Chloride 80-NET
UPS Systems from 60 to 500 kVA
Scope 4
System Description 4
Device Description 5
General Requirements 8
Mechanical Data 18
Environmental Conditions 18
Options 27
Parallel Configuration 29
3
Chloride80-NET UPS Systems from 60 to 500 kVA
4
Chloride80-NET UPS Systems from 60 to 500 kVA
3 Device Description
Chloride 80-NET is the result 3.3 Intelligent double conversion operating modes
of an innovative research and Chloride 80-NET will adopt intelligent double conversion technology which
development programme designed
allows the UPS to operate in double conversion or digital interactive mode
to offer users the most reliable power
supply at a minimum cost and the according to the selected priority. The UPS will operate as follows:
highest possible energy conversion
efficiency. 3.3.1 Double Conversion Mode (DCM)
3.1 Components
3.3.1.1 Normal (DCM)
The UPS will consist of the following
major components: The UPS inverter continuously supplies the critical AC load. The rectifier
• IGBT Rectifier derives power from the commercial AC source and converts it into DC power
• IGBT Battery Charger / Booster for the inverter and the battery charger. The battery charger keeps the
• IGBT Inverter
battery in a fully charged and optimum operational condition. The inverter
• Dedicated digital signal processor
(DSP) for each IGBT AC/DC, DC/AC converts the DC power into clean and regulated AC power which is supplied
converter to the critical load (conditioned line). The static switch monitors and ensures
• Micro-controller board for internal that the inverter tracks the bypass supply frequency. This ensures that any
and external signal management automatic transfer to the bypass supply (due to an overload etc.) is frequency
• Electronic static switch and bypass
synchronized and does not cause interruption to the critical load.
supply
• Manual maintenance bypass
switch 3.3.1.2 Overload (DCM)
• Matching battery cubicles In the event of an inverter overload, manual stop or failure, the static
switch will automatically transfer the critical load to the bypass line without
3.2 Microprocessor control
interruption.
and diagnostics
Operation and control of the UPS
will be provided through the use 3.3.1.3 Emergency (DCM)
of microprocessor- controlled Upon failure or reduction of the commercial AC source (see the Technical
logic. Indications, measurements Data table for tolerances) the inverter will supply the critical load, drawing
and alarms, together with battery
power from the associated battery through the battery Booster.
autonomy, will be shown on a
graphic liquid crystal display There will be no interruption to the critical load upon failure, reduction or
(LCD). The procedures for start up, restoration of the commercial AC source. While the UPS is powered by
shutdown and manual transfer of the batteries, indications will be provided of actual autonomy time
the load to and from bypass will
remaining as well the duration of the mains failure.
be explained in clear step-by-step
sequences on the LCD display.
3.3.1.4 Recharge (DCM)
Upon restoration of the commercial AC source, even where batteries are
completely discharged, the rectifier will restart automatically (walk in) and
gradually take over both the inverter and battery charger. This function will
be fully automatic and will cause no interruption to the critical load.
5
Chloride80-NET UPS Systems from 60 to 500 kVA
3.3.2 Digital Interactive Mode (DIM) deviation from the selected input degree of the overload and the UPS
If priority has been set to digital power tolerance levels. If the direct features. Visual and audio alarms
interactive mode, intelligent double line failure rate has been outside alert the user to the problem.
conversion technology will allow permitted parameters, Chloride
Chloride 80-NET to continuously 80-NET will supply the load from 3.3.2.4 Emergency (due to mains
monitor the condition of the input the conditioned line. The battery supply failure or variance beyond
supply, including its failure rate, charger supplies the energy tolerance limits, DIM)
to ensure maximum reliability for necessary for maintaining maximum If Chloride 80-NET is supplying
critical users. On the basis of the charge to the battery. the load via the direct line and the
analysis performed, it will decide bypass mains supply varies beyond
whether to supply the load through 3.3.2.2 Inverter stop (DIM) tolerance levels (adjustable using
the direct line or the conditioned If the inverter is stopped for any the software), the load will be
line. This operational mode, which reason there is no transfer to the transferred from the direct line to the
allows significant energy savings conditioned line and the load conditioned line. The load is powered
by increasing the overall AC/AC continues to be supplied by the from the mains via the rectifier and
inverter, (provided the input mains
efficiency of the UPS, up to 98%, direct line. The mains voltage and
remains within the tolerances stated
is primarily intended for general frequency values must be within
in chapter 12 & 13). Should the input
purpose ICT applications. However, the tolerance limits specified.
mains fall below the lower limit,
it does not provide the same output the batteries will be used to power
power quality as when the UPS 3.3.2.3 Overload (DIM) the load via the inverter. The user
operates in double conversion In the event of an overload with a is alerted to the battery discharge
mode. It will therefore be necessary duration in excess of the maximum by visual and audio alarms and the
to verify whether this mode is capacity specified for the bypass remaining autonomy is displayed
appropriate for special applications. static switch, the load is maintained on the LCD. During this process, it
Digital interactive mode is not on the direct line and a warning is possible to extend the remaining
available for parallel systems. message on the LCD display will autonomy by switching off non-
appear to warn the user about essential loads.
3.3.2.1 Normal (DIM) the potential risk related to this
The operating mode will depend condition. This default behavior 3.3.2.5 Return to normal
on the quality of the mains supply can be changed (via a Service conditions (DIM)
in the short-term past. If the accessible firmware setting) to When the mains supply returns to
line quality has remained within force a load transfer to the within tolerance limits,
permitted tolerance parameters in conditioned line (similar to that Chloride 80-NET will continue to
this timeframe, the direct line will described below), even if the bypass supply the load via the conditioned
line for a period of time dependant
provide continuous supply to the source is available. In the event of
on the direct line failure rate (the
critical AC load through the bypass an overload in conjunction with an
conditioned line draws power from
static switch. The IGBT inverter unsuitable bypass mains supply,
the mains not the battery).
control will remain in constant Chloride 80-NET will transfer the When the direct line has stabilized,
operation and synchronization load from the direct line to the Chloride 80-NET returns to normal
with the direct line without driving conditioned line (assuming operation. The battery charger
the IGBT. This ensures that the Chloride 80-NET was operating from automatically begins to recharge
load can be transferred to the the direct line) and the inverter the battery so that maximum
conditioned line without any will continue to supply the critical autonomy is guaranteed in the
break in supply where there is a load for a period dependant on the shortest possible time.
6
Chloride80-NET UPS Systems from 60 to 500 kVA
7
Chloride80-NET UPS Systems from 60 to 500 kVA
4 General Requirements
3.4.4 Serviceability and 4.1 Applied standards
commissioning Emerson Network Power operates Quality Management Systems which
The new Chloride 80-NET is
comply with ISO 9001, as well as Environmental Policies and Management
designed for easy installation and
serviceability thanks to the drawer- Systems that comply with ISO 14001.
design, making it a full modular Chloride 80-NET will carry the CE mark in accordance with the Safety European
service solution and considerably Directive 2006/95 (superseding the 73/23 and successive amendments)
minimising the time needed for
and European EMC directive 2004/108 (superseding the 89/336, 92/31 and
repairs.
All functional modules can be 93/68). Chloride 80-NET is designed and manufactured in accordance with the
removed by extracting the drawers following international standards:
from the front of machine. • IEC/EN62040-1-1 general and safety requirements
Each UPS will be equipped with
ID card, including all UPS working • EN62040-2 EMC requirements
parameters. This card, univocally • IEC/EN62040-3 operating requirements.
related to the UPS, reduces the • Classification according to IEC/EN 62040-3: VFI-SS-111
MDT to zero shortening service and
commissioning operations.
4.2 Safety
In terms of general and safety requirements, the UPS conforms to standard
IEC/EN 62040-1-1 governing use in unrestricted access locations.
4.5 Materials
All materials and components including the UPS will be new and of current
manufacture.
8
Chloride80-NET UPS Systems from 60 to 500 kVA
9
Chloride80-NET UPS Systems from 60 to 500 kVA
10
Chloride80-NET UPS Systems from 60 to 500 kVA
6.7 Battery management test will not cause any degradation battery life remaining, based on
Using advanced battery care (ABC) in terms of the battery system life real operating conditions such as
the Chloride 80-NET series will expectancy. temperature, discharge and charging
maximize battery running time by cycles, and discharge depth.
up to 50%. The main battery care 6.7.3 Ambient temperature
features are described as follows. compensated battery charger 6.7.6 Operations with shared
The float voltage will be battery bank
6.7.1 Operating parameters automatically adjusted as a function Although this configuration is not
When operating with a maintenance of the temperature in the battery recommended, it is possible to share
free, valve regulated lead acid compartment (-0.11% per °C)
a common battery bank between a
battery (VRLA), the parameters per in order to maximize battery
maximum of two UPS connected in
cell will be as follows: operating life.
parallel (see chapter 15 for details
• End of discharge voltage (V) 1.65 about parallel systems).
• Shutdown imminent alarm (V) 6.7.4 Time compensated end
The automatic battery test (see
1.75 of discharge voltage
6.7.2) will be significant if the
• Minimum battery test voltage When the discharge time exceeds
one hour, the shutdown voltage total system load (of the 2xUPS in
(V) 1.9 parallel) is equal to or greater than
• Nominal voltage (V) 2.0 will be automatically increased,
as shown in Figure 4 for VRLA, 20% (based on the UPS default
• Battery discharging alarm (V) 2.20
to avoid prolonged battery battery recharging values).
@ 20°C
discharge as a result of a light load. In any case this configuration is not
• Float voltage (V) 2.27 @ 20°C
recommended due to the negative
• High voltage alarm (V) 2.4
6.7.5 Remaining battery life impact on the overall system
Chloride 80-NET uses sophisticated reliability caused by the lack of
6.7.2 Automatic battery test
algorithms to determine the redundancy of the battery banks.
The operating condition of the
batteries will be automatically
tested by the control unit at
Voltage per cell
selectable intervals, e.g. weekly,
fortnightly or monthly.
1.80
A short-time discharge of the
battery will be made to confirm
that all the battery blocks and 1.75
11
Chloride80-NET UPS Systems from 60 to 500 kVA
12
Chloride80-NET UPS Systems from 60 to 500 kVA
7.9 Phase displacement temperatures, as shown in Figure compatibility with each installation
The phase angle displacement 5. In the most common conditions and means that the customer
between the three-phase voltages (25°C) Chloride 80-NET will provide doesn’t have to worry about future
will be: 10% more power than nominal. In modifications of the loads with a
• 120° ± 1° for balanced loads these conditions the battery charge different Power Factor. As it is shown
• 120° ± 3° for unbalanced loads will be reduced correspondingly. in Figure 6, it is clearly evident from
the two blue areas that every kind
(0, 0, 100%)
of load (leading or lagging) with
7.12 Symmetrical Power PF up to 1 will be supplied by the
7.10 Short circuit
Factor Output Diagram UPS without any derating since the
The inverter short circuit capacity
The full IGBT inverter is able to inverter will be able to work at 100%
of Chloride 80-NET for the first 10ms
supply, without derating, all kinds of its power.
will be 300% for any short circuit
of loads (leading and lagging) with
configuration. After the first 10ms,
a power factor up to 1. This behavior
it will limit the current to 150% for
is achieved thanks to the perfect
no longer than than 5s and then it dimensioning of all components of
will shut down. the output stage, which allows the
obtaining of a Power Factor output
7.11 Automatic upgrade of diagram perfectly symmetrical
inverter rated power respect to the zero. Thanks to
The inverter will automatically this feature, which is unique in
upgrade its power as a function the market, the Chloride 80-NET
of ambient and operating offers maximum flexibility and
110 20
KVA
0
25 50 75
KVA
20
105
100%
100 K VA
15 25 30 40 C° 100%
Lagging
13
Chloride80-NET UPS Systems from 60 to 500 kVA
14
Chloride80-NET UPS Systems from 60 to 500 kVA
15
Chloride80-NET UPS Systems from 60 to 500 kVA
16
Chloride80-NET UPS Systems from 60 to 500 kVA
9.3.5 2*16 Pole screw connector the LIFE®.net communication kit, order to predict near term problems.
for input and output contacts (TB1) providing connection to LIFE®.net In addition, it will be possible to
This 2*16-pole screw connector diagnostic service. control the UPS remotely.
allows the connection of: six LIFE®.net will allow the remote
individual configurable output and diagnosis of the UPS through the IP The communication of UPS data
four individual configurable input connection (Internet connection), to the LIFE® Command Center will
contacts which can be programmed telephone lines or GSM link in order be transmitted in the following
via PPVis (service software tool) to ensure maximum availability of conditions :
for a wide set of functions. This the UPS throughout its operational • ROUTINE: settable at intervals of
interface is SELV-isolated from the life. The monitoring will be a real
UPS primary circuits. The maximum between five minutes and two
24-hour, 365 day service thanks to
rating of the output contacts must a unique feature that allows trained days (typically once a day)
not exceed 24V and 1A (refer to the Service Engineers to remain in • EMERGENCY: when a problem
User Manual for further details). constant electronic contact with occurs or parameters are beyond
the service center, and therefore tolerance limits
9.3.6 LIFE®.net the UPS. The UPS will automatically
In order to increase the overall • MANUAL: following a request
dial up the service center at defined
availability of the system, Chloride intervals to provide detailed from the command center
80-NET will be delivered with information that will be analyzed in
During the call the command center
Output Contacts (lower row of the connector):
will:
PIN Status Preset Value
PIN 1 (left) Normally closed • Identify the UPS connected
Summary Alarm
PIN 2 Normally open
• Request the data stored in the UPS
PIN 3 Normally closed
Bypass Active
PIN 4 Normally open memory since the last connection
PIN 5 Normally closed
Low Battery • Request real-time information
PIN 6 Normally open
PIN 7 Normally closed from the UPS (selectable)
AC Fail
PIN 8 Normally open
PIN 9 Common to PIN1-PIN8 N/A
PIN 10 N/A N/A The service center will analyze
PIN 11 Normally closed
Selectable historical data and issue a regular
PIN 12 Normally open
PIN 13 Common to PIN11-PIN12 N/A detailed report to the customer
PIN 14 Normally closed
Selectable informing him of the UPS
PIN 15 Normally open
PIN 16 Common to PIN14-PIN15 N/A operational condition and any
Input Contacts (upper row of the connector): critical states.
PIN Status Preset Value The LIFE®.net center allows the
PIN 1 (left) Input 1 (24 VDC OUT) possibility of activating the LIFE®-
Selectable
PIN 2 Input 1 (24 VDC signal) SMS delivery system option, where
PIN 3 Input 2 (24 VDC OUT)
Selectable the customer may receive SMS
PIN 4 Input 2 (24 VDC signal)
notification which will be activated
PIN 5 Input 3 (24 VDC OUT)
PIN 6 Input 3 (24 VDC signal)
Selectable in the event of one of the following:
PIN 7 Input 4 (24 VDC OUT) • Mains power failure
Selectable
PIN 8 Input 4 (24 VDC signal) • Mains power recovery
PIN 9-16 N/A N/A • Bypass line failure
TB1 connector: the Interface is SELV - isolated from UPS primary circuits. • Load supplied by reserve.
17
Chloride80-NET UPS Systems from 60 to 500 kVA
10 Mechanical Data
10.1 Enclosure static bypass if an overheating of 10.4 Enclosure design
The UPS will be housed in a the converters occurs. The failed All surfaces of the enclosure will be
spacesaving modular enclosure with fan condition will be immediately finished with an electrostatically
front doors and removable panels notified by the UPS through all the applied epoxy coat. The coating
(protection as standard to IP 20). user interfaces and through the will have a thickness of at least 60
The enclosure will be made of zintec LIFE®.net service. microns. Standard colour of the
coated sheet steel and the doors will The cooling air entry will be on the enclosure will be RAL 7016.
be lockable. front and the air exit at the top of
the device. The enclosure will be 10.5 Access to integrated
10.2 Ventilation installed with at least 500 mm of subassemblies
Forced redundant air cooling will free space between the device and All internal subassemblies will be
ensure that all the components are roof of the enclosure in order to accessible for typical and most
operated within their specification. allow cooling air to exit unhindered. frequent maintenance from the
Airflow will be controlled according front of the unit via hinged doors.
to load demand. The UPS will also 10.3 Cable entry Rear access will not be required for
be capable of preserving normal From 60 to 120kVA installation or servicing. The UPS
operations even with one cooling
Cable entry will be from the bottom will be forkliftable from the side
fan out of operation (due to a
or side of the cabinet. Top cable after the removal of the bottom
failure) with 70% of the output
nominal load @ 25°C ambient entry will be available as an option. trim panels.
temperature.
If these conditions are not met From 160 to 500kVA
(with one fan failed), the UPS Cable entry, as standard, will be
will supply the load through the from the top, bottom or side.
11 Environmental Conditions
The UPS will be capable of 11.3 Altitude
withstanding any combination The maximum altitude without
of the environmental conditions derating will be 1000 metres above
listed below. It will operate without sea level (for higher altitudes
mechanical or electrical damage Chloride 80-NET complies with
or degradation of operating IEC/EN 62040-3).
characteristics.
18
Chloride80-NET UPS Systems from 60 to 500 kVA
12.2 Battery
Permissible battery voltage range (V) 396 to 700
DC/AC efficiency on battery operation @ nominal load (%) 95.7 95.7 95.9 95.9
19
Chloride80-NET UPS Systems from 60 to 500 kVA
20
Chloride80-NET UPS Systems from 60 to 500 kVA
21
Chloride80-NET UPS Systems from 60 to 500 kVA
12.6 Environmental
Location Indoor (free from corrosive gases and conductive dust)
Max altitude above sea level without derating (m) 1000 (for higher altitudes complies with IEC/EN 62040-3)
1) For tolerances see IEC/EN 60146-1 or DIN VDE 0558. The data refers to 25°C ambient temperature.
2) At nominal voltage and frequency.
3) Recommended average daily ambient temperature 35°C with a maximum of 40°C for 8 hours as requested for 62040 standard.
4) In the case of a split input configuration, the primary input and the bypass input must have a common neutral. The neutral conductor may be connected only to the
bypass or to primary mains, but it must be present (bypass and primary neutrals are connected inside the UPS).
5) Referred to 70% of nominal load.
6) With input voltage at nominal value and voltage distortion THD 1%.
7) Nominal apparent power loads with PF > 0.9 can be supplied with marginal limitation of other performances. Please contact Technical Support team
for further information.
8) In case of different levels of overload refer to the specific overload curve.
22
Chloride80-NET UPS Systems from 60 to 500 kVA
13.2 Battery
Permissible battery voltage range (V) 396 to 700
23
Chloride80-NET UPS Systems from 60 to 500 kVA
24
Chloride80-NET UPS Systems from 60 to 500 kVA
25
Chloride80-NET UPS Systems from 60 to 500 kVA
13.6 Environmental
Location Indoor (free from corrosive gases and conductive dust)
Max altitude above sea level without derating (m) 1000 (for higher altitudes complies with IEC/EN 62040-3)
1) For tolerances see IEC/EN 60146-1 or DIN VDE 0558. The data refers to 25°C ambient temperature.
2) At nominal voltage and frequency.
3) Recommended average daily ambient temperature 35°C with a maximum of 40°C for 8 hours as requested for 62040 standard.
4) In the case of a split input configuration, the primary input and the bypass input must have a common neutral. The neutral conductor may be connected only to the
bypass or to primary mains, but it must be present (bypass and primary neutrals are connected inside the UPS).
5) Referred to 70% of nominal load.
6) With input voltage at nominal value and voltage distortion THD 1%.
7) Nominal apparent power loads with PF > 0.9 can be supplied with marginal limitation of other performances. Please contact the Technical Support team
for further information.
8) In case of different levels of overload refer to the specific overload curve.
26
Chloride80-NET UPS Systems from 60 to 500 kVA
14 Options
Where options described in this 14.3 Remote alarm unit
chapter are added to the UPS, the A remote alarm panel will be available to display important individual
data presented in the standard messages from the UPS. Upon request, it will be possible to display up to four
technical data tables may vary. UPS systems. The length of the connecting cable must not exceed 300m.
Some options may not be available
contemporarily on the same UPS. 14.4 External battery circuit breaker
This option will include a fully rated circuit breaker and an additional
14.1 Integrated isolation auxiliary contact for monitoring its position by the UPS (via a dedicated
transformer input contact). The circuit breaker will be housed in a wall-mounted box and
Chloride 80-NET ratings from designed for battery systems which are mounted on racks. Furthermore,
60 to 200 kVA can be customized the circuit breaker will serve as a safety element for the cross section of the
to provide full galvanic isolation power cable between the UPS and the remotely placed battery system.
for specific load requirements by
adding an isolation transformer that 14.5 Battery management modules (only upon request)
can be housed in the UPS cabinet. With measuring modules connected to the battery blocks, enhanced battery
The transformer can be connected management will be possible offering the following features:
to the input (mains, bypass or both) • Measurement of the condition of each individual battery block by means of
or to the output of the UPS. separate battery measuring modules (BMM)
These options will provide the • Analysis of each battery block with measurement of the minimum and
following benefits: maximum voltage values.
• Full galvanic isolation for medical
and “most critical” applications 14.6 Top cable entry
• Installation with two independent Top cable entry is standard for Chloride 80-NET ratings from 160 to 500 kVA.
input sources with different neutrals For ratings from 60 to 120 kVA top cable entry is available as optional.
• Installation in distribution without
neutral 14.7 Dust filters
This option will improve the protection degree of the air entrance from IP20 to
Note: for ratings from 300 to 500 lP40 for specific applications such as a dusty environment. The filter will be
kVA the isolation transformer is housed in the UPS cubicle (IP20).
available in an external cabinet.
14.8 Empty battery cubicle
14.2 Parallel configurations Matching empty battery cubicles will be available including:
The Chloride 80-NET can be • Cubicle
connected in up to eight units in • Disconnecting device
parallel, without the need for an • Safety panel
additional parallel board, allowing • Connection terminals
maximum reliability and flexibility. • UPS/battery connection cables (available on request)
A single unit can be upgraded to a
parallel one at any time through a Two cubicle sizes will be available:
licence code which is univocally Width (mm) Depth (mm) Height (mm) Weight (kg)
related to the UPS and allows the Type A 820 858* 1780 210
service engineer to configure the Type B 1020 858* 1780 260
full set of parallel parameters.
See chapter 15. *including front handle (without handle 830 mm)
27
Chloride80-NET UPS Systems from 60 to 500 kVA
28
Chloride80-NET UPS Systems from 60 to 500 kVA
15 Parallel Configuration
15.1 Paralleling principle Power parallel modular configuration.
The Chloride 80-NET series of It will be possible to increase the For this purpose UPS systems of
uninterruptible power supply power of the system using a non- the same rating will be connected
systems will be connectable redundant parallel configuration in parallel to form multimodule
in parallel for multi module (redundancy coefficient = 0). configurations. The UPS parallel
configurations between units of the In this case all connected UPS units connection will either improve
same rating. will deliver the rated power and, reliability, the total output power,
The maximum number of UPS in in the event of a unit failure or or both.
parallel configuration will be eight. overload, the system will transfer The Chloride 80-NET is able to
The parallel connection of UPS will the load to reserve. A maximum connect up to eight units in parallel,
increase reliability and power. of eight UPS may be connected in without the need for an additional
parallel. parallel board, allowing maximum
Reliability reliability and flexibility.
If the installation requires more than Performance features A single unit, at any time, can be
one unit in redundant configuration The performance features of the upgraded to a parallel one through
the power of each UPS should not be parallel system are related to the UPS a licence code which is univocally
lower than Ptot/(N-1) where: systems employed. The distribution related to the UPS and allows the
Ptot = Total load power of the load is divided equally service engineer to configure the
N = Number of UPS units in parallel between the individual UPS systems. full set of parallel parameters. The
parallel option will simply consist
1 = Minimum coefficient of redundancy
15.2 Modular of screened data cables connected
Chloride 80-NET series’ UPS systems to the neighboring UPS modules
Under normal operating conditions,
will be capable of operating in a (closed loop ring bus).
the power delivered to the load will
be shared between the number
of UPS units connected to the
parallel bus. In case of overload the
UPS 1 UPS 2 UPS n
configuration may deliver PovxN
without transferring the load onto
the reserve, where:
Pov = Max overload power of a single UPS
N = Number of UPS units in parallel
BATT BATT
29
Chloride80-NET UPS Systems from 60 to 500 kVA
A multi-module system will system is being installed and no Therefore the reserve supply to the
be controlled and monitored redundancy is present. loads works with one central piece
automatically by controlling the For sizes bigger than those shown of equipment (MSS). Please refer to
individual UPS systems. in the table below, SBS becomes a fig. 9 for the single line diagram of
The parallel system control is special and will be provided upon the parallel system.
distributed among the units (no request. Please contact technical A centralized configuration offers
master/slave architecture). The support for details. maximum flexibility in positioning
bypass lines and inverters included
UPS blocks. It is possible to modify
in each UPS share the load. The load
15.4 Centralized Parallel the parallel configuration of Chloride
sharing among the UPS parallel
with MSS 80-NET from centralized to modular
system (“load on inverter” mode)
and vice versa (provided an MSS is
will be achieved with a tolerance
Centralized paralleling architecture included in the system).
of less than 5% at any system load
fraction (0 - 100%). enables UPS with inhibited bypass to For further details please contact
The loop ring bus will allow the be connected in parallel. Technical Support.
parallel to share the system load
even with an interruption in the UPS 1 UPS 2 UPS n MSS
data cable (first failure proof
system).
30
Chloride80-NET UPS Systems from 60 to 500 kVA
Notes
31
Chloride80-NET UPS Systems from 60 to 500 kVA
Notes
32
Chloride80-NET UPS Systems from 60 to 500 kVA
Notes
Ensuring The High Availability
Of Mission-Critical Data And Applications.
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Tel: +1 614 8880246
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
This publication is issued to provide outline information only and is not deemed
to form part of any offer and/or contract. The company has a policy of continuous Tel: +852 2572220
product development and improvement, and we therefore reserve the right to Fax: +852 28029250
vary any information without prior notice.