are system rated; 12.5 - 25 ton values are condensing unit only rated.
2. HACR type circuit breaker per NEC.

SS-SVX10D-EN 33
Electrical Data

Table 7. Electrical characteristics — compressor and condenser fan motors — 50 Hz


Compressor Motor Condenser Fan Motor
Unit Model Amps Amps
Tons
Number No. Volts Phase RLA LRA No. Volts Phase RLA LRA
(Ea.) (Ea.) (Ea.) (Ea.)
5 TTA061DD 1 380-415-50 3 10.9 74 1 380-415-50 1 1.6 3.8
6.25 TTA076DD 1 380-415-50 3 12.5 101 1 380-415-50 1 1.6 3.8
7 TTA086DD 1 380-415-50 3 15.2 142 1 380-415-50 1 1.9 5.8
TTA101DD 1 380-415-50 3 17.2 111 1 380-415-50 1 1.9 5.8
8.33 TTA101ED 2 380-415-50 3 8 51.5 1 380-415-50 1 1.9 5.8
TTA101FD 2 380-415-50 3 9.9 64 1 380-415-50 1 1.9 5.8
10.4 TTA126ED 2 380-415-50 3 10.9 75 1 380-415-50 1 1.9 5.8
TTA156ED 2 380-415-50 3 12.5 101 2 380-415-50 1 1.9 5.8
13
TTA156FD 2 380-415-50 3 12.5 101 2 380-415-50 1 1.9 5.8
TTA201ED 2 380-415-50 3 19.1 142 2 380-415-50 1 1.9 5.8
16.7
TTA201FD 2 380-415-50 3 19.1 142 2 380-415-50 1 1.9 5.8
20.9 TTA251FD 2 380-415-50 3 20.7 118 2 380-415-50 1 1.9 5.8
Note: Electrical characteristics reflect nameplate values and are calculated in accordance with UL and ARI
specifications.

Table 8. Unit wiring — condensing units — 50 Hz


Maximum Maximum Fuse
Unit Model Unit Operating Circuit Size or Maximum
Tons Number Voltage Ampacity Circuit Breaker
5 TTA061DD 380/415 15.2 20
6.25 TTA076DD 380/415 17.3 25
7 TTA086DD 380/415 20.9 25
TTA101DD 380/415 23.4 30
8.33 TTA101ED 380/415 19.9 25
TTA101FD 380/415 24.2 30
10.4 TTA126ED 380/415 26.4 30
TTA156ED 380/415 32 40
13
TTA156FD 380/415 32 40
TTA201ED 380/415 46.9 60
16.7
TTA201FD 380/415 46.9 60
20.9 TTA251FD 380/415 50.4 60
Note: HACR type circuit breaker per NEC

34 SS-SVX10D-EN
Charging Charts and Superheat
Figure 26. TTA061D Figure 29. TTA086D

TTA061D Ch a rg in g Cu rve TTA086D Ch a rg in g Cu rve

650 650
625 625
600 600
575 575
550 550
525 525

Dis c h a rg e P re s s u re , p s ig
Dis c h a rg e P re s s u re , p s ig

Re m o ve Re m o ve
500 500
c h a rg e c h a rg e
475 475
450 450
425 425
400 400
375 375
350
Ad d 350
Ad d
c h a rg e c h a rg e
325 325
300 300
275 275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

Figure 27. TTA073D Figure 30. TTA090D

TTA073D Ch a rg in g Cu rve TTA090D Ch a rg in g Cu rve

650 650
625 625
600 600
575 575
550 550
525 525
Dis c h a rg e P re s s u re , p s ig
Dis c h a rg e P re s s u re , p s ig

Re m o ve Re m o ve
500 500
c h a rg e c h a rg e
475 475
450 450
425 425
400 400
375 375
Ad d 350
Ad d
350
c h a rg e c h a rg e
325 325
300 300
275 275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

Figure 28. TTA076D Figure 31. TTA101D

TTA076D Ch a rg in g Cu rve TTA101D Ch a rg in g Cu rve

650 650
625 625
600 600
575 575
550 550
525 525
Dis c h a rg e P re s s u re , p s ig

Dis c h a rg e P re s s u re , p s ig

Re m o ve Re m o ve
500 500
c h a rg e c h a rg e
475 475
450 450
425 425
400 400
375 375
350
Ad d 350
Ad d
c h a rg e c h a rg e
325 325
300 300
275 275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

SS-SVX10D-EN 35
C h a r g i n g C h a rt s a n d S u p e r h e a t

Figure 32. TTA101E Figure 35. TTA120E


both compre s s ors running both compre s s ors running
TTA101E Ch a rg in g Cu rve (Ea c h Circ u it) TTA120E Ch a rg in g Cu rve (Ea c h Circ u it)

650 650
625 625
600 600
575 575
550 550
525 525

Dis c h a rg e P re s s u re , p s ig
Dis c h a rg e P re s s u re , p s ig

Re m o ve Re m o ve
500 500
c h a rg e c h a rg e
475 475
450 450
425 425
400 400
375 375
Ad d 350
Ad d
350
c h a rg e c h a rg e
325 325
300 300
275 275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

Figure 33. TTA101F Figure 36. TTA120F


both compre s s ors running both compre s s ors running
TTA101F Ch a rg in g Cu rve TTA120F Ch a rg in g Cu rve

650 650
625 625
600 600
575 575
550 550
525 525
Dis c h a rg e P re s s u re , p s ig

Dis c h a rg e P re s s u re , p s ig

Re m o ve Re m o ve
500 500
c h a rg e c h a rg e
475 475
450 450
425 425
400 400
375 375
350
Ad d Ad d
350
c h a rg e c h a rg e
325 325
300 300
275 275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

Figure 34. TTA120D Figure 37. TTA126E

TTA120D Ch a rg in g Cu rve both compre s s ors running TTA126E Ch a rg in g Cu rve (Ea c h Circ u it)

650 650
625 625
600 600
575 575
550 550
525 525
Dis c h a rg e P re s s u re , p s ig

Dis c h a rg e P re s s u re , p s ig

Re m o ve Re m o ve
500 500
c h a rg e c h a rg e
475 475
450 450
425 425
400 400
375 375
350
Ad d 350
Ad d
c h a rg e c h a rg e
325 325
300 300
275 275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

36 SS-SVX10D-EN
C h a r g i n g C h a rt s a n d S u p e r h e a t

Figure 38. TTA150E Figure 41. TTA180E


both compre s s ors running TTA150E Ch a rg in g Cu rve (Ea c h Circ u it) both compre s s ors running TTA180E Ch a rg in g Cu rve (Ea c h Circ u it)

650 650
625 625
600 600
575 575
550 550
525 525

Dis c h a rg e P re s s u re , p s ig
Dis c h a rg e P re s s u re , p s ig

Re m o ve Re m o ve
500 500
c h a rg e c h a rg e
475 475
450 450
425 425
400 400
375 375
Ad d 350
Ad d
350
c h a rg e c h a rg e
325 325
300 300
275 275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

Figure 39. TTA156E Figure 42. TTA180F


both compre s s ors running both compre s s ors running
TTA156E Ch a rg in g Cu rve (Ea c h Circ u it) TTA180F Ch a rg in g Cu rve

650 600
625 575
600 550
575
525
550
500
525 Re m o ve
Dis c h a rg e P re s s u re , p s ig

Dis c h a rg e P re s s u re , p s ig

Re m o ve 475
500 c h a rg e
c h a rg e 450
475
450 425
425 400
400 375
375 350
350
Ad d Ad d
c h a rg e 325
325 c h a rg e
300
300
275
275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

Figure 40. TTA156F Figure 43. TTA201E


both compre s s ors running both compre s s ors running
TTA156F Ch a rg in g Cu rve TTA201E Ch a rg in g Cu rve (Ea c h Circ u it)

600 650
575 625

550 600
575
525
550
500
Re m o ve 525
Dis c h a rg e P re s s u re , p s ig

Dis c h a rg e P re s s u re , p s ig

475 Re m o ve
c h a rg e 500
450 c h a rg e
475
425 450
400 425
375 400
350 375
Ad d 350
Ad d
325 c h a rg e
c h a rg e 325
300
300
275
275
250 250
225 225
200 200
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

SS-SVX10D-EN 37
C h a r g i n g C h a rt s a n d S u p e r h e a t

Figure 44. TTA201F Figure 47. TTA251F


both compre s s ors running both compre s s ors running TTA251F Ch a rg in g Cu rve
TTA201F Ch a rg in g Cu rve

650 650
625 625
600 600

575 575
550
550 Re m o ve
Re m o ve 525
Dis c h a rg e P re s s u re , p s ig

Dis c h a rg e P re s s u re , p s ig
525 c h a rg e
c h a rg e 500
500
475
475
450
450
425
425
400
400
375
Ad d Ad d c h a rg e
375 350
c h a rg e
350 325
325 300
300 275
275 250
250 225
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140

Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te m p e ra tu re Le a vin g OD Co il, °F

Figure 45. TTA240E Figure 48. TTA300F


both compre s s ors running both compre s s ors running TTA300F Ch a rg in g Cu rve
TTA240E Ch a rg in g Cu rve (Ea c h Circ u it)

650 650
625 625
600 600
575 575
550 550
525 Re m o ve
525
Dis c h a rg e P re s s u re , p s ig

Re m o ve
Dis c h a rg e P re s s u re , p s ig

500
c h a rg e
c h a rg e 500
475
475
450
450
425
425
400
400
375
350
Ad d 375
Ad d c h a rg e
c h a rg e 350
325
300 325

275 300
250 275
225 250
200 225
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140

Liq u id Te mp e ra tu re Le a vin g OD Co il, °F Liq u id Te m p e ra tu re Le a vin g OD Co il, °F

Figure 46. TTA240F


both compre s s ors running
TTA240F Ch a rg in g Cu rve

650
625
600
575
550
Re m o ve
Dis c h a rg e P re s s u re , p s ig

525
c h a rg e
500
475
450
425
400
Ad d
375
c h a rg e
350
325
300
275
250
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Liq u id Te mp e ra tu re Le a vin g OD Co il, °F

Table 9. TTA superheat with matched TWE air handler

Cooling Superheat

Condenser Air Handler Circuit 1 Circuit 2

TTA061D TWE076D 16.8 —

TTA073D TWE090D 16.8 —

38 SS-SVX10D-EN
C h a r g i n g C h a rt s a n d S u p e r h e a t

Table 9. TTA superheat with matched TWE air handler (continued)

Cooling Superheat

Condenser Air Handler Circuit 1 Circuit 2

TTA076D TWE076D 12.8 —

TTA086D TWE101D 15.5 —

TTA090D TWE090D 12.8 —

TTA101D TWE101D 15.5 —

TTA101E TWE101E 12.6 12.6

TTA101F TWE101D 11.4 —

TTA120D TWE120D 15.5 —

TTA120E TWE120E 12.6 12.6

TTA120F TWE120D 11.4 —

TTA126E TWE126E 13.6 13.6

TTA150E TWE150E 13.6 13.6

TTA156E TWE156E 18.4 18.4

TTA156F TWE156E 19.1 —

TTA180E TWE180E 18.4 18.4

TTA180F TWE180E 19.1 —

TTA201E TWE201E 15.2 15.2

TTA201F TWE201E 12.9 —

TTA240E TWE240E 15.2 15.2

TTA240F TWE240E 12.9 —

TTA251F TWE251E 16.2 —

TTA300F TWE251E 16.2 —

Notes:
1. An adjustable TXV is provided for each circuit in the TWE and TWA models. If the application causes the superheat to deviate from the values shown
above by more than 1 degree - after the system has achieved steady state - the TXV should be adjusted to provide the values shown as measured at
the compressor.
2. The values given above have been tested and are approved for the matched sets shown. If an alternate combination is used, an expansion device
should be used that provides 16-20°F degrees of superheat measured at the compressor.
3. Check and adjust superheat using this table, then compare with charging chart to determine if charge corrections are necessary.

SS-SVX10D-EN 39
Installation Checklist
Complete this checklist once the unit is installed to Insulated portions of liquid line exposed to
verify that all recommended procedures have been extremes in temperature?
accomplished before starting the system. Do not Performed initial leak test?
operate the system until all items covered by this
checklist are complete. Evacuated each refrigerant circuit to 500 microns?
Inspect unit location for proper required service Charged each circuit with proper amount of R-
clearances. 410A?
Inspect unit location for proper free air clearances.
Inspect unit location for secure, level mounting
Electrical Wiring
position. Provided unit power wiring (with disconnect) to
proper terminals in the unit control section?
Refrigerant Piping Installed system indoor thermostat?
Properly sized/constructed liquid and suction lines Installed system low voltage interconnecting wiring
connected to stubs at both the indoor and outdoor to proper terminals of outdoor unit, indoor unit and
units? system thermostat?
Insulated the entire suction line?

40 SS-SVX10D-EN
Pre-Start
Control Circuit Features drops below the Low Pressure Cut-Out setting. Once
the suction pressure has returned to normal, the
N o t e : Not all of these features may be required for your compressor and outdoor fans will cycle back on.
unit, check electrical schematic.
High Pressure Cut-Out (HPCO)
Discharge Temperature Limit (DTL)
This control’s sensor is located in the discharge line.
The control’s sensor is located on the discharge line. This device will shut off the compressor and the
This device will shut off the compressor and the outdoor fan(s) if the discharge pressure exceeds the
outdoor fan(s) if the discharge temperature exceeds the High Pressure Cut-Out’s setting. Once the discharge
DTL setting. Once the discharge temperature has pressure has returned to normal, the compressor will
returned to normal, the compressor will cycle back on. cycle back on.
Low Outdoor Ambient Cooling
WA R N I N G
The Evaporator Defrost Control is standard equipment
Prevent I nj ury!
on Air Handlers and will permit low ambient cooling
down to 50°F. For cooling operation down to 0°F, use an D u e t o a g e n c y s a f e t y r e q u i r e m e n t s , n o s ch r a d e r
Accessory Head Pressure Control on the outdoor unit. c o r e i s t o b e i n s t a l l e d b e n e a t h t h e H P C O. R e m o v a l
o f t h e H P C O w i t h o u t e v a c u a t i n g t h e s y s t e m ch a r g e
Evaporator Defrost Control (EDC) could cause injury and release of refrigerant.

This control is located in the Air Handler. The control’s


sensing tube is embedded vertically in the evaporator Internal Overload Protector (IOL)
coil, near the center. This device will stop the This device is embedded in the compressor. It will shut
compressor if the indoor coil temperature drops below off the compressor if the discharge temperature of the
its setting. The indoor air will still circulate across the compressor exceeds its design trip temperature.
coil bringing the temperature of the coil back up to the
cut-in temperature of the evaporator defrost control. N o t e : The IOL will put the compressor back in
operation once the compressor motor heat has
Low Pressure Cut-Out (LPCO) dropped below the trip setting; however, a check
of the refrigerant and electrical systems should
This control’s sensor is located in the suction (gas) line, be made to determine the cause and be
near the compressor. This control will stop the corrected.
compressor and the outdoor fans if suction pressure

SS-SVX10D-EN 41
Start-Up
Electromechanical Controls evaporator fan contactor also energizes on a call for
cooling and initiates evaporator fan operation.
The 24–volt, electromechanical controls feature a
control transformer and contactor pressure lugs for On units with dual circuits, the second stage of cooling
power wiring. Once the unit is properly installed and is initiated as a result of the 2-stage thermostat calling
pre-start procedures are complete, start the unit by for additional cooling.
turning the System Switch on the indoor thermostat to
either H E AT, C O O L or A U TO. The system should ReliaTel™ Controls
operate normally.
The ReliaTel™ Control is a microelectronic control
N OT I C E feature, which provides operating functions that are
significantly different than conventional
Equipment Damage! Electromechanical units. The ReliaTel™ Refrigeration
Ensure the disconnect for the indoor air handler is Module (RTRM) uses Proportional/Integral control
closed before operating the system. Operating the algorithms to perform specific unit functions that
o u t d o o r u n i t w i t h o u t t h e i n d o o r f a n e n e r g i ze d ca n govern the unit operation in response to application
cause unit trip-out on high pressure control and/or conditions.
l i q u i d f l o o d b a ck t o t h e c o m p r e s s o r. The RTRM provides compressor anti-short cycle timing
functions through minimum “O ff” and “O n ” timing to
General increase reliability, performance and to maximize unit
efficiency. Upon power initialization, the RTRM
Operation of the system cooling (and optional heating)
performs self-diagnostic checks to ensure that all
cycles is controlled by the position of the system switch
internal controls are functioning. It checks the
on the room thermostat. Once the system switch is
configuration parameters against the components
placed in either the H E AT or C O O L position, unit
connected to the system. The system LED located on
operation is automatic. The optional automatic
the RTRM module is turned “O n” within one second
changeover thermostat, when in the A U TO position,
after power-up if all internal operations are okay.
automatically changes to heat or cool with sufficient
room temperature change. Once the unit is properly installed and pre-start
procedures are complete, start the unit by turning the
Evaporator Fan (Indoor Supply Air) System Switch on the indoor thermostat to either
H E AT, C O O L or A U TO. The system should operate
The evaporator fan is controlled by an O N / A U TO normally.
switch on the room thermostat. With the switch
positioned at A U TO and the system operating in the
cooling mode, fan operation coincides with the cooling
N OT I C E
run cycles. If the system is equipped with heat and is Equipment Damage!
operating in the heating mode while the fan switch is at Ensure the disconnect for the indoor air handler is
A U TO, fan operation coincides with the heating run closed before operating the system. Operating the
cycles. When the fan switch is positioned at O N , fan outdoor unit without the indoor fan energized can
operation is continuous. cause unit trip-out on high pressure control and/or
l i q u i d f l o o d b a ck t o t h e c o m p r e s s o r.
Cooling Mode
With the disconnect switch in the O N position, current Control Cooling Mode
is supplied to the compressor sump heater(s), phase
monitor and control transformer. The sump heater(s) For Zone Sensor Control
supplies heat to the compressor(s) during the “O ff” When the system switch is set to the C O O L position
cycle. The phase monitor looks at the incoming power and the zone temperature rises above the cooling
to verify that there is no reversed phase, no phase setpoint, the RTRM energizes the compressor
imbalance, and no loss of phase. If the phase monitor contactor, provided the high and low pressure and the
detects any of these three conditions, it will shut off discharge temperature limit controls are closed. When
control voltage. The transformer steps down the line the compressor contacts close, the compressor and the
voltage to 24V for the low voltage control circuit. When outdoor fan motor start to maintain the zone
the room thermostat system switch is positioned at temperature to within ± 2°F of the sensor setpoint at
C O O L and the fan switch is at A U TO, the compressor the sensed location. On units with dual circuits, the
contactor energizes on a call for cooling. When the second stage of cooling is initiated as a result of the
contacts of the compressor contactor close, operation Proportional/Integral control algorithms calling for
of the compressor and condenser fan begins. The additional cooling.

42 SS-SVX10D-EN
S t a rt - U p

For Thermostat Control cooling requirement has been satisfied to enhance unit
When the room thermostat system switch is positioned efficiency. When the heating cycle is terminated, the
at C O O L and the fan switch is at A U TO, the RTRM evaporator fan relay coil is de-energized at the same
energizes the compressor contactor, provided the high time as the heater contactors. When the fan selection
and low pressure and the discharge temperature limit switch is set to the O N position, the RTRM keeps the
controls are closed. When the contacts of the evaporator fan relay coil energized for continuous fan
compressor contactor close, operation of the motor operation.
compressor and condenser fan begins. The evaporator
fan contactor also energizes on a call for cooling and
Control Heating Operation
initiates evaporator fan operation. On units with dual Electric heat is factory disabled on all split system units
circuits, the second stage of cooling is initiated as a with ReliaTel control (jumper placed between J2-1 and
result of the 2-stage thermostat calling for additional J2-2 RTRM inputs). To configure the unit for electric
cooling. heat, cut or remove the jumper wire between J2-1 and
N o t e : Irregular unit operation may occur when the unit J2-2 on the RTRM. All split system units with ReliaTel
is controlled with a triac-switching thermostat. control are also configured from the factory for only 1-
Please review the approved thermostat vendor stage of electric heat (jumper placed between J1-3 and
list for all recommended relay-switching J1-6 RTRM inputs). To configure the unit for 2-stages of
thermostats. electric heat, cut or remove the jumper placed between
J1-3 and J1-6 RTRM inputs.
Control Evaporator Fan Operation When the system switch is set to the H E AT position
When the fan selection switch is set to the A U TO and heating is required, the RTRM energizes the Heat 1
position, the RTRM energizes the evaporator fan relay relay coil on the RTRM. When the Heat 1 relay contacts
coil approximately 1 second after energizing the close, the first stage electric heat contactor is
compressor contactor coil in the cooling mode. In the energized. If the first stage of electric heat cannot
heating mode, the RTRM energizes the evaporator fan satisfy the heating requirement, the RTRM energizes
relay coil approximately 1 second before energizing the the Heat 2 relay coil on the RTRM. When the Heat 2
electric heat contactors. relay contacts close, the second stage electric heat
contactor is energized. The first and second stages of
The RTRM de-energizes the evaporator fan relay coil heat are cycled “O n” and “O ff” as required to maintain
approximately 60 seconds on dual compressor units the zone.
and 80 seconds on single compressor units after the

SS-SVX10D-EN 43
™ Controls
Service Test Modes for ReliaTel™
Test Modes Step Test Mode
Upon power initialization, the RTRM performs self- This method initiates the different components of the
diagnostic checks to ensure that all internal controls are unit, one at a time, by temporarily shorting across the
functional. It also checks the configuration parameters two test terminals for 2 to 3 seconds.
against the components connected to the system. The For the initial start-up of the unit, this method allows
system LED located on the RTRM module is turned the technician to cycle a component “O n” and have up
“O n ” within one second of power-up if internal to one hour to complete the check. Service Test Mode
operation is okay. will be ignored if a short is present across Test 1 and
Use one of the following “ Te s t ” procedures to bypass Test 2 at start-up.
some time delays and to start the unit at the control
panel. Each step of unit operation can be activated Resistance Test Mode
individually by temporarily shorting across the “ Te s t ”
This method can be used for start-up when a decade
terminals for 2 to 3 seconds. The system LED located
box for variable resistance outputs is available. This
on the RTRM module will blink when the test mode has
method initiates the different components of the unit,
been initiated. The unit can be left in any “ Te s t ” step
one at a time, when a specific resistance value is placed
for up to one hour before it will automatically
across the two test terminals. The unit will remain in
terminate, or it can be terminated by opening the main
the specific test mode for approximately one hour even
power disconnect switch. Once the test mode has been
though the resistance is left on the test terminals.
terminated, the system LED will glow continuously and
the unit will revert to the “ S y s t e m ” control.
There are three methods in which the “ Se r v i c e Te s t ”
can be cycled at LTB-Test 1(T1) and LTB-Test 2 (T2).

Table 10. Service test guide for component operation

TEST STEP MODE FAN COMP 1 COMP 2 HEAT 1 HEAT 2 OHMS

1 Fan On Off Off Off Off 2.2K

2 Cool 1 On On(a) Off Off Off 4.7K

3(b) Cool 2 On On(a) On(a) Off Off 6.8K

4(b) Heat 1 On Off Off On Off 10K

5(b) Heat 2 On Off Off On On 15K


(a) The condenser fans will operate any time a compressor is ON.
(b) Steps for optional accessories and non-applicable modes in unit will be skipped.

Auto Test Mode The unit will start the first test step and change to the
next step every 30 seconds. At the end of the test
This method is not recommended for start-up due to
mode, control of the unit will automatically revert to the
the short timing between individual component steps.
applied “ Sy s t e m ” control method. For unit test steps,
This method initiates the different components of the
test modes, and step resistance values to cycle the
unit, one at a time, when a fixed jumper is installed
various components, refer to Table 10, p. 44.
across the test terminals.

44 SS-SVX10D-EN
Troubleshooting
Troubleshooting ReliaTel™ outputs, and all of the external controls (relays,
contactors, etc.) that the RTRM outputs energize, for
Controls each respective mode. Proceed to Step 6.
WA R N I N G 6. Step the system through all of the available modes,
and verify operation of all outputs, controls, and
Li ve Electrical Components! modes. If a problem in operation is noted in any
Fai l ure t o fol l ow al l e le c tr ic a l s af et y pr ec a uti on s mode, you may leave the system in that mode for
when exposed to li ve electrical components could up to one hour while troubleshooting. Refer to the
r e s u l t i n d e a t h o r s e r i o u s i n j u r y. sequence of operations for each mode, to assist in
When it is necessary to work with li ve electrical verifying proper operation. Make the necessary
components, have a qualified licensed electrician repairs and proceed to Step 7 and Step 8.
or other indi vidual who has been properly trained
7. If no abnormal operating conditions appear in the
in handling li ve electrical components perform
test mode, exit the test mode by turning the power
these tasks.
“O ff” at the main power disconnect switch.
The RTRM has the ability to provide the service 8. Refer to the individual component test procedures if
personnel with some unit diagnostics and system other microelectronic components are suspect.
status information.
Before turning the main power disconnect switch “O ff,” System Status Checkout
follow the steps below to check the ReliaTel™
Refrigeration Module (RTRM). All diagnostics & system Procedure
status information stored in the RTRM will be lost when “ Sy s t e m S t a t u s ” is checked by using one of the
the main power is turned “O ff”. following two methods:
To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard Method 1
and use extreme care when performing service
If the Zone Sensor Module (ZSM) is equipped with a
procedures with the electrical power energized.
remote panel with LED status indication, you can check
N o t e : The J6 & J7 screw terminals must be tightened the unit within the space. If the ZSM does not have
in order to accurately measure voltage in the LED’s, use ”Method 2”, p. 46. BAYSENS010B,
required steps. BAYSENS011B, BAYSENS119A, BAYSENS020A,
1. Verify that the system LED on the RTRM is burning BAYSENS021A, BAYSENS023A, BAYSENS109 and
continuously. If the LED is lit, go to Step 3. BAYSENS110 all have the remote panel indication
feature. The LED descriptions are listed below.
2. If the LED is not lit, verify that 24 VAC is present
between J1-1 and J1-2. If 24 VAC is present, • L E D 1 ( Sy s t e m )
proceed to Step 3. If 24 VAC is not present, check – “O n ” during normal operation.
the unit main power supply, check transformer
– “O ff” if a system failure occurs or the LED fails.
(TNS1). Proceed to Step 3 if necessary.
– “ F l a s h i n g ” indicates test mode
3. Utilizing ”Method 1”, p. 45 or ”Method 2”, p. 46 in
the System Status Checkout Procedure section, • LED 2 (Heat)
check the following: – “O n ” when the heat cycle is operating.
• System status – “O ff” when the heat cycle terminates or the LED
• Heating status fails.
• Cooling status – “ F l a s h i n g ” indicates a heating failure.
N o t e : If a System failure is indicated, proceed to • LED 3 (Cool)
Step 4. If no failures are indicated, proceed to
Step 5. – “O n ” when the cooling cycle is operating.
4. If a System failure is indicated, recheck Step 1 and – “O ff” when the cooling cycle terminates or the
Step 2. If the LED is not lit in Step 1, and 24 VAC is LED fails.
present in Step 2, then the RTRM has failed. – “ F l a s h i n g ” indicates a cooling failure.
Replace the RTRM.
The following information describes the complete
5. If no failures are indicated, use one of the TEST listing of failure indication causes.
mode procedures described in the ”Service Test
Modes chapter,” p. 44 to start the unit. This
procedure will allow you to check all of the RTRM

SS-SVX10D-EN 45
Tr o u b l e s h o o t i n g

System Failure • H e a t O p e r a t i n g = approximately 32 VDC


Check the voltage between terminals 6 and 9 on J6, it • H e a t O ff = less than 1 VDC, approximately 0.75 VDC
should read approximately 32 VDC. If no voltage is • H e a t i n g F a i l u r e = voltage alternates between 32
present, a System failure has occurred. Refer to Step 4 VDC & 0.75 VDC
in the previous section for the recommended
troubleshooting procedure. Cool Failure
Cooling Failure Measure the voltage between terminals J6-8 & J6-6.
1. Cooling and heating set point (slide pot) on the • C o o l O p e r a t i n g = approximately 32 VDC
zone sensor has failed. Refer to the ”Programmable • C o o l O ff = less than 1 VDC, approximately 0.75 VDC
& Digital Zone Sensor Test”, p. 48.
• C o o l i n g F a i l u r e = voltage alternates between 32
2. Zone temperature thermistor ZTEMP on ZTS failed. VDC & 0.75 VDC
Refer to the ”Programmable & Digital Zone Sensor
To use LED’s for quick status information at the unit,
Test”, p. 48.
purchase a BAYSENS010B ZSM and connect wires with
3. CC1 or CC2 24 VAC control circuit has opened, alligator clamps to terminals 6 through 10. Connected
check CC1 & CC2 coils, and any of the controls each respective terminal wire (6 through 10) from the
below that apply to the unit (HPC1, HPC2, DTL1, Zone Sensor to the unit J6 terminals 6 through 10.
DTL2).
N o t e : If the system is equipped with a programmable
4. LPC1 has opened during the 3 minute minimum “on zone sensor, (BAYSENS119A, or BAYSENS023A),
time” during 4 consecutive compressor starts, the LED indicators will not function while the
check LPC1 or LPC2 by testing voltage between the BAYSENS010A is connected.
J1-8 & J3-2 terminals on the RTRM and ground. If
24 VAC is present, the LPCs have not tripped. If no
voltage is present, LPCs have tripped. Resetting Cooling and Heating
Simultaneous Heat and Cool Failure
Lockouts
Cooling Failures and Heating Lockouts are reset in an
WA R N I N G identical manner.”Method 1”, p. 46 explains resetting
Li ve Electrical Components! the system from the space; ”Method 2”, p. 46 explains
Fai l ure t o fol l ow al l e le c tr ic a l s af et y pr ec a uti on s resetting the system at the unit.
when exposed to li ve electrical components could N o t e : Before resetting Cooling Failures and Heating
r e s u l t i n d e a t h o r s e r i o u s i n j u r y. Lockouts check the Failure Status Diagnostics by
When it is necessary to work with li ve electrical the methods previously explained. Diagnostics
components, have a qualified licensed electrician will be lost when the power to the unit is
or other indi vidual who has been properly trained disconnected.
in handling li ve electrical components perform
these tasks. Method 1
• Emergency Stop is activated. To reset the system from the space, turn the M O D E
selection switch at the zone sensor to the O F F position.
Method 2 After approximately 30 seconds, turn the M O D E
selection switch to the desired mode, i.e. H E AT, C O O L ,
The second method for determining system status is or A U TO.
done by checking voltage readings at the RTRM (J6).
The system indication descriptions and the Method 2
approximate voltages are listed below.
To reset the system at the unit, cycle the unit power by
System Failure turning the disconnect switch O F F and then O N
Measure the voltage between terminals J6-9 & J6-6. Lockouts can be cleared through the building
management system. Refer to the building
• N o r m a l O p e r a t i o n = approximately 32 VDC
management system instructions for more
• S y s t e m F a i l u r e = less than 1 VDC, approximately information.
0.75 VDC
• Te s t M o d e = voltage alternates between 32 VDC & Zone Temperature Sensor (ZTS)
0.75 VDC
Service Indicator
Heat Failure
The ZSM SERVICE LED is a generic indicator that will
Measure the voltage between terminals J6-7 & J6-6. signal the closing of a Normally Open switch at any
time, providing the Indoor Motor (IDM) is operating.

46 SS-SVX10D-EN
Tr o u b l e s h o o t i n g

This indicator is usually used to indicate an airside fan Table 11. Typical indoor temperatures and values
failure. (continued)
The RTRM will ignore the closing of this Normally Zone Temperature Nominal Resistance
Open switch for 2 (±1) minutes. This helps prevent
nuisance SERVICE LED indications. 65°F or 18.3°C 13.49 Kohms

70°F or 21.1°C 11.9 Kohms

Temperature Tests 75°F or 23.9°C 10.50 Kohms

N o t e : These procedures are not for programmable or 80°F or 26.7°C 9.3 Kohms
digital models and are conducted with the Zone 85°F or 29.4°C 8.25 Kohms
Sensor Module electrically removed from the
system. 90°F or 32.2°C 7.3 Kohms

Test 1 - Zone Temperature Thermistor


Test 2 - Cooling Set Point (CSP) and
(ZTEMP)
Heating Set Point (HSP)
This component can be tested by measuring the
C o o l S P = Terminals 2 and 3
resistance between terminals 1 and 2 on the Zone
Temperature Sensor. See Table 11, p. 47 for typical Range = 100 to 900 Ohms approximate
indoor temperatures, and corresponding resistive H e a t S P = Terminals 2 and 5
values.
Range = 100 to 900 Ohms approximate
Table 11. Typical indoor temperatures and values

Zone Temperature
Test 3 - System Mode and Fan Selection
Nominal Resistance
The combined resistance of the M O D E selection switch
50°F or 10.0°C 19.9 Kohms
and the FA N selection switch can be measured
55°F or 12.8°C 17.47 Kohms between terminals 2 and 4 on the Zone Sensor. The
60°F or 15.6°C 15.3 Kohms
possible switch combinations are listed in Table 12, p.
47 with their corresponding resistance values.

Table 12. Test 3 - system mode and fan selection

Zone Sensor Unit/Fan


Resistance Valves(Ohms) Mode Local Unit Mode Local Fan Mode

2.32K Off/Auto Off Auto

4.87K Cool/Auto Cool Auto

7.68K Auto/Auto Auto Auto

10.77K Off/On Off On

13.32K Cool/On Cool On

16.13K Auto/On Auto On

19.48K Heat/Auto Heat Auto

27.93K Heat/On Heat On

35.0K Emergency Heat/Auto Emergency Heat Auto

43.45K Emergency Heat/On Emergency Heat On

Out of Range (Short) INVALID/Short Invalid (CV), Auto (VAV) Invalid

Out of Range (Open) INVALID/Open Invalid (CV), Off (VAV) Invalid

SS-SVX10D-EN 47
Tr o u b l e s h o o t i n g

Test 4 - LED Indicator Test (SYS ON, J6-11.


HEAT, & COOL)
WA R N I N G
WA R N I N G Li ve Electrical Components!
Li ve Electrical Components! Fa il u re to f ol lo w a ll el e ct ri c al s a fe ty p re c au ti ons
Fai l ure t o fol l ow al l e le c tr ic a l s af et y pr ec a uti on s when exposed to li ve electrical components could
when exposed to li ve electrical components could r e s u l t i n d e a t h o r s e r i o u s i n j u r y.
r e s u l t i n d e a t h o r s e r i o u s i n j u r y. When it is necessary to work with li ve electrical
When it is necessary to work with li ve electrical components, have a qualified licensed electrician
components, have a qualified licensed electrician or other indi vidual who has been properly trained
or other indi vidual who has been properly trained in handling li ve electrical components perform
in handling li ve electrical components perform these tasks.
these tasks.
2. Disconnect wires from J6-11 and J6-12. Measure
the voltage between J6-11 and J6-12, should be
Method 1 about 32 VDC.
Testing the LED using a meter with diode test function. 3. Reconnect wires to terminals J6-11 and J6-12.
Test both forward and reverse bias. Forward bias Measure voltage again between J6-11 and J6-12,
should measure a voltage drop of 1.5 to 2.5 volts, voltage should flash high and low every 0.5
depending on your meter. Reverse bias will show an seconds. The voltage on the low end will measure
Over Load, or open circuit indication if LED is about 19 VDC, while the voltage on the high end
functional. will measure from approximately 24 to 38 VDC.
Method 2 4. Verify all modes of operation, by running the unit
Testing the LED with an analog Ohmmeter. Connect through all of the steps in ”Service Test Modes for
Ohmmeter across LED in one direction, then reverse ReliaTel Controls,” p. 44.
the leads for the opposite direction. The LED should 5. After verifying proper unit operation, exit the test
have at least 100 times more resistance in reverse mode. Turn the fan on continuously at the ZSM, by
direction, as compared with the forward direction. If pressing the button with the fan symbol. If the fan
high resistance in both directions, LED is open. If low in comes on and runs continuously, the ZSM is good.
both directions, LED is shorted. If you are not able to turn the fan on, the ZSM is
defective.
Method 3
To test LED’s with ZSM connected to unit, test voltages RLCI Loss of Communications
at LED terminals on ZSM. A measurement of 32 VDC, If the RLCI loses input from the building management
across an unlit LED, means the LED has failed. system, the RTRM will control in the default mode after
I m p o rt a n t : Measurements should be made from LED approximately 15 minutes. If the RTRM loses the
common (ZSM terminal 6 to respective LED Heating and Cooling setpoint input, the RTRM will
terminal). control in the default mode instantaneously. The
temperature sensing thermistor in the Zone Sensor
Module is the only component required for the
Programmable & Digital Zone “ D e f a u l t M o d e” to operate.
Sensor Test
Testing Serial Communication Voltage
1. Verify 24 VAC is present between terminals J6-14 &

48 SS-SVX10D-EN
Maintenance
WA R N I N G Remove any accumulation of dust and/or dirt from
the unit casing.
H a z a r d o u s Vo l t a g e w / C a p a c i t o r s !
Remove corrosion from any surface and repaint.
F a i l u r e t o d i s c o n n e c t p o w e r a n d d i s ch a r g e
Check the gasket around the control panel door to
capacitor s before servicing could result in death or
ensure it fits correctly and is in good condition to
s e r i o u s i n j u r y. prevent water leakage.
D i s c o n n e c t a l l e l e c t r i c p o w e r, i n c l u d i n g r e m o t e
d i s c o n n e c t s a n d d i s ch a r g e a l l m o t o r s t a rt / r u n Inspect the control panel wiring to ensure that all
c a p a c i t o r s b e f o r e s e r v i c i n g . F o l l o w p r o p e r l o ck o u t / connections are tight and that the insulation is
tagout procedures to ensure the power cannot be intact.
i n a d v e rt e n t l y e n e r g i z e d . F o r v a r i a b l e f r e q u e n c y N o t e : Condenser fan motors are permanently
dri ves or other energy storing components lubricated.
p r o v i d e d b y Tr a n e o r o t h e r s , r e f e r t o t h e
Check refrigerant piping and fittings for leaks
a p p r o p r i a t e m a n u f a c t u r e r ’s l i t e r a t u r e f o r
a l l o w a b l e w a i t i n g p e r i o d s f o r d i s ch a r g e o f Inspect the condenser coils for dirt and debris. If the
c a p a c i t o r s . Ve r i f y w i t h a n a p p r o p r i a t e v o l t m e t e r coils appear dirty, clean them.
t h a t a l l c a p a c i t o r s h a v e d i s ch a r g e d .
For ad di ti on al i n for m at io n rega rdi ng t he s a fe Coil Cleaning
d i s ch a r g e o f c a p a c i t o r s , s e e P R O D - S V B 0 6 A - E N .
Regular coil maintenance, including annual cleaning-
enhances the unit's operating efficiency by minimizing:
N OT I C E • compressor head pressure and amperage draw
O p e r a t i n g U n d e r Va c u u m ! • water carryover
Do not operate or apply power to the compressor • fan brake horsepower
whi l e un de r a va c uu m . Fai l ure to fo ll ow t he s e • static pressure losses
instructions will result in compressor failure.
At least once each year — or more often if the unit is
Perform all of the indicated maintenance procedures at located in a “dirty” environment — clean the coil using
the intervals scheduled. This will prolong the life of the the instructions outlined below. Be sure to follow these
unit and reduce the possibility of costly equipment instructions as closely as possible to avoid damaging
failure. the coils. To clean refrigerant coils, use a soft brush and
a sprayer. Contact your local Parts Center for
appropriate detergents.
Monthly 1. Remove enough panels from the unit to gain safe
Conduct the following maintenance inspections once access to coil.
per month. 2. Straighten any bent coil fins with a fin comb.
Check unit wiring to ensure all connections are tight 3. Remove loose dirt and debris from both sides of the
and that the wiring insulation is intact. coil with a soft brush.
Inspect the condenser coils for dirt and debris. If the 4. Mix the detergent with water according to the
coils appear dirty, clean them. manufacturer's instructions. If desired, heat the
With the unit operating in the cooling mode, check solution to 150° F maximum to improve its
the suction and discharge pressures and compare cleansing capability.
them with Pressure Curve values in unit Service 5. Pour the cleaning solution into the sprayer.
Facts. Record these readings on the ”Maintenance
Log”, p. 50. 6. Spray the leaving-airflow side of the coil first; then
spray the opposite side of the coil. Allow the
cleaning solution to stand on the coil for five
Annually (Cooling Season) minutes.
The following maintenance procedures must be 7. Rinse both sides of the coil with cool, clean water.
performed at the beginning of each cooling season to 8. Inspect both sides of the coil; if it still appears to be
ensure efficient unit operation. dirty, repeat Step 7 and 8.
Perform all of the monthly maintenance 9. Reinstall all of the components and panels removed
inspections. in Step 1; then restore power to the unit.
With the unit operating, check unit superheat and 10. Using a fin comb, straighten any coil fins that were
record the reading in the ”Maintenance Log”, p. 50. inadvertently bent during the cleaning process.

SS-SVX10D-EN 49
50
Superheat (°F) Subcooling (°F)
Evaporator Entering Air Compressor (at compressor) (at service valve)

Ambient Suction Pressure Discharge Pressure


Temp. Dry Wet
Date (°F) Bulb Bulb (C1) (C2) (C1) (C2) Circuit #1 Circuit #2 Circuit #1 Circuit #2
Maintenance

Maintenance Log

Note: Perform each inspection once per month (during cooling season) while unit is operating

SS-SVX10D-EN
Wiring Diagram Matrix
Table 13. Wiring schematics R–410A cooling

Schematics Connection Diagrams


Refrig.
Model Number Capacity Circuit Voltage Hz Ph ReliaTel Elec. Mech. ReliaTel Elec. Mech.

TTA061DD 6 Single 380-415 50 3 2313-0403 2313-0404 23130416 2313-0413

TTA073D3 6 Single 208-230 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA073D4 6 Single 460 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA073DW 6 Single 575 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA073DK 6 Single 380 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA076DD 7.5 Single 380-415 50 3 2313-0403 2313-0404 23130416 2313-0413

TTA090D3 7.5 Single 208-230 60 3 2313-0403 2313-0404 2313-0416 2313-0413

TTA090D4 7.5 Single 460 60 3 2313-0403 2313-0404 2313-0416 2313-0413

TTA090DW 7.5 Single 575 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA090DK 7.5 Single 380 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA086DD 8.5 Single 380-415 50 3 2313-0403 2313-0404 23130416 2313-0413

TTA101DD 10 Single 380-415 50 3 2313-0403 2313-0404 23130416 2313-0413

TTA120D3 10 Single 208-230 60 3 2313-0407 2313-0408 2313-0417 2313-0414

TTA120D4 10 Single 460 60 3 2313-0403 2313-0404 2313-0416 2313-0413

TTA120DW 10 Single 575 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA120DK 10 Single 380 60 3 2313-0403 2313-0404 23130416 2313-0413

TTA101ED 10 Dual 380-415 50 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA120E3 10 Dual 208-230 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA120E4 10 Dual 460 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA120EW 10 Dual 575 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA120EK 10 Dual 380 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA101FD 10 Manif 380-415 50 3 2313-0411 2313-0412 2313-0418 2313-0415

TTA120F3 10 Manif 208-230 60 3 2313-0411 2313-0412 2313-0418 2313-0415

TTA120F4 10 Manif 460 60 3 2313-0411 2313-0412 2313-0418 2313-0415

TTA120FW 10 Manif 575 60 3 2313-0411 2313-0412 2313-0418 2313-0415

TTA120FK 10 Manif 380 60 3 2313-0411 2313-0412 2313-0418 2313-0415

TTA126ED 12.5 Dual 380-415 50 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA150E3 12.5 Dual 208-230 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA150E4 12.5 Dual 460 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA150EW 12.5 Dual 575 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA150EK 12.5 Dual 380 60 3 2313-0435 2313-0433 2313-0436 2313-0434

TTA156ED 15 Dual 380-415 50 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA180E3 15 Dual 208-230 60 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA180E4 15 Dual 460 60 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA180EW 15 Dual 575 60 3 2313-0403 2313-0404 2313-0425 2313-0421

SS-SVX10D-EN 51
Wiring Diagram Matrix

Table 13. Wiring schematics R–410A cooling (continued)

Schematics Connection Diagrams


Refrig.
Model Number Capacity Circuit Voltage Hz Ph ReliaTel Elec. Mech. ReliaTel Elec. Mech.

TTA180EK 15 Dual 380 60 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA156FD 15 Manif 380-415 50 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA180F3 15 Manif 208-230 60 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA180F4 15 Manif 460 60 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA180FW 15 Manif 575 60 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA180FK 15 Manif 380 60 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA201ED 20 Dual 380-415 50 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA240E3 20 Dual 208-230 60 3 2313-0407 2313-0408 2313-0426 2313-0422

TTA240E4 20 Dual 460 60 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA240EW 20 Dual 575 60 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA240EK 20 Dual 380 60 3 2313-0403 2313-0404 2313-0425 2313-0421

TTA201FD 20 Manif 380-415 50 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA240F3 20 Manif 208-230 60 3 2313-0410 2313-0409 2313-0428 2313-0424

TTA240F4 20 Manif 460 60 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA240FW 20 Manif 575 60 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA240FK 20 Manif 380 60 3 2313-0411 2313-0412 2313-0427 2313-0423

TTA251FD 25 Manif 380-415 50 3 2313-0445 2313-0444 2313-0449 2313-0447

TTA300F3 25 Manif 208-230 60 3 2313-0443 2313-0442 2313-0448 2313-0446

TTA300F4 25 Manif 460 60 3 2313-0445 2313-0444 2313-0449 2313-0447

TTA300FW 25 Manif 575 60 3 2313-0445 2313-0444 2313-0449 2313-0447

TTA300FK 25 Manif 380 60 3 2313-0445 2313-0444 2313-0449 2313-0447

Note: Wiring diagrams are available through e-Library or by contacting your local sales office.

The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2014 Trane All rights reserved
SS-SVX10D-EN 14 Jan 2014 We are committed to using environmentally
Supersedes SS-SVX10C-EN (August 2012) conscious print practices that reduce waste.

Das könnte Ihnen auch gefallen